NSi Industries LC200 User Manual

TORK
MODEL LC200
Dual Stage Lighting Controller
DESCRIPTION,
INSTALLATION & OPERATION
Description:
The Model LC200 consists of an electronic control and an electronic light sensor interact­ing. The unit offers separate control of two lighting zones, each with user settable on/off light level setpoints. The Electronic control also offers two digital inputs which will accept a contact closure from any TORK Timer(s), or existing EMS system to provide for inde­pendent time-of-day override if required.
Features:
Single electronic light sensor with swivel
(Model EPC-1) which can be mounted up to 1000 feet from controller
Dual outputs with independent adjustment
from 2 to 100 footcandles
Two independent “Time-of-Day” inputs
30 second delay on start-up
Power-On status indicator
Load status indication for each load
Installation:
1. Remove the Control from its enclosure, push tab to right and swing unit to left and remove.
2. Mount the enclosure at eye level using screws or other suitable fastening device.
TORK
1 GROVE ST., MT. VERNON, NY 10550 TEL: 914-664-3542
FAX: 914-664-5052
MLI-119(B)
®
NOTE: Disconnect all external power before wiring to prevent electrical shock or damage to equipment.
ply with appropriate codes.
3. KO’s top, bottom and side (1/2” and 3/4”) a. Use bottom or side KO’s for Input
power, and load wiring. See wiring dia- gram for connection.
*b. Use top KO’s for light sensor and
Time-of-Day control input wiring (rec- ommended wire size is 18 to 22 AWG twisted pair). See wiring diagram for connection.
4. The electronic light sensor Model EPC-1, can be mounted up to 1000 ft. away through a standard 1/2” SPT connection to an outdoor weatherproof junction box. Use suitable tape or sealant on nipple threads.
upright position.
connection.
Setting The Light Level Adjustment:
NOTE:
Stage 1 and Stage 2 must be done when ambient light levels fall to the actual point when electrical lighting is required.
1. Move SET/RUN switch to the SET position.
2. Rotate Stage 1 and 2 light level dial clock- wise to their maximum light level setting (position 10)
3. Wait until the ambient light falls to the point when Stage 1 electrical lighting is required. Rotate the Stage 1 light level dial counterclockwise until the lighting comes on.
4. Repeat step #3 above for Stage 2 electri- cal lighting.
5. Return the SET/RUN switch to the RUN position. The unit is now ready for operation.
NOTE: Disconnect all external power before wiring to prevent electrical shock or damage to equipment.
Wiring must com-
ply with appropriate codes.
3. KO’s top, bottom and side (1/2” and 3/4”) a. Use bottom or side KO’s for Input
power, and load wiring. See wiring dia­gram for connection.
*b. Use top KO’s for light sensor and
Time-of-Day control input wiring (rec­ommended wire size is 18 to 22 AWG twisted pair). See wiring diagram for connection.
4. The electronic light sensor Model EPC-1, can be mounted up to 1000 ft. away through a standard 1/2” SPT connection to an outdoor weatherproof junction box. Use suitable tape or sealant on nipple threads.
Must be mounted in the
upright position.
See wiring diagram for
connection.
Setting The Light Level Adjustment:
NOTE:
Setting the light level dials for both Stage 1 and Stage 2 must be done when ambient light levels fall to the actual point when electrical lighting is required.
1. Move SET/RUN switch to the SET position.
2. Rotate Stage 1 and 2 light level dial clock-
wise to their maximum light level setting (position 10)
3. Wait until the ambient light falls to the
point when Stage 1 electrical lighting is required. Rotate the Stage 1 light level dial counterclockwise until the lighting comes on.
4. Repeat step #3 above for Stage 2 electri-
cal lighting.
5. Return the SET/RUN switch to the RUN
position. The unit is now ready for operation.