NSi Industries EW103S User Manual

TORK EW101S/EW103S/EW120S
7 DAY Digital Time Switch
READ INSTRUCTIONS CAREFULLY BEFORE SETTING UNIT
INSTALLATION
UNIT IS TO BE INSTALLED BY A LICENSED ELECTRICIAN
1. To remove unit from enclosure: Push tab on right to swing unit to the left and remove.
3. Reinstall unit by reversing step #1 above and con­nect wires to unit as per suggested wiring diagrams. See illustration on back page.
4. A reset switch (located in the front of the unit above the LCD display) clears all memory. Slide the switch to the left and wait for 2-3 seconds. Then slide the switch to the right and the unit is ready for setting.
KEY FUNCTIONS
DAY: Press to select proper day of the week in the CLK (clock) mode and the SCH (schedule) mode.
HOUR: Press to set the hours in the CLK mode and in the SCH (schedule) mode.
MIN: Press to set the minutes in the CLK mode and in the SCH mode.
OVERRIDE: Press to alter the current load status (oper­ates in both AUTO and MAN modes).
MODE: Press to advance to next mode. Sequence is: CLK, SCH, AUTO, MAN. In the CLK and SCH modes, UNIT AUTOMATICALLY REVERTS TO THE AUTO MODE IF NO ENTRIES ARE MADE FOR 5 MINUTES.
DELETE: Press to delete the displayed information when in the SCH mode.
ON/OFF: Press to assign ON or OFF events. ENTER: Press to store the displayed information into
memory. Information will not be stored until ENTER
key is pressed.
NOTE: During settings, each press of the key will advance one number. For rapid advance, hold key in.
TO SET CLOCK
Press MODE key until display shows CLK. Press DAY key to select current day. Press HOUR key
to select current hour. Check A (AM) or P (PM). Press MIN key to select current minute. Press ENTER key and the clock is set for current time and day.
TO SET SCHEDULE
For convenience, write out your desired schedule on a separate paper.
If display does not show SCH, press mode key until dis­play shows SCH.
The display will Indicate it is ready to receive SCH setpoint #1. Press DAY key to set day(s).
Note: The following is a listing of the sets of days which can be set:
1. M, T, W, TH, F
2. S, SU (Saturday and Sunday only)
3. M, T, W, TH, F, S, SU
4. Individual days: M or T or W or TH or F or S or SU Press HOUR and MIN keys (check for AM or PM). Press
ON/OFF key for appropriate event. Press ENTER key to store the information and display
will indicate it is ready to receive SCH setpoint #2. Proceed for up to 14 setpoints. Then press MODE
key and unit will go to the AUTO (run) mode. In the AUTO mode, the unit will display current time and
day as well as load status (ON and OFF).
Note: When the unit is returned to the auto mode, check the load status of the current setting. If it is showing OFF but should be ON, press the override key. The unit will correct itself at the next scheduled event and no further alteration will be necessary.
REVIEW/MODIFY
1. CLOCK - ALTER TIME Press mode key until display shows CLK. Press DAY, HOUR, and MIN keys to change to the cor-
rect time. Press ENTER.
2. SCHEDULE - REVIEW Press mode key until display shows SCH. Press ENTER key repeatedly to review all the scheduled
entries.
3. SCHEDULE - MODIFY During the review (see previous section) any set point
can be modified or deleted. Use the HOUR, MIN and DAY keys to modify. Use the DELETE key to eliminate that event. Press ENTER key after each modification.
OVERRIDE - TEMPORARY
In order to temporarily change the current ON or OFF status of a load, simply press the override key when the unit is in the AUTO mode. The altered load status will flash. Override is in effect until the next scheduled event. In order to cancel the override, press override key again.
OVERRIDE - LONG TERM
Press mode key until display shows MAN (manual). Normal schedule will not be executed and the load status will remain unchanged as indicated. Press the OVERRIDE key to obtain the correct status or to alter the load status.
TORK
DIGITAL TIME SWITCH
EW101S 120VAC EW101S-2 240VAC EW101S-3 277VAC EW101S-24 24VAC
OUTPUT: SPST
EW103S 120VAC EW103S-2 240VAC EW103S-3 277VAC EW103S-24 24VAC
OUTPUT: DPST
EW120S 120VAC EW120S-2 240VAC EW120S-3 277VAC EW120S-24 24VAC
OUTPUT: SPDT
TORK
®
MLI-141(B) 1 GROVE STREET, MT. VERNON, NY 10550 TEL: 914-664-3542
FAX: 914-664-5052
Disconnect power at main panel prior to installing or servicing this time switch or the equipment connected to it.
Install and use in accordance with national and local electrical codes. Supply Connections: Use gauge specified (AWG # 10-16) suitable for 75
degrees C (167 degrees F). Use copper wire only.
Replace insulator before turning on electricity.
Resistive Inductive
Tungsten Pilot Duty
of Load
Resistive Inductive
Ballast Tungsten Pilot Duty
DRY CONTACT RATINGS
Type
of Load
Ballast
Type
Motor
120
VAC
30A 30A 20A 5A
470VA
Motor
1 HP
20A Resistive @ 28VDC
DRY CONTACT RATINGS
120VAC
N.O. N.C N.O. N.C
20A
10A
20A
10A
6A
3A
5A
3A
470
275
VA
1 HP
N.O. 20A Resistive @ 28VDC N.C. 10A Resistive @ 28VDC
240
277
VAC
VAC
30A
12A
30A
12A
6A
6A
5A
5A
470VA
690VA
2 HP
TIMER
SUPPLY
1 2
TIMER
SUPPLY
1 2
LLN
240VAC
20A
10A
20A
10A
6A
3A
5A
3A
470
275
VA
VA
VA
1/4
1/2
2 HP
HP
HP
TIMER
SUPPLY
1 2
SPST
3
LOAD
DPST
4
356
LOAD
N
277VAC
N.O. N.C
6A
3A
6A
3A
6A
3A
690 VA
SPDT
34 5
LOAD LOAD
4
NLN
LOAD
N
LN
N N