NSi Industries EW103 User Manual

Page 1
TORK EW101/EW103/EW120
7 DAY Digital Time Switch
READ INSTRUCTIONS CAREFULLY BEFORE SETTING UNIT
INSTALLATION
UNIT IS TO BE INSTALLED BY A LICENSED ELECTRICIAN
1. To remove unit from enclosure: Push tab on right to swing unit to the left and remove.
3. Install 9 volt alkaline battery (not supplied) by sliding battery cover in direction of arrow and removlng (located above key pad) Pull out the battery connector and con­nect the battery. Reinstall battery cover
Note: Unit can be fully programed using battery power only.
4. Reinstall unit by reverslng step #1 above and connect wires to unit as per suggested wiring diagrams See illus­tration on back page.
KEY FUNCTIONS
DAY: Press to select proper day of the week in the CLK (clock) mode and the SCH (schedule) mode.
HOUR: Press to set the hours in the CLK mode and in the SCH (schedule) mode.
MIN: Press to set the minutes in the CLK mode and in the SCH mode.
OVERRIDE: Press to alter the current load status (oper­ates in both AUTO and MAN modes).
MODE: Press to advance to next mode. Sequence is: CLK, SCH, AUTO, MAN. In the CLK and SCH modes, UNIT AUTOMATICALLY REVERTS TO THE AUTO MODE IF NO ENTRIES ARE MADE FOR 5 MINUTES.
DELETE: Press to delete the displayed information when in the SCH mode.
ON/OFF: Press to assign ON or OFF events. ENTER: Press to store the displayed information into
memory. Information will not be stored until ENTER
key is pressed.
NOTE: During settings, each press of the key will advance one number. For rapid advance, hold key in.
TO SET CLOCK
Press MODE key until display shows CLK. Press DAY key to select current day. Press HOUR key
to select current hour. Check A (AM) or P (PM). Press MIN key to select current minute. Press ENTER key and the clock is set for current time and day.
Page 2
TO SET SCHEDULE
For convenience, write out your desired schedule on a separate paper.
If display does not show SCH, press mode key until dis­play shows SCH.
The display will Indicate it is ready to receive SCH setpoint #1. Press DAY key to set day(s).
Note: The following is a listing of the sets of days which can be set:
1. M, T, W, TH, F
2. S, SU (Saturday and Sunday only)
3. M, T, W, TH, F, S, SU
4. Individual days: M or T or W or TH or F or S or SU Press HOUR and MIN keys (check for AM or PM). Press
ON/OFF key for appropriate event. Press ENTER key to store the information and display
will indicate it is ready to receive SCH setpoint #2. Proceed for up to 14 setpoints. Then press MODE
key and unit will go to the AUTO (run) mode. In the AUTO mode, the unit will display current time and
day as well as load status (ON and OFF).
Note: When the unit is returned to the auto mode, check the load status of the current setting. If it is showing OFF but should be ON, press the override key. The unit will correct itself at the next scheduled event and no further alteration will be necessary.
REVIEW/MODIFY
1. CLOCK - ALTER TIME Press mode key until display shows CLK. Press DAY, HOUR, and MIN keys to change to the cor-
rect time. Press ENTER.
2. SCHEDULE - REVIEW Press mode key until display shows SCH. Press ENTER key repeatedly to review all the scheduled
entries.
3. SCHEDULE - MODIFY During the review (see previous section) any set point
can be modified or deleted. Use the HOUR, MIN and DAY keys to modify. Use the DELETE key to eliminate that event. Press ENTER key after each modification.
OVERRIDE - TEMPORARY
In order to temporarily change the current ON or OFF status of a load, simply press the override key when the unit is in the AUTO mode. The altered load status will flash. Override is in effect until the next scheduled event. In order to cancel the override, press override key again.
OVERRIDE - LONG TERM
Press mode key until display shows MAN (manual). Normal schedule will not be executed and the load status will remain unchanged as indicated. Press the OVERRIDE key to obtain the correct status or to alter the load status.
Page 3
TORK
DIGITAL TIME SWITCH
EW101 120VAC EW101-2 240VAC EW101-3 277VAC EW101-24 24VAC
OUTPUT: SPST
EW103 120VAC EW103-2 240VAC EW103-3 277VAC EW103-24 24VAC
OUTPUT: DPST
EW120 120VAC EW120-2 240VAC EW120-3 277VAC EW120-24 24VAC
OUTPUT: SPDT
TORK
®
MLI-140(B) 1 GROVE STREET, MT. VERNON, NY 10550 TEL: 914-664-3542
FAX: 914-664-5052
Disconnect power at main panel prior to installing or servicing this time switch or the equipment connected to it.
Install and use in accordance with national and local electrical codes. Supply Connections: Use gauge specified (AWG # 10-16) suitable for 75
degrees C (167 degrees F). Use copper wire only.
Replace insulator before turning on electricity.
Resistive Inductive
Tungsten Pilot Duty
DRY CONTACT RATINGS
Type
of Load
Ballast
470VA
Motor
20A Resistive @ 28VDC
120
VAC
30A 30A 20A 5A
1 HP
240
277
VAC
VAC
30A
12A
30A
12A
6A
6A
5A
5A
470VA
690VA
2 HP
SPST
3
LOAD
DPST
4
356
LOAD
N
TIMER
SUPPLY
1 2
LLN
TIMER
SUPPLY
1 2
DRY CONTACT RATINGS
Type
120VAC
of Load
N.O. N.C N.O. N.C
Resistive
20A
Inductive
20A
Ballast
6A
Tungsten
5A
470
Pilot Duty
VA
Motor
1 HP
N.O. 20A Resistive @ 28VDC N.C. 10A Resistive @ 28VDC
10A 10A 3A 3A
275
240VAC
277VAC
N.O. N.C
20A
10A
6A 10A 3A 3A
275
VA 1/2 HP
TIMER
SUPPLY
1 2
3A
6A
3A
6A
3A
690 VA
SPDT
34 5
LOAD LOAD
20A 6A 5A
470
VA
VA
1/4
2 HP
HP
4
NLN
LOAD
N
LN
N N