TORK MODEL 1102
24 HR. TIME SWITCH
SWITCH: SPST
CONTACT RATINGS:
40 AMP 120-277VAC
20 AMP INDUCTIVE
120-277VAC SINGLE PHASE
40 AMP TUNGSTEN 120VAC
1000VA (120-277) PILOT DUTY
2HP 120VAC; 5HP 240VAC
TIMING MOTOR: 208-277VAC 60Hz
POWER CONSUMPTION:
3 WATTS MAX.
INSTALLATION AND OPERATING INSTRUCTIONS
TO SET ON AND OFF TIMES:
Light trippers turn ON. Dark trippers turn
OFF. Place tripper on dial edge as shown in
figure and set point of each tripper to desired
operating time. CAUTION: Note if selected
time is AM or PM. Hold tripper against dial
edge and firmly tighten knurled screw.
Disconnect power at main panel prior to installing or servicing this
time switch or the equipment connected to it.
Connect in accordance with national and local electrical codes.
Supply Connections: Use gauge specified (AWG # 8-14) suitable for
75 degrees C (167 degrees F)
TO SET DIAL TO TIME: Tur n dial counter-clockwise until correct time is indicated by arrow on nameplate.
FOR MANUAL OPERATIONS: Press down lever on right of nameplate to turn
ON. Press down lever on left of nameplate to turn OFF.
TO REMOVE MECHANISM FROM CASE: Press lever near case latch to
release mainplate and swing the movement out. To replace, insert mainplate projections in slots opposite latch and swing movement in until it latches.
For separate motor terminals,
remove bridge from terminals L & 1.
TORK
®
1 GROVE STREET, MT. VERNON, NY 10550 TEL: 914-664-3542
FAX: 914-664-5052
LI-562(A)
FOR 277 VAC
M
Removable
Bridge
▲
L
1X
2
H
N
FOR 120 VAC
LOAD
OFF TIME
(Dark Tripper)
MANUAL
OFF
LEVER
Dial Calibrations
Knurled Screw
O
F
TORK
F
➤
TIME
ON TIME
(Light Tripper)
MANUAL
O
ON
N
LEVER