NSi Industries 1102 User Manual

TORK MODEL 1102
24 HR. TIME SWITCH
SWITCH: SPST CONTACT RATINGS:
40 AMP 120-277VAC 20 AMP INDUCTIVE
120-277VAC SINGLE PHASE 40 AMP TUNGSTEN 120VAC 1000VA (120-277) PILOT DUTY 2HP 120VAC; 5HP 240VAC
TIMING MOTOR: 208-277VAC 60Hz POWER CONSUMPTION:
3 WATTS MAX.
INSTALLATION AND OPERATING INSTRUCTIONS
TO SET ON AND OFF TIMES:
Light trippers turn ON. Dark trippers turn OFF. Place tripper on dial edge as shown in figure and set point of each tripper to desired operating time. CAUTION: Note if selected time is AM or PM. Hold tripper against dial edge and firmly tighten knurled screw.
Disconnect power at main panel prior to installing or servicing this time switch or the equipment connected to it.
Connect in accordance with national and local electrical codes. Supply Connections: Use gauge specified (AWG # 8-14) suitable for
75 degrees C (167 degrees F)
TO SET DIAL TO TIME: Tur n dial counter-clockwise until correct time is indicat­ed by arrow on nameplate.
FOR MANUAL OPERATIONS: Press down lever on right of nameplate to turn ON. Press down lever on left of nameplate to turn OFF.
TO REMOVE MECHANISM FROM CASE: Press lever near case latch to release mainplate and swing the movement out. To replace, insert mainplate pro­jections in slots opposite latch and swing movement in until it latches.
For separate motor terminals,
remove bridge from terminals L & 1.
TORK
®
1 GROVE STREET, MT. VERNON, NY 10550 TEL: 914-664-3542
FAX: 914-664-5052
LI-562(A)
FOR 277 VAC
M
Removable
Bridge
L
1X
2
H
N
FOR 120 VAC
LOAD
OFF TIME
(Dark Tripper)
MANUAL
OFF
LEVER
Dial Calibrations
Knurled Screw
O F
TORK
F
TIME
ON TIME
(Light Tripper)
MANUAL
O
ON
N
LEVER