NSC Sicherheitstechnik Solution F1 Operating And Installation Manual

NSC Sicherheitstechnik GmbH 1/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
Fire Control Panel "Solution F1"
Operating and Installation Manual
Issue: August 2013
NSC Sicherheitstechnik GmbH 2/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
NSC Sicherheitstechnik GmbH 3/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
Content
1. Description of Control Panel :..................................................................................................... 7
LED indications:..........................................................................................................................7
LC module indications: ............................................................................................................... 8
Description of the push buttons:................................................................................................. 9
2. Menus for the end user :...........................................................................................................10
General Main menu for end user..............................................................................................10
FCP selection ........................................................................................................................... 10
Main menu "Switch on / switch off" ..........................................................................................10
Alarm counter ........................................................................................................................... 11
Changing the end user access code........................................................................................11
Diagnosis Menu........................................................................................................................ 11
Switching on/off: zones and single detectors........................................................................... 12
Switching on/off: OC-Outputs................................................................................................... 12
Switching on/off: 4 internal relays.............................................................................................12
Switching on/off: 3 internal power outputs ............................................................................... 13
Switching on/off: sounders / strobes ........................................................................................13
Switching on/off: Alarm Transmission Device (TD)..................................................................13
Switching on/off: Alarm transmission delay.............................................................................. 14
Switching on/off: Fire outputs................................................................................................... 14
Event memory ..........................................................................................................................14
Detector data............................................................................................................................ 14
Internal Modules (PCBs) : Overview ........................................................................................15
Network data ............................................................................................................................15
Example of Power Supply Voltages .........................................................................................15
Example of Power Supply Status Information..........................................................................16
Example of Power Outputs Voltages........................................................................................16
Example of Input voltages ........................................................................................................ 16
Example of displaying software version and Serial No............................................................ 16
Switching on/off: Addressable detectors.................................................................................. 17
Event memory: "Filter"..............................................................................................................17
Event memory: "Printing".......................................................................................................... 17
Table of detectors..................................................................................................................... 17
Internal Modules (PCBs): Details .............................................................................................20
Display of network adapters..................................................................................................... 20
Modem data..............................................................................................................................20
Display of FRP/LCD Panel ....................................................................................................... 21
Display of Modbus devices.......................................................................................................21
Details of network devices........................................................................................................21
Detector details of network devices..........................................................................................22
Example of detector data: MCP ...............................................................................................22
Example of detector data: Optical smoke detector .................................................................. 23
Example of detector data: Listec heat sensor cable SEC15.................................................... 24
Example of loop card details ....................................................................................................24
Example of details of a fire brigade repeater panel with fire brigade control panel ................. 24
Only for Hochiki ESP............................................................................................................... 24
Only for Apollo Discovery ......................................................................................................... 25
Only for Hochiki ESP............................................................................................................... 24
Example of "Zero point" and "Fire point" display...................................................................... 24
Only for Apollo Discovery ......................................................................................................... 25
3. Installer menus: ........................................................................................................................26
Access to the installer menu ....................................................................................................27
General Main menu for installer ...............................................................................................27
Main menu: Test functions .......................................................................................................28
Main menu: Automatic Controlling ...........................................................................................28
NSC Sicherheitstechnik GmbH 4/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
Main menu: Alarm configuration...............................................................................................28
Settings 1 of FCP .....................................................................................................................29
Settings 2 of FCP .....................................................................................................................29
Settings 3of FCP ......................................................................................................................30
Detector test (only for addressable detectors)......................................................................... 30
Menu "Manual Controlling"....................................................................................................... 31
Menu "Simulation" .................................................................................................................... 31
Menu "Revision" ....................................................................................................................... 31
Automatic Control: internal OC Outputs................................................................................... 32
Automatic Control: 4 internal Relays........................................................................................32
Automatic Control: 3 monitored Power outputs........................................................................ 32
Automatic Control: Output modules (loop)............................................................................... 32
Automatic Control: Input modules (loop)..................................................................................33
Automatic Control: 8 resistor monitored Inputs........................................................................ 33
Automatic Control: 2 monitored, conventional inputs...............................................................34
Select the kind of detectors to configure: Loop or conventional .............................................. 34
Detector settings.......................................................................................................................34
Zone settings............................................................................................................................ 34
Zone Alarm Coincidences ........................................................................................................35
Timer programs ........................................................................................................................ 35
Delay times of Main alarm (TD)................................................................................................36
To set date and time................................................................................................................. 36
To configure Holidays............................................................................................................... 37
System settings ........................................................................................................................ 37
Scan detectors..........................................................................................................................39
Delete Configuration................................................................................................................. 39
Delete Texts .............................................................................................................................39
Delete Events ........................................................................................................................... 39
Configuring macro push buttons S1 – S8.................................................................................39
Changing the installer access code..........................................................................................40
Selecting the panel language................................................................................................... 40
Configuring the interfaces ........................................................................................................40
Alarm and fault thresholds for conventional detectors............................................................. 40
Scanning RS485 devices .........................................................................................................41
Modem functions ...................................................................................................................... 41
Network settings....................................................................................................................... 41
Flash Update ............................................................................................................................ 42
Power outputs: Thresholds....................................................................................................... 42
Loop parameters ......................................................................................................................43
Options ..................................................................................................................................... 43
ESPA 4.4.4 Settings................................................................................................................. 43
Arcnet Baud rate.......................................................................................................................44
Sections.................................................................................................................................... 44
Network sections ...................................................................................................................... 44
FRP protocol sections ..............................................................................................................44
Webserver Settings .................................................................................................................. 44
Manual Control: internal OC Outputs....................................................................................... 45
Manual Control: 4 internal Relays ............................................................................................45
Manual Control: 3 monitored Power Outputs........................................................................... 46
Manual Control: Output modules (loop) ................................................................................... 46
Automatic Control: Settings for outputs.................................................................................... 46
Automatic Control: Functions ...................................................................................................47
Selection of displaying cause and effect events ...................................................................... 47
Automatic Control: Settings for output modules (loop)............................................................. 48
Automatic Control: Settings for sounders/ sounder modules (loop).........................................48
Automatic Control: Settings of 8 internal monitored inputs...................................................... 49
Configuring zones (loop) ..........................................................................................................49
Configuring conventional zones ...............................................................................................50
NSC Sicherheitstechnik GmbH 5/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
Analogue addressable detector’s sensitivity / modes / delays................................................. 50
To configure timer programs ....................................................................................................52
Interface protocols.................................................................................................................... 52
Interface baud rates..................................................................................................................53
Configuring thresholds for conventional detectors................................................................... 53
Maintenance............................................................................................................................. 53
Push button S_ settings............................................................................................................53
Zone LEDs................................................................................................................................53
Configuring the timer ................................................................................................................ 54
Cause and Effect events list..................................................................................................... 54
Cause and Effect events configuration..................................................................................... 54
Event codes.............................................................................................................................. 55
4. Mounting instruction .................................................................................................................57
5. Commissioning certificate FCP "Solution F1" ..........................................................................58
General..................................................................................................................................... 58
Checking the documentation.................................................................................................... 58
Checking the system components ...........................................................................................58
Checking the wiring system......................................................................................................59
Measure end of line resistors of conventional zones (without voltage)....................................59
Measure cable resistance of loop wiring (without voltage)....................................................... 59
Measurement of the end of line resistors of the monitored power outputs (without voltage)... 60
Measurement of the end of line resistors of the monitored inputs (without voltage)................ 60
Checking the end of line resistor on the RS485 bus................................................................ 60
Commissioning of the power supply.........................................................................................60
Scanning of internal an external components.......................................................................... 61
Detector modules .....................................................................................................................61
Serial devices ........................................................................................................................... 61
Addressable detectors/modules............................................................................................... 62
Checking of earth fault..............................................................................................................63
Measurement of loop voltage and current................................................................................ 63
Configure power outputs ..........................................................................................................64
Configuration of the fire control system.................................................................................... 64
Functional tests ........................................................................................................................65
6. Technical specifications:...........................................................................................................66
Power Supply ...........................................................................................................................66
Common technical data............................................................................................................ 67
Minimum/ maximum voltages/currents..................................................................................... 68
Fuse values .............................................................................................................................. 68
Cable parameter....................................................................................................................... 68
7. CE marking:.............................................................................................................................. 69
NSC Sicherheitstechnik GmbH 6/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
NSC Sicherheitstechnik GmbH 7/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
1. Description of Control Panel :
Picture of the control panel of the "Solution F1":
LED indications Dynamic functions keys F1 – F4,
Field programmable push buttons S1 – S8
The functions is individually indicated and mounting place for printer in the bottom line of the LC module
Key ‘Prog’: to select the main menu Keypad and cursor push buttons Key ‘external sounders off / on’ Key ‘internal buzzer off"// "LED test’ Key ‘Reset
LED indications:
LED : Description :
green LED "In Operation" The Fire Control Panel (FCP) is in operation. green LED "Day Mode" Indicates that the FCP is in "Day Mode". That means
the main alarm is delayed if a delay time is configured.
green LED "Night Mode" Indicates that the FCP is in "Day Mode". That means
the main alarm is NOT delayed and any alarm
activates the Fire Brigade immediately. green LED "Service" Indicates that the FCP is in "Service Mode". red LED "Main alarm" Indicates that the FCP is in Alarm condition. See LC
module for detailed information. If an alarm
transmission device (TD) is connected to the panel the
panel has tried to activate the TD. red LED "Internal alarm" Indicates that the FCP is in Alarm condition. See LC
module for detailed information. red LED "Fire Brigade alarmed" Indicates that the FCP has activated the alarm
transmission device (TD) to the Fire Brigade and the
TD gave a response to confirm the activation. (Input
NSC Sicherheitstechnik GmbH 8/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
"TD response” in the wiring diagrams can be used for
this confirmation signal). red LED "Fire Protection Equipment" Indicates that the FCP has activated one ore more fire
outputs. Fire outputs are outputs which are configured
to the "Fire outputs" on/off function. yellow LED "Fault" Indicates that the FCP is in fault condition. At least one
device (detector, module), input, output or system
component is not in normal condition. See LC module
for detailed information. yellow LED "Disabling" Indicates that at least one device (detector, module),
input or output is disabled (switched off). yellow LED "Transmission Device" (TD) In case of flashing this LED (and yellow LED "Fault" is
on) the TD is in fault condition.
In case this LED is on (and yellow LED "Disabled" is
on) the TD is switched off. yellow LED "Sounders" In case of flashing this LED (and yellow LED "Fault" is
on) one of the sounder outputs is in fault condition.
In case this LED is on (and yellow LED "Disabled" is
on) one of the sounder outputs is switched off. yellow LED "System"
The FCP itself is in fault condition. That means that
maybe the main board (micro controller) does not
work well and the correct function of the FCP is
not guaranteed. Please check immediately by the
installation company.
LC module indications:
The LC module is a graphics LCD which is automatically illuminated in the case of any event. That means if an alarm message, a fault message, a disabled message or just if any push button is pressed the LC module activated the illumination. Then detailed information is shown in the display. Either the LCD shows the information in 8 lines of alpha numerical texts or in a graphics mode like bar charts or columns.
Usually the FCP shows the condition of the panel in the middle of the LC module. There is in big letter the current status on a dark background. The following messages are possible :
IN OPERATION = normal condition ALARM = the FCP is in alarm condition T E S T ALARM = the FCP is in test alarm condition FAULT = the FCP is in fault condition SWITCH OFF = one or more devices of the FCP are switched off ACTIVATION = one or more outputs of the FCP are activated
If the user enters one of the menus (by pressing the push button "Prog") at the bottom line of the LC module he sees the dynamic function keys F1 – F4. Sometimes all 4 keys are used, sometimes only
NSC Sicherheitstechnik GmbH 9/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
one or two. It depends on the menu. Here we do not describe the function keys in details. Therefore please have a look into section 2.
Please note that : usually there are the following standard functions for
"F1" = "cancel" or "back". Means to leave the current menu and jump into the menu
above, and
"F4" = "Enter". Means to select (or confirm) the function which is marked in the LC
module by a black background.
Description of the push buttons:
The control panel of the FCP "Solution F1" contains a brand new technology of push buttons. There are no more mechanical push buttons or ordinary foil key pads but it is a pressure sensitive piezo lacquer technology which is printed on the aluminum plate. These push buttons must not be
adjusted and this technology has not known any attrition or abrasion for many years and it is very resistant to EMC interferences and detergents. An intelligent circuit detects any pressing of
the push buttons and confirms it by a beep.
The push buttons which are maybe not self-explanatory are these:
Push button : Description :
By this push button the user leaves the normal operation and enters the main menu of the FCP. See the detailed description in section 2.
This push button deactivates (switch off) the external sounder outputs in case of an alarm. This is a temporary deactivation because if another alarm comes in the sounders will be activated again.
This push button deactivates (switch off) the internal buzzer in case of an alarm or fault message. This is a temporary deactivation because if another message comes in the buzzer will be activated again.
In case of an alarm and if the alarm transmission is delayed, the delay time will be started.
If there is no alarm and no fault this push button activates an LED test.
This push button resets the FCP. In case of a key deposit alarm message you have to put in the installer code at first and afterwards press this button.
Field programmable push buttons (S1 – S8). See detailed description in the installer manual.
Use this push button in the menus to confirm your inputs line by line.
Use this push button in the menus to cancel your inputs.
Cursor control keypad.
NSC Sicherheitstechnik GmbH 10/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
2. Menus for the end user :
The following description contains all the menus for the end user. If the push button "Prog" is pressed it starts with the main menu.
No. Indication of the LC module : Description :
01
Main menu
1. Switch on/off
2. Alarm counter
3. End user code
4. Diagnosis
Cancel Installer Enter
Display on network devices
Main menu FCP 001
1. Switch on/off
2. Alarm counter
3. End user code
4. Diagnosis
Cancel FCP Installer Enter
General Main menu for end user
This menu appears immediately after pressing "Prog". The functions have the followings meanings :
1. To switch on / off detectors, input-/ output modules, day/night mode, zones and general outputs Jump to Menu 02
2. Indication of the alarm counter. This alarm counter cannot be set back. It is a 4 digit number (1 – 9999) Menu 03
3. To change the end user code Jump to Menu 04
4. To jump to the diagnosis menu Jump to
Menu 05
The push button "cancel" (F1) leads to the normal status indication of the FCP.
The function "FCP" (F2) is only available in networked fire control panels. After pressing F2 a list of all networked devices appears Menu 1.1 .
The push button "Installer" (F3) is to use for the installer company only. It leads to the menus for service and configuration.
The push button "Enter" (F4) selects (activates) the function which is marked by a black background. Instead you can also select the function by pressing the no. left in front of the functions (here : 1 – 4).
01.1
choose active device FCP 001 : ID- 001 +1 -1 Selection -> +10 <- -10 >FCP 001* Zone offset 10000 001< FCP 002 Zone offset 20000 002 RCP 003 Zone offset 00000 003
Cancel all Selection
FCP selection
On networked systems here you can choose a device for which the next switching function should be done.
You can scroll to a device by the cursor buttons and then activate this device by pressing "Selection" (F4). The next enable/disable function then will be executed for the chosen panel. To send a common command to all network devices you can push "all" (F3).
02
Switch on/off
1. Zones & detect. 5. Sounder/Strobe
2. Output 6. Alarm Transm
.Dev
3. Relay
7. Delay
4. Power Output
8. Fire Outputs
Cancel Enter
Main menu "Switch on / switch off"
1. Switching on/off of zones and detectors Jump to Menu 06
2. Switching on/off of OC-Outputs Jump to Menu 07
3. Switching on/off of Relays inside the FCP Jump to Menu 08
4. Switching on/off of 3 monitored power outputs Jump to Menu 09
NSC Sicherheitstechnik GmbH 11/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
Display on network devices
Switch on/off
1. Zones & detect. 5. Sounder/Strobe
2. Output
6. Alarm Trans.Dev.
3. Relay
7. Delay
4. Power Output
8. Fire Outputs
Cancel FCP Enter
5. Continuously switching on/off of sounders / strobes (incl. loop sounders) Jump to Picture 10
6. Switching on/off the alarm transmission device (TD) Jump to Picture 11
7. To activate / deactivate the alarm delay for the TD Jump to Picture 12
8. Temporary switching on/off the fire outputs. This means all outputs will be deactivated until this function is canceled Jump to Picture
13
The function "FCP" (F2) is only available in networked fire control panels. After pressing F2 a list of all networked devices appears Menu 1.1 .
03
Alarmcounter
FCP - Alarm : 0025 Testalarm : 0011
Network - Alarm : 0033 Testalarm : 0017
Cancel
Alarm counter
This alarm counter cannot be set back. It is a 4 digit number (1 – 9999). Test alarms (Detector test/revision) will be displayed by a separate counter. The lower two rows only will be displayed in networked systems. Here the Alarms and test alarms of other devices in the network will be counted.
04
End user
old access code : 0000 new access code : 3528
new access code : 3528
Cancel
Changing the end user access code
First you have to type the old access code, then you have to type two times the new access code.
Every line has to be confirmed with "OK". Example left side : old access code 0000 is replaced by
new access code 3528.
05
Diagnosis
1. Event memory 5. Voltages
2. Detector data 6. Power Outputs
3. Internal Modules 7. Inputs
4. Network 8. FCP data
Cancel Enter
Diagnosis Menu
1. To display the event memory on the LCD. The youngest message will be displayed first. Jump to Menu 14
2. To analyze the zones and detector data. A list of all zones with detectors will be displayed. You can investigate in the details Jump to Menu 15
3. A list with possible types of internal modules (PCBs) will be displayed Jump to Menu 16
4. Here a list of all recognized network devices will be displayed -> Jump to Menu 17.
5. A list will be displayed with real time measurements of power supply voltage and earth fault voltages. You can check power supply and earth fault messages here Example in Picture 18
6. A list will be displayed with real time measurements of the monitored power outputs. You can check fault messages here Example in Picture 19
7. A list will be displayed with real time measurements of the 8 monitored inputs. You can check fault messages here Example in Picture 20
8. To display FCP Software version and Serial
no. Example in Picture
21
NSC Sicherheitstechnik GmbH 12/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
06
Zones & detect. FCP 001
Status
from zone : 5
programmed zone text
To zone :
Cancel On Off Detect.
Switching on/off: zones and single detectors
You can switch off single zones or several zones simultaneously. This is done by using the "from … to… " function. Please type the zone number and confirm by "OK”. "Status" means the current status of the zone (e.g. normal, alarm, fault). To switch off the zone you have to press "Off" (F3) or for switching on the zone you have to press "On" (F2).
If only one zone shall be switched the line "to zone" can be missed and F2/F3 (on/off) can be pressed immediately. If single detectors shall be switched you have to type "Detect.” (F4) after the zone has been confirmed (do not use F2/F3 (on/off) in this case) Jump to Menu 22
07
Switch on/off RCP 003 from output : 001 normal to output : +1 -1 Selection -> +10 <- -10
>001 Output 001 Main processor
002 Output 002 Main processor
003 Output 003 Main processor
Cancel On Off Enter
Switching on/off: OC-Outputs
Here the 16 OC-outputs on the main processor board of the FCP "Solution F1” as well as the OC-outputs on the loop cards can be switched on/off.
The outputs are located like this : Outputs 1 – 16 : OC- Outputs on main board Outputs 17 – 24: OC- Outputs on 1. loop card Outputs 25 – 32: OC- Outputs on 2. loop card etc.
To switch on/off the outputs there are two possibilities you can choose :
a) To type the output no. directly by the key pad
and confirming with "OK". Please use the line "from output” and "to output” for this.
b) Select the outputs by using the cursor keys ↓
and ↑ (means 1 line up or 1 line down) or the cursor keys and (means 10 lines down or 10 lines up) and confirm the output numbers with "Enter" (F4) or "Ok”.
The actual "status" of the output (e.g. normal condition or active) will be displayed behind the number.
After selecting the output / outputs you have to switch them by pressing F3 ("off") or F2 ("on").
08
Switch on/off FCP 001 from relay : 001 normal to relay : +1 -1 Selection -> +10 <- -10
>001 Relay 001 Main processor
002 Relay 002 Main processor
003 Relay 003 Main processor
Cancel On Off Enter
Switching on/off: 4 internal relays
Here the 4 internal relays on the main processor board of the FCP "Solution F1” can be switched on/off.
To switch on/off the relays there are two possibilities you can choose :
a) To type the relay no. directly by the key pad
and confirming with "OK". Please use the line "from relay” and "to relay” for this.
b) Select the relays by using the cursor keys ↓
and ↑ (means 1 line up or 1 line down) or the cursor keys and (means 10 lines down or 10 lines up) and confirm the relay numbers with "Enter" (F4) or "OK”. Then press "Enter" (F4) to confirm the switching.
NSC Sicherheitstechnik GmbH 13/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
The actual "status" of the relay (e.g. normal condition or active) will be displayed behind the number.
After selection the relay / relays you have to switch them by pressing F3 ("off") or F2 ("on").
09
Switch on/off FCP 001 from power output : 001 normal to power output : +1 -1 Selection -> +10 <- -10
>001 Power Output 001 Main processor
002 Power Output 002 Main processor
003 Power Output 003 Main processor
Cancel On Off Enter
Switching on/off: 3 internal power outputs
Here the 3 internal power outputs on the main processor board of the FCP "Solution F1” can be switched on/off.
To switch on/off the relays there are two possibilities you can choose :
a) To type the power output no. directly by the
key pad and confirming with "OK". Please use the line "from power output” and "to power output” for this.
b) Select the power outputs by using the cursor
keys ↓ and ↑ (means 1 line up or 1 line down) or the cursor keys and (means 10 lines down or 10 lines up) and confirm the power output numbers with "Enter" (F4) or "OK”.
The actual "status" of the power output (e.g. normal condition, fault or active) will be displayed behind the number.
After selection the power output / power outputs you have to switch them by pressing F3 ("off") or F2 ("on").
10
Switch on/off FCP 001
1. Zones & detect. 5. Sounder/Strobe
2. Output 6. Alarm Transm
.Dev
3. Relay
7. Delay
4. Power Output 8. Fire Outputs
Cancel off
Switching on/off: sounders / strobes
After selecting this function in the switch on/off main menu you see at the bottom line of the LCD "off" (F3) or "on" (F2).
By pressing F3 all sounders / strobes will be switched off continuously.
Pay attention : By the function (F3) all sounders and strobes will
be switched off continuously. If another alarm comes in the sounders / strobes will not be activated again until they are switched on again.
11
Switch on/off FCP 001
1. Zones & detect. 5. Sounder/Strobe
2. Output 6. Alarm Trans.Dev.
3. Relay 7. Delay
4. Power Output 8. Fire Outputs
Cancel off
Switching on/off: Alarm Transmission Device (TD)
After selecting this function in the switch on/off main menu you see at the bottom line of the LCD "off" (F3) or "on" (F2).
By pressing F3 the Alarm transmission device will be switched off continuously.
The current status of the TD will additionally indicated by the yellow LED on the control panel.
NSC Sicherheitstechnik GmbH 14/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
12
Switch on/off FCP 001
1. Zones & detect. 5. Sounder/Strobe
2. Output 6. Alarm Transm
.Dev.
3. Relay 7. Delay
4. Power Output 8. Fire Outputs
Cancel on
Switching on/off: Alarm transmission delay
Here the delay of the alarm transmission device of the FCP "Solution F1” can be switched on/off.
After selecting this function you see at the bottom line of the LCD "off" (F3) or "on" (F2). "On” means to activate the delay (Day Mode)
The current status of the delay will be additionally indicated by the green LEDs (Day Mode, Night Mode) on the control panel. When the delay is activated there is an additional indication in the LC module ("Delay activated”)
Pay attention : To switch on the delay of the alarm transmission device is only possible if "Response time” and "Inspection time” in the menus "Alarm configurat. ­> Delay” is configured. This can only be done by the installer company.
13
Switch on/off FCP 001
1. Zones & detect. 5. Sounder/Strobe
2. Output 6. Alarm Transm
.Dev.
3. Relay
7. Delay
4. Power Output 8. Fire Outputs
Cancel off
Switching on/off: Fire outputs
This function disables in case of an alarm all outputs which have been configured with "yes" in the menu "Automat. Controlling" Selection 1 to 4 "Settings" "Operate like Fire Output".
These could be 3 internal power outputs, all OC­outputs, 4 internal relays and all loop output modules. After selecting this function you see at the bottom line of the LCD "off" (F3) or "on" (F2).
Pay attention : By the function (F3) all fire outputs will be switched off continuously. If an alarm comes in no output will be activated.
14
Event memory Message 00001 of 00391 Fault
Power output 001 wire break
08-07-2011 18:25:22 Cancel Filter print
Event memory
The last message (the youngest) is shown first in the upper area of the LC module. In the last but one line of the LCD data and time of the message are shown. This is the time when the event has appeared.
You can scroll with the cursor keys up and down the messages :
and : 1 line up or 1 line down
und : 10 lines down or 10 lines up By pressing F2 ("Filter") Jump to Menu 23 By pressing F3 ("print") Jump to Menu 24
15
Zone | existing | config.
> 0001 | 010 | 010
0002 | 010 | 010
0003 | 011 | 107
0004 | 003 | 127
0005 | 010 | 010
0006 | 021 | 117 Cancel Segment Details
Detector data
Here the zones which contain at least one detector are listed line by line (left column).
The middle column shows the number of detectors which were found during last loop scanning.
The right column "config." shows the number of
NSC Sicherheitstechnik GmbH 15/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
Segment | existing | Current
> 01 | 024 | 008,4mA
02 | 031 | 010,9mA
03 | 068 | 023,8mA
04 | 044
| 015,4mA
| |
| | Cancel Zone Details
detectors which were configured by configuration software or by manual operating on the control panel.
Ideally the numbers in the middle and right columns should be identical.
By pressing key F3 "Segment", the display will change to a list of segments with number of connected devices and current on each segment. Please select with the cursor keys the zone/segment which should be investigated more detailed and press "Details" (F4) Jump to Menu 25
16
Internal Modules
1. Loop card HOCHIKI ESP : 01
2. Loop card Apollo XP : 00
3. Conventional detector card : 00
4. Input-/output module : 00
Cancel Details
Cursor key "" show more :
5. Network interface card : 00
6. Modem : 00
7. RS485 device : 00
8. Modbus device : 00
Internal Modules (PCBs) : Overview
Here all possible types of internal modules (PCBs) are listed and behind them you can see how many modules are installed in the FCP (here: only 1 pc. Loop card Hochiki ESP).
These types of modules are possible (depending on software version) :
Loop card supporting Hochiki ESP detectors Loop card supporting Apollo XP95/Discovery
detectors
Conventional detector card Input- / Output module ARCNET network card Modem/Web server RS485 devices (LCD repeater panel) Modbus devices (Listec SCU800)
Please select with the cursor keys the module which should be investigated more detailed and press "Details" (F4) Jump to Menu 26
17
ID-| Type | Zone offset |Mode >001|FCP 001 | 01000 |Day *< 002|FCP 002 | 02000 |Night
003|RCP 001 | 00000 |Night
004|FCP 000 | 00000
|Night
005|FCP 000 | 00000 |Night
006|FCP 000 | 00000 |Night Cancel Details
Network data
Here you see a list of all network devices. The consecutive number corresponds to the configured network-ID of the device. In the column Type the device type and the device number will be displayed. The next column shows the configured Zone offset for each device. This zone offset will be added to the original zone number in case of messages from detectors/zones, if the display system for the network is configured to zone offset. The mode (day or Night) specifies, at which devices the delay for the transmission device is active or not. You can scroll through the list of network devices using the cursor keys. The * marks the device you are actual working on. By pressing "Details" (F4) you will get further information about the selected device Jump to Menu 27
18
Voltages
Power supply voltage : 28,15 V Battery charg. voltage : 27,72 V Pow. supply batt.volt. : 27,57 V Earth fault voltage : 1,57 V RTC battery : 3,07 V
Cancel Details
Example of Power Supply Voltages
The charging voltage should be in between 27,3V and 27,8V (20°C). This should be checked by voltage meter.
The nominal earth fault voltage should be 1,5V -1,7V. In case of any earth fault there will be a deviation of that voltage. By system parameter "earth fault threshold" you can define the threshold for earth fault recognition. "0" means highest sensitivity, "10" means lowest sensitivity for fault message display.
NSC Sicherheitstechnik GmbH 16/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
The RTC battery should be replaced, if the voltage drops below 2,1V. Leaving the menu by pressing F1 ("Cancel"). Further information by pressing F4 ("Details").
18.1
Power supply
S001A00.07
xx | xx | xx | xx |AcV |AcRi|AcE |Temp
- | - | - | - | OK | OK | OK | OK |
F1 | F2 | F3 | F4 | xx | xx |NT+ |NT- | OK | OK | OK | OK | - | - | OK | OK | actual temperature: 22,5°C Ri: 0037mOhm
Cancel
Example of Power Supply Status Information
First line shows firmware version of the power supply module. Status information is displayed according following table:
The values in parenthesis give information about faulty status, displayed as "F" instead of "OK". Additionally the actual temperature and the internal battery resistance will be displayed.
AcV battery low voltage (<21V) AcRi
battery internal resistance (> 400m) AcE information about battery shut down Temp high temperature (>50°C) F1 - F4 fused 24VDC output 1-4 NT+ high voltage power regulator NT- mains fault, low voltage power regulator
19
Power outputs No.: Volt Th.SC R-Act. Th.OC(Cal.) 1 : 1,89V 0735< 0994 <1117 (0997) Ohm
2 : 1,89V 0735< 0994 <1117 (0997) Ohm
3 : 1,89V 0735< 0994 <1117 (0997) Ohm
Cancel
Example of Power Outputs Voltages
following data of power outouts will be displayed:
output voltage (Volt)
short circuit threshold (Th.SC)
actual resistance (R-Act.)
open circuit threshold (Th.OC)
resistance of last calibration (Cal.)
Leaving the menu by pressing F1 ("Cancel").
20
Inputs
> 01. Input 01 : 03,04V
02. Input 02 : 03,04V
03. Input 03 : 03,05V
04. Input 04 : 03,07V
05. Input 05 : 03,03V
06. Input 06 : 03,06V Cancel
Example of Input voltages
In this menu voltages of the following inputs will be displayed:
Input 1-8
Monitored input KDB
Monitored input Ext. system
Feedback input 1 and 2
Leaving the menu by pressing F1 ("Cancel").
21
FCP data
Software version S040A12.00 Serial number 2909
/0067
S1 S2 S3 S4 S5 S6 S7 S9
Cancel
Example of displaying software version and Serial No.
Additionally the status of the special function keys is displayed. In this example key "S2" is active.
Leaving the menu by pressing F1 ("Cancel").
NSC Sicherheitstechnik GmbH 17/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
22
Zone 0005
Status
from detector : 1 normal evt. individual detector text
to detector : 3 normal
evt. individual detector text
Cancel On Off
Switching on/off: Addressable detectors
The first line of the LC module shows the zone where the detectors are located (here : 5).
It is possible just to switch off only one detector as well as several detectors. Please type the detector number and confirm by "OK”. "Status" means the current status of the detector (e.g. normal condition, alarm condition, fault condition). If a individual detector text has been configured, this text will be displayed right below the detector line after pressing "OK”.
For switching off you have to press "Off" (F3) or for switching on you have to press "On" (F2).
If only one detector shall be switched the line "to detector" can be missed and F2/F3 (on/off) can be pressed immediately.
23
Filter
1. Alarm x 5. Off -
2. Pre alarm x 6. Activation -
3. Test alarm - 7. Event memory x
4. Fault -
Cancel on
Event memory: "Filter"
The FCP Solution F1 saves all messages in their event memory.
This filter functions allow displaying only certain kind of messages in the LC module (e.g. only alarm messages). There are 6 different kinds of messages, which can be displayed in the LC module. If a message is marked with "x" this message will be displayed. If it is marked with "-" this message will not be displayed. You can switch from "x" to "-" by push button F3
("off”) and from "-" to "x” by push button F2 ("on”). Attention! If the filter for "event memory" is active filtered messages will not be sent to other network devices!
The example on the left side shows only alarm and pre alarm messages but all other kind of message are hidden.
24
Event memory
from message :
to message :
Cancel print
Event memory: "Printing"
Please type the number of messages and confirm every line by "OK": The last (youngest) message is message no. 1 and the oldest one is message no.
1034. After selecting the messages press F4 ("print") for printing. The print goes out through the interface which is selected by menu "Settings 2" -> "Interfaces".
25
Zone 0003 Detect. 002/010 No. |Type |Seg.|Add|Status 0
01|Conv. mo. CHQ_MZ|01:o|001|Normal
>002|Flashl.
CHQ_AB|01:o|002|Normal
003|Ion. det. AIE_E |01:o|003|Normal
004|opt. det. ALG_E |01:o|004|Normal
005|Conv. mo. CHQ_Z |01:o|005|Normal Cancel existing Details
Table of detectors
The first line of the LC module shows zone and number of the detector which is marked by ">" in the left column of the display area. Here in this example it is zone 0003 and detector 002 of 10 detectors in this zone at all.
The second column shows all configured detectors of this zone by name (abbreviated), doesn’t matter if they are connected to the panel or not. If you want to see only the connected detectors of this zone press
NSC Sicherheitstechnik GmbH 18/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
"existing" (F2). In this case the bottom line changes and "config." is written above F2. Additionally the number of detectors in line 1 will change, if there is a difference between connected and configured detectors for this zone. Pressing F2 again will show all configured detectors again.
One detector is shown per line. The grey line have the following meanings :
No. : Detector number within the displayed zone Type : Kind of detector, e.g. optical, MCP etc. This
information is automatically transmitted by the detectors to the FCP. The meanings of the abbreviations are :
1. Hochiki ESP
opt. det. ALG-EN Optical smoke detector Ion. det. AIE-E Ionisation smoke detect. Heat det. ATG-E Heat detector Multisen. ACA-E Multisensor Multisen. ACB-E Multisensor Heat MCP HCP-E Manual Call Point Sounder YBO-BS Sounder YBO-BSB Sounder CHQ-WS2
Base Sounder Base Sounder Beacon
Wall Sounder Sounderm. CHQ-DSC Sounder output module Inp.mod. CHQ_DIM Input module Zone mod.CHQ_SZM Mini convention. module Zone mod.CHQ_Z Conventional module Inp/Outp. CHQ_MRC Input-/output module Inp/Outp. CHQ_DRC Input-/output module Inp/Outp. CHQ_FIO Input-/output module Strobe CHQ-AB Addressable strobe Remote CHQ-ARI Addressable remote
indicator Ad. Sock. YCA_3H2 Addressable base Ad. Sock. YCA_5H2 Addressable base Inp/outp. CHQ-POM current controlled output Inp/outp. YBO-POM current controlled output CHQ-FIO-NT PSU monitoring CHQ-SIM Input module CHQ-PCM Input-/output module Stratos ASD System ASD control module
2. Apollo Discovery/XP95/Xplorer
opt. det. DISCOV. Optical smoke detector Ion. det. DISCOV. Ionisation smoke detect. CO detect.DISCOV. Co detector Heat det. DISCOV. Heat detector Multisen. DISCOV. Multisensor MCP DISCOV. Manual Call Point Sounder/Beacon DISCOV.
Sounder/Flash
Voicesounder DISCOV.
Voice Sounder
Voicesounder/Beac on DISCOV.
Voice Sounder/Flash
opt. det. XP95 Optical smoke detector
NSC Sicherheitstechnik GmbH 19/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
Ion. Det. XP95 Ionisation smoke detect. Heat det. XP95 Heat detector H.Thermo. XP95 Heat detector high
temperatur Multisen. XP95 Multisensor MCP XP95 Manual Call Point Sounderm. XP95 Sounder output module Inp.mod. XP95 Input module Zone mod. XP95 Conventional module Inp/Outp. XP95 Input-/output module Flame det. XP95 Flame detector Beam XP95 Beam detector Ref.Beam XP95 Beam detector with
reflector opt. det. XPlorer Optical smoke detector Heat det. XPlorer Heat detector H.Thermo. XPlorer Heat detector high
temperatur Sounder S90 Sounder output module IO S90 Input-/output module Ion. S90 Ionisation smoke detect. Zone S90 Conventional module Opt. S90 Optical smoke detector Thermo S90 Heat detector MCP S90 Manual Call Point
Seg. : Segment = Section of addresses with a
maximum of 254 Hochiki detectors, modules / base sounders and a maximum of 126 Apollo detectors, modules. The segments are partitioned on the loop card according this list :
Loop card 1 : Segment 1 and 2
Loop card 2 : Segment 3 and 4
Loop card 3 : Segment 5 and 6
Loop card 4 : Segment 7 and 8
Loop card 5 : Segment 9 and 10
Loop card 6 : Segment 11 and 12
Loop card 7 : Segment 13 and 14
Loop card 8 : Segment 15 and 16
Loop card 9 : Segment 17 and 18
o
: This is a symbol for a loop.
-
: This is a symbol for a stub line.
Adr. : Detector address (physical address stored
in the detector)
Status : Current status of the detector (e.g. normal
condition, alarm condition, fault condition, disabled condition)
By pressing F4 ("Details") it is possible to display more details of the detectors. That means analogue values, dust contamination, input bits and so on.
Jump to Picture 27 for Manual Call Points Jump to Picture 28 for optical smoke detector
NSC Sicherheitstechnik GmbH 20/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
26
Internal Modules 01/09 >01 Loop card HOCHIKI ESP
02 Conventional detector card
03 - 04 - 05 - 06 - Cancel Details
Internal Modules (PCBs): Details
The FCP displays the physically installed internal modules (PCBs) with their addresses (1-9). These are the addresses of the DIL switches on the PCBs.
Please select by the cursor keys the PCB which shall be investigated more detailed and press F4 ("Details") Jump to Picture 29
26.2
Arcnet 1 Arcnet 2
Station ID : 001 | 001
Next ID : 002 | 002
Receive : OK | OK
Token seen : OK | OK Send : OK | OK
Counter Reconfig.: 000 | 000
Cancel
Display of network adapters
Installed network adapters will be dispayed with the following informations:
Station ID (1-255) is the network number of the device (device no. set in the network configuration Menu 81).
Next ID (1-255) is the device number, to which the token will be passed.
Receive (OK or F) shows, if the network card is receiving data from another device.
Token seen (OK or F) shows, if the network card has seen the token even if it doesn’t take part at the network communication.
Send (OK or F) shows activity of the driver for sending.
Counter Reconfig. counts, how often this card initiated a network reconfiguration. Comparing this counter with other devices gives information about a damaged network component.
26.3
Display for analogue modem
Modem Call accept off
56000 P2109-V90 INSYS SmartSCM FD RCV56DPF-PLL L8
Cancel Details
Display for webserver module
Webserver NSC Webserver V03.03 IP-Address 192.168.0.127 Netmask 255.255.255.0 Network 192.168.0.0# Gateway 192.168.0.254# CONNECT Cancel
Modem data
If a telephone modem has been installed on the main board, this menu displays different information, dependant of the modem type (analogue, ISDN, Ethernet). Here you see as an example the data of the analogue modem.
Line 2: Product code Line 3: Firmware version Line 4: Modem version Line 5: Country code (FD=Europe) Line 6: Version of "Data pump"
In line 1 the actual modem status will be displayed. The modem only accepts an incoming call, if the automatic call acceptance has been activated in the Details menu (same as Menu 80) or in the installer Menu 80.
In the diagnosis menu for the webserver module the firmware version will be displayed. Below you see the network settings. The '#' sign says that settings for "Network" and "Gateway" are disabled. These parameters can be activated by the configuration software easily. Then the '#' sign won't be displayed anymore. The "Network" setting usually won't be used. "Gateway" is the address of the routers and has to be activated if external access to the webserver should be possible.
NSC Sicherheitstechnik GmbH 21/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
26.4
Internal Modules 01/63 >01 FRP with FBC
A B
02 Remote LCD Panel A
03 Remote LCD Panel A
04 FRP A B 05 - 06 - Cancel Details
Display of FRP/LCD Panel
Different protocol can be set to each serial interface of the FCP. (s. menu 113). On all interfaces set to "FRP protocol" connected devices will be scanned. The address range for these devices is 1-63. The device types will be shown as text.
Following devices are available:
FRP FRP with FBC FRP Munich FRP with FBC Munich Remote LCD Panel PC Management system LED mimic panel Voice Evacuation System EVA8
If Voice Evacuation System is connected via serial interface, it will automatically occupy address 63.
By characters "A" and "B" will be signalized, on which channels a device has been connected. For further information please press "Details" (F4) jump to menu 29.1
26.5
Modbus device 01/63 >01 LISTEC SCU 02 - 03 - 04 ­ 05 - 06 - Cancel Details
Display of Modbus devices
Different protocol can be set to each serial interface of the FCP. (s. menu 113). On all interfaces set to "Modbus protocol" connected devices will be scanned. The address range for these devices is 1-6. The device types will be shown as text.
Following devices are available:
LISTEC SCU
The address of a SCU800 will be set by the configuration software "Listterm". Addresses from 1-8 are possible. Internally the FCP handles each SCU800 like a loop card. Each cable section represents one segment. A maximum of 99 sensors is possible on each section. The sensors can be configured to any zone.
27
Network ID 002 FCP 002 ID-1 :002 Timeout 000
ID-2 :002 Timeout 000
Status 1 :00000000
Message :0951
from message :0951
Cancel Details
Details of network devices
The ID of first and second network card will be displayed and additionally you can see if there are still messages in the pipeline to be send to this device. If the counter behind "Message" is different to the counter behind "from message" not all messages have been transferred to this device.
Timeout shows missing communication to another network device in seconds. After 90 seconds a network fault will be displayed.
The bit sequence "Status 1" contains the following status information from right to left:
NSC Sicherheitstechnik GmbH 22/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
//bit 0 = Waiting for Acknowledge //bit 1 = last message not confirmed //bit 2 = Message synchronization //bit 3 = End of message synchronization //bit 4 = Active delay //bit 5 = Transmission device disabled //bit 6 = Main alarm
For further information please press "Details" (F4) jump to menu 27.1
27.1
Send-/Receive status 1000001 ↑↓# Send index 4573
Start index 0200
No. of detectors 504
Receive Index 704
Receive Timeout 20 Timeout transm.release 30 cancel Send ↑↓ Stop Receive
Detector details of network devices
In this menu receive and transmit of detector data between network devices can be controlled.
The register "Send-/Receive status" has following meaning:
//bit 0 = waiting for release //bit 1 = got release to send data //bit 2 = request for detector data //bit 3 = receiving detector data //bit 4 = sending data to web server //bit 5 = given release to send //bit 6 = sending necessary //bit 7 = sending data
The arrows in line 1 show receive and transmit activity. '#' signalises an occupied transmit buffer.
Send index value of 4573 means, that all detector data have been send to the selected network device.
The start index is the memory location, where entry of detector data for the selected network device starts.
The "no. of detectors" value represents the received quantity.
After successful receive the receive index value has to be the sum of start index + no. of detectors.
Communication can be manually controlled by the function keys:
F2 = send detector data F3 = communication stop F4 = receive detector data
28
0001/001 MCP CHQ-CP
Configured detector text
1 2 3 4 5 6 7 8
Inputs
|0| | | | | | | |
Outputs |0| | | | | | | |
Fault : missing
Cancel
Example of detector data: MCP
The input bits display the status of the alarm contact of the MCP or - in case of input modules – the status of the input bits of the module (high / low). The "Output” bits show – in case of output modules – which outputs are active or in fault condition.
NSC Sicherheitstechnik GmbH 23/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
Following status are possible:
0 = inactive
1 = active
x = reset
= open circuit
S = short circuit
U = undefined
The last but one line shows any additional fault information if the detector/module is not in normal condition (here: fault because detector is missing). Leaving the menu by pressing F1 ("Cancel").
28.1
Hochiki ESP
0002/001 opt. det. ALG-
E
Configured detector text
A-Value ████████ 0,8%/m Pre alarm███████████████ 2,7%/m Alarm
█████████████████ 3,4%/m
Cancel Calib. Details
Apollo
0002/001 opt. det. XP95
Configured detector text
A-Value █████ 025 Pre alarm ██████████ 045 Alarm ████████████ 055
Cancel
Compens. Details
Example of detector data: Optical smoke detector
The FCP displays the current values of the detector as horizontal bar charts. The meanings of the bars are :
Analogue value (measured in detector
chamber)
Pre alarm threshold
Alarm threshold
The percentage values on the right relates to the bar charts. The Pre alarm/alarm threshold depend on
a) the detector sensitivity which can be
adjusted
b) the mode if the detector is a multi sensor
Only for Hochiki ESP
The push button "Calib"ration (F3) can be used to calibrate an optical smoke detector or a multi sensor manually. This will be done by the panel usually automatically once a day (see Settings -> System settings -> Parameter 12). That means usually this is not necessary to do manually except :
1. after replacing a detector and if the fault message "Calibration fault" appears.
2. if after the daily automatic calibration the fault message "Calibration fault" appears.
The manual calibration process needs about 20 sec. If in the second case the fault message does not disappear the detector has to be replaced.
The push button "Details" (F4) shows the result of the last calibration of the detector Jump to Picture
30.
Only for Apollo
By pressing "Compens."ation (F3) an automatic smoke detector (Optical, Multi) can be readjusted manually. This should be done, if a polluted detector will be changed by a new one. By compensating the detector the drift value (Discovery) or the alarm threshold (XP95, XPlorer) will be reset. Without manual compensation the FCP will adjust these
NSC Sicherheitstechnik GmbH 24/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
values automatically but this process may last several hours..
The push button "Details" (F4) shows more information for Apollo Discovery detectors Jump to Picture 30.
28.2
Listec sensor cable SEC15
0002/001 LISTEC SEC15
Configured detector text
actual temperature
██████████ 022,6°C ██████████ 022,6°C
reference temperature
Cancel
Example of detector data: Listec heat sensor cable SEC15
The FCP displays the current values of the detector as horizontal bar charts. The meanings of the bars are :
actual temperature
reference temperature
The reference temperature follows the actual temperature with time delay.
The thresholds for pre alarm, alarm and the maximum/differential behavior will be configured in the SCU800. To change the settings you need the configuration software "Listterm".
29
Loop card HOCHIKI ESP
Software version : S060A03.09
Status : OK
Number of spurs : 2/4 Number of loops : Loop 1, Loop
2
Cancel
Example of loop card details
The display indicates that 4 spurs or 2 loops can be connected to this loop card.
Actually recognized are loop 1 and loop 2.
29.1
FRP with FBC Software version : S150A01.03 24V 1 : OK 24V 2 : Fault FBC : OK
Checksum : OK
Restart : OK Cancel
Example of details of a fire brigade repeater panel with fire brigade control panel
In case of a fault of a RS485 device this menu gives a hint about fault reason. In this example 24V supply voltage on input 2 of the FRP is missing.
30
Only for Hochiki ESP
0002/001 opt. det. ALG-
E
029 094 156 232 | | | | ______|______ ______|_____ Zeropoint Firepoint 61 190 Cancel
0002/001 Multisen ALG-
E
029 094 156 232 | | | | ______|______ ______|_____ Zeropoint Firepoint
61 190
Cancel
Only for Hochiki ESP Example of "Zero point" and "Fire point"
display
Zero point = quiescent analogue value (9-109 depending on detector type) Fire point = test alarm threshold (139-246 depending on detector type)
Out of these two values the actual smoke density and the alarm thresholds will be calculated. (s. picture
28). By calibrating the detector the smoke density will be set to 0 and the alarm thresholds will be readjusted. The zero point represents the pollution of the detector. In the bar charts on the left hand the limits and the standard values for the different detector types are demonstrated.
NSC Sicherheitstechnik GmbH 25/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
0002/001 Ion det. ACA-
E
008 110 138 246 | | | | ______|______ ______|_____ Zeropoint Firepoint 61 190 Cancel
Only for Apollo Discovery
0002/001 opt. det. DISCOV.
Date of manufact. : 09/11 Pollution : 16 Sensitivity : 3 Last revision : ­Det.LED flash at poll. : 0 Cancel
A pollution fault will be generated automatically at the following smoke densities::
opt. det. ALG-
E
+- 1,1 %/m
Multisen ALG-
E
+- 1,1 %/m
Ion det. ACA-
E
+- 0,17%/m
Only for Apollo Discovery
The Apollo "Discovery" series has the ability to store data in the flash memory of the detector itself. These data remains in memory even if the detector will be removed from the base. The reading and transmitting of the data will last about 1-2 seconds. Therefore you have a short delay before first value will be displayed.
The following data is available:
- date of manufacture of the detector in format MM/JJ
- pollution in the range 0-31.
16 = clean air value
<=3 and 31 = pollution fault
0 = fault with analogue value 4
- sensitivity 1-5 (s. Picture 111)
- date of last revision in format MM/JJ. If no revision alarm has been activated for this detector a "-".will be displayed.
- detector LED at polling
1 = LED flashes, if detector is polled.
0 = LED off, if detector is polled
this function can be set by system-parameter 8
NSC Sicherheitstechnik GmbH 26/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
3. Installer menus:
The following menus are available only for the installer as the access is protected by a separate access code. When the panel is shipped out by NSC the access code for the installer is:
00000
This access code can be changed by the installer. In any case it should be kept at a save place. When the installer has changed this access code it is unique and nobody else can operate in the installer menus of the panel.
Please keep the installer code (access code) in a save place.
It is the protection of the panel against wrong operation.
After pressing the push button you will enter the main menu of the FCP "Solution F1". Then please press
F3 ("Installer")
to enter the installer menus. After that the installer code is required.
To select sub menus you have the following possibilities:
Using the cursor keys and to mark the sub menu with the black background and then press F4 ("Enter") to confirm the selection.
Directly by pressing the number of the sub menu. No "Enter" button is necessary in this case.
Some times you will see a listing of e.g. outputs, inputs etc. in the LC module. In which case usually there is a selection bar like this:
+1 -1 Selection -> +10 <- -10
When there is such a selection bar you can use the cursor keys again and pressing F4 ("Enter") confirms the selection. The cursor keys and go one line down / up and the cursor keys and will go 10 lines down / up.
There are some more standard operating functions:
"Cancel" in the bottom line of the LC module (right above F1) means always jumping into the menu before
The "ESC" push button cancels the current typing but do not lead to a jump out of the menu.
Usually the bottom line of the LC module looks like this (if there are no additional options to F2 and F3):
Cancel Enter
NSC Sicherheitstechnik GmbH 27/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
No.
Indication of the LC module :
Description :
31
Installer
Access Code: *****
Cancel
Access to the installer menu
After pressing push button F3 ("Installer") the FCP requires the installer access code. Please type this code and confirm by F4 ("Enter”).
32
Main menu
1. Switch on/off
5. Test mode
2. Alarm counter 6. Autom.controlling
3. End user code 7. Alarm configurat.
4. Diagnosis
8. Settings
Cancel End use Enter
General Main menu for installer
This menu appears immediately after pressing "Prog". The functions have the followings meanings :
1. To switch on / off detectors, input-/ output modules, zones and general outputs Jump to Menu 02
2. Indication of the alarm counter. It is a 4 digit number (1 – 9999), resettable only in diagnosis function of configuration software.
3. To change the end user code Jump to Menu 04
4. To enter the diagnosis menu Jump to Menu 05
5. To enter the test mode. That are the following functions :
Detector test Manual Controlling Simulation Revision
Jump to Menu 33
6. To enter automatic control functions. These are :
OC outputs inside the FCP Relays inside FCP Power outputs of the FCP Output modules (on the loops) Input modules (on the loop) 8 monitored inputs of the main board 2 conventional inputs of the main
board
Jump to Menu 34
7. To enter alarm configuration. These are :
Configuring detectors / zones Alarm dependencies Configuring 16 timer programs Configuring alarm / fault delays
Jump to Menu 35
8. To enter settings menu. Which means :
To set data and time National holidays System settings Scanning of detectors To delete the configuration To delete detector texts To delete event memory To configure push buttons S1-S8 To change installer access code To select the language To configure the interfaces To configure conventional zones To scan RS485 devices
Settings 1 Jump to Menu
36
Settings 2 Jump to Menu 37
NSC Sicherheitstechnik GmbH 28/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
The push button "cancel" (F1) leads to the normal status indication of the FCP.
The push button "End user" (F3) is for entering the end user area.
The push button "Enter" (F4) selects (activates) the function which is marked by a black background. Instead you can also select the function by pressing the no. left in front of the functions (here: 1 – 8).
33
Test mode
1. Detector test
2. Manual Control
3. Simulation
4. Revision
Cancel Enter
Main menu: Test functions
As soon as this menu is selected the FCP is in the service mode. This will be indicated by the green LED "Service". After leaving this menu the green LED is off.
1. The function "Detector test" can be used to set individual detectors in alarm condition (electronically) Jump to Menu 50
2. "Manual Control" means manual controlling of the outputs. With a simple press on a push button an output can be activated Jump to Menu 51
3. "Simulation" can be used to set individual detectors in alarm condition without connected detectors (by software). This is useful for testing the panel outputs / indications as long as the panel is not installed Jump to Menu 52
4. "Revision" means a "One-Man-Test procedure" to set smoke and heat detectors in alarm by using special test equipment. During this procedure the FCP resets all alarms on the relevant zones automatically after a certain time Jump to Menu 53
34
Autom. Controlling
1. Output 5. Input module
2. Relay 6. Input
3. Power output 7. Monitored Input
4. Output module
Cancel Enter
Main menu: Automatic Controlling
The following options can be selected :
1. Configuration of internal OC outputs (on main board and loop cards) Jump to Menu 54
2. Configuration of 4 internal relays on main board Jump to Menu 55
3. Configuration of 3 internal monitored power outputs on main board Jump to Menu 56
4. Configuration of output modules on the loops Jump to Menu 57
5. Configuration of input modules on the loops Jump to Menu 58
6. Configuration of 8 internal digital inputs on main board Jump to Menu 59
7. Configuration of 2 internal monitored conventional inputs on main board Jump to Menu 60
35
Alarm co
nfigurat.
1. Zones 5. Timer program
2. Detector settings 6. Delay
3. Zone settings 7. Zone LEDs
4. Alarm coincidences
Cancel Enter
Main menu: Alarm configuration
The following options can be selected :
1. Sub menu "Zones" to configure detectors into zones Jump to Menu 61
2. Sub menu "Detector settings" to configure the detectors. E.g. day and night sensitivity, multi sensor modes, selecting timer programs for detectors, delay and pre-alarm
NSC Sicherheitstechnik GmbH 29/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
functions Jump to Menu 62
3. Sub menu "Zone settings" to configure the zones for 2-detector-dependency, internal alarm zones, technical or fault alarms etc. Jump to Menu 63
4. Sub menu "Alarm coincidences" to create alarm dependencies between two or more zones Jump to Menu 64
5. Sub menu "Timer programs" to configure up to 16 timer programs Jump to Menu 65
6. Sub menu "Delay" to configure "Response time" and "Inspection time" for the alarm transmission device (only relevant if the main alarm shall be investigated before passing to the Fire Brigade). Jump to Menu 66
7. by "Zone LEDs" the LEDs of zone LED PCB can be assigned to individual zones.
Jump to Menu M118
36
Settings 1
1. Date/Time 5. Delete program
2. Holidays 6. Delete texts
3. System settings 7. Delete Events
4. Scan detectors 8. Push buttons S_
Cancel more Enter
Settings 1 of FCP
1. To change date, time and day of the week Jump to Menu 67
2. To configure bank or national holidays which can be configured individually for any country Jump to Menu 68
3. To enter sub menu for system settings where some individual hardware and software features can be configured Jump to Menu 69
4. To enter sub menu for new scanning of addressable detectors Jump to Menu
70
5. To delete configuration of FCP. Before deleting there will be a security inquiry Jump to Picture 71
6. To delete detector texts. Before deleting there will be a security inquiry Jump to Picture 72
7. To delete all events in event memory. Before deleting there will be a security inquiry Jump to Picture 73
8. To enter sub menu for configuration of special push buttons S1 to S8 Jump to Menu 74
For another settings menu please press F3 ("more") to enter sub menu "Settings 2" Jump to Menu 37
37
Settings 2
1. Installer code 5. Scan RS485
2. Language 6. Modem
3. Interfaces 7. Network
4. Convent. Detect
. 8. Flash Update
Cancel more Enter
Settings 2 of FCP
1. To change installer access code Jump to Menu 75
2. To change the panel’s language Jump to
Menu 76
3. To enter sub menu of 3 serial interfaces
4. RS-232. It is possible to configure the interfaces with different protocols and different baud rates Jump to Menu 77
5. To configure alarm thresholds for conventional detectors so that it is possible to use conventional detectors of different manufacturers Jump to Menu 78
6. After pressing "5" the RS-485 devices connected to the RS-485 interfaces will be
NSC Sicherheitstechnik GmbH 30/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
scanned. The number of found RS-485 devices will be displayed in the last but one display line Jump to Picture 79
7. Opens input screen "Modem" Jump to Menu 80
8. Opens input screen for network settings Jump to Menu 81
9. Facilitates a software update of the main board using the configuration software Jump to Menu 82
For another settings menu please press F3 ("more") to enter sub menu "Settings 3" Jump to Menu 38
38
Settings 3
1. Power outouts 5. Arcnet
2. Loop parameters 6. Webserver
3. Options
4. Scan Modbus
Cancel Enter
Settings 3of FCP
1. Opens input screen to configure power output settings Jump to Menu 83
2. Opens input screen to configure loop settings Jump to Menu 84
3. Jumps into menu to unlock options  Menu
85
4. Scans Modbus devices connected to serial interfaces of the FCP.
5. Menu to change the network communication speed Menu 87
6. Opens the menu to configure the webserver module IP settings Sprung in Menu 91
50
Detector test Status
Zone : 2 Normal
Detector : 3 Normal
Alarm unset (outputs inactive) ! Cancel On set
Example of detector test :
Detector not yet in alarm :
0002/002 opt. det. ALG-E Evt. individual detector text
A-Value ████████ 0,0%/m Pre alarm███████████████ 2,7%/m Alarm
█████████████████ 3,4%/m
Cancel Calib. Details
Detector in alarm :
0002/002 opt. det. ALG-E Evt. individual detector text
A-Value ██████████████████████ 4,5%/m Pre alarm███████████████ 2,7%/m Alarm
█████████████████ 3,4%/m
Cancel Calib. Details
Detector test (only for addressable detectors)
First zone and detector number (within the zone) has to be typed. Every line has to be confirmed by "OK”.
The push button F4 ("set / unset") can be used to configure if the outputs of the FCP shall be activated during the test alarm or not. The current selection is displayed in the last but one line of the LC module (here : "outputs inactive").
After that the test alarm can be activated by pressing F2 ("On").
By using the "System Settings" (parameter 16) it is possible to configure an auto-reset of the test alarm condition or no auto-reset. In that case the test alarm
has to be reset by pressing "Reset" . The bar charts as in the example on the left side show
how the test alarm will arise (see A-value). If the analogue value passes the alarm threshold the detector goes into alarm condition.
NSC Sicherheitstechnik GmbH 31/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
51
Manual Controlling
1. Output
2. Relay
3. Power Output
4. Output module
Cancel Enter
Menu "Manual Controlling"
Please select the kind of output you want to activate manually (1-4). The possibilities are :
1. "Output" means internal OC-outputs on main board and loop cards Jump to Menu 100
2. "Relay" means 4 internal dry contact relays on main board Jump to Menu 101
3. "Power Output" means 3 internal monitored power outputs 24V / 500 mA on main board Jump to Menu 102
4. "Output module" means loop modules Jump to Menu 103
52
Simulation Status
Zone : 5 Normal
Detect. : 33
Alarm unset (outputs inactive) ! Cancel Alarm set
Menu "Simulation"
The purpose of the menu "Simulation" is to simulate alarm conditions of certain addressable detectors or certain conventional zones without having any detector connected. The sense is to test the configuration before installation of the panel.
Operating for a) addressable detector Please type the Zone and the Detector (Detector number, not physically address) and confirm every line by "OK”.
b) conventional zone Please type the Zone and as "Detector" type a "1" and confirm every line by "OK".
The push button F4 ("set") can be used to switch the function of the outputs: "set" means the outputs will be activated in case of a simulated alarm and "unset" means the outputs will not be activated. The test alarm will be activated by F2 ("Alarm") and the LC module displays "ALARM"
The alarm has to be reset by "Reset BMZ" . Press cancel to leave this menu.
53
Revision Status
from zone
: 2 Normal
to zone : 4 Normal
Cancel On Off
Menu "Revision"
The revision mode can be used to check the detectors by detector test equipment (e.g. Solo test equipment). When the detector is activated by the test equipment the alarm is displayed at the FCP and reset automatically after 30 sec. Please type in the number of the zones which shall be investigated by the revision mode. Every line has to be confirmed by "OK".
Please activate the revision mode for the selected zones by F2 ("on"). Pay attention: the zones in revision will be displayed at the panel as "disabled".
The alarm of such a zone will be displayed in the LC module as "T E S T A L A R M"
After having finished the revision do not forget to switch off the revision mode by F3 ("Off") because an alarm of these zones will not be transmitted to the fire brigade.
NSC Sicherheitstechnik GmbH 32/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
54
Autom.controlling Status
Output : 001 Normal
+1 -1 Selection ->+10 <--10
>001 Output 001 Main board
002 Output 002 Main board
003 Output 0
03 Main board
Cancel Enter
Autom.controlling Status
Output : 001 Normal
+1 -1 Selection ->+10 <--10
>001 Output 001 Main board
002 Output
002 Main board
003 Output 003 Main board
Cancel Settings Function Event
Automatic Control: internal OC Outputs
Please select the OC output which shall be configured by the cursor keys : , : Marker ">" one line up / one line down <-, -> : Marker ">" 10 lines up / 10 lines down or type the number of the OC output directly by using the keypad and confirm this by "OK”.
Underneath the grey line "Selection" the FCB indicates where the selected outputs are. OC outputs 1 to 16 are on the main board, any further outputs are on the additional loop cards : OC outputs 01 – 16 : on Main board OC outputs 17 – 24 : on loop card / convent. card 1 OC outputs 25 – 32 : on loop card / convent. card 2 etc. The selected output has to be confirmed by "OK” or by F4 ("Enter"). After this the last line of the LC module looks like the example left.
Press F2 ("Settings") Jump to Menu 104 (Menu 104 to assign on/off functions to the outputs)
Press F3 ("Function") Jump to Menu 105 (Menu 105 to link the outputs with fixed standard functions of activation)
Press F4 ("Event") Jump to Menu 106 (Menu 106 to configure cause and effects events when the output has to activate)
55
Autom.controlling Status
Relay : 001 Normal
+1 -1 Selection ->+10 <--10
>001 Relay 001 Main board
002 Relay 002 Main bo
ard
003 Relay 003 Main board
Cancel Enter
Automatic Control: 4 internal Relays
This configuration menu relates to 4 internal relays on the main board.
The operation is he same as described in Menu 54.
56
Autom.controlling Status
Power Output : 001 Normal
+1 -1 Selection ->+10 <--10
>001 Power Output1 Main board
002 Power Output2 Main board
003 Power Output3 Main board
Cancel Enter
Automatic Control: 3 monitored Power outputs
This configuration menu relates to 3 internal power outputs on the main board.
The operation is he same as described in Menu 54.
57
Output module
Segment :
Address :
Output :
Cancel
Automatic Control: Output modules (loop)
This configuration menu relates to the output modules on the loops.
Please type the loop number (”Seg.”) and the output module’s address and confirm every line by "OK”.
Because some of the modules (B02450/51-00 and B02460/61-00) have two separate outputs you can select the output (1 or 2) in the line "Output” and confirm by "OK”.
NSC Sicherheitstechnik GmbH 33/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
Example of loop 1, module addr. 99 :
Output module
Segment : 1
Address : 99
Output : 1
Cancel Module Sounder Event
See example of LCD display on left side.
Press F2 ("Module") or F3 ("Sounder") Jump to Menu 107 (Menu 107 to assign on/off functions to the output modules or to configure tones / volume for base sounders.)
Press F4 ("Event") Jump to Menu 106 (Menu 106 to configure cause and effects events when the output module has to activate)
58
Input module
Seg. :
Address :
Input :
Cancel Event
Automatic Control: Input modules (loop)
This configuration menu relates to the input modules on the loops.
You can use input modules to :
disable detectors / zones change the sensitivity of addressable
detectors (Day mode/Night mode)
activate outputs, relays and power outputs switch off the internal buzzer etc.
Please type the loop number ("Seg.”) and the output module’s address as well as the input number and confirm every line by "OK”. Press F4 ("Event") Jump to Menu 106
59
Autom.controlling Status
Input : 001 Normal
+1 -1 Selection ->+10 <--10 >001 Input 001 Main board 002 Input 002 Main board 003 Input 003 Main board Cancel Enter
Automatic Control: 8 resistor monitored Inputs
This configuration menu relates to the 8 monitored inputs on main board.
Please select the input which shall be configured by the cursor keys : , : Marker ">" one line up / one line down <-, -> : Marker ">" 10 lines up / 10 lines down or type the number of the input directly by using the keypad and confirm this by "OK”.
After selecting the input the last line of the LC module changes and you can choose :
Press F2 ("Settings") Jump to Menu 108 (Menu 108 to configure monitoring and delay of OC inputs) or
Press F3 ("Function") Jump to Menu 105 (selection of standard function for this input) or
Press F4 ("Event") Jump to Menu 106 (Menu 106 to configure cause and effects events when the output module has to activate)
NSC Sicherheitstechnik GmbH 34/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
60
Autom.controlling Status
Monitored Input : 001
+1 -1 Selection ->+10 <--10 >001 Monitored Input1 Main board 002 Monitored Input2 Main board
Cancel Enter
Automatic Control: 2 monitored, conventional inputs
This configuration menu relates to the both monitored conventional inputs on main board.
If no event is programmed each input has a standard function. These functions are :
conventional input
1 = Key deposit box Alarm
conventional input
2 = exting. syst. interface (VdS)
As soon as one event has been programmed the standard functions of this input will be out of order.
Please select the input which shall be configured by the cursor keys : , : Marker ">" one line up / one line down and confirm this by "OK” or by F4 ("Enter"). Then the function of F4 changes and please press F4 ("Event") Jump to Menu 106
61
Zones
1. Analogue Detect.
2. Convent. Detect.
Cancel Enter
Select the kind of detectors to configure: Loop or conventional
Here you select the kind of detectors which shall be configured: analogue addressable or conventional. The FCP "Solution F1" has the ability not only to configure analogue addressable detectors but conventional detectors too. That means you can assign to every hardware output for conventional detectors a software zone.
Please select the right detectors by the push buttons 1 or 2 : Pressing 1 Jump to Menu 109
Pressing 2 Jump to Menu
110
62
Detector settings
Seg. : 1 from Address : 2
to Address : 2
Cancel
Detector settings
This menu is to configure every single (analogue addressable) detector with some of the following functions :
Sensitivity for the day Day mode (only Multi sensor) Sensitivity for the night Night mode (only Multi sensor) Assigning a timer program Delay in case of alarm condition Delay in case of fault condition Pre-alarm
After typing loop no. and address(es) (please confirm every line by "OK") the LC module changes Jump to Menu 111
63
Zone settings Zone : 6 Cross detection : No Internal alarm zone : No Fault zone (non latching) : No Fault zone (latching) : No MCP zone : No Cancel No Yes save
Zone settings
Here you can configure certain settings for every software zone of the FCP. "Cross detection" means at least 2 detectors of this zone have to be in alarm to activate the transmission devices to the fire brigade. A "fault zone” does not activate an alarm but only a
NSC Sicherheitstechnik GmbH 35/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
Zone settings Alarm delay for convent. Detect.: No Extinguish Syst. Activ : No
Cancel No Yes save
fault message. "non latching" means a fault condition is automatically reset when the fault has disappeared.
By pressing the cursor push button "" you find two more functions :
"Alarm delay of conventional detectors”.
This means, an alarm on a conventional zone will be reset automatically by the FCP has to return within 60 seconds. Otherwise no alarm will be displayed on the FCP.
"Extinguish system active: zones with this
parameter set can activate an output, signalizing that an extinguishing system has been triggered.
Press the push button F2 ("No") for deactivating this functions and press F3 ("Yes") to activate the functions individually. Please confirm every line by OK When you have finished all settings for one zone please press F4 ("save") to save the configuration.
64
Alarm Coincidences 002/512 Zone 0007 with zone 0011
+1 -1 Selection ->+10 <--10 001:Zone 0003 with Zone 0022 >002:Zone 0000 with Zone 0000 003:Zone 0000 with Zone 0000 Cancel save
Zone Alarm Coincidences
Use this menu to create alarm coincidences of two or more zones. An alarm coincidence means that at least 2 zones have to be in alarm condition to activate the main alarm passing to the fire brigade station. If only one of the relating zones is in alarm there is only an internal alarm indication on the FCP. Way of operation :
You have to type the zones which shall be in alarm coincidence in the second display line. Therefore please use the keypad and confirm every zone by OK
After this press F4 ("save") to save the configuration.
The new zone coincidence will be taken over into the list just underneath the grey selection line. There you can see all alarm coincidence which are configured yet.
The marker ‚>’ at the left side of the LC display jumps to the next line just after you have configured a new zone coincidence.
65
Timer programs 01/16 >Timer program 01 Day Timer program 02 Night Timer program 03 Night Timer program 04 Night Timer program 05 Night Timer program 06 Night Cancel Weekday
Timer programs
The FCP "Solution F1" supports up to 16 different timer programs. A timer program has two different functions :
1) You can assign a timer program to detectors and zones to switch sensitivities or detector modes 4 times per day. (Menu 62 "Detector settings")
2) To switch from "day mode" to "night mode" and vice versa. During day mode the main alarm is not directly passed to the fire brigade but there is a delay to inspect the alarm condition (Menu 66 "Delay").
The notation "Day" respective "Night" behind the timer program number shows the actual status.
NSC Sicherheitstechnik GmbH 36/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
Please select a timer program by the cursor keys : , : Marker ">" one line up / one line down and then press F4 ("Weekday") Jump to Menu
112.
66
Delay
Response time : 180 Sec. Inspection time : 7 Min.
Timer program : 00
Cancel save
Delay times of Main alarm (TD)
These delay times – consisting of response time and inspection time – relates to the Main alarm and so usually to the transmission device (TD) of the fire brigade station. Way of operation : If a smoke detector detects an alarm and the panel is in day mode – delay is activated – the response time will be started immediately. Now the end user has the obligation to acknowledge the alarm condition by
pressing "internal buzzer off" Otherwise if that is not done, the main alarm is indicated and the fire brigade will be called. If the button is pressed the inspection time will be started and the user has several minutes to inspect the alarm. At the end of the inspection time the main alarm is indicated and the fire brigade will be called. He can avoid that by resetting the FCP.
If the user presses a MCP during one of the above described periods a main alarm will be activated immediately.
The response time can be 0 – 180 Sec. The inspection time can be 1 – 7 Min.
Please confirm every line by OK and press F4 ("save") to save the new delay times.
Pay attention : The delay can be linked to a timer program. This offers the possibility to configure the day and night mode individually for every weekday and – if necessary – to switch between day and night mode up to 4 times per day. So that means one of the timer programs should be reserved for this function if the user needs the day and night modes (Menu 65 "Timer programs"). If the user doesn’t need an automatic switching from day to night mode and vice versa you can switch it manually too. Therefore please have a look in "Main Menu"  "1. Switch on/off"  "7. Delay"
67
Date/Time Day : 09 Friday Month : 07 Winter Year : 04 Hour : 07 Minute : 46 Second : 39 Cancel Maintenanc save
To set date and time
Please type the right data line by line and confirm every line by OK Weekday for timer programs will be calculated automatically.
It is not necessary to configure summer or winter time because the panel does this automatically. This means at the last weekend in March and October the panel switches to summer or winter time. This can be deactivated if you go to "System settings" (Menu 69) item 7.
By pressing F3 ("Maintenance") a Maintenance interval can be configured. When this interval
NSC Sicherheitstechnik GmbH 37/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
elapsed, a fault message will be generated -> Menu
116.
When you have finished data, time and weekday please press F4 ("save") to save the new configuration.
68
Holidays Day : 25 Month : 12 +1 -1 Selection ->+10 <--10 01: Day 31 Month 12 >02: Day 00 Month 00 03: Day 00 Month 00 Cancel save
To configure Holidays
Please type the day of a holiday in the second line of the LC display and the month in the third line. The example on the left side shows Christmas holiday. Please confirm every line by OK
The marker ">" indicates the number of holiday which the user is configuring at the moment.
When you have finished day and month press F4 ("save") to save the holiday. It will be transferred into the list in the middle part of the LC display.
To cancel a holiday: Please put the marker ">" by the cursor push buttons , on the holiday which shall be erased and type "00" for day and month and save it by F4.
69
System settings
FBC settings : 00
+1 -1 Selection ->+10 <-­10 >01: FBC settings (0-3) 00 02: Transm. Device settings(0-2) 00 03: FCP cover contact (0-2) 01
Cancel save
*) If the German Fire Brigade Control Panel is connected to the "Solution F1" the following outputs are occupied :
- Output OC 01 – 06 on main board for NSC-FBC
- Output OC 01 – 07 on main board for SeTec-FBC
- Input 01 – 05 on main board (see wiring diagram)
System settings
Here the user can configure certain individual software and hardware settings which are listed in the table below. The marker ">" indicates the kind of setting which the user is configuring at the moment. It is displayed in the 2nd line of the LC module.
Please select the setting by the cursor keys and type the right value according the table below. The possible values are listed in brackets.
If all settings are configured please press F4 ("save") to save the new configuration. The FCP supports the following settings :
Nr. Parameter Value Description
01 FBC
0 no FBC
(Fire Brigade 1 *) NSC-FBC Control Panel) 2 *) SeTec-FBC 3 FBC
Switzerland
02
Transm. Device
0 Contin. signal (TD) 1 puls signal 2 puls signal and
puls feed back
03
FCP cover contact
0 Deactivated 1 Switch off TD
2 Switch on and
off TD
04
Mains fault delay
only with FBC Switzerland (s. Parameter 1)
0-30
0-60
Minutes
Minutes
NSC Sicherheitstechnik GmbH 38/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
The shielding will be controlled under the following conditions:
- During detector scanning
- ca. 15 seconds after FCP reset
- every 24h during detector calibration
"Reset first alarm" has the effect, that in case of cross zoning or cross detection the first alarm will be reset automatically after the configured period if during this time no further alarm rises.
The time "Calibration fault" determines a time, when a fault message caused by a calibration error during automatic 24h calibration will be displayed.
"Call acceptance after restart" has to be set to "1" if a build in telephone modem shall be automatically accept incoming calls after power up the system.
Parameter "printer" controls the line feed of a connected printer.
05
Fault reset
0 Automatically 1
by " "
06
Fault remind
0-30 Minutes or
0=no remind
07
Summer time switching
0 Automatically 1 Off
08
Detector LED flash at polling
0 Off 1 On
09
LED Intensity
(LEDs of FCP)
0-15 0= dark
7= standard 15= bright
10
Sounder output Activation
0 In case of
main alarm
1 At any alarm
11
Power Supply
0 NSC PSU 1 external:
1 channel
2 external:
2 channel
3 SLAT PSU 4 New NSC
PSU
12
Calibration time
0-24 Corresponds
to time
13
Earth fault detection
0 On 1 Off
14
Not used
15
Pre alarm
(for all detectors)
0 Off 1 On
16
Reset detector test
0 Automatic 1 Manual
17
RS485 channels
1,2 Corresponds
to the numbers of channels
18
Shielding control
0-1 0 = off
1 = on
19
Buzzer at information
0-1 0 = off
1 = on
20
Reset first alarm
0,
5-99
Minutes
21
Calibration fault
0-23 time (hour)
22
Call accept. after restart
0-1 0 = 0ff
1 = on
23
KDB activation
0-1 0 = main alarm
and feedback 1 = feedback
only
24
Printer
0-1 0 = CR (NSC
built in printer) 1 = CRLF (ext. printer)
NSC Sicherheitstechnik GmbH 39/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
70
Scan detectors
Loop card : 01
+1 -1 Selection ->+10 <--10
> Loop card 01
Cancel all Enter
Scan detectors
This menu relates to loop cards (addressable detectors) only.
The sense of this function is to scan all detectors of one loop card again to find some new installed detectors or if some detectors are removed. Always both loops of one loop card are scanned. Please type the address (IIC-BUS) of the loop card and confirm it by OK After pressing "Enter" (F4) a questions "Are you sure ?" appears on the LC module. If you confirm it by F4 ("Yes") the selected loop card starts scanning all connected detectors again. Alternative you can select all loop cards for new scanning by pressing F2 ("all"). Again the question "Are you sure ?" appears on the LC module and you can confirm it by F4 ("Yes”).
71
Delete program
Are you sure ?
No Yes
Delete Configuration
This function deletes all configurations besides the individual texts of the detectors. Even zones, macro push buttons and timer programs will be deleted.
Before deleting there will appear the question "Are you sure ?" on the LC module which has to be confirm by F4 ("Yes”).
These configurations will not be deleted :
Texts of the detector Event memory
72
Delete texts
Are you sure ?
No Yes
Delete Texts
This function deletes all individual texts of the detectors. Before deleting there will appear the question "Are you sure ?" on the LC module which has to be confirm by F4 ("Yes”).
73
Delete Events
Are you sure ?
No Yes
Delete Events
This function deletes the event memory. Before deleting there will appear the question "Are you sure ?" on the LC module which has to be confirm by F4 ("Yes”).
74
Push buttons S_ Push buttons S_ : 001
+1 -1 Selection ->+10 <--10
>001 Push button S_1
002 Push button S_1
003 Push button S_1 Cancel Settings Function Enter
Configuring macro push buttons S1 – S8
Please select the push button which shall be configured by the cursor keys : , : Marker ">" one line up / one line down or by typing the number of the push button on the keypad and confirm this by "OK” or by F4 ("Enter").
The marker ">" indicates the push button which the user is configuring now. Then press F4 ("Event") jump to menu 106
NSC Sicherheitstechnik GmbH 40/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
After selecting a push button an access code can be specified by pressing F2 ("settings") -> Sprung in
Menu 117
Press F3 ("Function") Jump to Menu 105 (selection of standard function for this push button)
75
Installer
old access code: 00000 new access code: 22351
new access code: 22351
Cancel
Changing the installer access code
First you have to type the old access code, and then you have to type two times the new access code.
Every line has to be confirmed with "OK". Example left side: old access code 00000 is replaced
by new access code 22351.
76
Language
1. German 5. Slovenian
2. English 6. Czech
3. French
7. Serbian
4. Dutch 8. Italian
Cancel more Enter
Selecting the panel language
Use this function to select the panel language on the LC module. Please choose one of the numbers offered on the LC module to select the right language. By pressing F3 "more", other languages can be chosen.
77
Interfaces
1. UART 1
2. UART 2
3. UART 3
4. USB
Cancel Protocol Baud rate
Configuring the interfaces
The FCP offers 3 different serial interfaces RS-232 (see wiring diagrams). UART 2 can also be used as RS-485 interface.
For every interface a certain protocol can be configured e.g. for printer, PC configuration etc. This means the FCP is easily to adapt to the required application and very flexible.
Please select UART 1, 2 or 3 by the cursor keys , and then press F2 ("Protocol") Jump to Menu 113
After that you can configure the "baud rate” by pressing F3 Jump to Menu 114
The USB interface will be used exclusively for programming, reading of the event memory and transmission of diagnosis data. The USB interface can be disabled/enabled through the control panel to initialise the interface or to prevent unwanted access to the system.
78
Convent. Detect.
Loop card : 3 from ML : 1 to ML : 8
Cancel
Alarm and fault thresholds for conventional ­detectors
This function enables the user to adjust every conventional zone individual relating alarm and fault thresholds. So nearly every detector on the fire market can be connected to the "Solution F1".
The conventional detector PCBs inside the "Solution F1" are preset for Hochiki CDX detectors and Apollo S65/Orbis.
For other detectors please have a look into their data sheet to adjust the right values.
NSC Sicherheitstechnik GmbH 41/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
In the example on the left side "Loop card" means conventional detector card and you have to type here the card address. Then type the zone(s) of this conventional detector card which shall be re­configured and after confirming every line by "OK” the LC display changes Jump to Menu 115
79
I N I T I A L I S A T I O N
RSRS485 Devices : 001
------------------
Scanning RS485 devices
The picture on the left side shows the scanning of the RS-485 devices. The line with the slashes "-" is running from left to right und during this time the RS­485 interfaces addresses all the connected devices.
In the last but one line of the LC module the FCP shows the number of RS-485 devices found. (here:
1).
80
Modem
1. Call accept on
2. Call accept off
3. Initialisation
4. Hang up
Cancel Terminal OK
Modem functions
If there is mounted a telephone modem in the FCP, from here you can send commands to the modem. These commands are:
1. Call accept on Will cause the modem to answer an external phone call.
2. Call accept off Disables the automatic call acceptance
3. Initialisation Initialises the modem with an ATZ command
4. Hang up Disconnects modem from telephone line
By pressing F2 "Terminal" the interface will be switched into a mode, in which commands directly could be sent to the modem by a PC connected to the COM interface. This makes modem configuration much easier. Modem settings could be changed by direct input of AT commands in the configuration software or in HyperTerminal.
81
Network
Network device : 003 Device no. : 003 Device type : 000 Zone offset : 03000 Offset/Device no. : Zone offset Cancel Sections scan save
Network settings
Each network card has its own ID-number in the range 1-255. This ID-number will be determined by input a number in line Network device. Please take care, that each number only exists one time in the whole network. The device number is the number that will be displayed in the panels LCD in case of a message. Existing device types are:
1. FCP = 000
2. RCP = 001 (Remote Control Panel)
The difference is that in a RCP all incoming messages will be stored in the event memory. A FCP only will save its own messages. Zone offset determines the starting number of zones for this FCP. Possible settings for Offset/Device no. are:
NSC Sicherheitstechnik GmbH 42/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
-
Device no.: Zone offset has to be "00000". The device number and the zone number will be displayed.
-
Zone offset: in case of a message from a detector/module the zone number plus configured zone offset will be displayed and not the device number. Attention: using
this system the network IDs have to be consecutive for all connected devices.
-
without: Zone offset has to be "00000". In case of a message from a detector/module the device number will not be displayed. By this setting all possible zone numbers "1­1024" can be split to different panels.
By selecting Sections you can define limitations concerning display of messages and control possibilities for networked devices. The standard setting allows display of every message from all networked panels and also unlimited controlling of all panels. Sections can be defined for networked panels and for devices communicating by "FRP protocol", i.e. LCD repeater panel -> menu 88
82
Flash Update
Are you sure ?
No Yes
Flash Update V3
Flash Update
ready
cancel
Flash Update V3
Flash Update
932
ready repeat
Flash Update
With this function you can update the software of the main board. The actual software version (e.g. S040A12.00.x) will be downloaded through RS232 interface by the NSC configuration software. The protocol for UART 1 has to be set to "PC" and the baud rate for UART 1 and the selected COM-interface of the computer has to be the same.
Since version "Flash Update V3" the
transmission can be done by USB.
After confirming the safety request with "yes" the opposite display will appear. Now you have to start the communication on the PC. Instead of "ready" then the number of transmitted kilobytes will be displayed. A transmission error will be signalised by "error" and by pressing "repeat" F4 key the procedure can be restarted.
Above key F1 "ready" will be displayed after transmission is completed. Pressing F1 will erase and reprogram the flash memory. Afterwards the FCP will automatically restart. You can check the new version in menu Diagnosis – FCP data.
83
Load resistance Tolerance No.: ( old) Norm OC-Tol. Th.OC Th.SC 1 : (0983) 0983 + 120 = 1103 , 0727 Ohm 2 : (0977) 0977 + 120 = 1097 , 0724 Ohm 3 : (0964) 0964 + 120 = 1084 , 0717 Ohm
Cancel Calib. save
Power outputs: Thresholds
Here the open circuit and short circuit thresholds for the 3 monitored power outputs will be adjusted. The thresholds depend on the load resistance of the connected device inclusive the line resistance. This total resistance can be ascertained automatically for each power output individually by pressing "Calib." F3. The
NSC Sicherheitstechnik GmbH 43/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
software then calculates the thresholds for open circuit and short circuit, dependant of the tolerance, which also can be changed manually.
84
Loop parameters
Loop : 1 Open circuit : 9999 mV Short circuit : 100 mA Number of detector LEDs : 4
Cancel save
Loop parameters
In this menu the values for open circuit and short circuit determined with the loop calculation program (Excel sheet) can be entered. Furthermore the number of detector LEDs, which will be activated simultaneously on a loop, can be specified in the range 3-12. This input is important for the maximum alarm current, which has influence on the maximum allowed cable length and, as a consequence, to the functionality of the system.
85
Options
1. ESPA 4.4.4
2. Modbus
3. VES
Cancel settings save
Options
Options are additional functions that are not part of the standard software. The release of these options has to be done by a 6 digit code you can request form NSC.
By pressing F3 "settings" you will enter the configuration menu for every option.
ESPA 4.4.4 -> Menu 86 Modbus -> the Modbus slave address can be set SAA -> no setting necessary
86
ESPA 4.4.4 Call address : 0001 Beep Coding : 1 Priority : 1 Call Status : 3 Text length : 16 Timeout : 010
Cancel save
ESPA 4.4.4 Settings
By ESPA 4.4.4 protocol all alarm messages and a common fault message will be transferred to a telephone server. The first 4 parameters refer to the ESPA 4.4.4 specification.
For alarm messages the configured "Call address" will be transmitted. As an option a common fault message can be transmitted. This option can be activated in the configuration software. The call address for common fault message also will be set in the configuration software.
Call address "5555" is a special case to realize communication with a call system of company "Winkel". With this Call address an additional text "Feuer" will be transmitted prior the configured customer text.
In the field "Text length" you can define, how many characters of the detector text will be send to the telephone serve. The input range is 16 up to 40. The "Timeout" is a delay for a fault message in case of communication error (10-255 sec).
NSC Sicherheitstechnik GmbH 44/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
87
Arcnet
1. 156K x
2. 2,5M
Cancel Off save
Arcnet Baud rate
The standard baud rate of the Arcnet network is 156KBaud. For diagnosis purpose under use of special hardware the baud rate can be set to 2,5MBaud.
Since software version S040A12.05 the baud rate setting will be stored permanently in flash memory.
88
Sections
1. Arcnet
2. RS485 device
Cancel Enter
Sections
Sections can be defined for networked panels and for devices communicating by "FRP protocol", i.e. LCD repeater panel Network sections -> menu 89 FRP protocol sections -> menu 90
89
Sections 0001/1000
Network-ID 001 Zon. 0001 – Zon. 0010 +1 -1 Selection ->+10 <--10 >0001: No. 001 Zon.0001 – Zon.0010 0002: No. 002 Zon.0038 – Zon.0040 0003: No. 003 Zon.0400 – Zon.0499 Cancel +100 -100 save
Network sections
To limit the display of messages and the control possibilities on a certain panel in a network, a maximum of 1000 sections can be configured.
In the left hand example 3 sections for 3 different network IDs have been programmed. As soon as any section has been defined for a certain network ID, all common messages, i.e. "Power supply fault", from this ID will automatically be displayed additionally to messages of the configured zones.
90
Sections 0001/1000 RS485 device 1 Network-ID 001 Zon. 0001 – Zon. 0010 +1 -1 Selection ->+10 <--10 >0001:Addr 01 No.001 Zon.0001 – Zon.0010 0002:Addr 02 No.001 Zon.0011 – Zon.0040 0003:Addr 03 No.001 Zon.0041 – Zon.0099
Cancel +100 -100 save
FRP protocol sections
After having selected a device out of the list of a maximum of 63 devices a maximum of 1000 sections can be defined to limit the display of messages, i.e. on a LCD repeater panel.
In the left hand example 3 sections for 3 different "FRP protocol" devices have been programmed. On the first device, i.e. a LCD repeater panel, only messages from zone 1 to zone 10 will be displayed, on the second device only messages from zone 11 to zone 40 and on the third device messages form zone 41 to 99. As soon as any section has been defined for a certain "FRP protocol" device, all common messages, i.e. "Power supply fault", from this ID will automatically be displayed additionally to messages of the configured zones.
91
Webserver
IP-Address : 192.168.0.127 Netmask : 255.255.255.0 Network : 192.168.0.0 Gateway : 192.168.0.254
Cancel "." UserInit save
Webserver Settings
The webserver settings generally should be done by the configuration software. Nevertheless the settings also can be changed at the control panel directly. If the webserver module has been recognized by tge FCP the first time, the basic configuration has to be made by the function "Delete program". Alternatively the settings can be initialized by loading a
NSC Sicherheitstechnik GmbH 45/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
configuration file into the FCP. With function key F3 ("UserInit") the User list in the
webserver module will be erased and set to the delivery status. After pressing F4 („save“) the changing will be stored in flash memory and transferred to the webserver module. The modified settings will be valid only after hardware reset of the webserver module.
For further information also see "B01380-00 Webserver User Manual ….pdf".
100
Manual control Status from Output : 001 Active to Output : +1 -1 Selection ->+10 <--10 >001 Output 001 Main board 002 Output 002 Main board 003 Output 003 Main board Cancel On Off Enter
Manual Control: internal OC Outputs
This menu to activate open collector outputs manually by the user / installer to test their function.
Please select the OC output which shall be activated by the cursor keys : , : Marker ">" one line up / one line down <-, -> : Marker ">" 10 lines up / 10 lines down or type the number of the OC output directly by using the keypad and confirm this by "OK” or by F4 ("Enter").
It is possible to operate several outputs simultaneously by using the "from – to” function.
Underneath the grey line "Selection" the FCB indicates where the selected outputs are. OC outputs 1 to 16 are on the main board, any further outputs are on the additional loop cards : OC outputs 01 – 16: on Main board OC outputs 17 – 24: on loop card / convent. card 1 OC outputs 25 – 32: on loop card / convent. card 2 etc.
After confirming the output the last line of the LC module changes and you can
activate the output by F2 ("On”) deactivate the output by F3 ("Off”)
The activations can be checked on the LC module because they will be displayed immediately or you can check the status as shown "Active” in the picture left side. If the output is not active it is indicated as "normal”.
101
Manual Control Status from relay : 001 Normal to relay : +1 -1 Selection ->+10 <--10 >001 Relay 001 Main board 002 Relay 002 Main board 003 Relay 003 Main board Cancel On Off Enter
Manual Control: 4 internal Relays
This menu to activate the 4 internal relay outputs on the main board manually by the user / installer to test their function.
The way of operation is the same as in Menu 100.
NSC Sicherheitstechnik GmbH 46/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
102
Manual Control Status from power output : 001 Normal to pow
er out :
+1 -1 Selection ->+10 <--10 >001 Power output1 Main board 002 Power output2 Main board 003 Power output3 Main board Cancel On Off Enter
Manual Control: 3 monitored Power Outputs
This menu to activate the 3 internal monitored power outputs on the main board manually by the user / installer to test their function.
The way of operation is the same as in Menu 100.
103
Manual Control Status Zone : 2 Normal
Detect : 3 Normal
Output/Relay : 1
Cancel On Off
Manual Control: Output modules (loop)
This menu to activate output modules on the loops. Please type :
the zone of the module
die number of the module within the zone
the output (1 or 2) of the module and confirm
every line by "OK”.
After confirming the output you can
activate the output by F2 ("On”) deactivate the output by F3 ("Off”)
The activations can be checked on the LC module because they will be displayed immediately or you can check the status as shown "Active” in the picture left side. If the output is not active it is indicated as "normal”.
104
Settings Output 001 On/Off like Fire Output : No On/Off like sounders : No On/Off like Transm.Dev. : No Off like buzzer : No Inactive by door cont. : No Delay : 000 Cancel No Yes save
Automatic Control: Settings for outputs
This menu offers the possibility to assign certain on/off switching functions to outputs. For example it is possible to link the on/off switching of the Alarm Transmission Device to an output and in that case the output is disabled at the same time the user disables the Alarm Transmission Device.
The following on/off switching functions are available :
On/Off like "Fire Outputs". This function
relates to the push button "Fire Outputs off” on the German Fire Brigade Control Panel. If this parameter is set to "yes” and the push button is pressed the relating outputs are disabled.
On/Off like "external sounders". This function
relates to the push button .
On/Off like "Alarm Transmission Device”
(TD).
On/Off like "buzzer off". This function relates
to the push button .
If the output shall be disabled by taking off
the cover of the housing set this parameter to "yes".
Here the user can configure a delay for the
activation of the output. The value for the delay is in seconds and the possible range is 0 – 240 s.
NSC Sicherheitstechnik GmbH 47/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
The functions are disabled by F2 ("No") and the functions are enabled by F3 ("Yes"). After setting the parameters please press F4 ("Enter") to save the configuration.
105
Functions for outputs
Function Output 001 Sounder/Strobe activation : No Tansm.Dev. activat. permanent : No Tansm.Dev. activat. impulse : No Saved Reply Message : No Reset FCP : No KDB output active : No Cancel No Yes save
Function Output 001 Buzzer : No
Cancel No Yes save
Functions for inputs
Function Input 001 Fire outputs : No Sounder : No Alarm Transm.Dev. : No Delay : No Buzzer off : No FCP Reset : No Cancel No Yes save
Functions for Push button S_ 001
Function Special Key 001
Fire outputs : No Sounder : No Alarm Transm.Dev. : No Delay : No
Cancel No Yes save
Automatic Control: Functions
Here the user can assign certain fixed functions to the inputs/outputs or special keys. For example he can assign the "sounder/strobe activation” to an output and in that case this output is activated and deactivated at the same time as the external sounders/strobes.
If one of these functions is used it is not possible to assign any other cause and effect events to the same output.
The sense is to create a parallel output to the listed outputs on the left side. The function "Saved Reply Message” is a special function of the German Alarm Transmission Device.
This device sends back a signal to the panel if the Fire Brigade is alarmed. This signal is acknowledged by the FCP and if this parameter is set to "yes” the relating output indicates this feed back signal by activation.
The functions are disabled by F2 ("No") and the functions are enabled by F3 ("Yes").
After setting the parameters please press F4 ("Enter") to save the configuration.
106
Autom.controlling Output 001
all events
Events for selection
Cancel Enter
Selection of displaying cause and effect events
A cause and effect event is a link / configuration of inputs and outputs combined with logical AND or OR.
Cause and effect events are possible at the FCP "Solution F1" for OC outputs, relays, power outputs, output modules, inputs, input modules und macro push buttons.
The user can choose if he wants to see all events in the LC module or just the events relating to the output he is configuring at the moment : "All Events" means all 2048 possible events will be displayed. "Events for selection" means only the cause and effect events of the selected input / output / push button will be displayed.
NSC Sicherheitstechnik GmbH 48/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
Please select your choice by the cursor keys : , : Marker ">" one line up / one line down and confirm this F4 ("Enter") Jump to Menu 121
107
Only for output modules
Settings Output module 01/099
Activation emergency mode : No On/off like fire output : No On/off like sounders : No
Cancel No Yes save
Only for sounders/sounder modules
Settings Output module 01/099
Activ. in case of emerg. mode : No not on/off like sounders : No intermittent : No Sounder group (0-15) : 00 Volume (0-10) : 04 Tone 1 (0-7) : 0 Tone 2 (0-7) : 0 Cancel No Yes save
Automatic Control: Settings for output modules (loop)
The example on the left side shows an output module of segment (loop) 1, address 99 (indicated in the first line of the LC module).
This menu offers the possibility to assign certain on/off switching functions to relay and sounder output modules. The following on/off switching functions are available :
Activation emergency mode
not available
On/Off like Fire Outputs - This function
relates to the push button "Fire Outputs off” on the German Fire Brigade Control Panel. If this parameter is set to "yes” and the push button is pressed the relating outputs are disabled.
On/off like sounders – output is controlled
by same functions as the sounders.
The functions are disabled by F2 ("No") and the functions are enabled by F3 ("Yes").
After setting the parameters please press F4
("Enter") to save the configuration.
Automatic Control: Settings for sounders/ sounder modules (loop)
For base sounders and sounder modules the following functions can be configured:
Activation emergency mode
not available
not on/off like sounders (by this function
the command "sounder off" can be suppressed for beacons with type code "sounder" (Apollo).
Intermittent (alternate) tone
(if it is "no" sounder will be activated continuously)
Sounder group – on each loop a maximum
of 15 sounder groups can be configured. That means several sounders can be subsumed into one group. The setting of the group will be made by software (Hochiki) or by DIP switch (Apollo).To activate all sounders of the group you just have to program events under "automatic controlling" for one device of this group..
The volume can be set in the range 0 (off)
up to ten. See appendix C. (table of tones and volumes for loop sounders).
The tone can be varied from 0 (off) up to 7.
See ap
pe
ndix C. (table of tones and
volumes
NSC Sicherheitstechnik GmbH 49/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
for loop sounders).
See technical device specification for details of functionality of each device type.
Note : Sounder output modules are generally operated like sounders / strobes connected to the monitored power
outputs : If the push button is pressed they are silenced.
108
Settings Input 001 with monitoring : No Switch : Yes Push button : No Activation delay : 000
Cancel No Yes save
Automatic Control: Settings of 8 internal monitored inputs
The picture on the left side shows an example of input 1 (indicated in the first line of the LC module).
These inputs can be configured :
With monitoring (only wire break) or without
(default value)
whether a switch or a push button is
connected to the input
With or without activation delay. The delay
can be adjusted in steps by one from 1 – 250 seconds.
0 means no delay.
The functions are disabled by F2 ("No") and the functions are enabled by F3 ("Yes"). After setting the parameters please press F4 ("Enter") to save the configuration.
109
Zones Seg. : 1 from address : 1 to address : 12 Zone : 32
from detector : 1
Cancel save
Configuring zones (loop)
Please type the loop number (”Seg.”) and the detector address (from – to). Segment = Section of addresses (loop) with a
maximum of 254 Hochiki detectors, modules / base sounders and a maximum of 126 Apollo detectors, modules. The segment are partitioned on the loop card according this list :
Loop card 1 : Segment 1 and 2 Loop card 2 : Segment 3 and 4 Loop card 3 : Segment 5 and 6 Loop card 4 : Segment 7 and 8 Loop card 5 : Segment 9 and 10 Loop card 6 : Segment 11 and 12 Loop card 7 : Segment 13 and 14 Loop card 8 : Segment 15 and 16 Loop card 9 : Segment 17 and 18
Address = Detector address (physical address stored
in the detector).
Zone = logical group of detectors (software zone)
where the detectors should be in
from detector = means the starting number of the
detector in the new zone.
Please confirm every line by "OK” and after finishing all lines press "save" (F4) to save the new configuration.
NSC Sicherheitstechnik GmbH 50/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
110
Zones Loop card : 3 from ML : 1 to ML : 8 from zone : 20
Cancel save
Configuring conventional zones
When using the FCP "Solution F1" the conventional zones are field programmable too :
Please type the address of the conventional detector card (PCB). That means the DIL switch address on the PCB (see wiring diagrams).
The following inputs in the lines "from ML" and "to ML" relates to the terminals on the conventional detector card (1-8). See wiring diagrams again. In the wiring diagrams and on the PCB itself they are marked by "ML”.
After this the user can select the new zone(s). "From zone” means the starting zone and any sequencing zones will be put into the next zones.
Please confirm every line by "OK” and after finishing press "save" (F4) to save the new configuration.
111
Sensitivity Day 4 Mode 3 Sensitivity Night 2 Mode 1 Timer program : 02 Delay on alarm : 000 Delay on fault : 000 Pre alarm
: No
Cancel No Yes save
Only for Hochiki ESP
Table of the detector sensitivities:
Sens. Opt.
ALG-EN
Heat ATG-E
Ion. AIE-E
0 2,0 % 50° 0,20 V 1 2,5 % 55 ° 0,24 V 2 3,0 % EN54 60° - A1S 0,28V EN54 3 3,5 % 66° 0,32 V 4 4,0 % 72° 0,36 V 5 4,5 % 78° - BS 0,40 V 6 5,0 % 83° 0,44 V 7 5,5 % 88° - CS 0,48 V
Table of multi sensor ACA-E modes:
Mode Operating
1 Multi sensor 2 Optical smoke detector 3 Heat detector 4 Heat + opt. Pre-alarm
Analogue addressable detector’s sensitivity / modes / delays
Selected detectors can be configured :
Only for Hochiki ESP
one of 8 sensitivities during the day (see
table in left column)
one of 8 sensitivities during the night (see
table in left column)
4 different modes for multi sensors ACA-E
(see table in left column)
2 different modes for multi heat sensors
ACB-E (see table in left column)
Mode 4 is a special setting for multi sensors ACA-E, where an alarm in optical part will cause a pre alarm at the FCP, independently of the parameter settings for pre alarm. An alarm in the heat component will activate an alarm in any case. If there is programmed an alarm delay for a multisensor in mode 4, this will have the effect, that a pre alarm of the optical part will change to an alarm after expiry of the delay. If the delay is 0 the optical component will never raise a real alarm.
NSC Sicherheitstechnik GmbH 51/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
Table of multi sensor ACA-E sensitivities and modes:
Sens. Mode 1 /2
Opt./ Multi
Mode 3 Heat
Mode 4 Heat+Opt.
1 2,0 % 50° 60°+2,0% 2 2,5 % 55 ° 78°+2,0% 3 3,0 % EN54 60° - A1S 60°+3,0% 4 3,5 % 66° 78°+3,0% 5 4,0 % 72° 60°+4,0% 6 4,5 % 78° - BS 78°+4,0% 7 - 83° 88°+2,5% 8 - 88° - CS 88°+3,5%
Table of multi sensor ACB-E modes:
Modus Meaning
1 Maximum Detector 2 Max.-Diff Detector
Table of multi sensor ACB-E sensitivities and modes:
Sens. Modus 1
Fix.
Modus 2 Fix. + Rate of rise
1 50° 60 °C - A1R + 14 K/min 2 55 ° 60 °C - A1 + 25 K/min 3 60° - A1S 78 °C – BR +16 K/min 4 66° 78 °C – B +25 K/min 5 72° 88 °C – CR + 16 K/min 6 78° - BS 88 °C – C + 25 K/min 7 83° ­8 88° - CS -
Only for Apollo
Table for detector sensitivities: Ionisation smoke detector Discovery
Sens. Alarm
threshold
Minimum time to alarm
1 0,45 5 Sec. 2 0,45 30 Sec. 3 0,70 5 Sec. 4 0,70 30 Sec. 5 1,0 5 Sec.
Optical smoke detector Discovery
Sens. Alarm
threshold
Minimum time to alarm
1 1,4 5 Sec. 2 1,4 30 Sec. 3 2,1 5 Sec. 4 2,1 30 Sec. 5 2,8 5 Sec.
Only for Apollo
one of 5 sensitivities during the day (see
table in left column)
one of 5 sensitivities during the night (see
table in left column)
the mode has no meaning and will be
automatically set by the sensitivities (see table in left column).
NSC Sicherheitstechnik GmbH 52/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
Heat detector Discovery
Sens. Class
EN54-5:2000
static alarm­temperature min. typ. max.
1 A1R 54 57 65. 2 A2 54 61 70 3 A2S 54 61 70 4 CR 84 90 100 5 CS 84 90 100.
Multi sensor Discovery
Sens. Alarm
threshold
Minimum time to alarm
1 1,1 Multi. 20 Sec. 2 2,1 Optical 30 Sec. 3 2,8 Multi. 20 Sec. 4 4,2 Multi. 20 Sec. 5 - Heat 30 Sec.
all automatic detectors XP95/XPlorer
Sens. Alarm
threshold
1 45 EN54 2 50 EN54 3 55 EN54 4 60 No EN54 5 64 No EN54
For all detector types
1 timer program for switching day / night
mode
an alarm delay time – if the detector detects
an alarm the acceptation of the alarm condition can be delayed here just to make sure that it is no false alarm. During this time the detector checks the alarm signal again and again.
an fault delay time which way of operation is
similar to the alarm delay above
Individual pre alarm of every detector
If you want to use the Timer program it must be configured before according menu 65. This timer program handles the day / night mode switching and switching from one sensitivity (mode) to another one and vice versa.
Please confirm every line by "OK” and after finishing press "save" (F4) to save the new configuration.
112
Timer program 01
1. Sunday 5. Thursday
2. Monday 6. Friday
3. Tuesday 7. Saturday
4. Wednesday
Cancel Enter
To configure timer programs
The example on the left side shows timer program 01. Please first select the day by using the cursor keys
, : Marker ">" one line up / one line down and confirm this by F4 ("Enter") or type the number of the day directly by using the keypad Jump to
Menu 120
113
Interfaces UART 1
1. Printer 5. Modbus SCU800
2. FRP 6. LED Tableau
3. PC 7. Modbus OPCx
4. ESPA 4.4.4 8. Modbus PLC
Cancel On save
Interface protocols
The example on the left side shows UART 1. Please select the protocol you want to assign to UART 1 by using the cursor keys. The following protocols are available :
Printer FRP (Fire Brigade Repeater Panel) PC configuration (Laptop) ESPA 4.4.4 (Option) LED mimic panel (old version WSK) Modbus SCU800 (Option) Modbus OPC (Option) Modbus PLC (Option)
After selecting the protocol it has to be activated by pressing F2 ("On"). The activation will be indicated in the 1st display line.
By pressing F3 ("Off") the protocol will be deactivated again.
Press "save" (F4) to save the new configuration.
NSC Sicherheitstechnik GmbH 53/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
114
Interfaces UART 1
1. 4800 5. 57600
2. 9600 x 6. 115200
3. 19200 7. 1200
4. 38400 8. 2400
Cancel Off save
Interface baud rates
The example on the left side selects baud rate of 9600 of UART 1.
The way or operation is similar to selecting the protocol as described above.
115
Convent. detect.
Open Cir
cuit [x0,01mA] : 0180
1. Alarm [x0,01mA] : 1000
2. Alarm [x0,01mA] : 3000
Reset time [x100ms] : 020
Cancel save
Configuring thresholds for conventional detectors
This menu is to configure several thresholds for conventional detectors. This is important if It is necessary to configure a threshold for open circuit (wire break), 1. and 2. alarm as well as a reset time fort he detectors which is needed in case of alarm reset. This time determines the period when the voltage on the line drops down to zero to reset all detectors on this line.
Press "save" (F4) to save the new configuration. If you have any doubts about these values for the
requested detectors have a look into their data sheet. If the FCP is shipped out by NSC the values above are adjusted for Hochiki CDX and Apollo S65 / Orbis.
116
Maintenance Day : 09 Status Month : 07 Off Year : 04 Hour : 07
Cancel On save
Maintenance
Here you can define a date for the next necessary maintenance. When this date is reached, a fault message will be generated.
By pressing F2 ("on") this function will be enabled. By pressing F4 ("save") the date will be saved.
117
Push button S_1
1. End user code x
2. Installer code
Cancel off save
Push button S_ settings
For the special push buttons S1-S8 the following access levels can be configured:
No code
End user code
Installer code
By F2 ("on") or F3 ("off") the code will be activated or deactivated.
By F4 ("save") the settings will be saved.
118
Zone LEDs LED-No. : Network-ID : Zone :
Cancel save
Zone LEDs
Number of LED, network-ID and zone number has to be put in. In a network one device can display zone status of other device.
By F1 ("Cancel") you will jump to the former menu. By F4 ("save") the settings will be saved.
NSC Sicherheitstechnik GmbH 54/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
120
Timer program 01 Sunday
time 1: 06:00 Day time 2: 18:00 Night time 3: 00:00 Night
time 4: 00:00 Night
Cancel Day Night save
Configuring the timer
The example on the left side shows timer program 01. The selected weekday is indicated in the 2. line of the LC module.
Please select first if you want to switch into day mode (F2) or night mode (F3) and then type in hour and minute. Please confirm hour and minute by "OK". The cursor runs automatically into the next line when you have confirmed the minute by OK
Day- and Night relates to the sensitivities/modes as described in Menu 111.
When you have finished press "save" (F4) to save the new configuration.
121
Event Output module 01/089/01 0001/2048 Output 001 Inactive >0001:Alarm 0001/000-0003/000 0002:Activation Relay 0001-0001 0003:Alarm 0032/000-0064/000 0004:free 0005:free Cancel insert delete Enter
Event Push button S1 0001/2048 ->Output 001 Inactive 0001:Alarm 0000/000-0000/000 0002:Activation Relay 0001-0001 0003:Alarm 0000/000-0000/000 >0004:free 0005:free Cancel insert delete Enter
Cause and Effect events list
The example on the left side shows an overview of all configured cause and effect events. The events are numbered from 1 to 2048. Behind the number the cause and effect type is displayed.
The first line of the LC module shows the device which shall be configured at the moment because this has been selected before. The last two digits (here :
01) indicates that output 1 of this module is selected. The second line of the LC module relates to the marker ">" and shows the configuration which is saved at the marker’s position. In the example above it is the first cause and effect event at all and it is an alarm event of OC output 01 (on the main board).
If you want to configure a new event you have to put the marker on a "free” event and type "Enter” (F4”) Jump to Menu 130
The FCP "Solution F1-6 and F1-18" support up to 2048 events.
The user can also "delete" (F3) events and "insert” (F2) new events in between existing events. Therefore the marker ">" has to be put at the right position. The sequence doesn’t really matter but if the user likes to have e.g. all cause and effect events of the loop output modules one under the other he can arrange it by inserting at the right place.
Left: Example of cause and effect event for macro push button S1.
130
Event 0004/2048 Output module 01/089/01 Inactive Code : Alarm FCP : 001 from zone : 0001 Detect. : 000 to zone : 0064 Detect. : 000 OR Cancel modify OK save
Cause and Effect events configuration
The example on the left side shows in line 1 that we are going to configure event 4 of 2048 possible events. The second line shows the selected device. In this case an Output module on loop 1, address 89 output 1. The kind of event which shall cause an effect is
NSC Sicherheitstechnik GmbH 55/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
always preset to "Alarm” (line 3 of the LC module). If you want to change it please press F2 ("modify") Jump to Menu 131
Otherwise confirm the code by pressing F3 ("OK"). The number of the FCP is always 1 besides there is a
network with several FCP interlinked. Then type the zone(s) and detector(s) which have to
be in alarm to activate this output module. If you want to select whole zone(s) (and no individual detectors) leave the detector = 000. Please confirm every input by "OK". Pay attention to the fact that the zone(s) and detector(s) can be configured logical "AND", "OR” or "AND NOT". That means (in case of AND) that all zones or detectors must be in alarm simultaneously to activate the output.
You can change between "AND", "OR” or "AND NOT" by F3. Then please press F4 ("save") to save the new cause and effect event.
131
Codes for outputs
Page 1
Code
1. Alarm 5. Switch off
2. Pre alarm 6. Reset FC Panel
3. Main alarm 7. Fault power sup
.
4. Fault 8. Mains fault
Cancel more Enter
Page 2
Code
1.Alarm autom. Det. 5. Delay activated
2.Alarm MCP 6. Tran.Dev. active
3.KDB alarm 7. Tran.Dev. disabl.
4.KDB unlocked 8. 2.Alarm
Cancel more Enter
Page 3
Code
1.Techn. Alarm. 5.Timer program
2.KDB output active
3.Testalarm
4.Activation
Cancel more Enter
Event codes
Please select desired code by input of corresponding number or by using arrow keys. Please confirm by pressing F4 ("Enter").
For codes "Alarm", "Pre alarm", "Main alarm", "Fault", "Switch off" and "Techn. Alarm" additionally zone and detector number can be put in. By code "Mains fault" i.e. the heater of the KDB can be switched of if it is supplied by FCP.
By code 1 and 2 outputs can be activated to verify the alarm source. Further codes for status messages are available. For code "2. Alarm" a zone number can be typed in. By this code a cross detection can be realized to activate an output if main alarm is additionally delayed by reaction/investigation time.
On events "Techn.Alarm", "KDB output active", "Test alarm" and "Activation" the output reacts according the messages of the FCP.
A special function is available by the code "Timer program". Outputs can be activated / deactivated by any of the available 16 timer programs automatically.
NSC Sicherheitstechnik GmbH 56/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
Codes for inputs
Page 1
Code
1. Alarm 5. Switch on/off
2. Pre alarm 6. Revision
3. Main alarm 7. Change sensit.
4. Fault 8. Activation
Cancel Enter
Page 2
Code
1. Active 5. Installer
2. Inact.
3. Information
4. End user
Cancel Enter
Codes for special keys
Code
1. Switch on/off
2. Change sensit.
3. Activation
Cancel Enter
For codes "Alarm", "Pre alarm", "Main alarm", "Fault" and "Switch off" additionally zone and
detector number can be put in.
To use it, a not existing address (virtual detector) has to be programmed to that zone/detector number.
(s.
Alarm configuration - Zones ->Menu 109)
. This also can be a detector on a not existing loop card. Then activation of an input simulates message from a detector and all programmable features of that detector (i.e. customer text) or that zone (i.e. alarm configuration) can be used.
By code "Revision" you can enter the one-man­revision mode by activation of an input.
By code "Activation" directly outputs, relays, power outputs or loop modules can be activated.
Code "Active" allows activating any system output by an input signal, i.e. a push button. The same output could be switched inactive by a different input choosing the code "Inactive".
Code "Information" means, that only an activation message will be generated but no alarm and no fault message.
Code "End user" gives you the opportunity to enter the second control level without typing in the end user password, i.e. by connecting a key switch to an input configured to "End user" code. Code "Installer" is the same for installer password.
NSC Sicherheitstechnik GmbH 57/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
4. Mounting instruction
1. First please remove the cover of the FCP. You will find the key on the backside of the panel housing.
2. The FCP "Solution F1" has a wall mounting housing. The B1 and B2 housings provide a drilling template for easier mounting. Use this template for drilling the holes.
3. Please use 8mm dowels for fixing the screws. Don’t put the batteries into the panel yet. Start with the upper screws; hang the back plate of the housing on the screws and then you can screw the lower holes.
4. The control panel can be opened by unscrewing the plastic screws only on the right side of the control panel, giving free access to the terminals for connecting the wires.
5. Don’t connect the panel to Mains AC yet. Use the wiring diagrams for connecting loops, conventional zones and sounders / strobes.
6. If you are connecting the shielding of the loop wires (the FCP "Solution F1" does NOT need that in any case but it can be advantageous to do so) then you have to connect the wire on both sides at the loop card.
7. Please connect peripheral components like LCD repeater panels, remote control panels etc.
8. Now you have to connect the Mains AC cable. Make sure that the Mains AC fuse on the power supply is plugged in.
9. Switch on Mains AC voltage.
10. If the internal buzzer sounds, please switch of by using push button .
11. Put the batteries on the bottom of the panel housing and fix them by using the cable fixer. Connect the batteries to the power supply by using the supplied cables (see wiring diagram).
12. Please follow the commissioning instruction.
NSC Sicherheitstechnik GmbH 58/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
5. Commissioning certificate FCP "Solution F1"
____________________________________________ ____________________________________________
Serial number Date of delivery
F1-6 :
F1-18 :
___________________________________________
Panel type (please mark) Commission/ Sight
____________________________________________
Installed by : date, technician
General
The commissioning according the national rules requires the complete and accurate installation of all components of fire control system, as it is specified in the engineering documents.
Checking the documentation
Document available
yes/no
Repository
Engineering order Final planning documents Updated planning documents Fire brigade documents
Checking the system components
You have to compare the quantity of planned components with the quantity of actually installed components.
Component Planned quantity Installed quantity
Fire control panel Modules for addressable detectors Modules for conventional detectors Automatic detectors Manual call points Input-/output modules Sounder modules Remote panel Fire brigade panel Fire brigade remote panel Transmission device Fire brigade key deposit box Key deposit box release device Additional power supply Sounder Flashlight Telephone server SCU800
NSC Sicherheitstechnik GmbH 59/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
Checking the wiring system
Before checking the wiring system you should disconnect all cables from the fire control panel by removing the pluggable terminals.
Measure end of line resistors of conventional zones (without voltage)
6k8 (±10%) end of line resistor measurable on each conventional zone?
Ο Fault check wiring and end of line resistor. Ο ok plug terminals in fire control panel
Measure cable resistance of loop wiring (without voltage)
If isolators are installed on the loop you only can measure the resistance of the minus wire. You have to measure the cable resistance of each loop. The minimum operating voltage for each
loop device will be calculated from the cable resistance and the loop current, which has to be measured later.
The resistance of the shielding also has to be written down in the following table. Additionally this measurement guarantees that the shielding isn’t interrupted in any loop device. As long as the shielding hasn’t been connected to earth in the FCP there must not be any other connection to earth potential (e.g. in a detector base).You can check this by measuring the resistance between the shielding and earth potential.
Loop card Loop ML-Wire
[}
Shielding
[]
Wiring without
earth fault
1 1
(ML-1-/ML-2-)
yes no
1 2
(ML-5-/ML-6-)
yes no
2 3
(ML-1-/ML-2-)
yes no
2 4
(ML-5-/ML-6-)
yes no
3 5
(ML-1-/ML-2-)
yes no
3 6
(ML-5-/ML-6-)
yes no
4 7
(ML-1-/ML-2-)
yes no
4 8
(ML-5-/ML-6-)
yes no
5 9
(ML-1-/ML-2-)
yes no
5 10
(ML-5-/ML-6-)
yes no
6 11
(ML-1-/ML-2-)
yes no
6 12
(ML-5-/ML-6-)
yes no
7 13
(ML-1-/ML-2-)
yes no
7 14
(ML-5-/ML-6-)
yes no
8 15
(ML-1-/ML-2-)
yes no
8 16
(ML-5-/ML-6-)
yes no
9 17
(ML-1-/ML-2-)
yes no
9 18
(ML-5-/ML-6-)
yes no
If the cable resistance is correct please plug the terminals in the FCP.
NSC Sicherheitstechnik GmbH 60/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
Measurement of the end of line resistors of the monitored power outputs (without voltage)
Power output
Key deposit box Sounder/flashlight Transmission device
1 depends on type
1K/1W
tolerance 10%
-
Ο fault Ο ok
2 -
1K/1W
tolerance 10%
1K/1W
tolerance 10%
Ο fault Ο ok
3 -
1K/1W
tolerance 10%
1K/1W
tolerance 10%
Ο fault Ο ok
The end of line resistor has to be mounted in the last device of the power output cable. The adaptation of open circuit and short circuit thresholds for the connected devices has to be done directly at the FCP. Please go to "Installer" -> "more" (F3) -> "more" (F3) -> "Power outputs".
Measurement of the end of line resistors of the monitored inputs (without voltage)
Input line End of line resistor
Key deposit box alarm
2,2K/0,5W
tolerance 10%
Ο fault Ο ok
Extinguish interface
3,3K/0,5W
tolerance 10%
Ο fault Ο ok
Checking the end of line resistor on the RS485 bus
End of line resistor activated at first and last device (jumper matched)?
Ο Ok Ο fault
Commissioning of the power supply
- plug 230VAC mains cable or check already plugged cable!
- switch on power supply for fire control panel!
The internal buzzer will be on: please switch off by pressing
NSC Sicherheitstechnik GmbH 61/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
Scanning of internal an external components Detector modules
After scanning process and uploading of the programming out of the flash memory all recognised components will be displayed in a list.
Example:
Internal Modules
1. Loop card HOCHIKI ESP : 01
2. Loop card Apollo XP : 00
3. Conventional detector card : 01
4. Input-/output module : 00
Cancel Details
Number of mounted detector modules correctly recognised?
Ο Ok Ο fault
By pressing the "Details" key F3 the addresses of the modules can be checked.
Example:
Internal Modules 1/09
>01 Loop card HOCHIKI ESP 02 Conventional detector card 03 - 04 - 05 - 06 - Cancel Details
Addresses of the mounted detector modules correctly set?
Ο Ok Ο fault
Serial devices
Afterwards the serial interfaces will be scanned for connected components. The result with the number of recognized devices will be noticed in the module list. .
Example:
Internal Modules
5. Network interface card : 00
6. Modem : 00
7. FBC/LCD panel : 04
8. Modbus device : 01
Cancel Details
Number of installed serial devices correctly recognized?
Ο Ok Ο fault
NSC Sicherheitstechnik GmbH 62/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
By pressing the "Details" key F3 the addresses of the modules can be checked.
Example:
Internal Modules
01/63
>01 FRP with FBC A B 02 Remote LCD Panel A 03 Remote LCD Panel A 04 FRP A B 05 - 06 -
Cancel Details
By letters "A" und "B" will be displayed, on which channel of the redundant RS485 bus each device has been connected.
Addresses of the RS485 devices correctly set?
Ο Ok Ο fault
Wiring of the RS485 devices correct?
Ο Ok Ο fault
Addressable detectors/modules
During the initialisation permanently a counter will be displayed which is counting the total number of all detectors and modules. After scanning the loop devices, a list of these devices will be displayed. This list will be visible each time the number of recognised detectors/modules has changed after scanning the loops. Therefore after first time initialisation process all new recognised detectors/modules will be listed.
Example:
Detector configuration 0001/0265 Seg. |Add| Error | Zone |Detect
>01 o 1|001| new | 0000 | 000 01 o 1|002| new | 0000 | 000 01 o 1|003| new | 0000 | 000 01 o 1|004| new | 0000 | 000 01 o 1|005| new | 0000 | 000 continue all ok ok
In line 1 the number of all recognised detectors and modules will be displayed. In the table for each device will be displayed:
- Segment, where the device is connected to
- Symbol for loop "o" or spur wiring "-"
- Number of loop/spur
- configured device address
- Error code ("new" in this example)
- programmed zone and detector number By pressing the "ok" key each single detector can be stored in the FCP programming, by pressing "all
ok" all connected devices will be stored in the FCP flash memory simultaneously.
NSC Sicherheitstechnik GmbH 63/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
Checking of earth fault
A constant voltage must not be measurable between potential earth and fire control panel potential there
Voltage between PE / - accumulator
Ο Ok Ο fault -> .............V
Voltage between PE / + accumulator
Ο Ok Ο fault -> .............V
In case of an earth fault this has to be localised by disconnecting single cables in the fire control panel. Then the earth fault has to be removed. The supervision of an earth fault can be deactivated by system parameter 13.
Measurement of loop voltage and current
Dependent of the used multimeter the voltage and the current will vary differently. This is caused by the modulated protocol between the FCP and the loop devices. For the measurement of the current the loop has to be separated on one side in the FCP and on the other side the current has to be measured on the ML+ or ML- wire. At the same time the loop devices have to be in the quiescent state. Decisive for a faultless operation is the fact, that all loop devices are supplied by a sufficient voltage (17V). The voltage drop on the cable has to be calculated form the quiescent current and the cable resistance measured under point 4.2.
Loop card Loop Voltage
33V ± 3V
Quiescent
current
[mA]
Voltage drop[V]
(quiescent current x
cable resistance)
1 1
(ML-1-/ML-2-)
1 2
(ML-5-/ML-6-)
2 3
(ML-1-/ML-2-)
2 4
(ML-5-/ML-6-)
3 5
(ML-1-/ML-2-)
3 6
(ML-5-/ML-6-)
4 7
(ML-1-/ML-2-)
4 8
(ML-5-/ML-6-)
5 9
(ML-1-/ML-2-)
5 10
(ML-5-/ML-6-)
6 11
(ML-1-/ML-2-)
6 12
(ML-5-/ML-6-)
7 13
(ML-1-/ML-2-)
7 14
(ML-5-/ML-6-)
8 15
(ML-1-/ML-2-)
8 16
(ML-5-/ML-6-)
9 17
(ML-1-/ML-2-)
9 18
(ML-5-/ML-6-)
NSC Sicherheitstechnik GmbH 64/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
Configure power outputs
Load resistance Tolerance No.: ( old) Norm OC-Tol. Th.OC Th.SC 1 : (0983) 0983 + 120 = 1103 , 0727 Ohm 2 : (0977) 0977 + 120 = 1097 , 0724 Ohm 3 : (0964) 0964 + 120 = 1084 , 0717 Ohm
Cancel Calib. save The thresholds depend on the load resistance of the connected device inclusive the line resistance.
This total resistance can be ascertained automatically for each power output individually by pressing "calib." F3. The software then calculates the thresholds for open circuit and short circuit. The resistance can also be measured with a multimeter and typed in directly using the keyboard.
Configuration of the fire control system
The configuration of the fire control system is very comprehensive and is mainly dependent of the largeness of installation. The details have to be specified in the planning documents. The following checklist describes the individual steps of the programming of the fire control panel:.
Programming Menu topic
Zones Alarm organisation
Ο Ok
Detector configuration
- sensitivity
- mode of multi sensors
- time program
- pre alarm
- alarm delay
Alarm organisation
Ο ok Ο not used Ο ok Ο not used Ο ok Ο not used Ο ok Ο not used Ο ok Ο not used
Detector texts by PC software
Ο ok Ο not used
Programming Menu topic
Zone parameters
- cross detection
- internal alarm zone
- fault zone
- manual call point (only for conventional detectors or modules)
Alarm organisation
Ο ok Ο not used Ο ok Ο not used Ο ok Ο not used Ο ok Ο not used
Cross zoning Alarm organisation
Ο ok Ο not used
Timer programs
- for delay
- for detector sensitivity
Alarm organisation
Ο ok Ο not used Ο ok Ο not used
Delay Alarm organisation
Ο ok Ο not used
Power outputs
- key deposit box
- sounders/flashlights
- transmission device
Automatic controlling
Ο ok Ο not used Ο ok Ο not used Ο ok Ο not used
Controlling of relays, outputs or output modules
Automatic controlling
Ο ok Ο not used
Loop sounders Automatic controlling
Ο ok Ο not used
Controlling by special keys Configuration
Ο ok Ο not used
System parameters Configuration
Ο ok Ο not used
Holidays Configuration
Ο ok Ο not used
NSC Sicherheitstechnik GmbH 65/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
Interfaces Configuration -> more
Ο ok Ο not used
Thresholds for conventional zones Configuration -> more
Ο ok Ο not used
Functional tests
Test
Measured value Test result
Normal operation
- green LED "Operation" lights
- green LED "Night" lights
Ο Ok Ο fault
Fire condition
- Test of all automatic detectors
- Test of all manual call points
The fire condition can be generated in the installer level by functions "test alarm" or "simulation".
Check display at FCP, remote panels and printer
Ο Ok Ο fault Ο Ok Ο fault
Fault condition
- loop
- power outputs
- monitored inputs
- RS485 bus
- battery
- mains fault (mains fault delay) Check display at FCP, remote panels and printer
..........
Min
Ο Ok Ο fault Ο Ok Ο fault Ο Ok Ο fault Ο Ok Ο fault Ο Ok Ο fault
Disabled condition
- detector
- zone
- power output Check display at FCP, remote panels and printer
Ο Ok Ο fault Ο Ok Ο fault Ο Ok Ο fault
Alarm devices
- transmission device activation
- flash lights
- sounders
Ο Ok Ο fault Ο Ok Ο fault Ο Ok Ο fault
Fire outputs
- relays
- outputs
- output modules
Ο Ok Ο fault Ο Ok Ο fault Ο Ok Ο fault
Current of FCP at mains fault Required bridge over time Required battery capacity
...............mA
………….h
…………Ah
Ο Ok Ο fault Ο Ok Ο fault
NSC Sicherheitstechnik GmbH 66/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
6. Technical specifications:
Power Supply
Mains voltage: 230V AC, -15% bis +10%, 50-60Hz Operating voltage: 24V DC (19,5V – 29,5V DC) Ripple 0,8 Vpp Max. load 330VA Version (B01620-0x) Max. Output current: 3,1 A (Imax a = Imax b) Max. Battery charge current: 3,6 A Max. load 180VA Version (B01622-0x) Max. Output current: 1,9 A (Imax a = Imax b) Max. Battery charge current: 2,3 A
The battery charge current can be limited in three levels: 1,3 A for 18 Ah battery, 2,3 A for 24 Ah battery or 3,6 A for 40 Ah and 65 Ah battery ( only 330VA version)
current consumption: 20 mA (without minimum load) Minimum load: 100 mA Battery charge voltage: 27,3V +/- 0,12V (at 20°C) Max. Battery internal resistance
for all battery types
400 m
Operating temperature: -5°C to +40°C Humidity: Max. 95% relative Humidness
NSC Sicherheitstechnik GmbH 67/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
Common technical data
Maximum number of zones per loop 127
Maximum number of addressable devices per loop
- Hochiki: 127 detectors/modules + 127 base sounders
- Apollo: 126 addressable devices
Maximum number of zones per FCP
- 1024 programmable
- 192 LED indicator
Maximum number of addressable devices per BMZ
- Hochiki: 2286 detectors/modules + 2286 base sounders
- Apollo: 2268 addressable devices
Alarm activation equipment per FCP 1 Quiescent current of FCP without loop cards: 90 mA Quiescent current loop card B01260-00/B01262-00 : 33 mA (without detectors) Quiescent current loop card B01270-00/B01272-00 : 38 mA (without detectors) Quiescent current of conventional card B01300-00 : 30 mA (without detectors) Quiescent current of conventional card B01310-00 : 35 mA (without detectors) Quiescent current of relay card: 4 mA Operating temperature: -5 to +40° C Humidity : Max. 95 % rel. Air humidity Housing : Steel sheet, RAL 7035 Safety class: IP 40 Dimensions housing A1, A2 : 540 x 492 x 162 mm (W x H x D) Weight FCP Solution F1-6 in housing A1, A2 : 14 kg Dimensions housing B1, B2 : 540 x 540 x 245 mm (W x H x D) Weight FCP Solution F1-18 in housing B1, B2 : 18,5 kg
NSC Sicherheitstechnik GmbH 68/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
Minimum/ maximum voltages/currents
Output loop card analogue
- voltage
- current
27 - 35 Volt 0 - 350 mA
Output conventional card
- voltage
- current
18 - 20 Volt 0 - 90 mA
OC output
- voltage
- current
0 - 30 Volt 0 - 50 mA
Power output
- voltage
- current
0,5 - 29 Volt 0 - 500 mA
Relay
- voltage
- current
0 - 30 Volt 0 – 1 A
Input
- voltage
- current
0 - 30 Volt 0 – 0,5 mA
Input extinguishing system
- voltage
- current
0 - 30 Volt 0 - 50 mA
Input KDB sabotage
- voltage
- current
0 - 30 V 0 - 50 mA
Fuse values
Power Supply Unit
- mains
- battery
- external 24V
3,15 A time lag 6,3 A super fast 500 mA time lag
Main board
- power output
- FBC Output
500 mA time lag 500 mA time lag
Cable parameter
- All installation cables
Fire system cable JY-(ST)Y-2x2x0,8
NSC Sicherheitstechnik GmbH 69/69 14.08.2013 Lange Wand 3 B01050 B01060 Operating Installation Manual Solution F1 20130814.doc 33719 Bielefeld Version S040A13.08
7. CE marking:
0786
NSC Sicherheitstechnik GmbH
Lange Wand 3
D-33719 Bielefeld
10
0786-CPD-20907
EN54-2:1997 + A1:2006 EN54-4:1997 + A1:2002 + A2:2006
Fire control panel for fire equipment inside of buildings
Solution F1
Available options:
- Output to the triggering of alarm devices (EN54-2, Cl. 7.8)
- Triggering of transmission devices for fire detections (EN54-2, Cl. 7.9)
- Output for the triggering of fire protection devices (EN54-2, Cl. 7.10)
- Fault surveillance of fire protection devices (EN54-2, Cl. 7.10.4)
- Delay of transmission (EN54-2, Cl. 7.11)
- Dependence of the fire detection condition on more than one alarm signal – dependence type A, B (EN54-2, Cl. 7.12)
- Alarmcounter (EN54-2, Cl. 7.13)
- Fault signals from points (EN54-2, Cl. 8.3)
- Output to the routing devices for fault signals (EN54-2, Cl. 8.9)
- Disablement of addressable points (EN54-2, Cl. 9.5)
- Test condition (EN54-2, Cl. 10)
- Standardized I/O interface (EN54-2, Cl. 11)
For technical data see chapter 6 of this manual.
Loading...