Vb= Voltage required by the 2-wire
Vin = V
TxIsoLoop-1 / TxIsoLoop-2
LOOP-POWERED ISOLATORS - OPERATING MANUAL V1.0x D
INTRODUCTION
The TxIsoLoop-1 and TxIsoLoop-2 are 0(4)-20 mA s ignal isolators
with one and two channels respectively. They provide signal
protection by electrically i solating the input signal from the output.
The 4-20 mA input is meas ured and an identical isol ated signal is
produced at the output. Its power is obtained from the 0(4)-20 mA
input loop, dropping the need for an external power supply.
CHARACTERISTICS
• Input/output galvanic isolation.
• Models for 1 or 2 channels.
• Don’t require power supply.
• High accuracy.
• Calibration free.
ESPECIFICAÇÕES
• Input Signal (INPUT): 0 to 20 mA; 4 to 20 mA
(check minimum current for proper operation)
• Max. Input voltage (Vin max.): 32 Vdc
• Voltage drop input/output without protection (Vdrop): < 3 Vdc
• Voltage drop input/output with protection (Vdrop): < 5 Vdc
• Output Signal (OUTPUT): 0(4) to 20 mA
• Max. Load (RL): 1450 R
• Accuracy: 0.2 % FS @ 0 a 60 ºC / RL= 250 R
0.3 % FS @ -20 a 75 ºC / RL= 250 R
• Operating current: > 0,1 mA
• Overload: < 40 mA; < 32 Vdc
• Response time: 2 ms @ RL= 250 R
• Isolation: 3000 Vac / 10 s
240 Vac continuous
• EMC: EN 61326-1
• Ambient temperature range: -20 to + 75 ºC
• Humidity: 20 a 90 %
• Case: ABS (60 %) + PC (40 %). Protection: IP40
• Wire gauge for connections: 0.14 a 1.5 mm²
• Recommended torque: 0.8 Nm
• Terminal blocks injected in Polyamide.
ELECTRICAL INSTALLATION
For proper operation, the TxIsoLoop requires some minimum
voltage in the input loop. This voltage can be found in two ways:
1. In type source devices (trans mitters, cont rollers, etc ), this voltage
is provided by the device itself.
Fig. 1 – TxIsoLoop typical connections
The minimum operating voltage can be calculated by the equation
below:
V1 = V
in
Where:
2. In sink type devices (2-wire transmitters ) the energy is provided by
an external power supply in series in the loop, as shown in Fig. 2.
Fig. 2 – TxIsoLoop us ed to isolate a 2-wire transmitter
In this arrangement, the p ower sup ply must prov ide enough v oltage
such as power both the 2-wire transmitter and the TxIsoLoop.
The minimum voltage required to allow proper operation can be
obtained from the equation below:
V1 = Vb +
V
in
Where:
Vin = V
V1= Power supply voltage
transmitter
drop
out
drop
out
+ ( I
out(máx)
out(máx)
x RL )
NOVUS AUTOMATION 1/2
ELECTRICAL WIRING
The figure below shows the wiring scheme.
Fig. 3 – TxIsoLoop-1 connections
SAFETY INFORMATION
Any control system design sh ould take into acc ount that any part of
the system has the potential to fail. Thi s product is not a protection
or safety device and its alar ms are not intended to protect against
product failures. Independent safety devices should be always
provided if personnel or property are at risk.
Product performance and specifications may be affected by its
environment and installation. It’s user’s responsibility to assure
proper grounding, shielding, cable routing and electrical noise
filtering, in accordance with local regulations, EMC standards and
good installation practices.
SUPPORT AND MAINTENANCE
This product contai ns no serviceable parts inside . Contact our local
distributor in case you ne ed authorized service. For troubl eshooting,
visit our FAQ at www.novusautomation.com
.
Fig. 4 – TxIsoLoop-2 connections
Fig. 5 – TxIsoLoop-1 a nd TxIsoLoop-2 connections with and wit hout pr otec t ion
RECOMENDATIONS FOR INSTALLATION
• Signal wires should be instal led in grounded conduits an d away
from power or contactor wires.
• The instrument should have its own power supply wires, which
should not be shared with electrical motors, coils, contactors, etc.
• Installing RC filters is strongly rec ommended at contac to r coi l s or
any other inductors.
• System failure should always be taken into account when
designing a control panel to avoid irreversible damage to
equipment or people.
MECHANICAL INSTALLATION
The transmitter is intended for DIN rail mounting:
LIMITED WARRANTY AND LIMITATION OF LIABILITY
NOVUS warrants to the original purchaser that this product is free
from defects in material and workmanship under normal use and
service within one (1) ye ar from the date of shipm ent from factory or
from its official sales channel to the original purchaser.
NOVUS liability under thi s warranty shall not in any case exceed the
cost of correcting d efects in the product o r of supplying replaceme nt
product as herein p rovided and upon the expirati on of the warranty
period all such liability shall terminate.
For complete informati on on warranty and liability limitations, check
appropriate section in our web site: www.novusautomation.com
.
Fig. 6 – Isolator dime nsions
NOVUS AUTOMATION 2/2