
NOVATEK-ELECTRO Ltd
Intelligent industrial electronics
TIME DELAY RELAY
REV-120
OPERATING MANUAL
The quality management system of development and production complies with the requirements
of ISO 9001:2015
Dear Customer,
Company thanks you for purchasing our products.
You will be able to use properly the product after carefully studying the Operating Manual.
Keep the Manual throughout the service life of the product.
www.novatek-electro.in

- 2 -
REV-120 NOVATEK-ELECTRO
ATTENTION! ALL REQUIREMENTS OF THIS OPERATION MANUAL ARE COMPULSORY TO BE MET!
WARNING! – PRODUCT TERMINALS AND INTERNAL COMPONENTS ARE UNDER
POTENTIALLY LETHAL VOLTAGE.
TO ENSURE THE PRODUCT SAFE OPERATION IT IS STRICTLY FORBIDDEN THE
FOLLOWING:
– TO CARRY OUT MOUNTING WORKS AND MAINTENANCE WITHOUT DISCONNECTING THE
PRODUCT FROM THE MAINS;
– TO OPEN AND REPAIR THE PRODUCT INDEPENDENTLY;
– TO OPERATE THE PRODUCT WITH MECHANICAL DAMAGES OF THE CASE.
IT IS NOT ALLOWED WATER PENETRATION ON TERMINALS AND INTERNAL ELEMENTS OF THE
PRODUCT.
During operation and maintenance the regulatory document requirements must be met, namely:
Regulations for Operation of Consumer Electrical Installations;
Safety Rules for Operation of Consumer Electrical Installations;
Occupational Safety in Operation of Electrical Installations;
Installation, adjustment and maintenance of the product must be performed by qualified personnel
having studied this Operation Manual.
The product is safe for use under keeping of the operating rules.

- 3 -
NOVATEK-ELECTRO REV-120
This Operation Manual is intended to familiarize you with arrangement, the requirements for safety,
operation and maintenance procedures of the time delay relay REV–120 (hereinafter referred to as the
"product", "REV–120").
The product meets the requirements of the following:
• Low-voltage switchgear; Part 1; General rules (IEC 60947-1);
• Low-voltage circuit breaker and controller; Part 6-2; multifunctional equipment; Control and safety
switching equipment (ІEC 60947-6-2);
• Electromagnetic compatibility; Industrial, scientific and medical RF equipment; electromagnetic
interference characteristics; standards and measuring procedure (CISPR 11);
• Electromagnetic compatibility; Part 4-2; Testing and measurement techniques; Electrostatic discharge
immunity test (IEC 61000-4-2).
Harmful substances in amounts exceeding maximum permissible concentrations are not available.
Terms and abbreviations:
• It periodically flashes – the indicator short-time enabling.
• It periodically is off – the indicator short-time disabling.
1. APPLICATION
1.1. Product application
The time delay relay REV-120 is the microprocessor-based device intended for on/off switching the load in
user-defined time intervals.
REV-120 can be operated by ten operation modes:
on-delay;
time delay when energizing;
periodic with on-delay;
periodic with time delay when energizing;
off-delay (when control contact opening);
pulse I (when control contact closing);
pulse II (when control contact opening);
on/off delay (according to control contact);
pitch of the load relay (during each control contact closing);
pulse generator of 0.5 s.
1.2. Software revision history
19.05.2016 v2 Primary version of the program
1.3. Controls, overall and mounting dimensions of REV–120
Controls, overall and mounting dimensions are shown in Fig.1.
1 – input contacts ~230/240 V L, N;
2 – input control contact S;
3 – regulator for setting the time interval ∆T;
4 – regulator for setting the time Т;
5 – regulator for setting the operation mode W;
6, 7 – output contacts of load relay:
NO1 / NO2 – normally open contact (further
NO);
NC1 / NC2 – normally closed contact
(further NC);
С1 / С2 – switching contact (further С);
8 – LED indicator of load relay ON;
9 – LED indicator of power ON.
Fig.1 – Controls, overall and mounting dimensions of REV–120

- 4 -
REV-120 NOVATEK-ELECTRO
1.4. Operation conditions
The product is designed for operation in the following conditions:
– Ambient temperature: from minus 30 to +55 °С;
– Atmospheric pressure: from 84 to 106.7kPa;
– Relative air humidity (at temperature of +25 °С): 30 … 80%.
ATTENTION! The product is not intended for operation in the following conditions:
– Significant vibration and shocks;
– High humidity;
– Aggressive environment with content in the air of acids, alkalis, etc., as well as severe contaminations
(grease, oil, dust, etc.).
2. SPECIFICATIONS
Basic specifications of REV–120 are given in Table 1.
Specifications of the load relay contacts are given in Table 2.
Table 1 – Basic Specifications
Operating supply voltage, V
Frequency of supply mains, Hz
Voltage at which service capability is maintained, V
Permissible harmonic configuration (unsinusoidality) of power supply voltage
Readiness time when energizing, s, no more than
Accuracy of time delay, %, no less than
Accuracy of time setting (accuracy of scale), %, no less than
Number of operation modes
Adjustment range of time is divided into 10 subranges
0.1 … 1 s
1 … 10 s
6 s … 1 min
1 … 10 min
6 min … 1 h
1 … 10 h
0.1 … 1 day
1 … 10 day
Continuously ON
Continuously OFF
Switchgear and control gear
Rated operating condition
Type and quantity of contacts (switching)
Protection rating of case
Protection rating of terminal box
Commutation lifetime of output contacts if cos=1:
- under load of 6 А, time, no less than
- under load of 1 А, time, no less than
Power consumption (under load), W, no more than
Permissible contamination level
Electric shock protection class
Rated insulation voltage, V
Rated impulse withstand voltage, kV
Wire cross-section for connection to terminals, mm²
Tightening torque of terminal screws, N*m
Overall dimensions, H x D x L, mm
Product installation (mounting) is on standard 35mm DIN rail
The product remains functional at any position in space
Case material is self-extinguishing plastic

- 5 -
NOVATEK-ELECTRO REV-120
Table 2 – Specifications of output contacts of the load relay
Max. current at
U~250 V, А
Max. permissible
continuous AC voltage, V
Max. current at
UDC=28 V, A
3. INTENDED USE
3.1. Preparation for operation
3.1.1. Preparation for connection:
Unpack the product (we recommend to keep the original packing for the entire warranty period of the
product operation);
Check the product for damage after transportation; in case of such damages detection, contact the
supplier or manufacturer;
Carefully study the Operation Manual (pay special attention to the connection diagram to power
the product);
If you have any questions regarding the installation of the product, please contact the manufacturer by
telephone number indicated at the end of this Operating Manual.
3.1.2. General
If the temperature of the product after transportation or storage differs from the temperature of the
environment at which it is supposed to be operated, then before connecting to the mains hold the product
under operating conditions within two hours (because there is possible moisture condensation on the
elements of the product).
ATTENTION!
THE PRODUCT IS NOT DESIGNED FOR LOAD COMMUTATION IN CASE OF SHORT CIRCUITS.
THEREFORE, THE LOAD POWER SUPPLY CIRCUIT SHOULD BE EQUIPPED WITH THE CIRCUIT
BREAKER FOR CURRENT OF 6 A MAXIMUM.
ATTENTION! ALL CONNECTIONS MUST BE PERFORMED WHEN THE PRODUCT IS DEENERGIZED.
Error when performing the installation works may damage the product and connected devices.
To ensure the reliability of electrical connections you should use flexible (stranded) wires with insulation for
voltage of no less than 450 V, the ends of which it is necessary to be striped of insulation for 5±0.5 mm and
tightened with bootlaces. The cable cross section to connect the load depends on current (power) of the load.
For example for the current of 6 A it is no less than 1.5 mm2. Wires fastening should exclude mechanical
damage, twisting and abrasion of the wire insulation.
IT IS NOT ALLOWED TO LEAVE EXPOSED PORTIONS OF WIRE PROTRUDING BEYOND THE
TERMINAL BLOCK.
For reliable contact it is necessary to perform tightening of screws of the terminal block with the force
specified in Table 1.
When reducing the tightening torque, the junction point is heated, the terminal block may be melted and
wire can burn. If you increase the tightening torque, it is possible to have thread failure of the terminal block
screws or the compression of the connected wire.
To improve operational properties of the product it is recommended to install the fuse or its
analogue for 1 A current in power supply circuit for REV-120.
3.2. Product connection
3.2.1. Adjustment of the product
Before connecting the device, you should configure it. Its setting is performed in the following order:
• The operation mode adjustment;
• The time interval adjustment;
• The time delay adjustment.
For precise positioning the regulators ∆T and W it is recommended to rotate them to the extreme left and
then turning right to count the desired number of positions (fixation of position).
Note – when changing the operation mode or time intervals of the product under the power supply, it is
necessary to consider that the changes will take effect only after de-energizing (for at least 1 s) and reenergizing of the product.

- 6 -
REV-120 NOVATEK-ELECTRO
ATTENTION! Not to break or rotate the regulators to excessive extent, please do not use excessive
force when performing installation operations.
3.2.1.1. The product operation mode adjustment
List of the REV-120 operation modes is given in table 3.
Find the desired mode of the product operation according to Table 3 and set the regulator for the operation
mode setting W to the required position (Fig.1 it.5).
Table 3 – Product operation modes
After energizing, the set delay time t (Т
regulator) occurs. During the delay time
the indicator ON of the load relay (Fig.1
it.8) periodically flashes.
At the end of the delay time the load
relay contacts NO and C are closed,
the indicator ON of the load relay is on
and the product goes into standby
mode until power-off.
Time delay when
energizing
After energizing, the load relay contacts
NO and C are closed, the indicator ON
of the load relay (Fig.1 it.8) is on and
the set delay time t (Т regulator) occurs.
During the delay time the indicator ON
of the load relay periodically is off.
At the end of the delay time the load
relay contacts are opened, the indicator
ON of the load relay is off and the
product goes into standby mode until
power-off.
After energizing, the set delay time t
(Т regulator) occurs. During the
delay time the indicator ON of the
load relay (Fig.1 it.8) periodically
flashes.
At the end of the delay time the load
relay contacts NO and C are closed
for the set time t and the indicator
ON of the load relay is on. During the
delay time the indicator ON of the
load relay periodically is off.
At the end of the delay time the load
relay contacts are opened, and the product starts fulfillment of algorithm from the
beginning.
Periodic with time delay
when energizing
After energizing, the load relay contacts
NO and C are closed, the indicator
ONof the load relay (Fig.1 it.8) is on and
the set delay time t (Т regulator) occurs.
During the delay time the indicator ON
of the load relay (Fig.1 it.8) periodically
is off.
At the end of the delay time the load
relay contacts NO and C are open for
the set time t and the indicator ON of
the load relay is off. During the delay
time the indicator ON of the load relay periodically flashes.
At the end of the delay time the product starts fulfillment of algorithm from the
beginning.

- 7 -
NOVATEK-ELECTRO REV-120
After energizing, the product goes
into standby mode, in this case the
load relay contacts NO and C are
open, and the indicator ON of the
load relay (Fig.1 it.8) is off.
When control contact S is closed
with power supply terminal L, the
load relay contacts are closed, the
indicator ON of the load relay is on
and the product goes into standby
mode.
When control contact S is open, the set delay time t (Т regulator) occurs. During the
delay time the indicator ON of the load relay periodically is off.
At the end of the delay time the load relay contacts are open, the indicator ON of the
load relay is off and the product goes into standby mode.
In case of repeated closing of the control contact S, the algorithm is repeated.
After energizing, the product goes
into standby mode, in this case the
load relay contacts NO and C are
open, and the indicator ON of the
load relay (Fig.1 it.8) is off.
When control contact S is closed,
the load relay contacts are closed,
the indicator ON of the load relay is
on and the set delay time t (Т
regulator) occurs. During the delay
time the indicator ON of the load
relay periodically is off.
At the end of the delay time the load relay contacts are open, the indicator ON of the
load relay is off and the product goes into standby mode.
In case of opening and repeated closing of the control contact S, the algorithm is
repeated.
After energizing, the product goes
into standby mode, in this case the
load relay contacts NO and C are
open, and the indicator ON of the
load relay (Fig.1 it.8) is off.
When control contact S is closed,
the product continues being in
standby mode.
When control contact S is open, the
load relay contacts are open, the
indicator ON of the load relay is on
and the set delay time t (Т regulator) occurs. During the delay time the indicator ON
of the load relay periodically is off.
At the end of the delay time the load relay contacts are open, the indicator ON of the
load relay is off and the product goes into standby mode.
In case of closing the control contact S, the algorithm is repeated.

- 8 -
REV-120 NOVATEK-ELECTRO
After energizing, the product goes
into standby mode, in this case the
load relay contacts NO and C are
open, and the indicator ON of the
load relay (Fig.1 it.8) is off.
When control contact S is closed, the
set delay time t (Т regulator) occurs.
During the delay time the indicator
ON of the load relay periodically
flashes.
At the end of the delay time the load relay contacts are closed, the indicator ON of
the load relay is on and the product goes into standby mode.
When control contact S is open, the set delay time t (Т regulator) occurs. During the
delay time the indicator ON of the load relay periodically is off.
At the end of the delay time the load relay contacts are open, the indicator ON of the
load relay is off and the product goes into standby mode.
In case of repeated closing of the control contact S, the algorithm is repeated.
After energizing, the product
goes into standby mode, in this
case the load relay contacts NO
and C are open, and the
indicator ON of the load relay
(Fig.1 it.8) is off.
When control contact S is
closed, the load relay contacts
and the indicator ON of the load
relay change its state to the
opposite, and the product switches to standby mode.
When control contact S is open, the product continues being in standby mode.
In case of repeated closing of the control contact S, the algorithm is repeated.
After energizing, the set delay time
t (Т regulator) occurs. During the
delay time the indicator ON of the
load relay (Fig.1 it.8) periodically
flashes.
At the end of the delay time the
load relay contacts NO and C are
closed for 0.5 s, the indicator ON of
the load relay is on for 0.5 s and
the product goes into standby
mode until power-off.
3.2.1.2. Time interval adjustment
List of time intervals is given in Table 4.
Find the required time interval in Table 4 and set the regulator setting for the time interval ∆T (Fig.1 it.3) to
the required position.
Table 4 – Time intervals

- 9 -
NOVATEK-ELECTRO REV-120
3.2.1.3. Time delay adjustment
Time delay adjustment is performed by the regulator for setting Т time.
Based on the selected time interval (it.3.2.1.2), set the required time delay.
3.2.2. Product connection
Connect the product in accordance with the diagram given in Fig.2.
QF1 – Circuit breaker (fuse), maximum current is 6 А;
Fig.2 – Product connection diagram
3.3. Use of the product
After the power supply to the product the indicator ON (Fig.1 it.9) is on, there is small pause (no more than
400 ms) before the product begins to operate according to the selected operation mode.
The enabled load relay status corresponds to the closed condition of the contacts NO1-C1 (NO2-C2) and
the open condition of the contacts NC1-C1 (NC2-C2).
The disabled load relay status corresponds to the open condition of the contacts NO1-C1 (NO2-C2) and
the closed condition of the contacts NC1-C1 (NC2-C2).
Periodic flashing of LED indicator of the load relay indicates the time delay after which the load relay will
on.
Periodic disabling of LED indicator of the load relay indicates the time delay after which the load relay will
off.
4. MAINTENANCE
4.1. Safety precautions
THE TERMINALS AND THE PRODUCT INTERNAL ELEMENTS CONTAINS POTENTIALLY
LETHAL VOLTAGE.
DURING MAINTENANCE IT IS NECESSARY TO DISABLE THE PRODUCT AND
CONNECTED DEVICES FROM THE MAINS.
4.2. Maintenance of the product must be performed by qualified service personnel.
4.3. Recommended frequency of maintenance is every six months.
4.4. Maintenance procedure:
1) Check the connection reliability of the wires, if necessary, clamp with the force specified in Table 1;
2) Visually check the integrity of the housing, in case of detection of cracks and damages to remove the
product from service and send for repair;

- 10 -
REV-120 NOVATEK-ELECTRO
3) If necessary, wipe with cloth the front panel and the product housing.
Do not use abrasives and solvents for cleaning.
5. SERVICE LIFE AND MANUFACTURER WARRANTY
5.1. The lifetime of the product is 10 years. Upon expiration of the service life, contact the manufacturer.
5.2. Shelf life is 3 years.
5.3. Warranty period of the product operation is 5 years from the date of sale.
During the warranty period of operation (in the case of failure of the product) the manufacturer is
responsible for free repair of the product.
ATTENTION! IF THE PRODUCT HAS BEEN OPERATED IN VIOLATION OF THE REQUIREMENTS OF
THIS MANUAL, THE MANUFACTURER HAS THE RIGHT TO REFUSE IN WARRANTY SERVICE.
5.4. Warranty service is performed at the place of purchase or by the manufacturer of the product.
5.5. Post-warranty service of the product is performed by the manufacturer at current rates.
5.6. Before sending for repair, the product should be packed in the original or other packing excluding
mechanical damage.
You are kindly requested, in case of return of the product and transfer it to the warranty (post-
warranty) service, in the field of the claims data, list the detailed reason for return.
6. TRANSPORTATION AND STORAGE
The product in the original package is permitted to be transported and stored at the temperature from
minus 45 to +60 °C and relative humidity of no more than 80 %.
7. ACCEPTANCE CERTIFICATE
REV–120 has been manufactured and accepted in accordance with the requirements of current technical
documentation and classified as fit for operation.
Seal Head of QCD Date of manufacture
_____________ _____________
8. CLAIMS DATA
_______________________________________________________________________________________
_______________________________________________________________________________________
_______________________________________________________________________________________
_______________________________________________________________________________________
The Company is grateful to you for the information about the quality of the product and suggestions for its
operation.
For all questions, please contact the manufacturer:
NOVATEK ELECTRO INDIA PVT. LTD.
C-30, Patparganj Industrial Area, F.I.E.
Delhi – 110092, INDIA;
Tel.: +91 11 42143253
Tel./fax: +91 11 43010600
www.novatek-electro.in
Date of sale __________