Noty an76 Linear Technology

Application Note 76
May 1999
OPTI-LOOP Architecture Reduces Output Capacitance and Improves Transient Response
John Seago
Removing output capacitors saves money and board space. Linear Technology’s OPTI-LOOPTM architecture allows you to use the output capacitors of your choice and compensate the control loop for optimum transient response and loop stability. Figure 1 shows the dramatic improvement possible with the OPTI-LOOP architecture. With the improvement shown in Figure 1, less capacitance is required or less expensive capacitors can be used. Load dynamics and supply tolerances will predict the minimum output capacitance required. The quality of loop compen­sation determines how close you can get to this minimum capacitance requirement in a real world system.
One of the least understood areas of power supply design is control loop compensation. Because of this, some manufacturers provide loop compensation inside the regu­lator IC. Internal compensation works best with one set of operating conditions and is sensitive to output capacitor characteristics. Consequently, more expensive output capacitors may be required to stabilize the loop because of the sensitivities of the internal IC compensation. The OPTI-LOOP architecture is intended to allow circuit designers to squeeze the most performance out of the output capacitors of their choice.
OPTI -LOOP COMPENSATION
C
OUT
= 1500µF
WHAT IS LOOP COMPENSATION?
Loop compensation is the adjustment of the control loop frequency response to assure loop stability and optimize the transient response of the power supply. The frequency response is determined by the gain and phase of the loop’s reaction to load current changes at all frequencies. A Bode plot is used to show the gain and phase of the frequency response.
LOOP COMPENSATION BASICS
This application note contains a brief refresher course in control loop basics. Frequency response is characterized by the effects of poles and zeros. Each pole has a corner frequency, caused by a resistance and capacitance, that determines the beginning of a 20dB/decade drop in volt­age gain. The pole also causes the phase to decrease by 90°, starting roughly one decade before the corner fre­quency and ending about one decade after the corner frequency. A zero has the opposite effect of a pole. It causes the gain to increase by 20dB/decade starting at its “RC” corner frequency and it adds 90° of phase shift, starting one decade before the corner frequency and ending one decade after the corner frequency. The effects of poles and zeros are additive, so that two poles at the same frequency cause a 40dB/decade roll-off in gain and a 180° phase shift over two decades. If a pole and zero occur at the same frequency, their effects cancel.
COMPETITION
OUTPUT VOLTAGE (50mV/DIV)
TIME (10µs/DIV)
Figure 1. Improved Transient Response with OPTI-LOOP Architecture
VIN = 15V
= 1.6V
V
O
I
= 30mA to 7A
O
= 1500µF
C
OUT
DSOL8 F01
The crossover frequency of the loop determines the band­width and transient response of the power supply. The crossover frequency is the frequency at which the loop gain is one (0dB). The higher the crossover frequency, the faster the power supply can respond to changes in load current.
, LTC and LT are registered trademarks of Linear Technology Corporation.
OPTI-LOOP is a trademark of Linear Technology Corporation.
AN76-1
Application Note 76
In a voltage mode DC/DC switching regulator system, the buck inductor and output capacitor form a double pole at their resonant frequency, causing a 40dB/decade gain roll-off and 180° phase shift. Since the inductor’s effect on a current mode control loop is largely cancelled by the current loop, it is generally easier to compensate a current mode regulator than a voltage mode regulator.
The first requirement of loop compensation is stability. If the error amplifier’s feedback becomes positive when the loop gain equals one, the regulator will oscillate. A loop oscillation appears as a sine wave riding on the DC output voltage at the unity-gain frequency of the control loop. This oscillation will generally occur in the frequency range of 1kHz to 20kHz. Don’t confuse switching frequency ripple or higher frequency ringing with a loop instability.
If a network analyzer is available, stability margins can be determined by measuring the gain and phase of the loop and observing the resulting Bode plot. The phase margin is the difference between the signal phase and –360° when the voltage gain is one (0dB). A 60° phase margin is preferred, but 45° is usually acceptable. The gain margin is the amount of negative gain present when the signal phase is zero (– 360°). A gain margin of – 10dB is normally considered acceptable. Generous gain and phase margins are very important because actual component values vary
over temperature and component values differ from unit to unit in production, causing the loop’s voltage gain and phase to vary accordingly. If the component values cause the phase to go to zero when the voltage gain is one, the regulator will oscillate. The goal is to provide the best gain and phase margins with the highest crossover frequency possible. A high crossover frequency results in a quick response to load current changes whereas high gain at low frequencies results in fast settling of the output voltage. Nonideal components and amplifier gain limitations gen­erally force a trade-off between high crossover frequency and large stability margins.
THE CONTROL LOOP
Figure 2 shows the simplified control loop for the LTC®1628 and LTC1735/LTC1736 current mode, synchronous buck regulators. The control loop has both DC gain and AC frequency response characteristics. The DC loop consists of the feedback resistors, the error amplifier, the DC resistance of the ITH pin components, the current com­parator, the sense resistor and the load resistor. The AC loop consists of the DC loop plus the output capacitor, capacitors C1 and C2 and the AC impedance of the ITH pin components.
INPUT
C
IN
AN76-2
TOP
MOSFET
BOTTOM
MOSFET
SWITCH
NODE
(LTC1735/LTC1736)
INDUCTOR
TG
BG
LTC1628
MOSFET
CONTROL
LOGIC
+
CURRENT
COMP
MODULATOR ERROR AMPLIFIER
30k
30k
R
SENSE
SENSE
(10mV TO 65mV)
0V TO 75mV
(0.3V TO 2.2V)
0.3V TO 2.4V
I
TH
C4
R3
C3
+
ERROR
AMP
gm = 1.4mS
SENSE
+
V
OSENSE
0.8V
Figure 2. Basic Control Loop of Current Mode, Switching Regulator
OUTPUT
R1
C1
C
R
OUT
LOAD
C2
R2
AN76 F02
Application Note 76
DC GAIN
DC gain is the small-signal loop gain under static test conditions. Load regulation is determined by DC gain, so the higher the gain, the lower the change in output voltage for a given DC load current variation. The DC gain is the product of the feedback resistor attenuation, the error amplifier voltage gain and modulator gain. The modulator consists of the current comparator, the MOSFETs and their drivers, the inductor, sense resistor, output capacitor and load resistance: basically the power path.
The feedback divider attenuation is:
A
= V
V(FB)
where: V V
is the output voltage of the power supply.
OUT
REF/VOUT
is 0.8V for products in the LTC1735 family and
REF
The error amplifier voltage gain is:
A
= g
V(EA)
where: g
m(EA)ZITH
is the transconductance of the error ampli-
m(EA)
fier, 1.4mS for products in the the LTC1735 family and Z
is the output impedance of the error amplifier in
ITH
parallel with any impedance connected to the ITH pin.
g
m(MOD)
= (V
RSENSE(MAX)/RSENSE
)/V
ITH(MAX)
= (0. 075V/0.015)/2.1V = 2.38S A
V(MOD)
= g
m(MOD)RLOAD
= (2.38S)(3.3V/3A) = 2.62 = 8.4dB DC Gain = (A
V(FB)
)( A
V(EA)
)(A
V(MOD)
)
= (0.242)(4592)(2.62) = 2911 = 69.3dB
FREQUENCY RESPONSE
Frequency response is the loop’s reaction to perturbations at all frequencies and is shown as gain and phase mea­surements on a Bode plot. The output capacitor and load resistance largely determine where the error amplifier poles and zeros need to be placed for optimum transient response and loop stability.
Output Capacitor Pole and Zero
The gain at very low frequencies is equal to the DC gain. Normally the first departure from that gain is the pole created by the load resistance and the output capacitance. The corner frequency of this pole is:
The transconductance of the modulator must be deter­mined before calculating the modulator gain. The modu­lator transconductance is:
g
m(MOD)
where: V R
SENSE
V
ITH(MAX)
= (V
RSENSE(MAX)/RSENSE
RSENSE(MAX)
is listed in the data sheet as 75mV,
)/V
ITH(MAX)
is the value of the current sense resistor and
is 2.1V for the no-load to full-load output
voltage swing of the error amplifier. The DC voltage gain of the modulator is:
A
where: g and R
V(MOD)
m(MOD)
LOAD
= g
m(MOD)RLOAD
is the transconductance of the modulator
= V
OUT/IOUT
.
As an example, the DC gain for the LTC1735/LTC1736 or the LTC1628 providing 3A at 3.3V is:
A
V(FB)
A
V(EA)
= V = g
/V
REF
OUT
m(EA)ZITH
= 0.8V/3.3V = 0.242 = –12.3 dB
= (1.4mS)(3.28M) = 4592 = 73.2 dB
where: 3.28M is the typical output impedance of the error amplifier without any external DC loading on the ITH pin.
fP = 1/(2πRLC
where: RL is the load resistance and C
OUT
)
is the output
OUT
capacitance. Notice that as the output current goes down, the equiva-
lent load resistance goes up, causing the pole frequency to decrease. The same is true when the output capacitance increases, that is, the pole frequency moves lower.
The amount of phase margin is largely determined by the zero formed by the output capacitance and capacitor ESR. The corner frequency of this zero is:
fZ = 1/(2πESR • C
OUT
)
It is interesting to note that doubling the number of like output capacitors will lower the pole frequency by half but will not change the zero frequency of the output capacitor. This is true because, as the capacitance doubles, the ESR is halved, yet the load resistance remains the same. Consequently, the product of RL and C product of ESR and C
remains the same. It is desirable
OUT
goes up, but the
OUT
that the crossover frequency be higher than the ESR zero
AN76-3
Application Note 76
frequency because the phase shift of the ESR zero is very helpful in achieving adequate phase margin.
Different types of capacitors have different amounts of ESR per µF of capacitance. The ESR of the output capacitor determines the output ripple voltage under static load conditions and greatly affects the output response to transient loads. For a 3A output, the inductor ripple current should be about 1A ESR should be about 0.05 for a 50mV
. Therefore, the output capacitor
P-P
output voltage
P-P
ripple. The difference in frequency response between Panasonic’s Specialty Polymer output capacitors and alu­minum electrolytic output capacitors, with 0.05 of ESR, is shown in Figures 3 and 4.
40
47µF
6.3V
30
0.05
20
= 1.1
R
L
10
0
GAIN (dB)
–10
–20
–30
–40
GAIN PHASE
110
Figure 3. Frequency Response of Specialty Polymer Capacitor Used in 3.3V, 3A Power Supply Output
40
1200µF
6.3V
30
0.048
20
RL = 1.1
10
GAIN (dB)
–10
–20
–30
–40
12Hz
0
GAIN PHASE
110
1
fZ =
2πESR(C
308Hz
100 10k1k
FREQUENCY (Hz)
1
fZ =
2πESR(C
fP =
120Hz
276Hz
100 10k1k
FREQUENCY (Hz)
fP =
)
OUT
fP =
3.08kHz
6.77kHz
fP =
)
OUT
27.6kHz
1.2kHz
fZ = 2.76kHz
1
2πR
LCOUT
677.6kHz
30.8kHz
fZ = 67.76kHz
100k
1
2πR
LCOUT
100k
1M
AN76 F03
1M
AN76 F04
PHASE (DEG)
45
0
–45
–90
–135
PHASE (DEG)
45
0
–45
–90
–135
Aluminum electrolytic capacitors are often selected for both the input and output of very low cost power supplies. Figure 3 shows a 3kHz pole for a 47µF, 6.3V, 0.05 Specialty Polymer capacitor. Figure 4 shows a 120Hz pole for a 1200µF, 6.3V, 0.05 aluminum electrolytic capaci- tor. In order to maintain the 0.05 ESR required to meet the output ripple requirement, the aluminum electrolytic capacitor requires 25 times the capacitance of the Spe­cialty Polymer capacitor, causing the aluminum electro­lytic capacitor to have a pole frequency at 4% of the specialty polymer capacitor.
The loop compensation must be quite different when aluminum electrolytic capacitors are used. It is unlikely that fixed internal compensation will work well with both types of capacitors. Although bandwidth will suffer when aluminum electrolytic capacitors are used, using an OPTI­LOOP architecture, the loop can be optimized for their use and stable operation achieved. The high ESR zero fre­quency of the Specialty Polymer capacitors makes the loop more difficult to compensate, but the bandwidth will be significantly higher as a result of the extra effort.
The Modulator
The modulator controls the inductor current as a function of the amplified error signal from the error amplifier. The transconductance of the modulator, calculated earlier, is determined by the maximum current allowed through the sense resistor divided by the maximum voltage swing of the error amplifier output at the ITH pin. The product of the modulator transconductance and the load resistance is the modulator gain for DC. The frequency response of the modulator is determined by multiplying the modulator gain at DC times the frequency response of the output capacitor and the load resistance. This is the same as changing the 0dB gain reference on Figures 3 and 4 to the modulator gain level. Consequently, the frequency response of the modulator is primarily determined by the output capacitor and the load resistance.
Figure 4. Frequency Response of Aluminum Electrolytic Capacitor Used in 3.3V, 3A Power Supply Output
AN76-4
Application Note 76
The Error Amplifier
The error amplifier provides most of the loop gain. After selecting the output capacitor, the control loop is compen­sated by tailoring the frequency response of the error amplifier. It has a transconductance of 1.4mS and an output resistance of 3M, so it provides a low frequency gain of 4600 or 73dB. The loop gain is the product of the error amplifier gain and the modulator gain, so the fre­quency response of the error amplifier, the output capaci­tor and load resistor determine the frequency response of the loop.
The AC behavior of the error amplifier is determined by C1, C2, C3, C4, R1, R2 and R3 as shown in Figure 2. The following relationships are given as a first approximation, since there is some interaction between the parts. As an example, the low frequency pole of the error amplifier is the dominant pole and is determined primarily by C3 and the output resistance of the error amplifier as shown by:
fP = 1/(2πR
However, R3 and C4 have a small effect on the actual corner frequency, since the series combination of C3 and R3 are in parallel with C4, which is in parallel with R Although all three impedances interact, the resistance of R3 is small compared to the impedance of C3 at the pole frequency, so its effect is small. The same is true of C4. Since the value of C4 is normally small compared to C3, the primary effect is determined by C3.
Resistor R3 adds a zero to the frequency response to control gain in the midfrequency range. This zero fre­quency is:
fZ = 1/(2πR3C3)
Capacitor C4 adds a pole to reduce very high frequency gain. Although frequently unnecessary for loop stability, C4 helps to filter the effects of PCB noise and output ripple voltage from the loop. It is desirable to have the error amplifier gain be less than zero dB at the switching frequency. The high frequency pole created by C4 is:
fP = 1/(2πR3C4)
The high frequency zero created by C1 and R1 can be very important for transient load applications. Capacitor C1 provides phase lead and acts like a speed-up capacitor to output voltage changes, so it tends to “short-out” R1 and
O(EA)
C3)
O(EA)
.
improve the high frequency response. This zero tends to produce a positive-going bump in the phase plot. Ideally, the peak of this bump is centered over the loop’s crossover frequency. The R1, C1 zero is located at:
fZ = 1/(2πR1C1)
The pole created by R2 and C2 is generally not critical for loop stability. It is frequently set at one half to one third of the switching frequency and is primarily used for noise filtering rather than loop compensation. The effect of C2 is normally countered by the value of R3. The R2, C2 pole frequency can be calculated by:
fP = 1/(2πR2C2)
ITH PIN COMPONENT VALUES
Selecting the best values for the loop compensation com­ponents is not as simple as selecting pole and zero frequencies for the ideal crossover frequency. Several other factors should be taken into account. The slew rate and amplitude of the load transient largely determine the ESR requirement of the output capacitor. The amount of capacitance used at the output is primarily determined by the type of capacitor used and partially determined by the load transient characteristics.
PCB-generated noise can have a considerable effect on the operation of a power supply. Problems caused by PCB noise should be corrected by layout improvements but this is not always possible. Proper decoupling and loop bandwidth limiting can significantly reduce the effects of PCB noise on regulator operation. However, reducing loop bandwidth will also reduce dynamic performance.
Good transient response and PCB noise reduction are opposing requirements when determining the values of the ITH pin components. The final loop compensation must have good stability margins. There are no equations that will yield component values to optimize the loop transient response, give good PCB noise reduction and provide the required stability margins. The equations given for pole and zero frequencies are handy references for predicting the effect a part change will have on the frequency response. Although gain can be calculated reasonably accurately, phase calculations tend to have large errors because of the many parasitics in the power path.
AN76-5
Application Note 76
The best procedure for optimizing the compensation com­ponent values in your circuit is to start with the values that are recommended in the regulator data sheet. This will generally result in a stable, but probably less than optimal loop compensation. Check the output for any signs of loop oscillation. If the loop is oscillating, try raising the value of C4 to a large value, 0.01uF. This will most likely produce a very sluggish but stable system to begin testing. Connect the load pulse test circuit of Figure 8 to the board and apply load steps approximately 25% of full load to see how the loop responds to these perturbations.
If the response is not as desired, remove the ITH pin components R3, C3 and C4. Connect an RC substitution box, through a short twisted pair of wires, between the I pin and SGND of the regulator. It is a good idea to terminate the wires from the RC substitution box with a 47pF capacitor located at C4. Set the substitution box for a series RC connection. Then, by adjusting the values of R and C, you can dial in the optimal response. Read the section “The Effect of Loop Compensation Components on Large-Signal Transients” presented later and use Figures 9 through 21 as a guide in determining which way to vary R and C.
Avoid excessive ringing in the transient waveform. Point C in Figures 6 and 7 shows a single overshoot bump that is acceptable. Two bumps constitute ringing which indicates poor phase margin. Once satisfactory compensation is obtained, install the selected component values on the board and verify the performance is similar to what was obtained with the RC box. Due to the effects of noise pickup and parasitics, there may be a little difference in the behavior of the system using the substitution box com­pared to using real parts on the board.
If stability margins cannot be measured, stable perfor­mance can be predicted if each compensation component value can be doubled or halved without causing excessive ringing in the transient waveform. The last step in the frequency compensation process should be to individu­ally change the values of C1, C2, C3, C4 and R3 to 50% and to 200% of their final value. If one value causes excessive ringing because of this change, compensation component values should be revaluated.
One thing to keep in mind is that no amount of fiddling with the compensation will make up for having inadequate output capacitors for the desired transient response. The
TH
goal is to obtain the best possible response from the chosen power path components. If this doesn’t meet the system requirements, the only solution is to add more output capacitors (to reduce ESR) or lower the inductor value and live with the increased output ripple.
In most cases, the final values selected for the loop compensation components will be a compromise between the best transient performance and the best PCB noise performance. Obviously, improving the board lay­out to decrease PCB noise is preferred over reducing loop bandwidth. The OPTI-LOOP architecture lets the designer decide how to optimize his circuit and still meet loop stability requirements. The final value set must provide adequate stability margins.
LARGE-SIGNAL vs SMALL-SIGNAL RESPONSE
As the load conditions change, the loop rapidly responds to the new requirements. The amount and rate of load change determines whether the loop response is called a large-signal response or a small-signal response. The difference between large-signal and small-signal response is whether the control loop maintains control of the output. Often this can be seen by looking at the output of the error amplifier. If the ITH pin voltage is between 0.3V and 2.4V, the loop is normally in control of the output and the load variation creates a small-signal response. If the ITH pin voltage is less than 0.3V or equal to 2.4V, the error amplifier is “railed” and the regulator is not operating in a linear region. An exception to the 0.3V to 2.4V rule is when the error amplifier is in slew limit. When the error amplifier is in slew limit, it does not control the loop because the load transient is occurring faster than the error amplifier can respond, so the output capacitors satisfy the transient current until the inductor current can “catch up.” During static operation the voltage on the ITH pin should be between 0.3V and 2.2V and is proportional to the load current.
The rules of loop compensation only apply to linear operation. Large-signal response temporarily takes the
loop out of operation. However, the loop must respond gracefully going into and out of large-signal response. Large-signal response occurs when the amplitude and rate of load current change are beyond what the supply can respond to. The wider the loop bandwidth, the faster the load transient the loop can respond to.
AN76-6
Application Note 76
The regulator’s large-signal response is determined by the ESR of the output capacitor, the inductance of the induc­tor, the input voltage and the bandwidth of the control loop. When the load change requires a large-signal response from the regulator, the slew rate of the error amplifier is very important. If R3 is too small or capacitors C3 or C4 are too large, it will take longer for the error amplifier’s output voltage to rail. During the time between the application of the load transient and the turn-on of the top MOSFET, the output capacitor must supply all of the current required by the load. Current supplied by the output capacitor develops a voltage drop across the ESR that subtracts from the output voltage. The lower the ESR, the lower the voltage loss when the output capacitor supplies load current.
After the top MOSFET turns on, the higher the input voltage and the lower the buck inductor value, the faster the output voltage will return to normal. The relationship of voltage, current and inductance is shown as:
LI
∆=∆t
E
L
where: EL is equal to VIN – V I = the inductor current change during t, where t = the time required for the inductor current to increase to the new load current level.
A lower inductor value produces a higher output current slew rate at the expense of higher output voltage ripple.
POWER SUPPLY TRANSIENT RESPONSE
System Supplies
One of the most important applications of the OPTI-LOOP architecture is loop compensation in transient load appli­cations. The system supply in most products today includes 5V and 3.3V. Most load transients on 5V supplies are caused by digital circuits and motors. Digital circuit transients are short in duration and vary from a few miliamps to several amps in amplitude. Load transients caused by floppy drives and other motors range in current from 0.5A to several amps during a period of 50ms to seconds, depending on how long it takes the motor to spin up. A properly designed circuit with adequate bandwidth can easily handle motor load transients.
, L = inductance value,
OUT
Most 3.3V supplies power digital and memory circuits where the transients are fast, short in duration and vary from miliamps to amps. The majority of digital circuit and memory transients should be handled by local decoupling capacitors at each IC. Local IC decoupling slows down and averages the actual transient load requirements of each IC so that the power supply control loop can handle the perturbations.
Core Voltage Supply
The transient requirements of modern CPU core supplies require large-signal response from the regulator. Conse­quently, the entire core voltage supply should be opti­mized for the needs of the CPU. The core voltage supply should be located as close to the CPU as possible, operate at the highest frequency possible with the lowest value of inductor possible and it should take its input power from the 5V power supply rather than the raw battery voltage. By operating the CPU regulator from the 5V supply, it can switch at a much higher frequency with a lower inductor value and higher efficiency. By keeping the voltage step­down ratio relatively small, the loop dynamics can be optimized.
Figure 5 shows the LTC1736 used as a core voltage regulator capable of supplying 10.2A from a 5V input supply at an output voltage selected by the five VID control lines. Typical output voltages range from 1.3V to 1.6V. Figure 6 shows a close-up of the large-signal response of the LTC1736 at the load. The load current changes from
0.2A to 10.2A in about 80ns. Point A shows the effect of ESL and trace inductance between the power supply and the load. Point B shows the effect of the ESR of the output capacitors and Point C shows where the buck inductor current starts to supply load current.
Figure 7 shows a picture of the output voltage when the load current rapidly changes from 10.2A to 0.2A. When the load current changes from full load to light load, the inductor current cannot change instantaneously so it discharges its stored energy into the output capacitor, developing a voltage drop across the capacitor ESR and producing an ESL spike due to the fast change of the load current. The ESL spike and the voltage drop across the ESR cause a temporary rise in output voltage.
AN76-7
Application Note 76
PGOOD
C3, 330pF
C4, 100pF
C2, 47pF
C6, 39pF
C7, 0.1µF
C1,47pF
R3, 33k
C5, 1000pF
1 2 3 4 5 6 7 8
9 10 11 12
C
OSC
RUN/SS I
TH
FCB SGND PGOOD SENSE SENSE V
FB
V
OSENSE
VID0 VID1
R6, 100k
R7, 100k
U1
LTC1736
+
EXT V
BOOST
INT V
PGND
VID V
VID4 VID3 VID2
SW V
BG
24
TG
23 22 21
IN
20
CC
19 18 17
CC
16
CC
15
VID4
14
VID3
13
VID2
VID1 VID0
+
Q1, FDS6680A
C8, 0.22µF
D1 CMDSH-3
C9
4.7µF
VID INPUT
C10 1µF
0.78µH
Q2, Q3 FDS6680A X 2
MBRS340T3
Figure 5. Core Voltage Supply with VID Control
D2
L1
C11
0.1µF
C12
+
150µF
6.3V
R4
0.004
C12, C13 = PANASONIC EEFUEOJ151R C14 TO C17 = PANASONIC EEFUEOG181R C18, C19 = TAIYO YUDEN LMK550BJ476KM L1 = COILCRAFT D05022-781HC R4 = IRC LRF2512-01-R004-J U1 = LINEAR TECHNOLOGY LTC1736CG
AN76 F05
+
R5 10
C13 150µF
6.3V
1.6V AT 10.2A
+
C14, C15 180µF 4V X 2
INPUT 5V
OUTPUT
V
OSENSE
LOCATE CAPACITORS NEAR LOAD
C18, C19 47µF
+ +
10V X5R X 2
C16, C17 180µF 4V X 2
B
50mV/DIV
C
1.6V
A
A: INDUCTANCE SPIKE B: ESR VOLTAGE DROP C: INDUCTOR CURRENT TO LOAD
1µs/DIV
AN76 F06
Figure 6. Close-Up View of Output Voltage During Low Current-to-High Current Transistion
A
C
1.6V
50mV/DIV
B
A: INDUCTANCE SPIKE B: ESR VOLTAGE C: INDUCTOR CURRENT = LOAD CURRENT
1µs/DIV
AN76 F07
Figure 7. Close-Up View of Output Voltage During High Current-to-Low Current Transistion
AN76-8
Application Note 76
R1
2.2
5W
SLEW RATE
CONTROL
R3
10k
R4 51
PULSE GENERATOR 100Hz TO 1kHz, 5V
AN76 F08
R2
2.2
10W
Q1
IRLZ44
TO 3.3V
OUTPUT
GND
A
Inductance Delays Transient Response
The load transient amplitude primarily determines the ESR required for the output capacitors. However, the induc­tance between the output capacitors and the CPU deter­mines the initial voltage sag at the CPU. This inductance is made up of the ESL of the output capacitors, trace induc­tance and connector inductance.
The core voltage regulator should be located very close to the CPU but some of the output capacitors should be located even closer. The trace lengths should be abso­lutely as short as possible between the power inputs of the CPU and the body of the bulk ceramic capacitors. These ceramic capacitors should be selected to supply the lead­ing edge transient current while the ESL of the other capacitors delays their contribution to the new load requirement. Additional low ESR tantalum or Specialty Polymer capacitors should be placed as close as possible to the ceramic capacitors. The rest of the output capacitors should be very close to the output of the core voltage regulator, but still less than 0.5" away from the filter capacitors located at the CPU.
A simple calculation shows the delaying effect of induc­tance at transient speeds.
XL = 2πfL
where: XL is the impedance of inductance, f is the fre­quency equal to 1/(actual load transition time) and L is the inductance of interest.
An XL of 1.25 can be calculated using the general rule of 20nH per inch of trace length, two 0.5" traces and a 100ns transition time. Since package inductances and trace inductance are in series with the ESR, the delaying effect of XL and ESR add to cause the leading edge voltage sag at the load. After ESL and the trace inductance charge up to the output current, the voltage drop across the ESR continues to decrease the output voltage. The effects of ESR and XL are shown at points A and B in both Figures 6 and 7. Clearly, series inductance must be very low (less than 1nH) for these designs to operate successfully.
Measuring Transient Response
Transient response should be measured across a ceramic capacitor as close to the input power pins of the CPU or other dynamic load as possible. Good high frequency measurement techniques are required. A common prac­tice is to solder bus wire leads to the ends of a 1µF capacitor nearest the power pins on the CPU. Extend these bus wire leads up from the board about 0.5". Disassemble the scope probe by removing the grabber so that the ground ring and center pin are exposed. Carefully touch the ground ring to the bus wire connected to the ground side of the 1µF capacitor and touch the probe center pin to the bus wire connected to the other side of the 1µF capacitor. This measurement technique will avoid most of the signal pickup common to oscilloscope measurements in noisy environments. Remember to check the transient response over the full range of input voltages and possible load current changes.
For preliminary testing, try using the load pulser circuit shown in Figure 8. It can be modified to test a wide variety of power supply circuits. Resistor R2 sets the minimum load current while both R1 and R2 determine the maxi­mum load current. Resistor R4 provides a 50 termina­tion for the square wave generator that drives Q1. The slew rate control, R3, controls the rate at which current is taken from the power supply under test.
For breadboard testing with the load pulser, change the values of R1, R2 and R3 as required. Measure the transient response across the last output capacitor using the raised­bus-wire and disassembled-scope-probe measurement technique.
Figure 8. Load Pulser Circuit
AN76-9
Application Note 76
The load pulser is a very simple circuit that can be used for general purpose loop response testing. The disadvantage of this circuit is the amount of inductance in the switched­current loop. This inductance slows the load current slew rate and causes ringing on the rising and falling edges. This simple test circuit is useful for observing the settling performance of the control loop but will not give good information on absolute transient response amplitude. A much more sophisticated test setup is required to evaluate this behavior. The best transient response testing can be done with the real load on the final PCB.
Another benefit of the OPTI-LOOP architecture is that simple passive component value changes can be made to fine tune the transient response and loop compensation on the final board, at any point in the development pro­gram, without board modifications.
The Effect of Loop Compensation Components on Large-Signal Transients
The circuit shown in Figure 5 was used to demonstrate the effect of individually changing the loop compensation component values by a factor of 10. Figure 9 shows the normal transient response with the values shown in the schematic. The frequency response of this circuit is shown in the Bode plot of Figure 10. The Bode plot indicates that this circuit has been optimized for fast transient response.
Figures 11 and 12 show the effects of changing C3 to 10pF and 3300pF, respectively. This capacitor normally deter­mines the low frequency pole of the error amplifier. As the capacitance value goes down, the pole frequency goes up. Figure 11 shows a slight additional ringing as the over­shoot returns to normal. Figure 12 shows the effect of decreasing the low frequency pole, thereby reducing the low frequency gain. Although the peak-to-peak amplitude of the transient didn’t change, it took much longer for the loop to return the output to normal. The Figure 13 Bode plot shows that increasing C3 to 3300pF caused the phase margin to drop from 47° down to 33° and decreased the gain margin to –7dB.
50mV/DIV
50mV/DIV
TRANSIENT CURRENT
0.2A TO 10.2A
AN76 F09
Figure 9. Transient Response with Normal Compensation Values Shown on Schematic
50
LTC1736
40
= 5V
V
IN
30
20
10
0
GAIN (dB)
–10
–20
–30
–40
110
C3 = 330pF C4 = 100pF C1 = 47pF R3 = 33k
CROSSOVER
FREQUENCY = 55kHz
GAIN MARGIN
= –9.5dB
100 10k1k
FREQUENCY (Hz)
PHASE MARGIN
47.1°
100k
180
120
60
0
–60
–120
–180
1M
AN76 F10
Figure 10. Bode Plot of LTC1736 Circuit
TRANSIENT CURRENT
0.2A TO 10.2A
1.6V
AN76 F11
Figure 11. Transient Response with C3 Changed from 330pF to 10pF
1.6V
PHASE (DEG)
AN76-10
TRANSIENT CURRENT
0.2A TO 10.2A
Application Note 76
TRANSIENT CURRENT
0.2A TO 10.2A
50mV/DIV
AN76 F12
Figure 12. Transient Response with C3 Changed from 330pF to 3300pF
50
LTC1736
40
= 5V
V
IN
C3 = 3300pF
30
C4 = 100pF
20
10
0
GAIN (dB)
–10
–20
–30
–40
110
C1 = 47pF R3 = 33k
CROSSOVER
FREQUENCY = 56kHz
100 10k1k
FREQUENCY (Hz)
PHASE MARGIN 33°
GAIN MARGIN
= –7dB
100k
1M
AN76 F13
Figure 13. Bode Plot of LTC1736 Circuit with C3 Changed from 330pF to 3300pF
1.6V
180
PHASE (DEG)
120
60
0
–60
–120
–180
50mV/DIV
50mV/DIV
1.6V
AN76 F14
Figure 14. Transient Response with R3 Changed from 33k to 330k
TRANSIENT CURRENT
0.2A TO 10.2A
1.6V
AN76 F15
Figure 15. Transient Response with R3 Changed from 33k to 3.3k
Figures 14 and 15 show the effects of changing R3 to 330k and 3.3k, respectively. This resistor sets the midfrequency gain and the zero frequency of the error amplifier. Increas­ing R3 to 330k increased the midfrequency gain and decreased the zero frequency without much effect on the transient response. Decreasing R3 to 3.3k increased the zero frequency and decreased the midfrequency gain, which caused high frequency ringing and an increase in peak-to-peak transient response. The high frequency ring­ing is an indication that the phase margin is dangerously low. Figure 16 shows a phase margin of 20.4° and a gain margin of –26dB. This increase in gain margin cannot improve circuit stability with a phase margin of 20.4°.
50
LTC1736
40
= 5V
V
IN
C3 = 330pF
30
C4 = 100pF
20
10
0
GAIN (dB)
–10
–20
–30
–40
110
C1 = 47pF R3 = 3.3k
CROSSOVER
FREQUENCY = 28.8kHz
100 10k1k
FREQUENCY (Hz)
PHASE MARGIN
20.4°
GAIN MARGIN
= –26dB
100k
AN76 F16
Figure 16. Bode Plot of LTC1736 Circuit with R3 Changed from 33k to 3.3k
AN76-11
180
120
60
0
–60
–120
–180
1M
PHASE (DEG)
Application Note 76
Figures 17 and 18 show the effects of changing C4 to 10pF and 1000pF, respectively. This capacitor normally deter­mines the high frequency pole of the error amplifier. Decreasing C4 to 10pF increased the high frequency pole but had little effect on the transient response. This will make the circuit more susceptible to noise however. By increasing C4 to 1000pF, the high frequency pole decreased so far that the peak-to-peak transient response doubled, with significant high frequency ringing on the rising and falling edges of the transient waveform. Figure 19 shows a phase margin of 14.4°, about 30% of the phase margin obtained when C4 = 100pF.
Figures 20 and 21 show the effects of changing C1 to 5pF and 470pF. This capacitor provides a little phase lead to improve transient response. No change is apparent when the value drops to 5pF but a slight improvement in peak­to-peak transient response can be observed when the value is increased to 470pF.
These waveforms show the type of changes that occur as one value is changed at a time. No damage will occur to the circuit or the load if the incremental changes are within a 10-to-1 range. If the top feedback resistor is open, the connection to the V
OSENSE
pulled high, the output voltage will increase until it equals the input voltage. Care should be taken to avoid this condition because output capacitors can be damaged, load resistors overtaxed or CPUs destroyed.
pin is opened or the ITH pin is
TRANSIENT CURRENT
0.2A TO 10.2A
50mV/DIV
- DSOL8 F18
Figure 18. Transient Response with C4 Changed from 100pF to 1000pF
50
LTC1736
40
V
= 5V
IN
C3 = 330pF
30
C4 = 1000pF C1 = 47pF
20
R3 = 33k
10
0
GAIN (dB)
–10
–20
–30
–40
110
CROSSOVER
FREQUENCY = 18.6kHz
GAIN MARGIN
100 10k1k
FREQUENCY (Hz)
= –24dB
Figure 19. Bode Plot of LTC1736 Circuit with C4 Changed from 100pF to 1000pF
PHASE MARGIN
14.4°
100k
1M
AN76 F19
1.6V
180
PHASE (DEG)
120
60
0
–60
–120
–180
TRANSIENT CURRENT
0.2A TO 10.2A
50mV/DIV
Figure 17. Transient Response with C4 Changed from 100pF to 10pF
AN76-12
AN76 F17
1.6V
50mV/DIV
TRANSIENT CURRENT
0.2A TO 10.2A
1.6V
DSOL8 F20
Figure 20. Transient Response with C1 Changed from 47pF to 5pF
Application Note 76
TRANSIENT CURRENT
0.2A TO 10.2A
50mV/DIV
Figure 21. Transient Response with C1 Changed from 47pF to 470pF
1.6V
AN76 F21
Common Values for System Supply Compensation
The dual version of the LTC1735, the LTC1628, shares the identical control circuitry of the LTC1735 and as such, has some distinct advantages over previous system power (5V and 3.3V) solutions. In addition, the LTC1628 oper­ates the two controller top switches 180° out of phase to minimize RMS input current. Since the system power requirements are less stringent than the CPU core require­ments, OPTI-LOOP architecture allows the use of signifi­cantly smaller output capacitors than were previously required. Special Polymer capacitors offer extremely low ESR but have less capacitance density than other capaci­tor types. OPTI-LOOP compensation provides the key to using the small capacitance values while providing ex­tremely good performance, small physical size, and low overall cost.
Oscilloscope photos and Bode plots are included in Figures 22 and 23, illustrating the benefit of the OPTI­LOOP architecture for the LTC1628 5V output using the basic circuit in Figure 24. The compensation components are changed as indicated in each figure for different values and types of output capacitor. The top two waveforms in each photo are the output voltage at the vertical sensitivity indicated in the top left corner and the output current at 1 ampere per division with a time scale of 100µs per divi- sion. The lower two traces are the same as above but at a time scale of 5µs per division. A 0.5A to 2A load step is used for a typical transient condition. The expanded scale indicates the response time of the switching regulator is normally several microseconds. A 47µF capacitor having low ESR offers a very acceptable output capacitor solution in applications requiring lowest cost and/or size. A 100µF capacitor can be used where an extra margin of stability and low ripple voltage are required. The 150µF to 220µF capacitance may be required in applications that require extremely low ESR for zero to full designed load current transient steps. Using two small 47µF capacitors provide stability, low ESR
and
a margin of safety in the event of a
single capacitor failure. Table 1 lists suggested OPTI-LOOP compensation values
for other types of output capacitors. Figure 24 was also used to verify the selected values in Table 1. Final compen­sation value selection should be fine tuned after the PC layout is done since the quality of the layout will affect the loop behavior.
AN76-13
Application Note 76
47µF Panasonic SP
VO = 5V
100mV/DIV
V
= 5V
O
100mV/DIV
60
50
40
30
20
10
GAIN (dB)
0
VIN = 15V V
O
–10
= 3A
I
O
C8 = 470pF
–20
R8 = 6.8k
–30
100 1k 10k 100k 1M
GAIN
= 5V
FREQUENCY (Hz)
I
O
1A/DIV
I
O
1A/DIV
PHASE
AN76F22a2
180
160
120
90
PHASE (DEG) 60
30
0
–30
–60
–90
100µF Panasonic SP
VO = 5V
50mV/DIV
= 5V
V
O
50mV/DIV
60
50
40
30
20
10
GAIN (dB)
0
VIN = 15V
= 5V
V
O
–10
= 3A
I
O
C8 = 220pF
–20
R8 = 15k
–30
100 1k 10k 100k 1M
GAIN
FREQUENCY (Hz)
I
O
1A/DIV
I
O
1A/DIV
PHASE
AN76F22b2
180
160
120
90
PHASE (DEG) 60
30
0
–30
–60
–90
150µF Panasonic SP
= 5V
V
O
50mV/DIV
= 5V
V
O
50mV/DIV
60
50
40
30
20
10
GAIN (dB)
0
VIN = 15V
= 5V
V
O
–10
= 3A
I
O
C8 = 100pF
–20
R8 = 15k
–30
100 1k 10k 100k 1M
FREQUENCY (Hz)
GAIN
I
O
1A/DIV
I
O
1A/DIV
PHASE
AN76F22c2
180
160
120
90
PHASE (DEG) 60
30
0
–30
–60
–90
Figure 22. LTC1628 Transient Response and Frequency Response with Panasonic SP Capacitors
47µF Sanyo OS-CON 120µF Sanyo OS-CON 220µF Sanyo OS-CON
VO = 5V
100mV/DIV
V
= 5V
O
100mV/DIV
60
50
40
30
20
10
GAIN (dB)
0
VIN = 15V
= 5V
V
O
–10
= 3A
I
O
C8 = 330pF
–20
R8 = 10k
–30
100 1k 10k 100k 1M
FREQUENCY (Hz)
GAIN
I
O
1A/DIV
I
O
1A/DIV
PHASE
AN76F23a2
180
160
120
90
PHASE (DEG)
60
30
0
–30
–60
–90
= 5V
V
O
50mV/DIV
= 5V
V
O
50mV/DIV
60
50
40
30
20
10
GAIN (dB)
0
VIN = 15V
= 5V
V
O
–10
= 3A
I
O
C8 = 150pF
–20
R8 = 10k
–30
100 1k 10k 100k 1M
GAIN
FREQUENCY (Hz)
I
O
1A/DIV
I
O
1A/DIV
PHASE
AN76F23b2
180
160
120
90
PHASE (DEG) 60
30
0
–30
–60
–90
V
= 5V
O
50mV/DIV
= 5V
V
O
50mV/DIV
60
50
40
30
20
10
GAIN (dB)
0
VIN = 15V V
–10
I
O
C8 = 100pF
–20
R8 = 10k
–30
100 1k 10k 100k 1M
O
= 3A
= 5V
GAIN
FREQUENCY (Hz)
I
O
1A/DIV
I
O
1A/DIV
PHASE
AN76F23c2
180
160
120
90
PHASE (DEG)
60
30
0
–30
–60
–90
AN76-14
Figure 23. LTC1628 Transient Response and Frequency Response with Sanyo OS-CON Capacitors
Application Note 76
28
FLTCPL
C16
GND
C2,180µF,4V
4.7µF
IN
V
5V TO
30V
SP CAP
+
D2
Q2b
Q2a
OUT1
V
5V
4A PK
SP CAP
+
R1,0.015
L1,8µH
Q1a
D1
Q1b
MBRM
140T3
C1,150µF,6V
50V
22µF
C18
0.1µF
R11,10
MBRM
140T3
OUT2
V
R2,0.015
L2,8µH
3.3V
4A PK
AN76 F22
SWITCHING FREQUENCY = 300kHz
D3, D4 = CMDSH-3TR
L1, L2 = SUMIDA CEP123-8ROMC
Q1, Q2 = FDS8936A
+
C3
0.1µF
27
26
25
24
IN
TG1
SW1
V
BOOST1
D3
D4
C15
1µF
23
22
21
20
CC
EXTV
CC
INTV
PGND
BG1
C4
0.1µF
19
18
17
16
15
BG2
BOOST2
SW2
TG2
RUN/SS2
C5,0.1µF
RUN/SS1
1
C13,180pF
SENSE+SENSE1–V
2
3
C11
1000pF
OSENSE1
4
R3,105k,1%
R5
20k,1%
FREQSET
5
STBYMD
6
FCB
7
U1
LTC1628
TH1
I
8
C7,100pF
R7,15k
OUT
SGND
3.3V
9
10
C8,100pF
33pF
C10
C19C21C20
0.01µF × 3
C9
TH2
I
11
33pF
R8,15k
V
12
OSENSE2
+
SENSE2–SENSE2
13
14
C12
1000pF
R4,63.4k,1%
R6,20k,1%
C14,180pF
C6,0.1µF
Figure 24. Dual Output System Supply for 5V and 3.3V
R9
1M
Information furnished by Linear Technology Corporation is believed to be accurate and reliable. However, no responsibility is assumed for its use. Linear Technology Corporation makes no represen­tation that the interconnection of its circuits as described herein will not infringe on existing patent rights.
R12
1M
R10
1M
TP1
3.3V
LDO
TP2
5V
AN76-15
Application Note 76
Table 1. Output Capacitor and Compensation on DC236A (LTC1628 Demo Board)
Test Conditions: VIN =15V, V Switching Frequency = 265kHz, Load Step = 1.5A to 2.6A
Output Capacitor
Panasonic SP 47µF/6.3V*1 27pF 100pF 22k 33pF Sanyo Oscon 47µF/6.3V*1 27pF 470pF 15k 33pF Sanyo Poscap TPC 150µF/4V*1 27pF 100pF 22k 33pF Sanyo Poscap TPC 100µF/6V*1 27pF 100pF 22k 33pF Sanyo Poscap TPC 68µF/10V*1 27pF 100pF 22k 33pF AVX Tantalum TPS 220µF/6.3V+10µF Ceramic
Test Conditions: VIN =15V, V Switching Frequency = 265kHz, Load Step = 0A to 2A
Panasonic SP 56µF/4V*1 100pF 150pF 15k 33pF
Test Conditions: VIN =15V, V Switching Frequency = 265kHz, Load Step = 0.5A to 3A
Panasonic SP*2 56µF/4V+10µF Ceramic 27pF 100pF 22k 33pF Sanyo Oscon 150µF/6.3V+10µF Ceramic 27pF 100pF 22k 33pF Sanyo Poscap TPC 150µF/4V*1+ Cer 10µF*2 27pF 100pF 33k 33pF Sanyo Poscap TPB 150µF/6.3V*2+ Cer 10µF*2 27pF 100pF 33k 33pF AVX Tantalum TPS 220µF/6.3V*1+Cer 10µF*1 27pF 100pF 33k 33pF AVX Tantalum TPS 330µF/6.3V*1+Cer 10µF*1 27pF 100pF 33k 33pF
= 3.3V/3A,
OUT
= 3.3V/3A,
OUT
= 3.3V/3A,
OUT
Compensation
C13,C14 C7,C8 R7,R8 C9,C10
27pF 100pF 33k 33pF
CONCLUSION
Control loop compensation is a very involved subject. The ability to improve the output voltage transient response is quite valuable. Optimizing circuit performance for tran­sient load applications without constraints on output capacitors allows the designer to get the most out of the power components. The fear that fixed compensation
Linear Technology Corporation
AN76-16
1630 McCarthy Blvd., Milpitas, CA 95035-7417
(408) 432-1900 ● FAX: (408) 434-0507
www.linear-tech.com
inside a regulator IC can lead to loop oscillation under certain conditions is valid, since the loop frequency response varies so much with different types of output capacitors. The OPTI-LOOP architecture provides the mechanism for obtaining the maximum performance from the lowest cost power supply.
an76 LT/TP 0599 4K • PRINTED IN USA
LINEAR TE CHNO LOGY CORP O R ATION 1999
Loading...