VA201T
The catalytic sensors of the 201T 
can be used to detect hundreds of 
different gases and inammable 
vapour concentrations
 

The 201T gas 
detection transmitter 
is designed to meet 
or exceed safety 
requirements in a 
variety of commercial 
and industrial 
applications.
User Friendly
10-step LED display• 
Proven sensing technology• 
Easy installation and operation•
Reliable
Field-proven protection• 
Robust RS-485 Modbus communication•
Versatile
Stand-alone or network configuration• 
Full compatibility with the Vulcain 301C •
controller
Original Architecture
Innovative and compact case design•
Benecial Options
Optional 4-20 mA and one relay output• 
Optional audible alarm and LCD display•
The 201T series transmitters are 
able to detect a wide range of toxic 
and explosive gases. The 201T gas 
detection transmitter can work in an 
addressable network mode with the 
301C controller through an RS-485 
Modbus link. They can also be used 
in a stand-alone conguration with 
an optional 4-20mA or alarm relay 
outputs.
The catalytic sensors of the 201T 
can be used to detect hundreds of 
different gasses and inammable 
vapour concentrations. Toxic 
gasses are detected by way 
of electrochemical cells, while 
metal-air battery cells are used to 
detect oxygen. Moreover, a second 
generation of semi-conductor 
detectors offer a highly effective 
solution for a variety of different 
applications.
General Specication
Uses
Power Requirement
Size
Weight
Display
Visual Indicators
Relay Output 
Rating
Audible Alarm
Optional Outputs
Sensing Technology
Q1-type Sensor
Q2-type Sensor
Detection
Ratings and Certications:
Certied to
Conforms to
Work horse transmitter of a gas detection network to be used with the 301C controller providing a cost-effective solution to gas related hazards and energy 
management
7-27 VAC, 24-38 VDC, 250 mA
8.4 x 5.3 x 2.25 in. (21.3 x 13.4 x 5.7 cm)
0.88 lb (0.4kg)
10-step LED or LCD
Failure Indication: Yellow LED (Available in network configuration only) 
Normal Operation: Green LED
5A, 30VDC or 250 VAC (resistive load)
65 dBA at 3 ft. / 1 m
RS-485 Modbus, 4-20mA, Alarm relay
Toxic: Electrochemical 
Combustibles: Catalytic 
Oxygen: Diffusion fuel cell
Refrigerants: Solid-state 
Carbon Monoxide: Electrochemical
Carbon Monoxide (CO) 0-50 ppm
Nitrogen Dioxide (NO
Oxygen (O
Combustibles 0-100% LEL — +/- 3% +/- 5% — 0 - 95% RH, 
Refrigerants (R134a) —  0-2000 ppm — +/- 10% — 40 - 100% RH, 
CAN/CSA C22.2 No. 61010-1
ANSI/UL 61010-1 
Gas Detected Detection Range Accuracy Operating Humidity Range Operating Temperature Range
Q1 Q2 Q1 Q2 Q1 Q2 Q1 Q2
0-100 ppm 
0-250 ppm (std) 
0-500 ppm
) 0-10 ppm — +/- 3% — 15 - 90% RH, 
2
) 0-1 ppm — +/- 3% — 5 - 95% RH, 
2
 116662
0-250 ppm +/- 3% +/- 5% 0 - 90% RH 
non-condensing
continuous
continuous
10 - 95% RH 
non-condensing
— -22 to 122°F 
— -4 to 131°F
non-condensing
non-condensing
-4 to 122°F 
(-20 to +50°C) 
(-30 to +50°C)
(-20 to +55°C)
—  4 to 104°F
— 32 to 122°F
-4 to 122°F 
(-20 to +50°C)
—
—
(-10 to +40°C)
(0 to +50°C)
Please Note:
While every effort has been made to ensure  
accuracy in this publication, no responsibility  
can be accepted for errors or omissions.  
Data may change, as well as legislation, and you  
are strongly advised to obtain copies of the most 
recently issued regulations, standards, and guidelines. 
This publication is not intended to form the  
basis of a contract. 
© 2007 Honeywell Analytics
H_201T_DS01002_V3
10/09
© 2009 Honeywell Analytics
HWA6076