This control panel complies with the following NFPA standards:
NFPA 72-1993 Central Station Signaling Systems (Automatic, Manual, and Waterflow). Protected
Premises Unit (Requires NOTI-FIRE 911A/911AC DACT or MS5012 Slave Communicator).
NFPA 72-1993 Local (Automatic, Manual, Waterflow and Sprinkler Supervisory) Protective Signaling
Systems.
NFPA 72-1993 Auxiliary (Automatic, Manual, and Waterflow) Protective Signaling Systems. (Requires
4XTM.)
NFPA 72-1993 Remote Station (Automatic, Manual, and Waterflow) Protective Signaling Systems.
(Requires 4XTM or NOTI•FIRE 911A/911AC DACT.)
NFPA 72-1993 Proprietary (Automatic, Manual, and Waterflow) Protective Signaling Systems. (Requires
Potter EFT-C McCulloh Transmitter.)
IIAdditional Information
Note: Before proceeding, the installer should be familiar with the following documents and standards:
NFPA 72 National Fire Alarm Code
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers - Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1638 Visual Signaling Appliances
UL 1971 Signaling Devices for the Hearing Impaired
CAN/ULC-S524-M91 Standard for Installation of Fire Alarm Systems
CAN/ULC-S527-M87 Standard for Control Units for Fire Alarm Systems
Other:
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction
Notifier Device Compatibility Document,15378.
ADA Americans with Disabilities Act
4
SFP-400B 15124:G1 06/24/97
1.0 The SFP-400B
1.1Features
o Microprocessor-controlled.
o Power-limited on all circuits except Municipal
Box Output.
o Alarm and trouble resound.
o Four Style B Initiating Device Circuits.
o Two Style Y Notification Circuits.
o General alarm and trouble relays.
o Optional module for 4 zone relays (4XZM).
o Optional transmitter module (4XTM). Com-
plies with NFPA 72 Auxiliary and Remote
Station Protective Signaling systems.
o Optional supervised remote annunciator
(RZA-4X). Requires LED Interface Module
(4XLM).
o Optional digital communicator (NOTI-FIRE
911A/911AC). Complies with NFPA 721993 Central Station and Remote Station
Protective Signaling systems.
o Waterflow Input Option.
o Supervisory Input Option.
1.2Circuits
oComplies with NFPA 72 Proprietary Protective
Signaling System (requires Potter EFT-C
McCulloh Transmitter).
o One Man Walk Test.
o Disable/enable controls per Initiating Device
Circuit.
o Last Event Recall.
o Battery/Earth fault supervision.
o Fuse protection on all Notification Appliance
Circuits.
o Unregulated output power, 2.25 amperes.
o 7 AH to 15 AH battery options, up to 90 hours
standby.
o Resettable and non-resettable regulated power
outputs.
o Extensive transient protection.
o Watchdog timer to supervise microprocessor
(includes MICRO FAIL LED).
o Output circuits protected against false activa-
tions.
o Slide-in zone identification labels.
o Steel cabinet 14.5" wide by16" high by 5" deep.
o Dead-front dress panel option (DP-400B).
o Alarm verification option.
Input Circuits
Initiating Device Circuit 1 (Style B)
Initiating Device Circuit 2 (Style B)
Initiating Device Circuit 3 (Style B)
Initiating Device Circuit 4 (Style B)
The SFP-400B has mounting slots for two option boards. Two of the three option modules may be installed.
(see Section
Transmitter Module (4XTM)
The Transmitter Module provides a supervised output for local energy
municipal box transmitter (for NFPA 72-1993 Auxiliary Protective Signaling
System) and alarm and trouble reverse polarity circuits (for NFPA 72-1993
Remote Station Protective Signaling System). Also included is a DISABLE
switch and disable trouble LED.
polarity circuit will open on trouble if no alarm exists.
For Local Energy Municipal Box service (NFPA 72-1993 Auxiliary Fire
Alarm System)
Supervisory current: 5.0 mA.
Trip current: 0.35 amps (subtracted from Notification Appliance power).
Coil Voltage: 3.65 VDC.
Coil resistance: 14.6 ohms.
Maximum allowable wire resistance between panel and trip coil: 3 ohms.
Municipal Box wiring can leave the building.
For Remote Station service (NFPA 72-1993 Remote Station Fire Alarm
System):
Maximum load for each circuit: 10 mA.
Reverse polarity output voltage: 24 VDC.
Remote Alarm and Remote Trouble wiring can leave the building.
"Optional Modules"
)
As a jumper option, the alarm reverse
LED Interface Module (4XLM)
The LED Interface Module supports the RZA-4X Remote Annunciator
module. Annunciator wiring is supervised for open conditions by this
module. The Annunciator Driver Module mounts to the main board, occupying one of the two option connectors.
Notes:
Maximum voltage/current, each output: 27.6V/8mA.
Outputs are power limited.
Zone Relay Module (4XZM)
The Zone Relay module provides Form-C contacts for the following:
As a jumper option, the first four relays described below can be made silenceable.
•Alarm Zone 1
•Alarm Zone 2
•Alarm Zone 3
•Alarm Zone 4 or Supervisory (see Section
"Output Circuits"
)
•System Alarm
•System Trouble
Dry Form-C contacts rated:
2.0 amps @ 30 VDC (resistive),
0.5 amps @ 30 VAC (resistive).
Note: Use the Disconnect Switch located below the relays to disconnect the relays.
SFP-400B 15124:G1 06/24/97
7
911AC Digital Communicator
The Noti•Fire 911AC is a stand-alone, three
channel Digital Alarm Communicator Transmitter (DACT) designed to provide for offpremises monitoring of a fire alarm control
panel. The 911AC is triggered by the alarm,
trouble, and/or supervisory contacts received
from the control panel and converts them into
digital transmission format. It communicates
with a digital receiver by means of one of two
transmission formats, BFSK or Pulsed Fast
Signal Round format.
Install the Noti•Fire 911AC Digital Communicator in accordance with the 911AC Installation Manual.
Interconnections between the control panel and the digital communicator are illustrated in Figure B-3.
Power Requirements: 24 VDC, 30 mA in Normal; 138 mA while communicating; 166.8 mA with alarm and
trouble relays while communicating.
Retard time and Reset time must be programmed for zero seconds when connecting the alarm initiating
circuit to an existing control panel.
For more detailed instructions, refer to the Noti•Fire 911AC manual, P/N 74-06200-005-A.
Note: 12V panels (SFP-400B) must use the 911AC.
1.4Remote Annunciator
Notifier Remote Annunciator (RZA-4X)
The Remote Annunciator mounts on a standard single-gang box, and provides LED
indication of the following:
•Alarm Zone 1 (red)
•Alarm Zone 2 (red)
•Alarm Zone 3 (red)
•Alarm Zone 4 (red)
•System Trouble LED (yellow)
A Local Trouble Sounder and Silence Switch are also provided. All LED wiring is
supervised for open conditions. Any open condition will cause the System Trouble
LED to illuminate. Slide-in paper labels permit an easy change of zone information.
Note: The Remote Annunciator requires the use of an LED Interface module (4XLM).
8
SFP-400B 15124:G1 06/24/97
1.5Specifications
AC Power
For the SFP-400B: 120 VAC, 50/60 Hz, 1.2 amps
For the SFP-400BE: 220/240 VAC, 50 Hz, 0.6 amps
Wire size: minimum #14 AWG with 600V insulation
Battery (lead acid only)
Maximum Charging Circuit: 27.6V, 1.5 amps
Maximum Battery Capacity: 15 AH
(Batteries larger than 7 AH require Notifier BB-17 or similar UL listed battery cabinet).
Initiating Device Circuits
Power-limited circuitry
Operation: Style B (Class B)
Normal Operating Voltage: 24 VDC (ripple = 1.0V peak-to-peak)
Alarm current: 15 mA minimum
Short circuit current: 40 mA maximum
Maximum detector current in standby: 2 mA (max) per zone
Maximum loop resistance: 200 ohms
End-of-line resistor: 4.7K, 1/2-Watt
Detector loop current is sufficient to ensure operation of one alarmed detector per zone.
Supervisory current: 5 mA (including end-of-line resistor)
AC Circuit
Breaker
Notification Appliance Circuits
Power-limited circuitry
Maximum allowable voltage drop due to wiring: 2 VDC
Normal Operating Voltage: 24 VDC
Total current available to all external devices: 2.25 amps.
Maximum signaling current per circuit: 1.5 amps
End-of-line resistor: 4.7K, 1/2-Watt (part # 71252 UL listed)
Alarm and Trouble Relays
Dry Form-C contacts rated: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive). All relays
must be connected to a power-limited power supply.
Four-wire Smoke Detector Power
Up to 200 mA is available for powering 4-wire smoke detectors.
Maximum ripple voltage: 1.0 V p/p
Non-resettable Power
Total DC current available from this output is up to 200 mA (subtracted from four-wire smoke power).
Maximum ripple voltage: 1.0 V p/p
Unregulated Power
Total DC current available for powering external devices is 0.5 amp (subtracted from 2.25 amps available
to notification appliance circuits).
Maximum ripple voltage: 100 mV p/p
Note: For device compatibility data, refer to the Device Compatibility Chart.
SFP-400B 15124:G1 06/24/97
9
Door = 14.218"
Backbox = 14"
Cabinet = 3.047"
Backbox = 3.0"
Door = 14.718"
Backbox = 14.5"
10
Trim Ring
(TR-2-R)
Figure 1.5-1: Cabinet Dimensions
SFP-400B 15124:G1 06/24/97
2.0System Operation
2.1System Status LEDs
Alarm, Trouble and Supervisory LEDs will flash on and off until the event(s) has been acknowledged
(TONE or ALARM SILENCE), at which point the LED will illuminate steadily.
AC POWER
Green LED that illuminates steadily to indicate presence of AC power.
SYSTEM ALARM
Red LED that flashes when an alarm occurs.
ALARM TEST
Red LED that illuminates during Walk Test.
SUPERVISORY
Yellow LED that flashes upon activation of a
supervisory device (such as tamper switch)
on Zone 4.
SYSTEM TROUBLE
Yellow LED that flashes for any trouble condition, including those associated with option
boards.
CIRCUIT TROUBLE
Yellow LED that flashes for trouble conditions
on output circuits (notification).
ALARM SILENCED
Yellow LED that illuminates steadily when the
ALARM SILENCE switch has been pushed
after an alarm.
POWER TROUBLE
Yellow LED that flashes for low or disconnected batteries and earth fault conditions.
BATT
Yellow LED that illuminates steadily on
motherboard when battery is low or not detected (not visible through door).
EARTH
Yellow LED that illuminates steadily on
motherboard during a ground fault condition
(not visible through door).
MICRO FAIL
Yellow LED that illuminates on motherboard
when watchdog timer detects microprocessor
failure (not visible through door).
SFP-400B 15124:G1 06/24/97
11
Loading...
+ 25 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.