Notifier SFP-400B User Manual

SFP-400B
FIRE ALARM CONTROL PANEL
AC POWER
SYSTEM ALARM
ALARM TEST
SUPERVISORY
TROUBLE
CIRCUIT
TROUBLE
ALARM
SILENCED
POWER
TROUBLE
TONE
SILENCE
ALARM
SILENCE
ALARM
ACTIVATE
ZONE 1
ZONE 2
ZONE 3
ZONE 4
RESET
Doc.# 15124:G1 ECN 97-192
Installation Precautions - Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm
control panel. Disconnect all sources of power before servicing. Control unit and
associated equipment may be damaged by removing and/or inserting cards,
modules, or interconnecting cables while the unit is energized. Do not attempt to
install, service, or operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software Changes: To ensure
proper system operation, this product must be tested in accordance with NFPA 72-
1993 Chapter 7 after any programming operation or change in site-specific software.
Reacceptance testing is required after any change, addition or deletion of system
components, or after any modification, repair or adjustment to system hardware or
wiring.
All components, circuits, system operations, or software functions known to be
affected by a change must be 100% tested. In addition, to ensure that other
operations are not inadvertently affected, at least 10% of initiating devices that are
not directly affected by the change, up to a maximum of 50 devices, must also be
tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49O C/32-120O F
and at a relative humidity of 85% RH (non-condensing) at 30O C/86O F.
However, the useful life of the system's standby batteries and the electronic
components may be adversely affected by extreme temperature ranges and
humidity. Therefore, it is recommended that this system and its peripherals be
installed in an environment with a nominal room temperature of 15-27O C/60-80
F.
Verify that wire sizes are adequate for all initiating and indicating device loops.
Most devices cannot tolerate more than a 10% I.R. drop from the specified device
voltage.
Like all solid state electronic devices, this system may operate erratically or can
be damaged when subjected to lightning induced transients. Although no system is
completely immune from lightning transients and interferences, proper grounding will
reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to
an increased susceptibility to nearby lightning strikes. Consult with the Technical
Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards.
Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching
of the enclosure. When possible, make all cable entries from the sides or rear.
Before making modifications, verify that they will not interfere with battery,
transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over tightening may damage
threads, resulting in reduced terminal contact pressure and difficulty with screw
terminal removal.
This system contains static-sensitive components. Always ground yourself with a
proper wrist strap before handling any circuits so that static charges are removed
from the body. Use static suppressive packaging to protect electronic assemblies
removed from the unit.
O
Follow the instructions in the installation, operating, and programming manuals.
These instructions must be followed to avoid damage to the control panel and
associated equipment. FACP operation and reliability depend upon proper
installation.
Fire Alarm System Limitations
An automatic fire alarm system - typically made up of smoke detectors, heat
detectors, manual pull stations, audible warning devices, and a fire alarm control
with remote notification capability can provide early warning of a developing fire.
Such a system, however, does not assure protection against property damage or
loss of life resulting from a fire.
Any fire alarm system may fail for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such
as in chimneys, in walls, or roofs, or on the other side of closed doors. Smoke
detectors also may not sense a fire on another level or floor of a building. A second
floor detector, for example, may not sense a first floor or basement fire. Further-
more, all types of smoke detectors - both ionization and photoelectric types, have
sensing limitations. No type of smoke detector can sense every kind of fire caused
by carelessness and safety hazards like smoking in bed, violent explosions,
escaping gas, improper storage of flammable materials, overloaded electrical
circuits, children playing with matches, or arson.
IMPORTANT! Smoke detectors must be installed in the same room as the
control panel and in rooms used by the system for the connection of alarm
transmission wiring, communications, signaling, and/or power. If detectors are
not so located, a developing fire may damage the alarm system, crippling its
ability to report a fire.
While installing a fire alarm system may make lower insurance
rates possible, it is not a substitute for fire insurance!
FCC Warning
Audible warning devices such as bells may not alert people if these devices are
located on the other side of closed or partly open doors or are located on another
floor of a building.
A fire alarm system will not operate without any electrical power. If AC power fails,
the system will operate from standby batteries only for a specified time.
Rate-of-Rise heat detectors may be subject to reduced sensitivity over time. For
this reason, the rate-of-rise feature of each detector should be tested at least once
per year by a qualified fire protection specialist.
Equipment used in the system may not be technically compatible with the control.
It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central
monitoring station may be out of service or temporarily disabled.
The most common cause of fire alarm malfunctions, however, is inadequate
maintenance. All devices and system wiring should be tested and maintained by
professional fire alarm installers following written procedures supplied with each
device. System inspection and testing should be scheduled monthly or as required
by National and/or local fire codes. Adequate written records of all inspections should
be kept.
WARNING: This equipment generates, uses, and can radiate radio frequency
energy and if not installed and used in accordance with the instruction manual, may
cause interference to radio communications. It has been tested and found to comply
with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC
Rules, which is designed to provide reasonable protection against such interference
when operated in a commercial environment. Operation of this equipment in a
residential area is likely to cause interference, in which case the user will be required
to correct the interference at his own expense.
Technical Publishing Document PRECAULG.P65 12/31/96
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise
emissions from digital apparatus set out in the Radio Interference Regulations of the
Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits radioelectriques depassant les
limites applicables aux appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par le ministere des Communica-
tions du Canada.
Table of Contents
I NFPA Standards ...............................................................4
II Additional Information..................................................... 4
1.0 The SFP-400B.......................................................................................5
1.1 Features......................................................................................................... 5
1.2 Circuits ........................................................................................................... 5
1.3 Optional Boards ............................................................................................. 7
1.4 Remote Annunciator ...................................................................................... 8
1.5 Specifications................................................................................................. 9
2.0 System Operation..............................................................................11
2.1 System Status LEDs .................................................................................... 11
2.2 Control Switches .......................................................................................... 12
2.3 Zone Status LEDs........................................................................................ 12
2.4 Supervisor y .................................................................................................. 13
2.5 Zone Disable................................................................................................ 13
2.6 Last Event Recall ......................................................................................... 13
3.0 Installation Procedure.......................................................................14
3.1 General ........................................................................................................ 14
3.2 Initiating Device Circuits............................................................................... 15
3.3 4-Wire Smoke Detector Connections........................................................... 16
3.4 Output Circuits ............................................................................................. 17
3.5 Power ........................................................................................................... 18
3.6 Optional Modules ......................................................................................... 19
3.7 Dip Switch Location and Descriptions.......................................................... 24
Appendix A: Power Calculations...........................................................25
Appendix B: NFPA Standard-Specific Requirements..........................27
Trouble Shooting Table............................................................................ 34
SFP-400B 15124:G1 06/24/97
3
I NFPA Standards
This control panel complies with the following NFPA standards:
NFPA 72-1993 Central Station Signaling Systems (Automatic, Manual, and Waterflow). Protected Premises Unit (Requires NOTI-FIRE 911A/911AC DACT or MS5012 Slave Communicator). NFPA 72-1993 Local (Automatic, Manual, Waterflow and Sprinkler Supervisory) Protective Signaling Systems. NFPA 72-1993 Auxiliary (Automatic, Manual, and Waterflow) Protective Signaling Systems. (Requires 4XTM.) NFPA 72-1993 Remote Station (Automatic, Manual, and Waterflow) Protective Signaling Systems. (Requires 4XTM or NOTI•FIRE 911A/911AC DACT.) NFPA 72-1993 Proprietary (Automatic, Manual, and Waterflow) Protective Signaling Systems. (Requires Potter EFT-C McCulloh Transmitter.)
II Additional Information
Note: Before proceeding, the installer should be familiar with the following documents and standards:
NFPA 72 National Fire Alarm Code
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes UL 217 Smoke Detectors, Single and Multiple Station UL 228 Door Closers - Holders for Fire Protective Signaling Systems UL 268 Smoke Detectors for Fire Protective Signaling Systems UL 268A Smoke Detectors for Duct Applications UL 346 Waterflow Indicators for Fire Protective Signaling Systems UL 464 Audible Signaling Appliances UL 521 Heat Detectors for Fire Protective Signaling Systems UL 864 Standard for Control Units for Fire Protective Signaling Systems UL 1481 Power Supplies for Fire Protective Signaling Systems UL 1638 Visual Signaling Appliances UL 1971 Signaling Devices for the Hearing Impaired CAN/ULC-S524-M91 Standard for Installation of Fire Alarm Systems CAN/ULC-S527-M87 Standard for Control Units for Fire Alarm Systems
Other:
NEC Article 300 Wiring Methods NEC Article 760 Fire Protective Signaling Systems Applicable Local and State Building Codes Requirements of the Local Authority Having Jurisdiction Notifier Device Compatibility Document,15378. ADA Americans with Disabilities Act
4
SFP-400B 15124:G1 06/24/97
1.0 The SFP-400B
1.1 Features
o Microprocessor-controlled. o Power-limited on all circuits except Municipal
Box Output.
o Alarm and trouble resound. o Four Style B Initiating Device Circuits. o Two Style Y Notification Circuits. o General alarm and trouble relays. o Optional module for 4 zone relays (4XZM). o Optional transmitter module (4XTM). Com-
plies with NFPA 72 Auxiliary and Remote Station Protective Signaling systems.
o Optional supervised remote annunciator
(RZA-4X). Requires LED Interface Module (4XLM).
o Optional digital communicator (NOTI-FIRE
911A/911AC). Complies with NFPA 72­1993 Central Station and Remote Station Protective Signaling systems.
o Waterflow Input Option. o Supervisory Input Option.
1.2 Circuits
o Complies with NFPA 72 Proprietary Protective
Signaling System (requires Potter EFT-C McCulloh Transmitter).
o One Man Walk Test. o Disable/enable controls per Initiating Device
Circuit.
o Last Event Recall. o Battery/Earth fault supervision. o Fuse protection on all Notification Appliance
Circuits.
o Unregulated output power, 2.25 amperes. o 7 AH to 15 AH battery options, up to 90 hours
standby.
o Resettable and non-resettable regulated power
outputs.
o Extensive transient protection. o Watchdog timer to supervise microprocessor
(includes MICRO FAIL LED).
o Output circuits protected against false activa-
tions.
o Slide-in zone identification labels. o Steel cabinet 14.5" wide by16" high by 5" deep. o Dead-front dress panel option (DP-400B). o Alarm verification option.
Input Circuits
Initiating Device Circuit 1 (Style B) Initiating Device Circuit 2 (Style B) Initiating Device Circuit 3 (Style B) Initiating Device Circuit 4 (Style B)
Output circuits
Notification Appliance Circuit 1 (Style Y) Notification Appliance Circuit 2 (Style Y)
Front Panel Control Switches
Switch 1 Tone Silence Switch 2 Alarm Silence Switch 3 Alarm Activate Switch 4 System Reset
SFP-400B 15124:G1 06/24/97
5
Figure 1.0-1: SFP-400B Installation Diagram
6
SFP-400B 15124:G1 06/24/97
1.3 Optional Boards
The SFP-400B has mounting slots for two option boards. Two of the three option modules may be installed. (see Section
Transmitter Module (4XTM)
The Transmitter Module provides a supervised output for local energy municipal box transmitter (for NFPA 72-1993 Auxiliary Protective Signaling System) and alarm and trouble reverse polarity circuits (for NFPA 72-1993 Remote Station Protective Signaling System). Also included is a DISABLE switch and disable trouble LED.
polarity circuit will open on trouble if no alarm exists.
For Local Energy Municipal Box service (NFPA 72-1993 Auxiliary Fire Alarm System) Supervisory current: 5.0 mA. Trip current: 0.35 amps (subtracted from Notification Appliance power). Coil Voltage: 3.65 VDC. Coil resistance: 14.6 ohms. Maximum allowable wire resistance between panel and trip coil: 3 ohms. Municipal Box wiring can leave the building. For Remote Station service (NFPA 72-1993 Remote Station Fire Alarm System): Maximum load for each circuit: 10 mA. Reverse polarity output voltage: 24 VDC. Remote Alarm and Remote Trouble wiring can leave the building.
"Optional Modules"
)
As a jumper option, the alarm reverse
LED Interface Module (4XLM)
The LED Interface Module supports the RZA-4X Remote Annunciator module. Annunciator wiring is supervised for open conditions by this module. The Annunciator Driver Module mounts to the main board, occupy­ing one of the two option connectors.
Notes:
Maximum voltage/current, each output: 27.6V/8mA. Outputs are power limited.
Zone Relay Module (4XZM)
The Zone Relay module provides Form-C contacts for the following:
As a jumper option, the first four relays described below can be made silenceable.
Alarm Zone 1
Alarm Zone 2
Alarm Zone 3
Alarm Zone 4 or Supervisory (see Section
"Output Circuits"
)
System Alarm
System Trouble
Dry Form-C contacts rated:
2.0 amps @ 30 VDC (resistive),
0.5 amps @ 30 VAC (resistive).
Note: Use the Disconnect Switch located below the relays to disconnect the relays.
SFP-400B 15124:G1 06/24/97
7
911AC Digital Communicator
The Noti•Fire 911AC is a stand-alone, three channel Digital Alarm Communicator Trans­mitter (DACT) designed to provide for off­premises monitoring of a fire alarm control panel. The 911AC is triggered by the alarm, trouble, and/or supervisory contacts received from the control panel and converts them into digital transmission format. It communicates with a digital receiver by means of one of two transmission formats, BFSK or Pulsed Fast Signal Round format.
Install the Noti•Fire 911AC Digital Communicator in accordance with the 911AC Installation Manual. Interconnections between the control panel and the digital communicator are illustrated in Figure B-3.
Power Requirements: 24 VDC, 30 mA in Normal; 138 mA while communicating; 166.8 mA with alarm and trouble relays while communicating.
Retard time and Reset time must be programmed for zero seconds when connecting the alarm initiating circuit to an existing control panel.
For more detailed instructions, refer to the Noti•Fire 911AC manual, P/N 74-06200-005-A.
Note: 12V panels (SFP-400B) must use the 911AC.
1.4 Remote Annunciator
Notifier Remote Annunciator (RZA-4X)
The Remote Annunciator mounts on a standard single-gang box, and provides LED indication of the following:
Alarm Zone 1 (red)
Alarm Zone 2 (red)
Alarm Zone 3 (red)
Alarm Zone 4 (red)
System Trouble LED (yellow)
A Local Trouble Sounder and Silence Switch are also provided. All LED wiring is supervised for open conditions. Any open condition will cause the System Trouble LED to illuminate. Slide-in paper labels permit an easy change of zone information.
Note: The Remote Annunciator requires the use of an LED Interface module (4XLM).
8
SFP-400B 15124:G1 06/24/97
1.5 Specifications
AC Power
For the SFP-400B: 120 VAC, 50/60 Hz, 1.2 amps For the SFP-400BE: 220/240 VAC, 50 Hz, 0.6 amps Wire size: minimum #14 AWG with 600V insulation
Battery (lead acid only)
Maximum Charging Circuit: 27.6V, 1.5 amps Maximum Battery Capacity: 15 AH (Batteries larger than 7 AH require Notifier BB-17 or similar UL listed battery cabinet).
Initiating Device Circuits
Power-limited circuitry Operation: Style B (Class B) Normal Operating Voltage: 24 VDC (ripple = 1.0V peak-to-peak) Alarm current: 15 mA minimum Short circuit current: 40 mA maximum Maximum detector current in standby: 2 mA (max) per zone Maximum loop resistance: 200 ohms End-of-line resistor: 4.7K, 1/2-Watt Detector loop current is sufficient to ensure operation of one alarmed detector per zone. Supervisory current: 5 mA (including end-of-line resistor)
AC Circuit Breaker
Notification Appliance Circuits
Power-limited circuitry Maximum allowable voltage drop due to wiring: 2 VDC Normal Operating Voltage: 24 VDC Total current available to all external devices: 2.25 amps.
Maximum signaling current per circuit: 1.5 amps End-of-line resistor: 4.7K, 1/2-Watt (part # 71252 UL listed)
Alarm and Trouble Relays
Dry Form-C contacts rated: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive). All relays must be connected to a power-limited power supply.
Four-wire Smoke Detector Power
Up to 200 mA is available for powering 4-wire smoke detectors. Maximum ripple voltage: 1.0 V p/p
Non-resettable Power
Total DC current available from this output is up to 200 mA (subtracted from four-wire smoke power). Maximum ripple voltage: 1.0 V p/p
Unregulated Power
Total DC current available for powering external devices is 0.5 amp (subtracted from 2.25 amps available to notification appliance circuits). Maximum ripple voltage: 100 mV p/p
Note: For device compatibility data, refer to the Device Compatibility Chart.
SFP-400B 15124:G1 06/24/97
9
Door = 14.218" Backbox = 14"
Cabinet = 3.047"
Backbox = 3.0"
Door = 14.718"
Backbox = 14.5"
10
Trim Ring
(TR-2-R)
Figure 1.5-1: Cabinet Dimensions
SFP-400B 15124:G1 06/24/97
2.0 System Operation
2.1 System Status LEDs
Alarm, Trouble and Supervisory LEDs will flash on and off until the event(s) has been acknowledged (TONE or ALARM SILENCE), at which point the LED will illuminate steadily.
AC POWER
Green LED that illuminates steadily to indi­cate presence of AC power.
SYSTEM ALARM
Red LED that flashes when an alarm occurs.
ALARM TEST
Red LED that illuminates during Walk Test.
SUPERVISORY
Yellow LED that flashes upon activation of a supervisory device (such as tamper switch) on Zone 4.
SYSTEM TROUBLE
Yellow LED that flashes for any trouble condi­tion, including those associated with option boards.
CIRCUIT TROUBLE
Yellow LED that flashes for trouble conditions on output circuits (notification).
ALARM SILENCED
Yellow LED that illuminates steadily when the ALARM SILENCE switch has been pushed after an alarm.
POWER TROUBLE
Yellow LED that flashes for low or discon­nected batteries and earth fault conditions.
BATT
Yellow LED that illuminates steadily on motherboard when battery is low or not de­tected (not visible through door).
EARTH
Yellow LED that illuminates steadily on motherboard during a ground fault condition (not visible through door).
MICRO FAIL
Yellow LED that illuminates on motherboard when watchdog timer detects microprocessor failure (not visible through door).
SFP-400B 15124:G1 06/24/97
11
Loading...
+ 25 hidden pages