Notifier Selectable Output Notification Appliances User Manual

Indoor Ceiling
Horn/Strobe
Outdoor Ceiling
Strobe
Indoor Wall
Horn/Strobe
Indoor Ceiling
Strobe
Indoor Wall
Horn
Outdoor Wall
Strobe
7087pho1.jpg
7087pho4.jpg
7087pho3.jpg
7087pho2.jpg
7087pho5.jpg
7087pho6.jpg
SpectrAlert® Advance
Selectable Output Notification Appliances
System Sensor® SpectrAlert® Advance selectable-output horns, strobes and horn/strobes are rich with features guaran­teed to cut installation times and maximize profits. The Spec­trAlert Advance series of notification appliances is designed to simplify your installations, with features such as: plug-in designs, instant feedback messages to ensure correct installa­tion of individual devices, and eleven field-selectable candela settings for wall and ceiling strobes and horn/strobes.
More specifically, when installing Advance products, first attach a universal mounting plate to a four-inch square, four­inch octagon, or double-gang junction box. The two-wire mounting plate attaches to a single-gang junction box.
Then, connect the notification appliance circuit wiring to the SEMS terminals on the mounting plate.
Finally, attach the horn, strobe, or horn/strobe to the mounting plate by inserting the product’s tabs in the mounting plate’s grooves. The device will rotate into position, locking the prod­uct’s pins into the mounting plate’s terminals. The device will temporarily hold in place with a catch until it is secured with a captured mounting screw.
SpectrAlert Advance products allow you to choose:
• 12 or 24 volts.
• 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, or 185 can­dela by way of a rear-mounted slide switch and front view­ing window.
• Horn tones and volume by way of a rotary switch.
• The SpectrAlert Advance series includes outdoor notifica­tion appliances. Outdoor strobes and horn/strobes (two­wire and four-wire) are available for wall or ceiling. Outdoor horns are available for wall only. All System Sensor outdoor products are rated between –40°F and 151°F (–40°C and 66°C) in wet or dry applications.
Models available:
• Indoor wall-mount: horn, strobe, 2-wire horn/strobe, 4-wire horn/strobe.
• Indoor ceiling-mount: strobe, 2-wire horn/strobe, 4-wire horn/strobe.
• Outdoor wall-mount: horn, strobe, 2-wire horn/strobe, 4­wire horn/strobe.
• Outdoor ceiling-mount: strobe, 2-wire horn/strobe, 4-wire horn/strobe.
Features
• Plug-in design.
• Same mounting plate for wall- and ceiling-mount units.
• Shorting spring on mounting plate for continuity check before installation.
• Captive mounting screw.
• Tamper-resistance capability.
• Field-selectable candela settings on wall and ceiling units: 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, 185.
• Automatic selection of 12 or 24 volt operation at 15 and 15/ 75 candela.
• Outdoor wall and ceiling products.
DN-7087:C1
Audio/Visual Devices
• Outdoor products rated from –40°F and 151°F (–40°C and 66°C).
• Outdoor products rainproof per UL50 (NEMA 3R) and weatherproof per NEMA 4X, IP56
• Minimal intrusion into the backbox.
• Horn rated at 88+ dbA at 16 volts.
• Rotary switch for tone selection.
• Three horn volume settings.
• Electrically compatible with existing SpectrAlert products.
Engineering Specifications
SpectrAlert Advance horns, strobes, and horn/strobes shall mount to a standard 4.0" x 4.0" x 1.5" (10.16 x 10.16 x 3.81 cm) backbox, 4.0" (10.16 cm) octagonal backbox, or a double­gang backbox. Two-wire products shall also mount to a single­gang 2.0" x 4.0" x 1.875" (5.08 x 10.16 x 4.763 cm) backbox. A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, Spec­trAlert Advance products, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-coded notifi­cation appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12­volt rated notification appliance circuit outputs shall operate between 9 and 17.5 volts; 24-volt rated notification appliance circuit outputs shall operate between 17 and 33 volts. Indoor SpectrAlert Advance products shall operate between 32°F and 120°F (0°C and 49°C) from a regulated DC, or full-wave-recti­fied, unfiltered power supply. Strobes and horn/strobes shall have field-selectable candela settings including 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, 185.
DN-7087:C1 • 11/9/11 — Page 1 of 4
STROBE
Strobe Current Draw, UL Maximum (mA RMS)
Candela
8 – 17.5 V 16 – 33 V
DC FWR DC FWR
Standard Candela Range
15 123 128 66 71
15/75 142 148 77 81
30 NA N/A 94 96
75 NA NA 158 153
95 NA NA 181 176
110 NA NA 20 2 195
115 NA NA 21 0 205
High Candela Range
135 NA NA 228 207
150 NA NA 246 220
177 NA NA 281 251
185 NA NA 286 258
Horn Current Draw, UL Maximum (mA RMS)
Sound
Pattern
dB
8 – 17.5 V 16 – 33 V
DC FWR DC FWR
Temporal High 57 55 69 75
Temporal Medium 44 49 58 69
Temporal Low 38 44 44 48
Non-temporal High 57 56 69 75
Non-temporal Medium 42 50 60 69
Non-temporal Low 41 44 50 50
Coded High 57 55 69 75
Coded Medium 44 51 56 69
Coded Low 40 46 52 50
The strobe shall be a System Sensor SpectrAlert Advance Model _______ listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-sig­naling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appli­ances, flashing at 1 Hz over the strobe’s entire operating volt­age range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system.
HORN/STROBE COMBINATION
The horn/strobe shall be a System Sensor SpectrAlert Advance Model _______ listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn/strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act require­ments for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector sys­tem. The horn shall have three audibility options and an option to switch between a Temporal 3 pattern and a Non-Temporal (continuous) pattern. These options are set by a multiple posi­tion switch. On four-wire products, the strobe shall be powered independently of the sounder. The horn on horn/strobe models shall operate on a coded or non-coded power supply.
OUTDOOR PRODUCTS
SpectrAlert Advance outdoor horns, strobes and horn/strobes shall be listed for outdoor use by UL and shall operate between –40°F and 151°F (–40°C and 66°C). The products shall be listed for use with a System Sensor outdoor/weather­proof backbox with half-inch and three-fourths-inch conduit entries.
SYNCHRONIZATION MODULE
The module shall be a System Sensor Sync•Circuit MDL3R or MDL3W listed to UL 464 and shall be approved for fire protec­tive service. The module shall synchronize SpectrAlert strobes at 1 Hz and horns at Temporal 3. Also, while operating the strobes, the module shall silence the horns on horn/strobe models over a single pair of wires. The module shall mount to a 4.688" x 4.688" x 2.125" (11.906 x 11.906 x 5.398 cm) back­box. The module shall also control two Style Y (class B) cir­cuits or one Style Z (Class A) circuit. The module shall synchronize multiple zones. Daisy-chaining two or more syn­chronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply.
Operating Specifications
Standard operating temperature: 32°F to 120°F (0°C to 49°C).
K Series operating temperature: –40°F to 151°F (–40°C to 66°C).
Humidity range: 10% to 93% non-condensing (indoor products).
Strobe flash rate: 1 flash per second.
Nominal voltage: regulated 12 VDC/FWR or regulated 24 VDC/FWR. NOTE: Full Wave Rectified (FWR) voltage is a
non-regulated, time-varying power source that is used on some power supply and panel outputs.
Operating voltage range: 8 V to 17.5 V (12 V nominal); or 16 V to 33 V (24 V nominal). NOTE: P, S, PC, and SC prod-
ucts will operate at 12 V nominal only for 15 cd and 15/75 cd.
Input terminal wire gauge: 12 to 18 AWG (3.31 to 0.821 mm²).
Ceiling-mount dimensions (including lens): 6.8" diame­ter x 2.5" deep (17.3 cm diameter x 6.4 cm deep).
Wall-mount dimensions (including lens): 5.6" H x 4.7" W x 2.5" D (14.2 cm H x 11.9 cm W x 6.4 cm D).
Horn dimensions: 5.6" H x 4.7" W x 1.3" D (14.2 cm H x
11.9 cm W x 3.3 cm D).
Agency Listings and Approvals
The listings and approvals below apply to SpectrAlert Advance Selectable Output Notification Devices. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing sta­tus.
UL Listed: S4011 (HR__, HW__, P2__, P4__, PC2__, PC4__ models); S5512 (models SCR, SCRH, SCW, SCWH, SR, SRH, SW, SWH); S3593 (SCRHK, SCRK, SRHK, SRK).
ULC Listed: S4011 (HRA, HRKA); S5512 (typically “A” models, with exception of outdoor strobes). See Canadian
data sheet for listings and specifications.
FM approved
MEA: 452-05-E
CSFM: 7125-1653:0186 (SCR, SCRH, SCW, SCWH, SR, SRH, SW, SWH); 7300-1653:0188 (P2_, P4_, PC2_, PC4_ modules); 7135-1653:0189 (HR, HRK, HW); 7300- 1653:0187 (SCRHK, SCRK, SRHK, SRK).
Page 2 of 4 — DN-7087:C1 • 11/9/11