Notifier RP-2002C User Manual

RP-2002C
Agent Release Control Panel
General
The RP-2002C is a six-zone FACP for single and dual hazard agent releasing applications. The RP-2002C provides reliable fire detection, signaling and protection for commercial, indus­trial and institutional buildings requiring agent-based releasing. The RP-2002C is compatible with System Sensor’s i tors which are conventional smoke detectors that can transmit a maintenance trouble signal to the FACP indicating the need for cleaning and a supervisory ‘freeze’ signal when the ambi­ent temperature falls below the detector rating of approxi­mately 7.22°C. In addition, the control panel is compatible with conventional input devices such as two-wire smoke detectors, four-wire smoke detectors, pull stations, waterflow devices, tamper switches and other normally-open contact devices. Refer to the Notifier Device Compatibility Document for a com­plete listing of compatible devices.
Four outputs are programmable as NACs (Notification Appli­ance Circuits) or releasing circuits. Three programmable Form-C relays (factory programmed for Alarm, Trouble and Supervisory) and 24 VDC special application resettable and non-resettable power outputs are also included on the main circuit board. The RP-2002C supervises all wiring, AC voltage, battery charger and battery level.
Activation of a compatible smoke detector or any normally­open fire alarm initiating device will activate audible and visual signaling devices, illuminate an indicator, display alarm infor­mation on the panel’s LCD, sound the piezo sounder at the FACP, activate the FACP alarm relay and operate an optional module used to notify a remote station or initiate an auxiliary control function.
Features
• Listed to Standard ULC-S527-99.
• Designed for agent releasing standards NFPA 12, 12A, 12B, and 2001.
• Meets International Building Code (IBC) seismic require­ments.
• Disable/Enable control per input zone and output zone.
• Extensive transient protection.
• Dual hazard operation.
• Adjustable pre-discharge, discharge and waterflow delay timers.
• Cross-zone (double-interlock) capability.
• Six programmable Style B (Class B) IDCs (Initiating Device Circuit).
• System Sensor i
• Four programmable Style Y (Class B) output circuits - (spe­cial application power).
• Strobe synchronization:
System SensorWheelock
• Three programmable Form-C relays.
• 7.0 amps total 24 VDC output current.
• Resettable and non-resettable output power.
• Built-in Programmer.
3
series detector compatible.
3
detec-
Canadian DN-60444:B1
Conventional Releasing Panels
• ANN-BUS for connection to optional devices (up to 8 total of any of the following):
N-ANN-80 Remote LCD AnnunciatorN-ANN-I/O LED DriverN-ANN-S/PG Printer Module (only one allowed per panel)N-ANN-RLY Relay ModuleN-ANN-LED Annunciator Module (built-in)
• 80-character LCD display (backlit).
• Real-time clock/calendar with daylight savings time control.
• History log with 256 event storage.
• Piezo sounder for alarm, trouble and supervisory.
• 24 volt operation.
• Low AC voltage sense.
• Outputs Programmable for: – Releasing Circuits or NACS
• NACs programmable for:
Silence InhibitAuto-SilenceStrobe SynchronizationSelective Silence (horn-strobe mute)Temporal or Steady SignalSilenceable or Non-silenceableRelease Stage Sounder
• Automatic battery charger with charger supervision.
• Optional Trim Ring TR-CE (red) for semi-flush mounting the cabinet.
• Optional N-CAC-5X Class A Converter Module for Outputs and IDCs.
• Optional 4XTM Municipal Box Transmitter Module.
• Optional Digital Alarm Communicators (411, 411UD, 411UDAC).
• Optional ANN-SEC card for a secondary ANN-BUS
DN-60444:B1 • 12/22/11 — Page 1 of 4
PROGRAMMING AND SOFTWARE:
• Custom English labels (per point) may be manually entered or selected from an internal library file.
• Programmable Abort operation.
• Three programmable Form-C relay outputs.
• Pre-programmed and custom application templates.
• Continuous fire protection during online programming at the front panel.
• Program Check automatically catches common errors not linked to any zone or input point.
USER INTERFACE:
• Integral 80-character LCD display with backlighting.
• Real-time clock/calendar with automatic daylight savings adjustments.
• ANN-Bus for connection to annunciators.
• Audible or silent walk test capabilities.
• Piezo sounder for alarm, trouble, and supervisory.
Controls and Indicators
LED INDICATORS
• FIRE ALARM (red).
• SUPERVISORY (yellow).
• TROUBLE (yellow).
• AC POWER (green).
• ALARM SILENCED (yellow).
• DISCHARGED (red).
• PRE-DISCHARGE (red indicator).
• ABORT (yellow indicator).
CONTROL BUTTONS
• ACKNOWLEDGE.
• ALARM SILENCE.
• SYSTEM RESET (lamp test).
• DRILL.
AC Power – TB1
RP-2002C: 120 VAC, 60 Hz, 3.66 amps.
Wire size: minimum #14 AWG (2.0 mm tion.
• Supervised, nonpower-limited.
Battery (sealed lead acid only) – J12:
Maximum Charging Circuit - Normal Flat Charge: 27.6 VDC @ 1.4 amp. Supervised, nonpower-limited.
Maximum Charger Capacity: 18 Amp Hour battery (two 18 Amp Hour batteries can be housed in the FACP cabinet. Larger batteries require separate battery box such as the BB-26 or NFS-LBBR).
Minimum Battery Size: 12 Amp Hour.
Initiating Device Circuits - TB4 and TB6
• Zones 1 - 5 on TB4.
• Zone 6 on TB6.
• Supervised and power-limited circuitry.
• Style B (Class B) wiring with Style D (Class A) option.
• Normal Operating Voltage: Nominal 20 VDC.
• Alarm Current: 15 mA minimum.
• Short Circuit Current: 40 mA max.
• Maximum Loop Resistance: 100 Ohms.
• End-of-Line Resistor: 4.7K Ohms, 1/2 watt (PN 71252).
• Standby Current: 4 mA.
2
) with 600V insula-
Refer to the Notifier Device Compatibility Document for listed compatible devices.
Notification Appliance and Releasing Circuit(s) - TB5 and TB7
• Four Output Circuits.
• Style Y (Class B) or Style Z (Class A) with optional con­verter module.
• Special Application power.
• Supervised and power-limited circuitry.
• Normal Operating Voltage: Nominal 24 VDC.
• Maximum Signaling Current: 7.0 amps (3.0 amps maximum per NAC).
• End-of-Line Resistor: 4.7K Ohms, 1/2 watt (PN 71252).
• Max. Wiring Voltage Drop: 2 VDC.
Refer to the Notifier Device Compatibility Document for com­patible listed devices.
Form-C Relays - Programmable - TB8
• Relay 1 (factory default programmed as Alarm Relay)
• Relay 2 (factory default programmed as fail-safe Trouble Relay)
• Relay 3 (factory default programmed as Supervisory Relay)
• Relay Contact Ratings:
2 amps @ 30 VDC (resistive)0.5 amps @ 30 VAC (resistive)
Auxiliary Trouble Input – J6
The Auxiliary Trouble Input is an open collector circuit which can be used to monitor external devices for trouble conditions. It can be connected to the trouble bus of a peripheral, such as a power supply, which is compatible with open collector cir­cuits.
Special Application Resettable Power - TB9
Operating Voltage: Nominal 24 VDC.
Maximum Available Current: 500 mA - appropriate for powering 4-wire smoke detectors (see note).
• Power-limited Circuitry.
Refer to the Notifier Device Compatibility Document for com­patible listed devices.
NOTE: Total current for resettable power, nonresettable power and Output Circuits must not exceed 7.0 amps.
Special Application Resettable or Nonresettable Power ­TB9
Operating Voltage: Nominal 24 VDC.
Maximum Available Current: 500 mA (see note 1).
• Power-limited Circuitry.
• Jumper selectable by JP31 for resettable or nonresettable power.
Refer to the Notifier Device Compatibility Document for com­patible listed devices.
Page 2 of 4 — Canadian DN-60444:B1 • 12/22/11
Loading...
+ 2 hidden pages