RP-2002C
Agent Release Control Panel
General
The RP-2002C is a six-zone FACP for single and dual hazard
agent releasing applications. The RP-2002C provides reliable
fire detection, signaling and protection for commercial, industrial and institutional buildings requiring agent-based releasing.
The RP-2002C is compatible with System Sensor’s i
tors which are conventional smoke detectors that can transmit
a maintenance trouble signal to the FACP indicating the need
for cleaning and a supervisory ‘freeze’ signal when the ambient temperature falls below the detector rating of approximately 7.22°C. In addition, the control panel is compatible with
conventional input devices such as two-wire smoke detectors,
four-wire smoke detectors, pull stations, waterflow devices,
tamper switches and other normally-open contact devices.
Refer to the Notifier Device Compatibility Document for a complete listing of compatible devices.
Four outputs are programmable as NACs (Notification Appliance Circuits) or releasing circuits. Three programmable
Form-C relays (factory programmed for Alarm, Trouble and
Supervisory) and 24 VDC special application resettable and
non-resettable power outputs are also included on the main
circuit board. The RP-2002C supervises all wiring, AC voltage,
battery charger and battery level.
Activation of a compatible smoke detector or any normallyopen fire alarm initiating device will activate audible and visual
signaling devices, illuminate an indicator, display alarm information on the panel’s LCD, sound the piezo sounder at the
FACP, activate the FACP alarm relay and operate an optional
module used to notify a remote station or initiate an auxiliary
control function.
Features
• Listed to Standard ULC-S527-99.
• Designed for agent releasing standards NFPA 12, 12A, 12B,
and 2001.
• Meets International Building Code (IBC) seismic requirements.
• Disable/Enable control per input zone and output zone.
• Extensive transient protection.
• Dual hazard operation.
• Adjustable pre-discharge, discharge and waterflow delay
timers.
• Cross-zone (double-interlock) capability.
• Six programmable Style B (Class B) IDCs (Initiating Device
Circuit).
• System Sensor i
• Four programmable Style Y (Class B) output circuits - (special application power).
• Strobe synchronization:
– System Sensor
– Wheelock
• Three programmable Form-C relays.
• 7.0 amps total 24 VDC output current.
• Resettable and non-resettable output power.
• Built-in Programmer.
3
series detector compatible.
3
detec-
Canadian DN-60444:B1
Conventional Releasing Panels
• ANN-BUS for connection to optional devices (up to 8 total of
any of the following):
– N-ANN-80 Remote LCD Annunciator
– N-ANN-I/O LED Driver
– N-ANN-S/PG Printer Module (only one allowed per panel)
– N-ANN-RLY Relay Module
– N-ANN-LED Annunciator Module (built-in)
• 80-character LCD display (backlit).
• Real-time clock/calendar with daylight savings time control.
• History log with 256 event storage.
• Piezo sounder for alarm, trouble and supervisory.
• 24 volt operation.
• Low AC voltage sense.
• Outputs Programmable for:
– Releasing Circuits or NACS
• NACs programmable for:
– Silence Inhibit
– Auto-Silence
– Strobe Synchronization
– Selective Silence (horn-strobe mute)
– Temporal or Steady Signal
– Silenceable or Non-silenceable
– Release Stage Sounder
• Automatic battery charger with charger supervision.
• Optional Trim Ring TR-CE (red) for semi-flush mounting the
cabinet.
• Optional N-CAC-5X Class A Converter Module for Outputs
and IDCs.
• Optional 4XTM Municipal Box Transmitter Module.
• Optional Digital Alarm Communicators (411, 411UD,
411UDAC).
• Optional ANN-SEC card for a secondary ANN-BUS
DN-60444:B1 • 12/22/11 — Page 1 of 4
PROGRAMMING AND SOFTWARE:
• Custom English labels (per point) may be manually entered
or selected from an internal library file.
• Programmable Abort operation.
• Three programmable Form-C relay outputs.
• Pre-programmed and custom application templates.
• Continuous fire protection during online programming at the
front panel.
• Program Check automatically catches common errors not
linked to any zone or input point.
USER INTERFACE:
• Integral 80-character LCD display with backlighting.
• Real-time clock/calendar with automatic daylight savings
adjustments.
• ANN-Bus for connection to annunciators.
• Audible or silent walk test capabilities.
• Piezo sounder for alarm, trouble, and supervisory.
Controls and Indicators
LED INDICATORS
• FIRE ALARM (red).
• SUPERVISORY (yellow).
• TROUBLE (yellow).
• AC POWER (green).
• ALARM SILENCED (yellow).
• DISCHARGED (red).
• PRE-DISCHARGE (red indicator).
• ABORT (yellow indicator).
CONTROL BUTTONS
• ACKNOWLEDGE.
• ALARM SILENCE.
• SYSTEM RESET (lamp test).
• DRILL.
AC Power – TB1
• RP-2002C: 120 VAC, 60 Hz, 3.66 amps.
• Wire size: minimum #14 AWG (2.0 mm
tion.
• Supervised, nonpower-limited.
Battery (sealed lead acid only) – J12:
• Maximum Charging Circuit - Normal Flat Charge: 27.6
VDC @ 1.4 amp. Supervised, nonpower-limited.
• Maximum Charger Capacity: 18 Amp Hour battery (two
18 Amp Hour batteries can be housed in the FACP cabinet.
Larger batteries require separate battery box such as the
BB-26 or NFS-LBBR).
• Minimum Battery Size: 12 Amp Hour.
Initiating Device Circuits - TB4 and TB6
• Zones 1 - 5 on TB4.
• Zone 6 on TB6.
• Supervised and power-limited circuitry.
• Style B (Class B) wiring with Style D (Class A) option.
• Normal Operating Voltage: Nominal 20 VDC.
• Alarm Current: 15 mA minimum.
• Short Circuit Current: 40 mA max.
• Maximum Loop Resistance: 100 Ohms.
• End-of-Line Resistor: 4.7K Ohms, 1/2 watt (PN 71252).
• Standby Current: 4 mA.
2
) with 600V insula-
Refer to the Notifier Device Compatibility Document for listed
compatible devices.
Notification Appliance and Releasing Circuit(s) - TB5 and
TB7
• Four Output Circuits.
• Style Y (Class B) or Style Z (Class A) with optional converter module.
• Special Application power.
• Supervised and power-limited circuitry.
• Normal Operating Voltage: Nominal 24 VDC.
• Maximum Signaling Current: 7.0 amps (3.0 amps maximum
per NAC).
• End-of-Line Resistor: 4.7K Ohms, 1/2 watt (PN 71252).
• Max. Wiring Voltage Drop: 2 VDC.
Refer to the Notifier Device Compatibility Document for compatible listed devices.
Form-C Relays - Programmable - TB8
• Relay 1 (factory default programmed as Alarm Relay)
• Relay 2 (factory default programmed as fail-safe Trouble
Relay)
• Relay 3 (factory default programmed as Supervisory Relay)
• Relay Contact Ratings:
– 2 amps @ 30 VDC (resistive)
– 0.5 amps @ 30 VAC (resistive)
Auxiliary Trouble Input – J6
The Auxiliary Trouble Input is an open collector circuit which
can be used to monitor external devices for trouble conditions.
It can be connected to the trouble bus of a peripheral, such as
a power supply, which is compatible with open collector circuits.
Special Application Resettable Power - TB9
• Operating Voltage: Nominal 24 VDC.
• Maximum Available Current: 500 mA - appropriate for
powering 4-wire smoke detectors (see note).
• Power-limited Circuitry.
Refer to the Notifier Device Compatibility Document for compatible listed devices.
NOTE: Total current for resettable power, nonresettable power and
Output Circuits must not exceed 7.0 amps.
Special Application Resettable or Nonresettable Power TB9
• Operating Voltage: Nominal 24 VDC.
• Maximum Available Current: 500 mA (see note 1).
• Power-limited Circuitry.
• Jumper selectable by JP31 for resettable or nonresettable
power.
Refer to the Notifier Device Compatibility Document for compatible listed devices.
Page 2 of 4 — Canadian DN-60444:B1 • 12/22/11