Notifier ONYX FirstVisio User Manual

7051cov-10.JPG
DN-7051:E2 • A0-185
ONYX FirstVision™
Interactive Firefighters’ Display
Network Systems

General

With ONYX FirstVision, emergency responders can immedi­ately gather the information needed to accurately pinpoint the source of the fire and the rate at which it’s spreading. Crucial information is easy to access with a spatial, graphical depiction of the location of activated detectors and detector sequence of activation for one or multiple buildings. In addition, ONYX First Vision is an interactive interface. It displays a summary of building floor plans with detailed information about the build ing. Details can include locations for all fire alarm devices; water supplies; evacuation routes; access routes; chemical and structural hazards in the building; and shutoffs for gas, power, and HVAC.
-
-
-

Features

GENERAL
• 22" LCD touch-screen.
• Interfaces with ONYX® Series panels or NOTI•FIRE•NET (version 5.0 or higher) through the NFN Gateway over Ethernet.
• Compatible with standard and High Speed NOTI•FIRE•NET™.
• Supports the following additional languages: French (Cana­dian), Hebrew, Korean, Portuguese, Spanish, Thai, and Chinese (Traditional and Simplified).
• Supports multiple gateways for large networks and cam­puses.
USER INTERFACE
• Large intuitive display shows building floor plans in a cam­pus footprint with respective active fire alarm devices, water supplies, evacuation routes, access routes, gas, power and HVAC shutoffs, and chemical and structural hazards in the building.
• Detailed information for active devices or critical building icons on the floor plan.
• Easy access to building, emergency contacts, site plan, and alarm event information.
• Able to print screenshots.
• Stores MSDS (Materials Safety Data Sheet) attachment.
• User download of event log file.
EVENT NOTIFICATION
• Graphic and text event notification of fire, supervisory, secu­rity, and medical events.
• Fast automatic navigation to floors and locations of the emergency events.
• Priority based event list display.
• First alarm display to identify where the emergency started.
• Time sequence display of activated detectors to track smoke progression.
• Configurable sound notification with silence selection.
• Configurable to unlock door based on events.
SYSTEM SETUP
• Screen development tool can easily import building floor plan CAD drawings (as a .wmf, .bmp, or .jpg file) and Veri Fire® Tools databases.
• Standard icon library indicates fire alarm and critical build­ing devices.
• Ethernet and USB ports available for transferring screen database information.

Specifications

NOTE: Dimensions are subject to change. Contact NOTIFIER for further information.
Enclosure Dimensions: 24.53" W X 21.92" H X 3.47" D (62.30 cm H x 55.68 cm W x 8.81 cm D).
Door Dimensions: 26.70" W X 23.06" H X 0.41" D (67.81 cm H x 58.57 cm W x .10 cm D).
Power Requirements: Regulated, filtered 24 VDC @ 3.0 A via non-resettable power supply, UL/ULC Listed for fire-pro tective signaling use.
Temperature Range: 0°C – 50°C (32°F – 120°F).

Listings and Approvals

These listings and approvals apply to ONYX FirstVision™.
UL/ULC Listed: S5697
MEA: 286-07-E
CSFM: 7300-1525:0103
FDNY: COA#6070
-
-
DN-7051:E2 • 5/15/2014 — Page 1 of 4

Ordering Information

NOTI•FIRE•NET™
Network version 5.0
(standard or high-speed)
NFS2-30300
NFS2-640 AM2020/
AFP1010
IP connection over Ethernet
ONYX FirstVision™
7051cov-10.JPG; cab4c.wmf,
nfngw3.bmp
NFN-GW-EM-3 Network Control
Module
GRAPHICAL ICON KEY
Activated Smoke Detector
Gas Tank
Area of Refuge
Master Sprinkler Shutoff
Activated Duct Detector
Halon
Fire Phone
Power Shutoff
Activated Pullstation
Hydrant
Fire Service Keybox
Room Contains Hazardous Materials
Activated Sprinkler Device
HVAC Shutoff
Fire Service Display
Stairs
Activated Heat Detector
Locked Door
Gas Shutoff
Standp ipe
WARRANTY: This product is warrantied for a period of 36 months. The PC and monitors are warranted from date of pur­chase for a period of 36 months. Please refer to NOTIFIER’s
mited Warranty Policy for additional information.
Li
FIRSTVISION-LCD: ONYX Fi
rstVision™ User Interface soft-
ware and hardware package. Includes 22" LCD touch-screen,
ard Ethernet, and USB ports. Also includes one software
Onbo license and screen configuration software (FirstVision-SCT). Does not include backbox, order separately.
FIRSTVISION-ENC: ONYX F
irstVision™ backbox enclosure
and door.
Additional required components:
• NOTI•FIRE•NET Gateway (P/N NFN-GW-EM-3 or NFN­GW
-PC-xx series).
Firefighters’ Display
• NCM-W, NCM-F or HS-NCM/WMF/WSF/MFSF for connec­tion to NOTI•FIRE•NET™.
• Standard Ethernet network cable with RJ45 connectors.
• Standard Ethernet network cable with RJ45 connectors and
b/switch or Standard Ethernet crossover cable.
hu
• PC with Windows® 7 Professional and available Ethernet or
ort (used for programming).
USB p

Applications

An ONYX FirstVision™ display is an ideal component of a NOTIFIER fire system providing real-time fire system status to firefighters. ONYX FirstVision™ interfaces directly to ONYX Series control panels and an entire NOTI•FIRE•NET network.