Notifier NRX-SMT3 Maintenance Manual

N200-300-00 I56-4205-002
DESCRIPTION
The NRX-SMT3 radio sensor is a battery operated RF device designed for use with the NRXI-GATE radio gateway. It contains a wireless transceiver
and runs on a Notier addressable re system (using a compatible proprietary communication protocol).
It is a multi-criteria smoke and heat detector (58oC Rate-of-Rise). An infra-red sensor adds further detection ability and increased immunity to false alarms. The sensor plugs into the B501RF wireless sensor base.
This device conforms to EN54-25, EN54-5 (Class A1R) and EN54-7. It complies with the requirements of 2014/53/EU for conformance with the
RED directive.
SPECIFICATIONS
Supply Voltage: 3.3 V Direct Current max. Standby Current: @ 3V: 120 µA (typical in normal operating mode) Red LED Current Max: 4mA Re-sync time: 35s (max time to normal RF communication from device power on) Batteries: 4 X Duracell Ultra123 Battery Life: 4 years @ 25oC Radio Frequency: 865-870 MHz; RF output power: 14dBm (max) Range: 500m (typ. in free air) Relative Humidity: 10% to 93% (non-condensing)
INSTALLATION
This equipment and any associated work must be installed in accordance with all relevant codes and regulations.
Figure 1 details the installation of the B501RF base.
Spacing between radio system devices must be a minimum of 1m
Figure 2 details attaching the sensor head to the base.
Anti-Tamper Features
The base includes a feature that, when activated, prevents removal of the sensor from the base without the use of a tool. See Figures 3a and 3b for
details on this.
Head Removal Warning - An alert message is signalled to the CIE via the Gateway when a head is removed from its base.
Figure 4 details the battery installation and the location of the rotary
address switches.
Important
Batteries should only be installed at the time of commissioning
Warning
Using these battery products for long periods at temperatures below
-20°C can reduce the battery life considerably (by up to 30% or more)
Observe the battery manufacturer’s precautions for use and
requirements for disposal
SETTING THE ADDRESS
Set the loop address by turning the two rotary decade switches on the
underside of the sensor (see gure 4), using a screwdriver to rotate the wheels to the desired address. The device will take one sensor address on the loop. Select a number between 01 and 159 (Note: The number of addresses available will be dependent on panel capability, check the panel
documentation for information on this).
PROGRAMMING
To load network parameters into the RF sensor, it is necessary to link the RF gateway and the RF sensor in a conguration operation. At commissioning time, with the RF network devices powered on, the RF gateway will connect and programme them with network information as necessary. The
RF sensor then synchronises with its other associated devices as the RF
mesh network is created by the gateway. (For further information, see the Radio Programming and Commissioning Manual - ref. N200-306-00.)
NOTE: Do not run more than one interface at a time to commission devices in an area.
NRX-SMT3
WIRELESS MULTI-CRITERIA FIRE SENSOR
INSTALLATION AND MAINTENANCE INSTRUCTIONS
E N G L I S H
Figure 1: B501RF Mounting
B501RF
Figure 2: Attaching Sensor Head to Base
Figure 3a: Activation of Tamper Resist Feature
PLASTIC LEVER
BREAK TAB AT DOTTED LINE BY TWISTING TOWARDS CENTRE OF BASE
Figure 3b: Removing Sensor Head From Base
M4
50-60 mm
USE A SMALL-BLADED SCREWDRIVER TO PUSH PLASTIC IN THE DIRECTION OF THE ARROW
LINE UP MARK ON SENSOR HEAD WITH BULGE ON BASE AND TURN CLOCKWISE
BULGE
MARK ON SENSOR HEAD
+=
250 g
(66 g)
136 g
48 g
107
mm
-30°C
40°C
32 mm
104 mm
72 mm
Notier by Honeywell, Brooks Road, Lewes, East Sussex, BN7 2BY, UK
I 56- 4205- 002
N200-300-00 I56-4205-002
LED INDICATORS AND FAULT DESCRIPTION
The radio sensor has two LED indicators that show the status of the device.
4c
NOTE POLARITY
4a
Figure 4: Battery Installation and
Rotary Address Switches
4 x Duracell
Ultra 123
TESTING
Magnet Test
Position the magnet (M02-04-00) as shown in Figure 5, after identifying the straight line ridge on the sensor base. To aid positioning, the sensor LEDs will turn on green for 1s when the alarm switch activates. The device will turn off all delays and lters for 10 minutes. After this period, the device returns to its normal mode.
Smoke Testing
Using smoke, or a synthetic smoke aerosol, subject the sensor to controlled amounts of smoke in accordance with local codes of practice. The sensor should signal an alarm to the CIE via the Gateway within 30 seconds.
Direct Heat Testing (Hair dryer of 1000-1500 watts).
Aim the heat toward the sensor from the side. Keep the heat source about 15 cm away to prevent damage to the cover during testing. The sensor should signal an alarm to the CIE via the Gateway when the temperature at the sensor reaches 58°C.
Following testing, reset the alarm indication at the CIE (re panel).
CLEANING
Use a ne brush, vacuum cleaner and/or clean, compressed air to remove dust and debris from the sensing chamber, sensing chamber cover and thermistor as required (take care to avoid damaging the thermistor). Figure 6 shows how to remove the covers.
Arrows on the plastic indicate the positioning when replacing the chamber
cover and air guide.
Note
When replacing batteries, all 4 will need to be replaced
LIMITATIONS OF SMOKE SENSORS
These smoke sensors will only work when connected to a compatible control panel. Smoke detectors have operating limitations. They will not sense res where smoke does not reach the sensor, and may respond differently to varying types of smoke. Consideration must be given to the environment when selecting and siting re sensors.
Smoke sensors cannot last forever, and we recommend replacement after 10 years.
Figure 5: Test Magnet Position
MARK ON BASE
TEST MAGNET
Figure 6: Cleaning the Sensor
SENSOR COVER
COVER REMOVAL TABS
THERMISTOR AIR GUIDE
SENSING CHAMBER COVER AND SCREEN
INFRA-RED SENSOR
THERMISTOR
OPTICAL SENSING CHAMBER
+
+
+
+
12
3
4
4b
4d
ROTARY ADDRESS SWITCHES
+
Sensor Status LEDs
Sensor Status LED State Meaning
Power-on initialisation
(no fault)
Long Green pulse Device is un-commissioned
(factory default)
3 Green blinks Device is commissioned
Fault Blink Amber every 1s. Device has an internal trouble
Un-commissioned
Red/Green double-blink every 14s (or just Green when communicating).
Device is powered and is waiting to be
programmed.
Sync
Green/Amber double-blink every 14s (or just Green when communicating).
Device is powered, programmed and trying to find/join the RF network.
Normal
Controlled by panel; can be set to Red ON, periodic blink Red or OFF.
RF communications is established; device is working properly.
Idle (low power mode) Amber/Green double-blink every 14s
Commissioned RF network is in standby;
used when the gateway is powered off.
Magnet test 1s green pulse when test magnet
activates the internal switch.
Device signals Alarm, all delays are removed for 10 minutes.
EN54-25: 2008 / AC: 2010 / AC: 2012
Components using radio links
EN54-5: 2000 - Class A1R / A1: 2002
Heat detectors
EN54-7: 2000 / A1: 2002 / A2: 2006
Smoke detectors
0333 16
DOP-IRF015
Pittway Tecnologica S.r.l.
Via Caboto 19/3, 34147 Trieste, Italy
Patents Pending
Notier by Honeywell, Brooks Road, Lewes, East Sussex, BN7 2BY, UK
EU Declaration of Conformity
Hereby, Notier by Honeywell declares that the
radio equipment type NRX-SMT3 is in compliance
with directive 2014/53/EU
The full text of the EU DoC can be requested from:
HSFREDDoC@honeywell.com
N200-300-00 I56-4205-002
72 mm
32 mm
104 mm
DESCRIZIONE
Il sensore NRX-SMT3 è un dispositivo a radiofrequenza alimentato a batteria, progettato per essere impiegato con il gateway radio NRXI-GATE. Contiene un ricetrasmettitore e viene integrato in un sistema antincendio indirizzabile tramite un protocollo di comunicazione proprietario .
L’unità rivela fumo e calore (come un rivelatore termovelocimetrico da 58oC). Un sensore a infrarossi integra la capacità di rivelazione e aumenta l’immunità ai falsi allarmi. Il sensore va ssato al softto tramite la base B501RF.
Il dispositivo è a norma EN54-25, EN54-5 (Classe A1R) ed EN54-7, e rispetta i requisiti dello standard 2014/53/EU in conformità alla Direttiva
RED.
SPECIFICHE TECNICHE
Tensione di alimentazione: 3,3 V CC max Corrente di standby: 120 µA a 3 V CC (tipica in modo di
funzionamento normale) Corrente LED rosso: 4 mA max. Tempo di ris incronizzazio ne: 35 s (tempo max dall’accensione del dispositivo alla
normale comunicazione RF quando la rete è attiva) Batterie: 4 Duracell Ultra 123 Durata delle batterie: 4 anni a 25oC Frequenza radio: 865-870 MHz; Potenza di uscita RF: 14 dBm (max) Portata: 500 m (tipico in aria libera) Umidità relativa: dal 10% al 93% (senza condensa)
INSTALLAZIONE
L’installazione del presente dispositivo e di eventuali impianti associati deve essere eseguita in conformità ai codici e i regolamenti pertinenti.
Nella gura 1 è illustrata in dettaglio l’installazione della base B501RF.
La distanza tra i dispositivi di un sistema radio deve essere di almeno 1 metro.
Nella gura 2 è illustrato in dettaglio il montaggio del sensore sulla base.
Funzioni antimanomissione
La base è dotata di un dispositivo antimanomissione che, una volta attivato, impedisce la rimozione del sensore senza l’impiego di un utensile. Vedere le gure 3a e 3b per altre informazioni.
Avviso di rimozione del sensore - Un messaggio di avviso viene trasmesso al pannello di controllo tramite il gateway quando un sensore viene rimosso dalla base.
Nella gura 4 sono illustrati l’alloggiamento delle batterie e i selettori rotanti.
Importante - Installare le batterie esclusivamente al momento della messa in esercizio.
Attenzione - L’uso di prodotti a batteria a temperature inferiori a -20°C per periodi prolungati può ridurre considerevolmente la durata delle
batterie (no al 30% o più).
Rispettare le avvertenze del produttore delle batterie in merito al loro impiego e smaltimento.
IMPOSTAZIONE DELL’INDIRIZZO
Per impostare l’indirizzo, usare i due selettori rotanti situati sul lato inferiore del sensore (vedere gura 4) ruotandoli servendosi di un cacciavite in modo da comporre l’indirizzo desiderato. Il dispositivo radio occupa l’indirizzo di un sensore cablato sulla linea. Selezionare un numero tra 01 e 159 (Nota: il numero di indirizzi a disposizione dipende dal pannello di controllo.
Consultare la documentazione del pannello per ulteriori informazioni).
PROGRAMMAZIONE
Per congurare un sensore radio, è necessario seguire una procedura di programmazione (congurazione) che coinvolge anche il gateway: una volta programmato con i dati della rete, il gateway è in grado di congurare tutti i dispositivi radio ad esso associati, già installati nella loro posizione denitiva. (Per ulteriori informazioni, consultare il Manuale di messa in esercizio e programmazione radio - rif. N200-306-00.)
NOTA: Non eseguire in contemporanea più di una procedura di
congurazione alla volta.
NRX-SMT3
ISTRUZIONI DI INSTALLAZIONE E MANUTENZIONE PER SENSORE
RADIO ANTI-INCENDIO A TRIPLA TECNICA DI RIVELAZIONE
Figura 1: Montaggio B501RF
B501RF
Figura 2: Montaggio del sensore sulla base
Figura 3a: Attivazione della funzione antimanomissione
LINGUETTA DI PLASTICA
ROMPERE LA LINGUETTA IN CORRISPONDENZA DELLA LINEA TRATTEGGIATA TORCENDOLA IN DIREZIONE DEL CENTRO DELLA BASE
Figura 3b: Rimozione del sensore dalla base con
funzione antimanomissione attivata
M4
50-60 mm
USARE UN CACCIAVITE A TAGLIO PER SPINGERE LA LINGUETTA ANTIMANOMISSIONE IN DIREZIONE DELLA FRECCIA
INSERIRE IL SENSORE ALLINEANDO IL RIFERIMENTO SULLA CALOTTA ALL’ALLOGGIAMENTO DEL MAGNETE SULLA BASE, QUINDI RUOTARE IN SENSO
ORARIO
RIFERIMENTO
SULLA
CALOTTA
+=
250 g
(66 g)
136 g
48 g
107
mm
-30°C
40°C
ITALIANO
ALLOGGIAMENTO DEL MAGNETE
Notier Italia S.r.l. Via Grandi, 22-20097-San Donato Milanese (MI), Italia
Loading...
+ 7 hidden pages