NI-100(A)
NI-100(A) in B210LP(A) Base
B210-1951.jpg
Intelligent Addressable Ionization
Detector for FireWarden Systems
General
The NI-100(A) addressable, low-profile, plug-in ionization
detector uses a state-of-the-art ionization sensing chamber to
provide open-area protection and is used exclusively with
NOTIFIER’s FireWarden Series addressable Fire Alarm Con-
trol Panels (FACPs). The ionization detector is used to sense
products-of-combustion and report the measured level of such
products to the fire alarm control panel. Since this detector is
addressable, it will help emergency personnel quickly locate a
fire during its early stages, potentially saving precious rescue
time while also reducing property damage. Two LEDs on each
sensor light to provide a local, visible sensor indication.
Remote LED annunciator capability is available as an optional
accessory, PN RA100Z(A)
Features
SLC loop
• Two-wire loop connection.
• Unit uses base for wiring.
Addressing
• Addressable by device.
• Rotary, decimal addressing: 01 – 99 with FireWarden-1002, 01 – 50 with FireWarden-50.
Architecture
• Unique single-source, dual-chamber design to respond
quickly and dependably to a broad range of fires.
• Sleek, low-profile design.
• Integral communications and built-in type identification.
• Built-in tamper-resistant feature.
• Removable cover and insect-resistant screen for simple
field cleaning.
Operation
• Withstands air velocities up to 1,200 feet-per-minute (6.1 m/
sec.) without triggering a false alarm.
• Factory preset at 1.5% nominal sensitivity for panel alarm
threshold level.
• Visible LED “blinks” when the unit is addressed (communicating with the fire panel) and latches on in alarm.
Mechanicals
• Sealed against back pressure.
• Direct surface mounting or electrical box mounting.
• Base mounts to: single-gang box, 3.5" (8.89 cm) or 4.0"
(10.16 cm) octagonal box, or 4.0" (10.16 cm) square electrical box (using a plaster ring).
APPLICATIONS
Use ionization detectors in life-safety applications to provide a
broad range of fire-sensing capability, especially fast, flaming
fires. Where smoldering fires are anticipated, a photoelectric
sensor may provide faster response.
CONSTRUCTION
These detectors are constructed of off-white plastic. NI-100(A)
plug-in, low-profile smoke detectors are designed to commercial standards and offer an attractive appearance.
DN-6996:B • A1-300
Addressable
Installation
NI-100(A) plug-in detectors use a detachable mounting base
to simplify installation, service and maintenance.
Mount base (all base types) on an electrical backbox which is
at least 1.5" (3.81 cm) deep. For a chart of compatible junction
boxes, see DN-60054.
NOTE: Because of the inherent supervision provided by the SLC
loop, end-of-line resistors are not required. Wiring “T-taps” or
branches are permitted for Style 4 (Class B) wiring.
Operation
Each NI-100(A) uses one of 99 possible addresses on the
FireWarden-100-2 or one of 50 possible addresses on the
FireWarden-50 Series Signaling Line Circuit (SLC). It
responds to regular polls from the system and reports its type
and status.
The NI-100(A) addressable ionization sensor’s unique unipolar
chamber responds quickly and uniformly to a broad range of
smoke conditions and can withstand wind gusts up to 1,200
feet-per-minute (6.01 m/sec.) without sending an alarm level
signal. Because of its unipolar chamber, the NI-100(A) is
approximately two times more responsive than most ionization
sensors. This makes it a more stable detector.
Specifications
Volta g e r a n g e : 15 – 32 VDC (peak).
Standby current: 300 μA @ 24 VDC.
LED current: 6.5 mA @ 24 VDC (latched “ON”).
Air velocity: 1,200 ft./min. (6.1 m/sec.) maximum.
Size: 2.0" (51 mm) high; base determines diameter.
– B210LP(A): 6.1" (15.5 cm) diameter.
– B501(A): 4.1" (10.4 cm) diameter.
– B200SR(A): 6.875" (17.46 cm) diameter.
– B224RB(A): 6.2" (15.748 cm) diameter.
DN-6996:B • 12/07/2011 — Page 1 of 2
Weight: 3.6 oz. (102 g).
Temperature: 0°C to 49°C (32°F to 120°F).
Relative humidity: 10% – 93%, noncondensing.
Listings and Approvals
Listings and approvals below apply to the NI-100(A) detector.
In some cases, certain modules may not be listed by certain
approval agencies, or listing may be in process. Consult factory for latest listing status.
• UL Listed: S1115.
• ULC Listed: S1115.
• CSFM: 7271-0028:0233.
• MEA: 319-02-E Vol. II.
• Maryland State Fire Marshal: permit 2173.
• FM approved.
Product Line Information
NOTE: “A” suffix indicates ULC Listed model.
NI-100: Addressable ionization detector; B210LP base
included.
NI-100A: Same as above with ULC Listing; B210LPA base
included.
INTELLIGENT BASES
NOTE: “A” suffix indicates ULC Listed model.
NOTE: For details about intelligent bases and their mounting, see
DN-60054.
B210LP(A): Plug-in detector base (included); standard U.S.
flanged low-profile mounting base.
B210LPBP: Bulk pack of B210LP; package contains 10.
B501
(A): Standard European flangeless mounting base.
B501BP: Bulk pack of B501; package contains 10.
B200SR
sound output with ANSI Temporal 3 or continuous tone.
Replaces B501BH series bases in retrofit applications.
B224RB
nals: up to 14 AWG (2.0 mm²). Relay type: Form-C. Rating: 2.0
A @ 30 VDC resistive; 0.3 A @ 110 VDC inductive; 1.0 A @
30 VDC inductive.
B224BI(A): Plug-in System Sensor isolator detector base.
Maximum 25 devices between isolator bases (see DN-6994).
ACCESSORIES
F110: Retrofit flange to convert B210LP(A) to match the
B710LP(A) profile, or to convert older high-profile bases to
low-profile.
F110BP: Bulk pack of F110; package contains 15.
F210: Replacement flange for B210LP(A) base.
RA100Z(A): Remote LED annunciator. 3 – 32 VDC. Mounts to
a U.S. single-gang electrical box. For use with B501(A) and
B210LP(A) bases only.
SMB600: Surface mounting kit
M02-04-00:Test magnet.
(A): Intelligent sounder base capable of producing
(A): Plug-in System Sensor relay base. Screw termi-
M02-09-00: Test magnet with telescoping handle.
XR2B: Detector removal tool. Allows installation and/or
removal of detector heads from bases in high ceiling applications.
XP-4: Extension pole for XR2B. Comes in three 5-foot (1.524
m) sections.
T55-127-010: Detector removal tool without pole.
BCK-200B: Black detector covers; box of 10.
WCK-200B: White detector covers; box of 10.
NOTIFIER® is a registered trademark of Honeywell International Inc.
©2011 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com