Notifier NH-100 User Manual

NH-100(A) in B210LP(A) Base
B210-2251.jpg
DN-6997:D • A1-320
NH-100(A) Series
Intelligent Addressable Thermal Detectors for FireWarden Series
Addressable

General

The NOTIFIER NH-100(A) Series thermal detectors are addressable sensors that use a state-of-the-art thermistor sensing circuit for fast response. These sensors provide open­area protection and are intended for use with FireWarden Series (FireWarden-100-2 and FireWarden-50) and Spartan (NSP-25) addressable Fire Alarm Control Panels (FACPs).
The NH-100(A) and NH-100R(A) sensors provide fixed tem­perature alarm detection at 135°F (57°C). The NH-100R(A) sensor also responds to rate-of-rise conditions of greater than 15°F (8.3°C) per minute. The NH-100H(A) is a fixed high-tem perature detector that activates at 190°F (88°C). These ther­mal detectors provide addressable property protection in a variety of applications.
Two LEDs on each sensor light to provide a local, visible sen­sor indication. Remote LED annunciator capability is available using an optional accessory, the RA100Z.

Features

SLC loop:
• Two-wire SLC loop connection.
• Unit uses base for wiring.
Addressing:
• Addressable by device.
• Rotary, decimal addressing: 01 – 99 with FireWarden-100­2, NSP-25, 01 – 50 with FireWarden-50.
Architecture:
• Sleek, low-profile, stylish design.
• State-of-the-art thermistor technology for fast response.
• Integral communications and built-in device-type identifica­tion.
• Built-in tamper resistant feature.
• Built-in functional test switch activated by external magnet.
Operation:
• Factory preset at 135°F (57°C) for the NH-100(A) and NH­100R(A); 190°F (88°C) for the NH-100H(A).
• Rate-of-rise triggers at 15°F (8.3°C) per minute for the NH­100R(A).
• 360°-field viewing angle of the visual alarm indicators (two bicolor LEDs). LEDs blink red in Normal condition and turn on steady red in Alarm.
• Visible LEDs “blink” every time the unit is addressed.
Mechanicals:
• Sealed against back pressure.
• SEMS screws for wiring of the separate base.
• Designed for direct-surface or electrical-box mounting.
• Plugs into separate base for ease of installation and main­tenance.
• Separate base allows interchange of photoelectric, ioniza­tion and thermal sensors.
Other system features:
• Remote test feature from the panel.
• Walk test with address display.
-
• Low standby current.
• 94-5V plastic flammability rating.
Options:
• Remote LED output connection to optional RA100Z remote LED annunciator.
• Flanged surface mounting kit.

Installation

NH-100(A) Series plug-in intelligent thermal detectors use a detachable base to simplify installation, service and mainte nance. Installation instructions are shipped with each detector.
Mount base (all base types) on an electrical backbox which is at least 1.5" (3.81 cm) deep. For a chart of compatible junction boxes, see DN-60054.
NOTE: Because of the inherent supervision provided by the SLC loop, end-of-line resistors are not required. Wiring “T-taps” or branches are permitted for Style 4 (Class “B”) wiring only.

Applications

Use thermal detectors for protection of property.

Construction

These detectors are constructed of off-white fire-resistant plastic. The NH-100(A) Series plug-in intelligent thermal detectors are designed to commercial standards and offer an attractive appearance.

Operation

Each NH-100(A) Series detector uses one of 99 (FireWarden­100-2, NSP-25) or 50 (FireWarden-50) possible addresses on a control panel SLC loop. It responds to regular polls from the control panel and reports its type and the status. If it receives a test command from the panel (or a local magnet test), it stimu lates its electronics and reports an alarm. It blinks its LEDs when polled and turns the LEDs on when commanded by the panel. The NH-100(A) Series offers features and performance that represent the latest in thermal detector technology.
-
-
DN-6997:D • 5/17/13 — Page 1 of 2
Made in the U.S. A.

Spefications

Size: 2.1" (5.3 cm) high; base determines diameter.
– B210LP(A): 6.1" (15.5 cm) diameter. – B501(A): 4.1" (10.4 cm) diameter. – B200SR(A): 6.875" (17.46 cm) diameter. – B224RB(A): 6.2" (15.748 cm) diameter.
Shipping weight: 4.8 oz. (137 g).
Installation temperature:
NH-100(A), NH-100R(A): –4°F to 100°F (–20°C to 38°C).NH-100H(A): –4°F to 150°F (–20°C to 66°C).
Humidity range: 10% to 93% relative humidity (noncon-
densing).
Voltage range: 15 to 32 VDC peak.
Standby current: 300 μA @ 24 VDC (one communication
every five seconds with LED blink enabled).
LED current: 6.5 mA @ 24 VDC.
Mounting: B210LP(A) flanged base, included. See “Product
Line Information: Intelligent Bases” if using a different base.
Fixed-temperature setpoint: 135°F (57°C) for the NH-100 and NH-100R(A)(A); 190°F (88°C) for the NH-100H(A).
Rate-of-rise detection: responds to greater than 15°F (8.3°C) per minute.

Listings and Approvals

Listings and approvals below apply to the NH-100(A) Series detectors. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status.
UL Listed: S747.
ULC Listed: S747.
CSFM: 7270-0028:0234.
MEA: 387-02-E Vol. II.
FM approved.

Product Line Information

NOTE: “A” suffix indicates ULC Listed model.
NH-100: Intelligent thermal sensor; 135° F (57° C); B210LP base included.
NH-100A: Same as NH-100 but with ULC Listing; B210LPA base included.
NH-100R: Same as NH-100 with rate-of-rise feature; B210LP base included.
NH-100RA: Same as NH-100R but with ULC Listing; B210LPA base included.
NH-100H: Intelligent fixed high-temperature thermal detector; 190° F (88° C); B210LP base included.
NH-100HA: Same as NH-100H but with ULC Listing; B210LPA base included.
INTELLIGENT BASES
NOTE: “A” suffix indicates ULC Listed model.
NOTE: For details about intelligent bases and their mounting, see
DN-60054.
B210LP(A): Plug-in detector base (included); standard U.S. flanged low-profile mounting base.
B210LPBP: Bulk pack of B210LP; package contains 10.
B501(A): Standard European flangeless mounting base.
B501BP: Bulk pack of B501; package contains 10.
B200SR(A): Intelligent sounder base capable of producing
sound output with ANSI Temporal 3 or continuous tone. Replaces B501BH series bases in retrofit applications.
B224RB(A): Plug-in System Sensor relay base. Screw termi­nals: up to 14 AWG (2.0 mm²). Relay type: Form-C. Rating: 2.0 A @ 30 VDC resistive; 0.3 A @ 110 VDC inductive; 1.0 A @ 30 VDC inductive.
B224BI(A): Plug-in System Sensor isolator detector base. Maximum 25 devices between isolator bases (see DN-6994).
ACCESSORIES
F110: Retrofit flange to convert B210LP(A) to match the B710LP(A) profile, or to convert older high-profile bases to low-profile.
F110BP: Bulk pack of F110; package contains 15.
F210: Replacement flange for B210LP(A) base.
RA100Z(A): Remote LED annunciator. 3 – 32 VDC. Mounts to
a U.S. single-gang electrical box. For use with B501(A) and B210LP(A) bases only.
SMB600: Surface mounting kit
M02-04-00:Test magnet.
M02-09-00: Test magnet with telescoping handle.
XR2B: Detector removal tool. Allows installation and/or
removal of detector heads from bases in high ceiling applica
-
tions.
XP-4: Extension pole for XR2B. Comes in three 5-foot (1.524 m) sections.
T55-127-010: Detector removal tool without pole.
NOTIFIER® and FireWarden® are registered trademarks of Honeywell International Inc. ©2013. All rights reserved. Unauthorized use of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Page 2 of 2 — DN-6997:D • 5/17/13
Loading...