NH-100(A) in B210LP(A) Base
B210-2251.jpg
DN-6997:D • A1-320
NH-100(A) Series
Intelligent Addressable Thermal
Detectors for FireWarden Series
Addressable
General
The NOTIFIER NH-100(A) Series thermal detectors are
addressable sensors that use a state-of-the-art thermistor
sensing circuit for fast response. These sensors provide openarea protection and are intended for use with FireWarden
Series (FireWarden-100-2 and FireWarden-50) and Spartan
(NSP-25) addressable Fire Alarm Control Panels (FACPs).
The NH-100(A) and NH-100R(A) sensors provide fixed temperature alarm detection at 135°F (57°C). The NH-100R(A)
sensor also responds to rate-of-rise conditions of greater than
15°F (8.3°C) per minute. The NH-100H(A) is a fixed high-tem
perature detector that activates at 190°F (88°C). These thermal detectors provide addressable property protection in a
variety of applications.
Two LEDs on each sensor light to provide a local, visible sensor indication. Remote LED annunciator capability is available
using an optional accessory, the RA100Z.
Features
SLC loop:
• Two-wire SLC loop connection.
• Unit uses base for wiring.
Addressing:
• Addressable by device.
• Rotary, decimal addressing: 01 – 99 with FireWarden-1002, NSP-25, 01 – 50 with FireWarden-50.
Architecture:
• Sleek, low-profile, stylish design.
• State-of-the-art thermistor technology for fast response.
• Integral communications and built-in device-type identification.
• Built-in tamper resistant feature.
• Built-in functional test switch activated by external magnet.
Operation:
• Factory preset at 135°F (57°C) for the NH-100(A) and NH100R(A); 190°F (88°C) for the NH-100H(A).
• Rate-of-rise triggers at 15°F (8.3°C) per minute for the NH100R(A).
• 360°-field viewing angle of the visual alarm indicators (two
bicolor LEDs). LEDs blink red in Normal condition and turn
on steady red in Alarm.
• Visible LEDs “blink” every time the unit is addressed.
Mechanicals:
• Sealed against back pressure.
• SEMS screws for wiring of the separate base.
• Designed for direct-surface or electrical-box mounting.
• Plugs into separate base for ease of installation and maintenance.
• Separate base allows interchange of photoelectric, ionization and thermal sensors.
Other system features:
• Remote test feature from the panel.
• Walk test with address display.
-
• Low standby current.
• 94-5V plastic flammability rating.
Options:
• Remote LED output connection to optional RA100Z remote
LED annunciator.
• Flanged surface mounting kit.
Installation
NH-100(A) Series plug-in intelligent thermal detectors use a
detachable base to simplify installation, service and mainte
nance. Installation instructions are shipped with each detector.
Mount base (all base types) on an electrical backbox which is
at least 1.5" (3.81 cm) deep. For a chart of compatible junction
boxes, see DN-60054.
NOTE: Because of the inherent supervision provided by the SLC
loop, end-of-line resistors are not required. Wiring “T-taps” or
branches are permitted for Style 4 (Class “B”) wiring only.
Applications
Use thermal detectors for protection of property.
Construction
These detectors are constructed of off-white fire-resistant
plastic. The NH-100(A) Series plug-in intelligent thermal
detectors are designed to commercial standards and offer an
attractive appearance.
Operation
Each NH-100(A) Series detector uses one of 99 (FireWarden100-2, NSP-25) or 50 (FireWarden-50) possible addresses on
a control panel SLC loop. It responds to regular polls from the
control panel and reports its type and the status. If it receives a
test command from the panel (or a local magnet test), it stimu
lates its electronics and reports an alarm. It blinks its LEDs
when polled and turns the LEDs on when commanded by the
panel. The NH-100(A) Series offers features and performance
that represent the latest in thermal detector technology.
-
-
DN-6997:D • 5/17/13 — Page 1 of 2
Spefications
Size: 2.1" (5.3 cm) high; base determines diameter.
– B210LP(A): 6.1" (15.5 cm) diameter.
– B501(A): 4.1" (10.4 cm) diameter.
– B200SR(A): 6.875" (17.46 cm) diameter.
– B224RB(A): 6.2" (15.748 cm) diameter.
Shipping weight: 4.8 oz. (137 g).
Installation temperature:
– NH-100(A), NH-100R(A): –4°F to 100°F (–20°C to 38°C).
– NH-100H(A): –4°F to 150°F (–20°C to 66°C).
Humidity range: 10% to 93% relative humidity (noncon-
densing).
Voltage range: 15 to 32 VDC peak.
Standby current: 300 μA @ 24 VDC (one communication
every five seconds with LED blink enabled).
LED current: 6.5 mA @ 24 VDC.
Mounting: B210LP(A) flanged base, included. See “Product
Line Information: Intelligent Bases” if using a different base.
Fixed-temperature setpoint: 135°F (57°C) for the NH-100
and NH-100R(A)(A); 190°F (88°C) for the NH-100H(A).
Rate-of-rise detection: responds to greater than 15°F (8.3°C)
per minute.
Listings and Approvals
Listings and approvals below apply to the NH-100(A) Series
detectors. In some cases, certain modules may not be listed
by certain approval agencies, or listing may be in process.
Consult factory for latest listing status.
• UL Listed: S747.
• ULC Listed: S747.
• CSFM: 7270-0028:0234.
• MEA: 387-02-E Vol. II.
• FM approved.
Product Line Information
NOTE: “A” suffix indicates ULC Listed model.
NH-100: Intelligent thermal sensor; 135° F (57° C); B210LP
base included.
NH-100A: Same as NH-100 but with ULC Listing; B210LPA
base included.
NH-100R: Same as NH-100 with rate-of-rise feature; B210LP
base included.
NH-100RA: Same as NH-100R but with ULC Listing; B210LPA
base included.
NH-100H: Intelligent fixed high-temperature thermal detector;
190° F (88° C); B210LP base included.
NH-100HA: Same as NH-100H but with ULC Listing; B210LPA
base included.
INTELLIGENT BASES
NOTE: “A” suffix indicates ULC Listed model.
NOTE: For details about intelligent bases and their mounting, see
DN-60054.
B210LP(A): Plug-in detector base (included); standard U.S.
flanged low-profile mounting base.
B210LPBP: Bulk pack of B210LP; package contains 10.
B501(A): Standard European flangeless mounting base.
B501BP: Bulk pack of B501; package contains 10.
B200SR(A): Intelligent sounder base capable of producing
sound output with ANSI Temporal 3 or continuous tone.
Replaces B501BH series bases in retrofit applications.
B224RB(A): Plug-in System Sensor relay base. Screw terminals: up to 14 AWG (2.0 mm²). Relay type: Form-C. Rating: 2.0
A @ 30 VDC resistive; 0.3 A @ 110 VDC inductive; 1.0 A @
30 VDC inductive.
B224BI(A): Plug-in System Sensor isolator detector base.
Maximum 25 devices between isolator bases (see DN-6994).
ACCESSORIES
F110: Retrofit flange to convert B210LP(A) to match the
B710LP(A) profile, or to convert older high-profile bases to
low-profile.
F110BP: Bulk pack of F110; package contains 15.
F210: Replacement flange for B210LP(A) base.
RA100Z(A): Remote LED annunciator. 3 – 32 VDC. Mounts to
a U.S. single-gang electrical box. For use with B501(A) and
B210LP(A) bases only.
SMB600: Surface mounting kit
M02-04-00:Test magnet.
M02-09-00: Test magnet with telescoping handle.
XR2B: Detector removal tool. Allows installation and/or
removal of detector heads from bases in high ceiling applica
-
tions.
XP-4: Extension pole for XR2B. Comes in three 5-foot (1.524
m) sections.
T55-127-010: Detector removal tool without pole.
NOTIFIER® and FireWarden® are registered trademarks of Honeywell
International Inc.
©2013. All rights reserved. Unauthorized use of this document is strictly
prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Page 2 of 2 — DN-6997:D • 5/17/13