MODELS
NFX-WCF-WC = Beacon Non Isolation
NFXI-WCF-WC = Beacon Isolation
GENERAL
The range of intelligent AV devices are designed to be connected to analogue addressable re
alarm systems.
These devices must only be connected to control panels that use a compatible proprietary
analogue addressable communication protocol.
These devices receive their power from the loop, and can be controlled via the communication
protocol(s).
Models NFXI-WCF-WC include in built isolation providing short circuit protection of the loop.
Up to 159 addresses are available. (consult the panel instructions to conrm compatibility)
These are selected via the two rotary switches. The ‘tens’ digits range from 0 to 15 and the ‘units’
from 0 to 9.
Note: if the control equipment is not capable of taking more than 99 module addresses, a fault
condition will be generated for every address over 99.
INSTALLATION INSTRUCTIONS FOR WALL AND CEILING
MOUNTED ADDRESSABLE HIGH-OUTPUT EN54-23 BEACON
SPECIFICATIONS NFX-WCF-WC, NFXI-WCF-WC
Signaling Line Supply Voltage (non isolation) 15 to 29VDC (24VDC typical)
Signaling Line Supply Voltage (isolation) 15 to 29VDC (24VDC typical)
Max peak power 800mW
Beacon ash rate 0.5Hz
Max current consumption @ 20V (non isolation)
40mA
Max current consumption @ 20V (isolation) 40mA
Quiescent Current 450uA
Operating temperature range -25 to +70oC
Relative humidity 93% (± 3%) - non condensing
Terminal Size Terminal Size 2.5mm2 - maximum
Note: This product is classied as both `C` and `W` category device to EN54:23 standard for visual
alarm devices.
CONTINUITY SPRING
The B501AP incorporates a continuity spring
between terminals 2 and 4. This allows the
continuity of the eld wiring to be checked
without the need for the device to be present.
Inserting the device will disengage the spring.
Removing the device will close the loop.
ANTI TAMPER LOCK
The B501AP also includes
a tamper resistant feature
that when activated prevents
removal of the unit without
the use of a special tool.
This method is consistent
with the anti tamper feature
across all devices using
this base. This prevents
the device being turned to
enable its release.
Breakout
For isolator specication refer to document SP11-2848 available on request
Note: Bung seal must
be tted with the deep back box.
1
2
3
4
+
_
+
_
If the deep back box option is required then the
wall gasket must be tted behind the deep base,
and the sealing o-ring tted after attaching the low
prole base.
1
2
INSTALLATION
Afx B501AP to a suitably at wall. Terminate
the cable to the appropriate terminals. For
surface mount wiring the cable can enter
the B501AP via
the break outs
provided.
Locate the main
assembly on
to the base by
rotating until it
locks into place.
TERMINAL
CONNECTIONS
IP RATING
(IP 21C)
Deep Back box (IP 65*)
To achieve IP21 rating for ceiling mount the IP21
seal must be tted to the product. For wall mounted applications the IP21 seal is not required to
achieve IP21C.
IP33C is certied by LPCB to EN54-3 and EN54-
23. *IP65 is certied by UKAS Accredited test
facility.