Notifier NFS-320, NFS-C, NFS-320SYS, NFS-E, NFS-320SYSE Operation Manual

...
Fire Alarm Control Panel
NFS-320/E/C,
NFS-320SYS/E
Operations Manual
Document 52747 06/16/2011 Rev:
P/N 52747:E1 ECN 11-336
E1
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system—typically made up of smoke detectors, heat detectors, manual pull st ati ons, audib le warning devices, and a fire alarm control panel with remote notification capability—can provi de early warn ing of a develop
­ing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detec­tors be located throughout a protected premise following the recommendations of the current edition of the National Fire Protection Association S tandard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommen
­dations contained in the Guides for Proper Use o f System Smoke Detectors, which are made available at no charge to all installing dealers. These documents can be found at http:// www.systemsensor.com/html/applicat.html. A study by the Federal Emergency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire al arm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behi nd walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a first­floor or basement fire.
Particles of combustion or “smoke” from a developing fire may not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow.
• Smoke particles may become “cold,” stratify, and not reach
the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air
outlets.
• Smoke particles may be drawn into air returns before
reaching the detector.
The amount of “smoke” present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ion
­izing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires d evelop in dif ferent ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of flammable materials, etc.).
Heat detectors do not sense particles of combustion and alarm only when heat on their sensors incre ases at a predete r
­mined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over t ime. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire pro
­tection specialist. Heat detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the sys
­tem for the connection of alarm transmission wiring, communi­cations, signaling, and/or power. If detectors are not so located, a developing fire may damage the alarm system, crip
­pling its ability to report a fire.
Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building . Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol or medica
-
tion. Please note that:
• Strobes can, under certain circumstances, cause seizures
in people with conditions such as epilep sy.
• Studies have shown that certain people, even when they
hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property owner's responsi
­bility to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from st and by batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.
Equipment used in the system may not be technically com­patible with the control panel. It is essential to use only equip­ment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against tele
­phone line failure, backup radio transmission systems are rec­ommended.
The most common cause of fire alarm malfunction is inade­quate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA stan
­dards. At a minimum, the requirements of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent maintenance. A main
­tenance agreement should be arranged through the local man­ufacturer's representative. Maintenance should be scheduled monthly or as required by National and/or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records of all inspections should be kept.
Limit-C1-2-2007
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associ
­ated equipment may be damaged by removing and/or insert­ing cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood.
CAUTION - System Re-acceptance Test after Software Changes: To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any pro
­gramming operation or change in site-specific software. Re­acceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All compo
­nents, circuits, system operations, or sof tware functions known to be affected by a change must be 100% tested. In addit ion, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49º C/32-120º F and at a relative humidity 93% ± 2% RH (non
­condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic com
­ponents may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27º C/60-80º F.
Verify that wire sizes are adequate for all initia ting and indi­cating device loops. Most devices cannot tol erate more than a 10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may operate erratically or can be damaged when subject ed to light
­ning induced transients. Although no system is completely immune from lightning transients and interference, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Ser
­vices Department if any problems are anticipated or encoun­tered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifi
­cations, verify that they will not interfere with battery, trans­former, or printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over­tightening may damage threads, resulting in reduced terminal contact pressure and difficulty wit h screw terminal removal.
This system contains static-sensitive components. Always ground yourself with a proper wrist strap before han
­dling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the inst al lati on, opera ting, and pr o­gramming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and rel iability depend upon prop er inst allatio n.
Precau-D1-9-2005
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing devices pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when devices are operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interfer­ence, in which case the user will be required to correct the interference at his or her own expense.
Canadian Requirements
This digital apparatus does not exce ed the Class A limit s for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Cana­dian Department of Communications.
Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edict e p ar l e ministere des Communications du Canada.
HARSH™, NIS™, and NOTI•FIRE•NET™ are all trademarks; and Acclimate® Plus, FlashScan®, NION®, NOTIFIER®, ONYX®, ONYXWorks®, UniNet®, VeriFire®, and VIEW® are all registered trademarks of Honeywell International Inc. Echelon® is a registered trademark and LonWorks™ is a trademark of
Echelon Corporation. ARCNET® is a registered trademark of Datapoint Corporation. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation.
©2011 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
NFS-320/E/C, NFS-320SYS/E Operations Manual — P/N 52747:E1 06/16/2011 3
Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly recommend that you download the most current version of software for each product prior to commissioning any system. Contact T echnical Support with any questions about software and the appropriate version for a specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online Help or printed manuals, you can email us.
Please include the following information:
•Product name and version number (if applicable)
•Printed manual or online Help
•Topic Title (for online Help)
•Page number (for printed manual)
•Brief description of content you think should be improved or corrected
•Your suggestion for how to correct /improve documentation
Send email messages to:
FireSystems.TechPubs@honeywell.com
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services.

Table of Contents

Section 1: General Information................................................................................................8
1.1: UL 864 Compliance.......................................................................................................................................8
1.2: About This Manual........................................................................................................................................8
1.2.1: Cautions and Warnings........................................................................................................................8
1.2.2: Typographic Conventions....................................................................................................................8
1.2.3: Supplemental Information...................................................................................................................9
1.2.4: Shortcuts to Operating Functions......................................................................................................10
1.3: Introduction to the Control Panel ................................................................................................................10
Section 2: Use of the Controls...............................................................................................11
2.1: Introduction..................................................................................................................................................11
2.2: System Status Indicator LEDs.............................................................. .......................................................11
2.3: Control Keys................................................................................................................................................12
2.3.1: Acknowledge/Scroll Display.............................................................................................................12
2.3.2: Signal Silence....................................................................................................................................13
2.3.3: System Reset .....................................................................................................................................13
2.3.4: Drill....................................................................................................................................................14
2.3.5: Lamp Test..........................................................................................................................................14
2.4: Programming Keypad..................................................................................................................................14
Section 3: Operation of the Control Panel............................................................................16
3.1: Overview......................................................................................................................................................16
3.2: Normal Mode of Operation .........................................................................................................................16
3.3: Fire Alarm Mode of Operation....................................................................................................................17
3.3.1: How the Control Panel Indicates a Fire Alarm..................................................................................17
3.3.2: How to Respond to a Fire Alarm.......................................................................................................17
3.3.3: Interpreting Fire Alarm Type Codes .................................................................................................18
3.4: Carbon Monoxide (CO) Alarm Mode of Operation....................................................................................20
3.4.1: How the Control Panel Indicates a CO Alarm ..................................................................................20
3.4.2: How to Respond to a CO alarm.........................................................................................................20
3.4.3: Interpreting CO Alarm/Supervisory Type ID Codes.........................................................................21
3.5: System Trouble Mode of Operation ............................................................................................................21
3.5.1: How the Control Panel Indicates a System Trouble..........................................................................21
3.5.2: How to Respond to a System Trouble...............................................................................................22
3.6: Security Alarm Mode of Operation.............................................................................................................23
3.6.1: How the Control Panel Indicates a Security Alarm...........................................................................23
3.6.2: How to Respond to a Security Alarm................................................................................................23
3.6.3: Interpreting Security Type Codes......................................................................................................24
3.7: Active Supervisory Signal Mode of Operation ...........................................................................................24
3.7.1: How the Control Panel Indicates an Active Supervisory ..................................................................24
3.7.2: How to Respond to an Active Supervisory .......................................................................................25
3.7.3: How to Interpret Supervisory Type Codes........................................................................................25
3.8: Pre-Alarm Warning Mode of Operation......................................................................................................26
3.8.1: How the Control Panel Indicates a Pre-Alarm Warning ...................................................................26
3.8.2: How to Respond to a Pre-Alarm Warning.........................................................................................27
3.9: Disabled Points Mode of Operation ............................................................................................................28
3.10: Non-Alarm Mode of Operation ....................................................... ..........................................................28
3.10.1: Purpose of Non-Alarm Points..........................................................................................................28
3.10.2: How the Control Panel Indicates an Active Fire Control................................................................29
3.10.3: How the Control Panel Indicates an Active Non-Fire Point .... .......................................................29
3.11: Active Trouble Monitor Mode of Operation..............................................................................................29
3.11.1: How the Control Panel Indicates an Active Trouble Monitor .........................................................29
3.11.2: How to Respond to an Active Trouble Monitor..............................................................................30
3.12: Output Circuit Trouble Mode of Operation...............................................................................................30
3.12.1: Overview ............................................................................................. ............................................30
NFS-320/E/C, NFS-320SYS/E Operations Manual — P/N 52747:E1 06/16/2011 5
Table of Contents
3.12.2: How the Control Panel Indicates a NAC Trouble ...........................................................................31
3.12.3: How the Control Panel Indicates a Control/Relay Trouble.............................................................31
3.12.4: How to Respond to a NAC or Control/Relay Trouble ....................................................................32
3.13: Operation of Special System Timers .........................................................................................................32
3.13.1: What are System Timers?................................................................................................................32
3.13.2: How to View System Timer Selections...........................................................................................32
3.13.3: How System Timers Work ..............................................................................................................32
3.14: Waterflow Circuit Operation......................................................................................................................33
3.15: Style 6 and Style 7 Operation ....................................................................................................................33
Section 4: Read Status Operation.........................................................................................34
4.1: Introduction..................................................................................................................................................34
4.2: What is Read Status?........................ .................................. .................................. ........................................34
4.2.1: Quick Reference Key Sequences.......................................................................................................34
4.3: Entering Read Status.................................... ................................................................................................34
4.4: Viewing and Printing a Read Status.............................................................................................................35
4.4.1: How to View Read Status of Devices, Zones, & System Settings....................................................35
4.4.2: How to View Read Status for Event and Alarm History...................................................................44
4.4.3: How to Print Points, Event and Alarm History .................................................................................45
4.4.4: How to View and Print Hidden Event and Alarm History................................................................47
Appendix A: Special Zone Operation ...................................................................................49
A.1: Overview.....................................................................................................................................................49
A.2: Releasing Zones (R0-R9)............................................................................................................................49
A.2.1: Purpose of Releasing Zones .............................................................................................................49
A.2.2: How to View Releasing Zone Selections .........................................................................................50
A.2.3: How Releasing Zones Operate .........................................................................................................50
A.3: Time, Date, and Holiday Functions............................................................................................................52
A.3.1: Overview...........................................................................................................................................52
A.3.2: How to View Time Control Selections.............................................................................................52
A.3.3: How to View Holiday Function Selections ......................................................................................53
A.3.4: How Time Control and Holiday Functions Work ............................................................................53
A.4: NAC Coding ...............................................................................................................................................54
A.4.1: Overview of Coding..........................................................................................................................54
A.4.2: How to View Coding (F8) Selections...............................................................................................54
A.4.3: How to Respond to an Alarm with Coding.......................................................................................55
A.5: Presignal and Positive Alarm Sequence (PAS) Operation..........................................................................55
A.5.1: Overview...........................................................................................................................................55
A.5.2: What is Presignal and PAS? .............................................................................................................55
A.5.3: How to View Presignal and PAS Selections ....................................................................................56
A.5.4: How to Respond to an Alarm with Presignal Delay Timer (no PAS)..............................................56
A.5.5: How to Respond to an Alarm with Presignal Delay Timer (PAS selected) .....................................57
Appendix B: Intelligent Detector Functions........................................................................58
Appendix C: Remote Terminal Access.................................................................................60
C.1: General Description.....................................................................................................................................60
C.2: Operating Modes.........................................................................................................................................60
C.2.1: Local Terminal Mode (LocT)...........................................................................................................60
C.2.2: Local Monitor Mode (LocM)............................................................................................................61
C.2.3: Remote Terminal Mode (RemT).......................................................................................................61
C.3: Using the CRT-2 for Read Status ................................................................................................................62
C.3.1: Overview...........................................................................................................................................62
C.3.2: Accessing Read Status Options.........................................................................................................62
C.3.3: Read Point.........................................................................................................................................63
C.3.4: Display Devices in Alarm or Trouble...............................................................................................63
C.3.5: Display All Programmed Points .......................................................................................................64
C.3.6: Step-through History .........................................................................................................................64
6 NFS-320/E/C, NFS-320SYS/E Operations Manual — P/N 52747:E1 06/16/2011
Table of Contents
C.3.7: View All History...............................................................................................................................64
C.3.8: Step-through Alarm History .............................................................................................................64
C.3.9: View All Alarm History....................................................................................................................64
C.4: Using the CRT-2 for Alter Status ................................................................................................................64
C.4.1: Overview...........................................................................................................................................64
C.4.2: Accessing Alter Status Options ........................................................................................................65
C.4.3: Enable or Disable Detectors, Modules or Zones ..............................................................................65
C.4.4: Change Alarm and Pre-Alarm Levels...............................................................................................66
C.4.5: Clear Verification Counter................................................................................................................66
C.4.6: Clear the Entire History Buffer................................. .. ......................................................................66
C.4.7: Set the Pre-Alarm for Alert or Action...............................................................................................67
Appendix D: Point and System Troubles Lists....................................................................68
D.1: Point (Device) Troubles ..............................................................................................................................68
D.2: System Troubles..........................................................................................................................................69
Index.........................................................................................................................................72
NFS-320/E/C, NFS-320SYS/E Operations Manual — P/N 52747:E1 06/16/2011 7

Section 1: General Information

!
!

1.1 UL 864 Compliance

This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864 9th Edition.

1.2 About This Manual

1.2.1 Cautions and Warnings

This manual contains cautions and warnings to alert the reader as follows:
CAUTION:
Information about procedures that could cause programming errors, runtime errors, or equipment damage.
WARNING:
Indicates information about procedures that could cause irreversible damage to the control panel, irreversible loss of programming data or personal injury.

1.2.2 Typographic Conventions

This manual uses the following typographic conventions as listed in below:
When you see Specifies Example
text in small caps the text as it appears in the
LCD display or on the control panel
text in quotes a reference to a section or a
LCD menu screen
bold text In body text, a number or
character that you enter italic text a specific document NFS-320 Installation Manual a graphic of the key In a graphic, a key as it
appears on the control panel
Table 1.1 Typographic Conventions in this Manual
NOTE: In this manual, the term NFS-320 is used to refer to the NFS-320, NFS-320E, and
NFS-320C, NFS-320SYS and NFS-320SYS/E unless otherwise noted.
MARCH TIME is a selection that appears in the
LCD display; or Press the
“Read Status”; specifies the Read S tatus section or menu screen
Press 1; means to press the number “1” on the keypad
Press means to press the Escape key
ENTER key
8 NFS-320/E/C, NFS-320SYS/E Operations Manual — P/N 52747:E1 06/16/2011
About This Manual General Information

1.2.3 Supplemental Information

The table below provides a list of documents referenced in this manual, as well as documents for selected other compatible devices. The document series chart (DOC-NOT) provides the current document revision. A copy of this document is included in every shipment.
Compatible Conventional Devices (Non-addressable) Document Number
Device Compatibility Document 15378
Fire Alarm Control Panel (FACP) and Main Power Supply Installation Document Number
NFS-320/E/C Installation, Operations, and Programming Manuals NFS-320C Canadian Applications Addendum
NFS-320SYS/E/C Installation Manual 53717 SLC Wiring Manual 51253 Note: For individual SLC Devices, refer to the SLC Wiring Manual
Off-line Programming Utility Document Number
VeriFire® Tools CD help file VERIFIRE-TCD
Power Supplies, Auxiliary Power Supplies & Battery Chargers Document Number
ACPS-2406 Installation Manual 51304 ACPS-610 Instruction Manual 53018 APS-6R Instruction Manual 50702 APS2-6R Instruction Manual 53232 CHG-120 Battery Charger Manual 50641 FCPS-24S6/FCPS-24S8 Field Charger/Power Supply Manual 51977
Networking Document Number
High-Speed Network Communication Module 54014 High-Speed Noti•Fire•Net Instruction Manual 54013 Noti•Fire•Net Manual, Network Version 5.0 & Higher 51584 ONYXWorks™ Workstation Hardware & Software Application: Installation and Operation Manual 52342 ONYXWorks™ NFN Gateway (PC Platform) Installation & Operation Manual 52307 ONYXWorks™ NFN Gateway (Embedded Platform) Installation & Operation Manual 52306 NCM-W/F Installation Document 51533 NCS ONYX® Network Control Station Manual, Network Version 4.0 & Higher 51658 NCA-2 Network Control Annunciator Manual 52482 NCA Network Control Annunciator Manual 51482
System Components Document Number
Annunciator Control System Manual 15842 ACM-8R Annunciator Control Module Manual 15342 FDU-80 Remote Annunciator Manual 51264 LCD-80 Liquid Crystal Display Annunciator 15037 LCD2-80 Liquid Crystal Display Annunciator 53242 LDM Series Lamp Driver Annunciator Manual 15885 SCS Smoke Control Manual (Smoke and HVAC Control Station) 15712 DPI-232 Direct Panel Interface Manual 51499 TM-4 Installation Document (Reverse Polarity Transmitter) 51490 UDACT Manual (Universal Digital Alarm Communicator/Transmitter) 50050 FireVoice-25/50 & FireVoice-25/50ZS Manual 52290 RA100Z Remote LED Annunciator Installation Document I56-0508
52745, 52746, 52747
52745CDN
Table 1.2 Supplemental Documentation
NFS-320/E/C, NFS-320SYS/E Operations Manual — P/N 52747:E1 06/16/2011 9
General Information Introduction to the Control Panel

1.2.4 Shortcuts to Operating Functions

T o the left of each program function, you’ll find a keypad shortcut, which contains a series of keypad entries required to access the program function. All shortcuts start with the control panel in normal operation.
For example, the keypad shortcut to the left, shows how to enter the Read Status function with the control panel in normal operation, as well as how to exit the function.

1.3 Introduction to the Control Panel

The NFS-320 is a modular, intelligent Fire Alarm Control Panel (FACP) with features suitable for most applications. Following is a list of operating features available.
Alarm Verification selection, to reduce unwanted alarms, for intell igent detector points
Positive Alarm Sequence (PAS) and Presignal per NFPA 72
Silence Inhibit timer and Auto Silence timer for Notification Appliance Circuits (NACs)
March time/temporal code for Notification Appliance Circuits (NACs)
Programmable Signal Silence, System Reset, and Alarm Activate functions through monitor modules
Automatic time-of-day and day-of-week control functions, with holiday option
Intelligent Sensing with nine field-adjustable Pre-Alarm levels with programmable Control-By-Event (CBE)
Operate automatic smoke or heat detector sounder base on action Pre-Alarm level, with general evacuation on alarm level
Security alarm point option with separate audible signal code
Audible alarm signaling options
Programmable Control-By-Event control of outputs from individual alarm or supervisory addressable devices
Networks with other FACPs and equipment for large applications.
10 NFS-320/E/C, NFS-320SYS/E Operations Manual — P/N 52747:E1 06/16/2011

Section 2: Use of the Controls

Control Keys (Refer to page 12).
Status Indicator LEDs (Refer to Section 2.2 below)
Programming Keypad (Refer to page 14
Function keys (Refer to page 14
Cursor movement (arrow) keys,
ESC key, and ENTER key. (Refer to page 14
NFS2_640-keypad.wmf
80-character (2 x 40) Liquid Crystal Display.(LCD)

2.1 Introduction

Listing of the controls and indicators and where to find information on their use:
Operating Components Covered in
Twelve System Status Indicator LEDs “System Status Indicator LEDs” on page 11
Five Control Keys “Control Keys” on page 12
Programming Keypad “Programming Keypad” on page 14
Figure 2.1 NFS-320 Control Panel Keys and Indicators

2.2 System Status Indicator LEDs

The control panel contains 12 labeled LEDs described in Table 2.1.
Indicator Color When Active To Turn Of f
CONTROLS ACTIVE
POWER Green Lights when the proper primary AC power is
Green LIghts when the panel assumes control of local
operation as primary display.
applied. Remains lit while power is applied.
Turns off automatically when another panel assumes control of local operation.
Always lit with AC power applied.
Table 2.1 Descriptions of System Status Indicator LEDs (1 of 2)
NFS-320/E/C, NFS-320SYS/E Operations Manual — P/N 52747:E1 06/16/2011 11
Use of the Controls Control Keys
Indicator Color When Active To Turn Off
PRE-DISCHARGE Red Lights when any of the releasing zones have been
activated, but have not yet discharged a releasing agent.
DISCHARGE Red Lights when any of the releasing zones are active
and in the process of discharging a releasing agent.
ABORT ACTIVE Yellow Lights when an abort switch has been activated.
FIRE ALARM Red Flashes when a non-acknowledged fire alarm
exists. Lights steadily after you acknowledge the fire alarm.
PRE-ALARM Red Flashes when a non-acknowledged fire Pre-Alarm
exists. Lights steadily after you acknowledge the Pre-Alarm.
Turns off automatically when no releasing zones are in the pre-discharge state.
Turns off automatically when no releasing zones are discharging a releasing agent.
*
Turns off automatically when an abort switch has been pressed and its timer is still counting down.
Clear the alarm condition and reset the system.
Clear the pre-alarm condition. (An Action Pre-Alarm requires a system reset.)
SECURITY Blue Flashes when a non-acknowledged Security alarm
SUPERVISORY Yellow Flashes when a non-acknowledged Supervisory
SYSTEM TROUBLE
SIGNALS SILENCED
POINT DISABLED
Yellow Flashes when a non-acknowledged system trouble
Yellow Lights steadily after a fire alarm condition occurs
Yellow Lights when one or more system devices are
exists. Lights steadily after you acknowledge the alarm.
condition exists. Lights steadily after you acknowledge the event.
exists. Lights steadily after you acknowledge the trouble.
and after you press outputs. Flashes to indicate that some silenceable outputs are on and some are off.
disabled.
SIGNAL SILENCE to silence all
Clear the Security alarm condition and reset the system.
Clear the condition (Supervisory inputs require a system reset if they are latching. Refer to information.).
Clear the trouble condition.
Press SYSTEM RESET. DRILL will also turn off the LED.
Enable the device or remove the disabled device from the system program.
Table 3.4 page 26 for latching
Table 2.1 Descriptions of System Status Indicator LEDs (2 of 2)
* Activation of a Manual Release Switch will overri de Predischarge Delay and override an active Abort
Release Switch, resulting in an immediate agent release.

2.3 Control Keys

The control panel provides five Control Keys as described below:

2.3.1 Acknowledge/Scroll Display

Use the ACKNOWLEDGE/SCROLL DISPLAY key to respond to new alarm or trouble signals. When pressed, the control panel does the following:
Silences the panel sounder
Changes all active LED indicators from flashing to steady
Sends an Acknowledge message to the History buffer and installed printers, CRT-2 terminals, and FDU-80 annunciators
Sends a signal to silence the sounders on the FDU-80 and ACS annunciators
12 NFS-320/E/C, NFS-320SYS/E Operations Manual — P/N 52747:E1 06/16/2011
Control Keys Use of the Controls
You can also press this key to display multiple alarms or troubles. If more than one alarm or trouble exists, the control panel displays the next alarm or trouble for 3 seconds (or until you press the
ACKNOWLEDGE/SCROLL DISPLAY key), then displays the next alarm or trouble.
NOTE: If Local Control is set to “0” (NO), the FACP will not respond to ACKNOWLEDGE, and the piezo will not sound.

2.3.2 Signal Silence

Use the SIGNAL SILENCE key to silence the panel sounder and turn off all audio and visual devices connected to Notification Appliance Circuits. When pressed, the control panel does the following:
Turns off the panel sounder
Turns off all silenceable output circuits
•Lights the SIGNALS SILENCED LED
Sends a SIGNALS SILENCED message to the History buffer and installed printers, CRT-2 terminals, and FDU-80 annunciators
Partial Signal Silence
When some active outputs are silenced and others remain constant, the SIGNALS SILENCED LED will flash
NOTE: If Local Control is set to “0” (NO) or “2” (Partial Control), the FACP will not respond to
SIGNAL SILENCE.

2.3.3 System Reset

Use the SYSTEM RESET key to reset the control panel. When pressed, the control panel does the following:
Clears ALL active inputs
Interrupts resettable power
Sends a “System Reset” message to the History buffer, and installed printers, CRT-2 terminals, and FDU-80 annunciators
Decouples from Noti•Fire•Net, if connected, for 60 seconds to allow Cooperative Control By Event (CCBE) to clear.
If any alarm or trouble exists after you press the SYSTEM RESET key, all NACs, contr ol output s, and panel audio and visual indicators will reactivate.
NOTE: Trouble conditions will not clear and re-report upon reset.
NOTE: If Local Control is set to “0” (NO), the FACP will not respond to SYSTEM RESET.
NFS-320/E/C, NFS-320SYS/E Operations Manual — P/N 52747:E1 06/16/2011 13
Use of the Controls Programming Keypad

2.3.4 Drill

Use the DRILL key to manually activate all silenceable outputs and Notification Appliance Circuits. To prevent accidental activation, you must press the control panel does the following:
Turns on all silenceable NACs
Turns off the SIGNALS SILENCED LED
Sends a Manual Evacuate message to the History buffer and installed printers, CRT-2 terminals, and FDU-80 annunciators
NOTE: If Local Control is set to “0” (NO) or “2” (Partial Control), the FACP will not respond to DRILL.
DRILL key for 2 seconds. When pressed, the

2.3.5 Lamp Test

Use the LAMP TEST key to test the control panel LEDs and the panel sounder. When pressed and held, the control panel does the following:
Lights all control panel LEDs
Turns on the panel sounder
Lights all segments of the LCD display. When the LAMP TEST key is held for longer than five seconds, the LCD will display the Software Revisions.

2.4 Programming Keypad

The programming keypad includes:
Function keys: DETECTOR, MODULE, OUTPUT, BATTERY LEVELS, NEXT SELECTION, PREVIOUS
SELECTION, RECALL LAST ENTRY, and INCREMENT NUMBER
ENTER key
Cursor movement keys: ESC/LEFT ARROW key, UP key, RIGHT key, DOWN key
Alphabetic and numeric keys, with LOWER CASE selection key
Shown below is the Programming Keypad, with descriptions for the keys.
14 NFS-320/E/C, NFS-320SYS/E Operations Manual — P/N 52747:E1 06/16/2011
Programming Keypad Use of the Controls
LOWER CASE key – press with an alphabetic key to enter lower case characters
DETECTOR key – press
to select a detector
OUTPUT key – press to select a
Notification Appliance Circuit
MODULE key – press to select a
control/relay or monitor module
NEXT SELECTION key – press to display the next item in a list
or display the device at the next highest address
PREVIOUS SELECTION key – press to display the previous item
in a list or display the device at the next lowest address
Arrow keys – press to move the cursor one place in the direction of the arrow
ESC key – press to exit a selection or
move the cursor one place to the left
ENTER key – press to complete
or save an entry. Also press to enter Programming
Numeric keys – press to enter numeric characters. Press with Lower Case key for symbols.
Alphabetic keys – press to enter alphabetic characters
S
PACE – press to enter a space
NFS640-keypad3.cdr
BATTERY LEVELS key – press
to check the voltage and charging status of the batteries.
NFS-320/E/C, NFS-320SYS/E Operations Manual — P/N 52747:E1 06/16/2011 15
Figure 2.2 Programming Keypad

Section 3: Operation of the Control Panel

!
SYSTEM NORMAL 01:56P 041511 Tue

3.1 Overview

This section contains instructions for operating the control panel. Listed below are the topics detailed in this section:
Section Refer to Page
3.2, "Normal Mode of Operation" page 16
3.3, "Fire Alarm Mode of Operation" page 17
3.4, "Carbon Monoxide (CO) Alarm Mode of Operation" page 22
3.5, "System Trouble Mode of Operation" page 23
3.5, "System Trouble Mode of Operation" page 21
3.6, "Security Alarm Mode of Operation" page 23
3.7, "Active Supervisory Signal Mode of Operation" page 24
3.8, "Pre-Alarm Warning Mode of Operation" page 26
3.9, "Disabled Points Mode of Operation" page 28
3.10, "Non-Alarm Mode of Operation" page 28
3.11, "Active Trouble Monitor Mode of Operation" page 29
3.12, "Output Circuit Trouble Mode of Operation" page 30
3.13, "Operation of Special System Timers" page 32
3.14, "Waterflow Circuit Operation" page 33
3.15, "Style 6 and Style 7 Operation" page 33
This manual also contains information on operating the control panel in the appendixes, listed as follows:
Appendix A, “Special Zone Operation”, on page 49
Appendix B, “Intelligent Detector Functions”, on page 58
Appendix C.3, “Remote Terminal Mode Functions”, on page 62
Appendix D, “Point and System Troubles Lists”, on page 68
WARNING:
When used for CO2 releasing applications, observe proper precautions as stated in NFPA 12. Do not enter the protected space unless physical lockout and other safety procedures are fully completed. Do not use software disable functions in the panel as lockout.

3.2 Normal Mode of Operation

The system operates in Normal mode when no alarms or troubles exist. In Normal mode, the control panel displays a System Normal message as follows
Figure 3.1 Sample System Normal Message
16 NFS-320/E/C, NFS-320SYS/E Operations Manual — P/N 52747:E1 06/16/2011
Fire Alarm Mode of Operation Operation of the Control Panel
Status banner
Type Code of initiating device
Custom descriptor for this device location
Device address
Time and date of trouble
Extended 12 character custom label
ALARM: PULL STATION INTENSIVE CARE UNIT EASTERN WING Z004 03:10P 011511 2M147
Zone
In Normal mode, the control panel does the following functions at regular intervals:
Polls all SLC devices and the four NACs to check for valid replies, alarms, troubles, circuit integrity, supervisory signals, etc.
Checks power supply troubles and batteries at 10-second intervals
Sends a supervisory query on the optional FDU-80 and verifies proper response
Refreshes the LCD display and the optional FDU-80 display and updates time
Scans for any keypad or Control Key entries
Performs a detector automatic test operation
Tests system memory
Monitors for microcontroller failure

3.3 Fire Alarm Mode of Operation

3.3.1 How the Control Panel Indicates a Fire Alarm

When an initiating device (detector or monitor module) activates, the control panel does the following:
Produces a steady audible tone
Activates the System Alarm relay (TB4)
Flashes the FIRE ALARM LED
Displays a Type Code that indicates the type of device that activated the fire alarm
•Displays ALARM in the status banner on the LCD display, along with information specific to the device, as shown below:
NFS-320/E/C, NFS-320SYS/E Operations Manual — P/N 52747:E1 06/16/2011 17
Figure 3.2 Sample Fire Alarm Display
Sends an Alarm message to the LCD display, History buffer and installed printers, FDU-80 annunciators, and CRT-2s.
Latches the control panel in alarm. (You can not return the control panel to normal operation until you correct the alarm condition and reset the control panel)
Initiates any Control-By-Event actions
Starts timers (such as Silence Inhibit, Auto Silence)
Activates the general alarm zone (Z00)

3.3.2 How to Respond to a Fire Alarm

If the control panel indicates a fire alarm, you can do the following:
To silence only the panel sounder: Press the ACKNOWLEDGE/SCROLL DISPLAY key. The local sounder will silence and the FIRE
ALARM LED will change from flashing to steady.
The control panel will send an acknowledge message to the LCD display, history buffer, and installed printers, FDU-80 annunciators, and CRT-2s.
Operation of the Control Panel Fire Alarm Mode of Operation
Status banner
Time and date of the Alarm Silenced
SIGNALS SILENCED 03:12P 011508 Tue
To silence the panel sounder and any activated outputs that are programmed as silenceable: Press the SIGNAL SILENCE key . The FIRE ALARM LED and SIGNALS SILENCED LED light steady. The control panel sends an Signal Silenced message to the History buffer and installed
printers, FDU-80 annunciators, and CRT-2s. The figure below shows a sample Alarm Silenced message.
Figure 3.3 Sample Alarm Silenced Message
1. Check the Alarm message for the location and type of trouble.
2. Correct the condition causing the alarm.
3. When you finish correcting the alarm condition, press the
SYSTEM RESET key to return the
control panel to normal operation (indicated by the “System Normal” message). The control panel sends a “System Normal” message to the LCD display, History buffer and installed printers, FDU-80 annunciators, and CRT-2s.

3.3.3 Interpreting Fire Alarm Type Codes

The Type Code that displays in the Alarm message indicates the function of the point that initiates the fire alarm. For example, a monitor module with a
PULL STATION Type Code means that the
monitor module connects to a manual pull station. The table below lists the Type Codes that can appear in an alarm message:
Type Code
Latching
(Y/N)
Purpose What it does
Monitor Modules
Blank Y Indicates activation of a device with no description Lights FIRE ALARM LED and activates CBE HEAT DETECT Y Indicates activation of a conventional heat detector Lights FIRE ALARM LED and activates CBE MONITOR Y Indicates activation of an alarm-monitoring device Lights FIRE ALARM LED and activates CBE PULL STATION Y Indicates activation of a manual fire-alarm-activating
device, such as a pull station. RF MON MODUL Y Indicates activation of a wireless alarm-monitoring device Lights FIRE ALARM LED and activates CBE RF PULL STA Y Indicates activation of a wireless manual fire-alarm-
activating device, such as a pull station SMOKE CONVEN Y Indicates activation of a conventional smoke detector
attached to an FZM-1 SMOKE DETECT Y Indicates activation of a conventional smoke detector
attached to an FZM-1 WATERFLOW Y Indicates activation a waterflow alarm switch Lights FIRE ALARM LED and activates CBE EVACUATE SW N Performs Drill function Activates all silenceable outputs MAN. RELEASE Y Indicates activation of a monitor module programmed to
a releasing zone to perform a releasing function. MANREL DELAY Y Indicates activation of a monitor module programmed for
a release output SECOND SHOT N Provides second activation of releasing zone after soak
timer has expired. CO MONITOR* Y Indicates activation of a CO conventional detector Activates CBE, does not light an indicator at
Lights FIRE ALARM LED and activates CBE
Lights FIRE ALARM LED and activates CBE
Lights FIRE ALARM LED and activates CBE
Lights FIRE ALARM LED and activates CBE
Lights FIRE ALARM LED and activates CBE
Lights FIRE ALARM LED and activates CBE
Indicates ACTIVE and activates CBE
the control panel.
Detectors
SMOKE(ION) Y Indicates activation of an ion smoke detector Lights FIRE ALARM LED and activates CBE SMOKE(DUCT I) Y Indicates activation of a duct ion smoke detector Lights FIRE ALARM LED and activates CBE
Table 3.1 Fire Alarm Type Codes (1 of 2)
18 NFS-320/E/C, NFS-320SYS/E Operations Manual — P/N 52747:E1 06/16/2011
Fire Alarm Mode of Operation Operation of the Control Panel
Type Code
SMOKE(PHOTO) Y Indicates activation of a photo smoke detector Lights FIRE ALARM LED and activates CBE RF_PHOTO Y Indicates activation of a wireless photoelectric smoke
SMOKE(DUCTL) Y Indicates activation of a duct laser detector Lights FIRE ALARM LED and activates CBE SMOKE(DUCTP) Y Indicates activation of a duct photo smoke detector Lights FIRE ALARM LED and activates CBE SMOKE(HARSH)* Y Indicates activation of a HARSH smoke detector Lights FIRE ALARM LED and activates CBE SMOKE(LASER) Y Indicates activation of a laser smoke detector Lights FIRE ALARM LED and activates CBE SMOKE(BEAM) Y Indicates activation of a beam smoke detector Lights FIRE ALARM LED and activates CBE SMOKE(DUCTL) Y Indicates activation of a duct laser smoke detector Lights FIRE ALARM LED and activates CBE AIR REF Y Indicates activation of a laser air reference detector. L ights FIRE ALARM LED and activates CBE HEAT Y Indicates activation of a 190oF intelligent thermal detector Lights FIRE ALARM LED and activates CBE HEAT+ Y Indicates activation of a 190oF adjustable threshold
HEAT(ANALOG) Y 135oF intelligent thermal sensor Lights FIRE ALARM LED and activates CBE HEAT (ROR) Y 15oF per minute rate-of-rise detector Lights FIRE ALARM LED and activates CBE SMOKE ACCLIM Y Indicates activation of detector without freeze warning Lights FIRE ALARM LED and activates CBE SMOKE (ACCL+) Y Indicates activation of a detector with freeze warning Lights FIRE ALARM LED and activates CBE SMOKE MULTI* Y Multi sensor smoke detector Lights FIRE ALARM LED and activates CBE PHOTO/CO* Y Indicates activation of the Photo, Heat, or CO element of
PHOTO/CO (P SUP)*
PHOTO/CO (C SUP)*
*FlashScan mode only
Latching
(Y/N)
detector
intelligent thermal detector
a detector
Y Indicates activation of the Photo, Heat or CO element of
a detector.
Y Indicates activation of the Photo, Heat or CO element of
a detector.
Purpose What it does
Lights FIRE ALARM LED and activates CBE
Lights FIRE ALARM LED and activates CBE
Lights FIRE ALARM LED for photo and heat, no LED will light for a CO alarm. Photo and heat will activate CBE, CO alarm activates special function zone FC and sixth CBE zone only (sixth CBE zone programmable via VeriFire Tools)
Lights FIRE ALARM LED for heat, no LED will light for a CO alarm, supervisory LED will light for photo alarm, heat and photo will activate CBE, CO alarm activates special function zone FC and sixth CBE zone only (sixth CBE zone programmable via VeriFire Tools)
Lights FIRE ALARM LED for heat and photo alarms, will light supervisory LED for CO alarm, photo and heat alarms will activate CBE, CO alarm will activate sixth CBE zone only (sixth CBE zone programmable via VeriFire Tools)
Table 3.1 Fire Alarm Type Codes (2 of 2)
NFS-320/E/C, NFS-320SYS/E Operations Manual — P/N 52747:E1 06/16/2011 19
Operation of the Control Panel Carbon Monoxide (CO) Alarm Mode of Operation
Status banner
Type Code of initiating device
Custom descriptor for this device location
Device address
Time and date of trouble
Extended 12 character custom label
ALARM: CO INTENSIVE CARE UNIT EASTERN WING Z004 03:10P 011511 2M147
Zone
Status banner
Time and date of the Alarm Silenced
SIGNALS SILENCED 03:12P 011511 Tue

3.4 Carbon Monoxide (CO) Alarm Mode of Operation

3.4.1 How the Control Panel Indicates a CO Alarm

When a CO alarm from a FCO-851 or monitor module with a CO monitor activates due to a CO alarm event, the control panel does the following:
Produces a pulsed audible tone (if the piezo is enabled)
Displays a CO alarm event that indicates the type of device that activated the CO alarm
•Displays ALARM in the status banner on the LCD display, along with information specific to the device, as shown below:
Figure 3.4 Sample CO Alarm Display
Sends a CO alarm message to the LCD display, remote annunciators, History buffer, installed printers, and CRT-2s.
Latches the control panel in CO alarm. (You can not return the control panel to normal operation until you correct the CO alarm condition and reset the control panel.)
Initiates any Control-By-Event actions and activates special function zone FC.
20 NFS-320/E/C, NFS-320SYS/E Operations Manual — P/N 52747:E1 06/16/2011

3.4.2 How to Respond to a CO alarm

If the control panel indicates a CO alarm, you can do the following:
To silence only the panel sounder:
Press the ACKNOWLEDGE/SCROLL DISPLAY key. The local sounder will silence. The control panel will send an acknowledge message to the LCD display, remote annunciators,
history buffer, installed printers, and CRT-2s
To silence the panel sounder and any activated outputs that are programmed as silenceable:
Press the SIGNAL SILENCE key. The SIGNAL SILENCE LED will light steady. The control panel sends an Signal Silenced message to the History buffer, installed printers, remote
annunciators, and CRT-2s. The figure below shows a sample Alarm silenced message.
Figure 3.5 Sample Alarm Silenced Message
1. Check the Alarm message for the location and type of trouble.
2. Correct the condition causing the CO alarm.
3. When you finish correcting the CO alarm condition, press the control panel to normal operation (indicated by the “System Normal” message). The control panel sends a “System Normal” message to the LCD display, History buffer, instal led printe rs, FDU-80 annunciators, and CRT-2s.
SYSTEM RESET key to return the
System Trouble Mode of Operation Operation of the Control Panel

3.4.3 Interpreting CO Alarm/Supervisory Type ID Codes

The Type Code that displays in the CO alarm message indicates the function of the point that initiates the CO alarm. For example, a monitor module with a the monitor module monitors a conventional CO Detector. The table below lists the Type Codes
that can appear in an alarm message:
CO MONITOR Type Code means that
Type Code
Latching
(Y/N)
Purpose What it does
Monitor Modules
CO Monitor* Y Indicates activation of a CO conventional detector Activates CBE, CO alarm does not light an
indicator at the control panel.
Detectors
Photo/CO* Y Indicates activation of the Phot o, Heat, or CO element of
a detector
Photo/CO (C Sup)* Y Indicates activation of the Photo, Heat or CO element of
a detector.
Photo/CO (P Sup)* Y Indicates activation of the Photo, Heat or CO element of
a detector.
*FlashScan mode only
Table 3.2 CO Alarm Type Codes
Activates CBE, CO alarm does not light an indicator at the control panel.
Activation of the Heat or Photo elements will light an indicator at the control panel. Activation of the CO element will light the
SUPERVISORY LED. Activates the CBE
Activation of the Heat element will light an indicator at the control panel. Activation of a CO alarm will not light an indicator at the control panel. Activation of the Photo element will light the
SUPERVISORY LED. Activates the CBE

3.5 System Trouble Mode of Operation

3.5.1 How the Control Panel Indicates a System Trouble

The system goes into system trouble when the control panel detects an electrical fault. If no fire alarms exist, the control panel does the following:
Produces a pulsed audible tone
Activates the Trouble relay (TB4)
Flashes the SYSTEM TROUBLE LED
Displays a Type Code that indicates the type of device with a trouble.
•Displays TROUBLE in the status banner on the LCD display as well as the type of trouble and information specific to the device, as shown in
Figure 3.6 below.
Sends a Trouble message to the LCD display, history buffer and installed printers, FDU-80 annunciators, and CRT-2s.
NOTE: If a fire alarm exists when a trouble exists, the SYSTEM TROUBLE LED lights, but the Alarm message appears in the LCD display.
NFS-320/E/C, NFS-320SYS/E Operations Manual — P/N 52747:E1 06/16/2011 21
Operation of the Control Panel System Trouble Mode of Operation
Type of event
Type of device
Custom descriptor for this device location
Device address
Time and date of trouble
Type of trouble
Extended 12 character custom label
TROUBL PULL STATION INTENSIVE CARE UNIT EASTERN WING INVREP 03:14P 011511 2M147
Time and date of Acknowledge
Status banner
ACKNOWLEDGE 03:15P 011511 Tue
TROUBL MONITOR MODULE ADDRESS M021 Z00 OPEN CIRCUIT 08:10A 041508 2M021 TROUBL MONITOR MODULE ADDRESS M022 Z00 OPEN CIRCUIT 08:12A 041508 2M022
Typical Trouble message that appears on the LCD display:
Figure 3.6 Sample Trouble Message

3.5.2 How to Respond to a System Trouble

If the control panel indicates a trouble, you can do the following:
1. Press the ACKNOWLEDGE/SCROLL DISPLAY key to silence the panel sounder and switch the
SYSTEM TROUBLE LED from flashing to steady—regardless of the number of troubles, alarms,
security and supervisory signals.
NOTE: Pressing the SIGNAL SILENCE key when only troubles exist, gives the same result as pressing the ACKNOWLEDGE/SCROLL DISPLAY key.
2. The control panel sends an Acknowledge message to the History buffer and installed printers, FDU-80 annunciators, and CRT-2s.
Figure 3.7 Sample Acknowledge Message
3. Check the trouble message for the location and type of trouble.
Figure 3.8 Sample Trouble Messages on CRT-2 or Printer
4. Correct the condition causing the trouble. If the trouble clears, the control panel sends a Clear Trouble message to the History buffer and installed printers, FDU-80 annunciators, and CRT-2s.
If all troubles clear and no supervisory signals or fire alarms exist, the control panel does the following:
Returns to Normal operation (indicated by the “System Normal” message)
Sends a “System Normal” message to the LCD display, History buffer and installed printers, FDU-80 annunciators, and CRT-2s
Restores troubles automatically - even if troubles are not acknowledged
If multiple trouble conditions exist in the system, the LCD and optional CRT-2 and FDU-8 0 annunciators display automatically step through each trouble every 3 seconds in the following order:
1. Alarms, in order of address
2. Supervisory, in order of address
3. Troubles, in order of address
22 NFS-320/E/C, NFS-320SYS/E Operations Manual — P/N 52747:E1 06/16/2011
Security Alarm Mode of Operation Operation of the Control Panel
ACTIVE SECURITY INTENSIVE CARE UNIT EASTERN WING Z004 03:17P 041511 2M147
Status Banner
Type Code
Custom descriptor for this device location
Device address
Time and date of trouble
Zone
Press the ACKNOWLEDGE/SCROLL DISPLAY key and the display stops on the current trouble event for 1 minute, then begins to automatically step through remaining troubles. To manually step through remaining troubles, press the
ACKNOWLEDGE/SCROLL DISPLAY key.
Refer to Appendix D, “Point and System Troubles Lists”, on page 68 for explanations of troubles that appear on the display.

3.6 Security Alarm Mode of Operation

3.6.1 How the Control Panel Indicates a Security Alarm

The system goes into Security mode when a monitor module point programmed with a Security Type Code activates. If no fire alarm exists, the control panel does the following:
Produces a warbling audible tone
Turns on the Security relay (TB5)
Flashes the SECURITY LED (blue)
Displays a Type Code that indicates the type of security alarm being generated
•Displays ACTIVE in the status banner on the control panel, along with information specific to the device
Sends a Security message to the LCD display, History buffer, and in stalled printers, FDU-80 annunciators, and CRT-2s
Sends a Security message to the proprietary receiver via the network, if applicable.
NOTE: If a fire alarm exists, and there are silenced alarms (the SIGNALS SILENCED LED is lighted), a Security alarm will resound the panel sounder.
A Typical security message that appears on LCD display:
Figure 3.9 Sample Security Alarm Message

3.6.2 How to Respond to a Security Alarm

A Security Type Code latches the control panel. To return the control panel to normal operation, you must correct the condition causing the security condition, then reset the control panel. If the control panel indicates a security alarm, take the following action:
NOTE: If a fire alarm exists, and there are silenced alarms (the SIGNALS SILENCED LED is lighted), a Security alarm will resound the panel sounder.
1. Press the ACKNOWLEDGE/SCROLL display key to silence the panel sounder and switch the
SECURITY LED from flashing to steady—regardless of the number of troubles, alarms,
supervisory, and security signals. The control panel sends a Security message to the History buffer and installed printers, FDU-80 annunciators, and CRT-2s.
2. Correct the condition that activated the Security point.
NFS-320/E/C, NFS-320SYS/E Operations Manual — P/N 52747:E1 06/16/2011 23
Loading...
+ 53 hidden pages