While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system—typically made up of
smoke detectors, heat detectors, manual pull stations, audible
warning devices, and a fire alarm control panel with remote
notification capability—can provide early warning of a developing fire. Such a system, however, does not assure protection
against property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the
recommendations of the current edition of the National Fire
Protection Association Standard 72-1999 (NFPA 72-1999),
manufacturer's recommendations, State and local codes, and
the recommendations contained in the Guide for Proper Use
of System Smoke Detectors, which is made available at no
charge to all installing dealers. A study by the Federal Emergency Management Agency (an agency of the United States
government) indicated that smoke detectors may not go off in
as many as 35% of all fires. While fire alarm systems are
designed to provide early warning against fire, they do not
guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply
may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors. Smoke detectors
also may not sense a fire on another level or floor of a building.
second-floor detector, for example, may not sense a first-
floor or basement fire.
Particles of combustion or “smoke” from a developing fire
may not reach the sensing chambers of smoke detectors
because:
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow.
• Smoke particles may become “cold,” stratify, and not reach
the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air
outlets.
• Smoke particles may be drawn into air returns before
reaching the detector.
The amount of “smoke” present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm at
various levels of smoke density. If such density levels are not
created by a developing fire at the location of detectors, the
detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing
limitations. Detectors that have photoelectronic sensing
chambers tend to detect smoldering fires better than flaming
fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires
better than smoldering fires. Because fires develop in different
ways and are often unpredictable in their growth, neither type
of detector is necessarily best and a given type of detector
may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and violent
explosions (caused by escaping gas, improper storage of
flammable materials, etc.).
Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise
heat detectors may be subject to reduced sensitivity over time.
For this reason, the rate-of-rise feature of each detector
should be tested at least once per year by a qualified fire protection specialist. Heat detectors are designed to protect
property, not life.
IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so
located, a developing fire may damage the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert people
if these devices are located on the other side of closed or
partly open doors or are located on another floor of a building.
Any warning device may fail to alert people with a disability or
those who have recently consumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause seizures
in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they
hear a fire alarm signal, do not respond or comprehend the
meaning of the signal. It is the property owner's responsibility to conduct fire drills and other training exercise to
make people aware of fire alarm signals and instruct them
on the proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can
cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical
power. If AC power fails, the system will operate from standby
batteries only for a specified time and only if the batteries have
been properly maintained and replaced regularly.
Equipment used in the system may not be technically compatible with the control panel. It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a
premise to a central monitoring station may be out of service
or temporarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended.
The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in
excellent working order, ongoing maintenance is required per
the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of Chapter 7 of NFPA
72-1999 shall be followed. Environments with large amounts
of dust, dirt or high air velocity require more frequent maintenance. A maintenance agreement should be arranged
through the local manufacturer's representative. Maintenance
should be scheduled monthly or as required by National and/
or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records
of all inspections should be kept.
Precau-L-4-2003.fm
2NFS-3030 Installation PN 51330:C 10/28/2003
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be
connected to the fire alarm control panel. Disconnect all
sources of power before servicing. The control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is
energized. Do not attempt to install, service, or operate this
unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software
Changes. To ensure proper system operation, this product
must be tested in accordance with NFPA 72-1999 Chapter 7
after any programming operation or change in site-specific
software. Reacceptance testing is required after any change,
addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested.
In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not
directly affected by the change, up to a maximum of 50
devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at 0°C
to 49°C (32°F to 120°F) and at a relative humidity (noncondensing) of 85% at 30°C (86°F) per NFPA, and 93% ± 2% at
32°C ± 2°C (89.6°F ± 1.1°F) per ULC. However, the useful life
of the system's standby batteries and the electronic components may be adversely affected by extreme temperature
ranges and humidity. Therefore, it is recommended that this
system and all peripherals be installed in an environment with
a nominal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a
10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to lightning-induced transients. Although no system is completely
immune from lightning transients and interferences, proper
grounding will reduce susceptibility. Overhead or outside
aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or
encountered.
Disconnect AC power and batteries prior to removing or
inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure. When possible, make
all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal
removal.
Though designed to last many years, system components
can fail at any time. This system contains static-sensitive
components. Always ground yourself with a proper wrist strap
before handling any circuits so that static charges are
removed from the body. Use static-suppressive packaging to
protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to
avoid damage to the control panel and associated equipment.
FACP operation and reliability depend upon proper installation
by authorized personnel.
Precau-L-4-2003.fm
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual, may
cause interference to radio communications. It has been
tested and found to comply with the limits for class A
computing device pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when operated in a
commercial environment. Operation of this equipment in
a residential area is likely to cause interference, in which
case the user will be required to correct the interference
at his own expense.
Acclimate Plus™, AWACS™, HARSH™, NOTI•FIRE•NET™, ONYX™, and VeriFire™ are trademarks, and FlashScan®, UniNet®, and VIEW® are
registered trademarks of NOTIFIER. NION™ is a trademark of NIS. NIS™ and Notifier Integrated Systems™ are trademarks and NOTIFIER® is a
registered trademark of Fire•Lite Alarms, Inc. Echelon® is a registered trademark and LonWorks™ is a trademark of Echelon Corporation. ARCNET® is a
registered trademark of Datapoint Corporation. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. LEXAN® is a registered
trademark of GE Plastics, a subsidiary of General Electric Company.
NFS-3030 Installation PN 51330:C 10/28/20033
Canadian Requirements
This digital apparatus does not exceed the Class A limits
for radiation noise emissions from digital apparatus set
out in the Radio Interference Regulations of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par le
ministere des Communications du Canada.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have
any comments or suggestions about our online Help or printed manual, you can email
us.
Please include the following information:
•Product name and version number (if applicable)
•Printed manual or online Help
•Topic Title (for online Help)
•Page number (for printed manual)
•Brief description of content you think should be improved or corrected
•Your suggestion for how to correct/improve documentation
Send email messages to:
TechPubs@fla-whq.com
Please note this email address is for documentation feedback only. If you have any
technical issues, please contact Technical Services.
4NFS-3030 Installation PN 51330:C 10/28/2003
Table of Contents
Table of Contents
Section 1 About This Manual ..........................................................................................................7
1.1 Standards and Other Documents ...........................................................................................7
Standards and Other DocumentsSection 1 About This Manual
Section 1 About This Manual
1.1 Standards and Other Documents
This Fire Alarm Control Panel complies with the following NFPA standards:
NFPA 12A Halon 1301 Extinguishing Systems
NFPA 13 Sprinkler Systems
NFPA 15 Water Spray Systems
NFPA 16 Foam/Water Deluge and Foam/Water Spray Systems
NFPA 17 Dry Chemical Extinguishing Systems
NFPA 17A Wet Chemical Extinguishing Systems
NFPA 72-1999 Central Station Fire Alarm Systems (Automatic, Manual and Waterflow) Protected
Premises Unit (requires Notifier UDACT).
NFPA 72-1999 Local (Automatic, Manual, Waterflow and Sprinkler Supervisory) Fire Alarm Systems.
NFPA 72-1999 Auxiliary (Automatic, Manual and Waterflow) Fire Alarm Systems (requires TM-4).
NFPA 72-1999 Remote Station (Automatic, Manual and Waterflow) Fire Alarm Systems
NFPA 72-1999 Proprietary (Automatic, Manual and Waterflow) Fire Alarm Systems (Protected
Premises Unit).
NFPA 2001 Clean Agent Fire Extinguishing Systems
The installer should be familiar with the following documents and standards:
NFPA 72-1999 Initiating Devices for Fire Alarm Systems
NFPA 72-1999 Inspection, Testing and Maintenance for Fire Alarm Systems
NFPA 72-1999 Notification Appliances for Fire Alarm Systems
Underwriters Laboratories
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers - Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1971 Visual Signaling Appliances
UL 1076 Proprietary Burglar Alarm Systems
Underwriters Laboratories of Canada (ULC)
ULC-S527-99 Standard for Control Units for Fire Alarm Systems
ULC S524 Standard for the Installation of Fire Alarm Systems
Other
EIA-485 and EIA-232 Serial Interface Standards
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction
Canadian Electrical Code, Part 1
NFS-3030 Installation PN 51330:C 10/28/20037
Section 1 About This ManualStandards and Other Documents
1.2 Supplemental Documentation
The table below provides a list of documents referenced in this manual, as well as documents for
selected other compatible devices. The document series chart (DOC-NOT) provides the current
document revision. A copy of this document is included in every shipment.
Table 1 Related Documentation (Sheet 1 of 2)
Compatible Conventional Devices (Non-addressable)Document Number
Device Compatibility Document15378
Fire Alarm Control Panel (FACP) and Main Power Supply InstallationDocument Number
NFS-3030/E FACP Installation, Operations, and Programming Manuals
(Note: Where used in this manual, NFS-3030 refers to both NFS-3030 and NFS-3030E)
Voice Alarm System Manual51252
SLC Wiring Manual51253
Note: For individual SLC Devices, refer to the SLC Wiring Manual
Off-line Programming UtilityDocument Number
VeriFire™ Tools CD help fileVERIFIRE-TCD
Cabinets & ChassisDocument Number
CAB-3/CAB-4 Series Cabinet Installation Document15330
UDACT Manual (Universal Digital Alarm Communicator/Transmitter)50050
ACT-2 Installation Document51118
VEC 25/50 Manual50686
RM-1 Series Remote Microphone Installation Document51138
RA400Z Remote LED Annunciator DocumentI56-508
RFX Wireless Interface Manual51012
51330, 51345, 51344
8NFS-3030 Installation PN 51330:C 10/28/2003
Cautions and WarningsSection 1 About This Manual
Table 1 Related Documentation (Sheet 2 of 2)
UZC-256 Universal Zone Coder Manual15216
UZC-256 Programming Manual15976
XP Transponder Manual15888
XP10-M Ten Input Monitor Module Installation DocumentI56-1803
XP5 Series Manual50786
XP6-C Supervised Control Module Installation DocumentI56-1805
XP6-MA Six Zone Interface Module Installation DocumentI56-1806
XP6-R Six Relay Control Module Installation DocumentI56-1804
XPIQ Audio Transponder Manual51013
Note: Where used in this manual, NFS-3030 refers to both NFS-3030 and NFS-3030E. The term CPU
refers to the main circuit board for the fire alarm control panel’s central processing unit (see Section 2.2
“System Components” for a more detailed list of part numbers.)
1.3 Cautions and Warnings
This manual contains cautions and warnings to alert the reader as follows:
CAUTION: Information about procedures that could cause programming errors, runtime errors,
!
or equipment damage.
WARNING: Indicates information about procedures that could cause irreversible damage to the
!
control panel, irreversible loss of programming data or personal injury.
NFS-3030 Installation PN 51330:C 10/28/20039
Section 2 System OverviewSystem Description
C
A
bberized k
Opti
ACS devi
Section 2 System Overview
2.1 System Description
2.1.1 Standard Features
•
onnections to easily mount from one to ten
Signaling Line Circuit (SLC) loops
• Network operation
• Uses Notifier’s VIEW® early warning fire
detection and the FlashScan® or CLIP
families of detectors and modules
• Alarm, Trouble, Supervisory and Security
relays
• Support for 32 annunciator addresses with
either 64 or 96 points each.
• Supports Style 4, Style 6, Style 7 SLC loops
• Logic Equations
• Multi-line display
• Ability to activate local sounder or relay bases
in alarm or pre-alarm
• Easy connection to VeriFire Tools
programming utility
• The basic system power supply is addressable,
charges sealed lead-acid batteries ranging in
capacity from 25 to 200 amp hours, and
provides 4.5 amps of power for use by the
CPU.
• Easy connection to auxiliary power supplies
and battery chargers for custom design of very
large systems.
• Diagnostic LEDs and switches
• Ground fault detection
• Supports up to 12 panel circuit modules,
including input module IZM-8RK
• Support for Remote Text Display (LCD-160)
• Support for Display and Control Center (DCC)
functionality
Refer to Section 2.2 “System Components” for descriptions of the various optional modules.
•Ru
“QWERTY” keyboard layout, a 640-character
LCD display, indicator LEDs, and switches.
• Separately ordered Loop Control Modules and
Loop Expander Modules provide up to ten
SLC loops.
eypad with a standard
•
onal equipment includes:
UDACT Universal Digital Alarm
Communicator/Transmitter, ACM-8R remote
relay module to provide additional relay
points, audio and voice components, and panel
circuit modules.
2.1.3 System Limitations
System expansion must take into consideration the following:
1.The physical limitations of the cabinet configuration.
2.The electrical limitations of the system power supply.
3.The capacity of the secondary power source (standby batteries).
ces,
10NFS-3030 Installation PN 51330:C 10/28/2003
System ComponentsSection 2 System Overview
2.2 System Components
Central Processing Unit (CPU). The central processing unit for an NFS-3030/E system can be
ordered with a keypad/display (P/N CPU-CPU-3030D) or without a keypad/display (P/N CPU3030ND). CPU-3030D serves as “primary display” version for ULC applications. CPU-3030ND is
intended for use in network applications; LEDs and momentary switches on the printed circuit board
mimic those on the keypad to enable operation and trouble-shooting at the panel when it is used without
a local primary display.
Power supply. The main power supply is AMPS-24/AMPS-24E, which provides +24 VDC power
and a battery charger for a basic system. Auxiliary power supplies and/or battery chargers are available
to customize large systems.
Enclosures. Four cabinet sizes are available; doors and backboxes are ordered separately. “A” size
backboxes hold one row of modules, “B” size backboxes hold two rows, “C” size backboxes hold three
rows, and “D” size backboxes hold four rows. See Section 2.4 “System Cabinets” for basic description.
A variety of dress panels, trim rings, and blank modules are available to accompany specific
combinations of system equipment; contact Notifier for a complete parts list.
SLC Loops: LCM-320, LEM-320. To provide one SLC loop, connect one LCM-320 to the panel.
Connect an LEM-320 to the LCM-320 to provide a second loop. Up to five pairs of modules can be
installed on the panel to provide a maximum of ten SLC loops.
Network connection. Connect an NCM-W or NCM-F to provide a connection to Noti•Fire•Net
(network version 5.0 or higher).
Annunciators. The NFS-3030 supports ACM-24AT/ACM-48A (and their expanders) with either 64
or 96 points at an address, as well as ACM-16AT/ACM-32A (and their expanders) with 64 points at an
address and Notifier’s other ACS devices. (See Section 2.5 “Compatible Equipment” if looking for
specific ACS devices).
Panel Circuit Modules. These include both output modules (ICM-4RK/ICE-4, CRM-4RK/CRE-4,
ARM-4, VCM-4RK/VCE-4, DCM-4RK/VCE-4) and input modules (IZM-8RK/IZE-A).
Note: For information about VCM-4RK and DCM-4RK, see the Voice Alarm System Manual.
2.3 Product Diagram
The control panel electronics are contained on one printed circuit board (PCB) that holds the central
processing unit (CPU). The CPU can be purchased with or without keypad and display; (see Section 2.2
“System Components” for P/N details). Connections are identical on both versions. The following
figure illustrates the location of the various connections, switches, jumpers and LEDs on the circuit
board. See Section 3 “Installation” for more details.
NFS-3030 Installation PN 51330:C 10/28/200311
Section 2 System OverviewProduct Diagram
Figure 1 CPU Connections
Note: Relay circuits are power-limited only if
connected to a power-limited signal source.
Relays are rated for 2A@30Vdc resistive.
Note: Dotted line indicates location of optional keypad & LCD display
SW3 Acknowledge
SW4 Signal Silence
SW5 System Reset
SW6 Lamp Test
3030board.cdr
Lithium battery for backup of
on-board memory (See Section 3.5.1
“Memory-Backup Battery”.)
12NFS-3030 Installation PN 51330:C 10/28/2003
Product DiagramSection 2 System Overview
The keyboard/display
assembly is shown in
Figure 2. As shown in
Figure 3, LEDs on the
keyboard/display are
repeated on the printed
circuit board. This
enables operation and
trouble-shooting when
the panel is used without
the display assembly.
Figure 2 CPU-3030D (Shown with Two Annunciators)
CPU-3030D-ACS.cdr
Figure 3 Status Indicator LEDs
LED1 Power (Green)
LED3 Fire Alarm (Red)
LED8 Pre-Alarm (Red)
LED7 Security (Blue)
LED9 Supervisory (Yellow)
LED6 System Trouble (Yellow)
LED10 Other Event (Yellow)
LED11 Signals Silenced (Yellow)
LED12 Point Disabled (Yellow)
LED5 CPU Failure (Yellow)
LED4 Factory Use Only
LEDs on Printed Circuit BoardLEDs on Keypad
3030-leds.cdr, 3030keypadleds.cdr
2.3.1 Main Power Supply
The AMPS-24/E addressable main power supply provides a total of 4.5 A to the CPU. During normal
operation it recharges batteries ranging in capacity from 25 to 200 amp-hours. Refer to the AMPS-24/E Manual for details.
Refer to Section A “Electrical Specifications” to determine whether your system requires an auxiliary
power supply.
NFS-3030 Installation PN 51330:C 10/28/200313
Section 2 System OverviewSystem Cabinets
2.4 System Cabinets
The CPU and modules are installed in a CAB-4 series backbox. There are four different sizes available,
holding from one to four rows of equipment plus batteries (up to two 25AH batteries). Backboxes are
ordered separately from doors. The doors can be mounted on the left or the right side of the cabinet;
reversible hinges are provided so that this choice can be made in the field. Doors open a full 180 degrees
and have locks. Mounting methods include surface-mounting or semi-flush mounting on a wall between
16 inch (406.4 mm) on-center studs. A trim ring option is available for semi-flush mounting.
External measurements for each cabinet size are provided below. Refer to CAB-3/CAB-4 Series Cabinet Installation Document (shipped with your cabinet) for specific mounting drawings and dimensions.
A-size backbox
(one row)
B-size backbox
(two rows)
C-size backbox
(three rows)
D-size backbox
(four rows)
The CPU and adjacent first-row modules mount in chassis CHS-M3. Additional rows of modules mount
in the cabinet using CHS-4N (shipped in kit CHS-4MB), CHS-4L, or other chassis compatible with
CAB-4 series enclosures.
Some additional components available in the CAB-4 series include:
DP-DISPAn Inner Dress Panel for covering the backbox area surrounding various
24.125 in (612.78 mm) wide
20.125 in (511.18 mm) tall
5.218 in (132.54 mm) deep
Optional trim ring TR-A4
24.125 in (612.78 mm) wide
28.625 in (727.08 mm) tall
5.218 in (132.54 mm) deep
Optional trim ring TR-B4
24.125 in (612.78 mm) wide
37.250 in (946.15 mm) tall
5.218 in (132.54 mm) deep
Optional trim ring TR-C4
24.125 in (612.78 mm) wide
45.875 in (1165.23 mm) tall
5.218 in (132.54 mm) deep
Optional trim ring TR-D4
modules.
BMP-1Blank Module Plate for covering an unused module position. Provides another
location for mounting option boards such as TM-4 or NCM-W.
MP-1BBlank panel for covering panel circuit modules in second, third, or fourth rows of
backbox.
BP-4Battery dress panel.
DP-1BHigh-profile battery cover
ADP-4BAnnunciator dress panel
14NFS-3030 Installation PN 51330:C 10/28/2003
Compatible EquipmentSection 2 System Overview
2.5 Compatible Equipment
Compatible Notifier and System Sensor equipment that connects directly to the CPU is listed below.
These are the most common devices at time of publishing; the most complete list of compatible
intelligent SLC loop devices is provided in the SLC Wiring Manual; for conventional non-addressable
equipment see the Device Compatibility Document. These devices are UL and ULC listed unless
marked otherwise (in parentheses next to the product). Other control panels and their equipment can
also be connected in a network, via Noti•Fire•Net Version 5.0; refer to the Noti•Fire•Net Version 4.0 &
Higher Installation Manual for details. Some products are documented in a separate manual; see
Section 1.2 “Supplemental Documentation”.
XP6-C Supervised Control Module
XP6-R Six Relay Control Module
XP10-M Ten Input Monitor Module
XP6-MA Six Zone Interface Module
System Sensor Compatible Equipment
A2143-00 End of Line Resistor Assembly
Transmitter
16NFS-3030 Installation PN 51330:C 10/28/2003
Preparing for InstallationSection 3 Installation
Section 3 Installation
3.1 Preparing for Installation
Choose a location for the fire alarm system that is clean, dry, and vibration-free with moderate
temperature. The area should be readily accessible with sufficient room to easily install and maintain it.
There should be sufficient space for cabinet door(s) to open completely.
Carefully unpack the system and inspect for shipping damage. Count the number of conductors needed
for all devices and find the appropriate knockouts. (Refer to Section 3.16 “UL Power-limited Wiring
Requirements” for selection guidelines.)
Before installing the fire alarm system, read the following:
• Review the installation precautions at the front of this manual.
• Installers should be familiar with the standards and codes specified in Section 1.1 “Standards
and Other Documents”.
• All wiring must comply with the National and Local codes for fire alarm systems.
• Do not draw wiring into the bottom 9 inches (22.86 cm) of the cabinet except when using a
separate battery cabinet; this space is for internal battery installation.
• Review installation instructions in Section 3.2 “Installation Checklist”.
WARNING: Make sure to install system components in the sequence listed below. Failure to do so
!
can damage the control panel and other system components.
WARNING: Wear a static discharge strap on wrist to prevent equipment damage.
!
3.2 Installation Checklist
The checklist that follows contains references to information included in other manuals; see Section 1.2
“Supplemental Documentation” for document part numbers.
Table 2 Installation Checklist (Sheet 1 of 2)
TaskRefer to:
1.Mount the cabinet backbox to the wall.Section 3.3 “Mounting a Cabinet”
2.Attach CPU to chassis Section 3.5 “Attaching the CPU & Chassis”
3.Attach panel circuit modules and
option boards (e.g. SLC loop modules,
network control modules, and other
devices of the same size) to chassis.
4.Attach chassis to backbox as
appropriate for system design
5.Wire Notification Appliance Circuits,
Initiating Device Circuits, and Relays
6.Attach & wire other system components
Voice Alarm System components Voice Alarm System Manual
Annunciators and other ACS
devices
Remote Data Port devicesLCD-160 Manual
• Section 3.6 “Attaching Option Boards”
• Section 3.7 “Attaching Panel Circuit Modules”
• Section 3.14 “Connecting Specific Option Boards”
• Installation document for the specific device
Section 3.4 “Laying Out Equipment in Cabinet and Chassis”
• Section 3.8 “Initiating Device Circuits with IZM-8RK/IZE-A”
• Section 3.9 “NACs with ICM-4RK⁄ICE-4”
• Section 3.10 “Form-C Relays on the CPU”
• Section 3.11 “Form-C Relays with CRM-4RK/CRE-4”
• Section 3.12 “Form-C Relays with Auxiliary Relay Module (ARM-4)”
ACS Manual, LCD-80 Manual, etc.
NFS-3030 Installation PN 51330:C 10/28/200317
Section 3 InstallationInstallation Checklist
Table 2 Installation Checklist (Sheet 2 of 2)
TaskRefer to:
Printer or other output device(s)Section 3.18 “Installing Printers”
Network devicesNoti•Fire•Net Version 4.0 & Higher Manual, and/or
Installation document for specific device(s)
7.Wire the Signaling Line Circuits.Section 3.19 “Wiring a Signaling Line Circuit (SLC)” and SLC Wiring
Manual
8.Calculate the proper battery rating.Main Power Supply Manual
9.Install main power supply & batteries in
separate enclosure. Run cable to main
& optional power supplies, DC power
outputs, relays, etc.
WARNING: Do not activate power at this time. Do NOT connect batteries.
Section 3.15 “Connecting Power Sources and Outputs”
Section 3.16 “UL Power-limited Wiring Requirements”
!
Main power supply.Main Power Supply Manual
BB-100/200 Cabinet Installation Instructions
Auxiliary power supply and/or
external battery charger
10.Check that all mounting holes are secured to insure a proper Earth Ground connection.
11.Connect wire shielding to Earth Ground.
12.Remove insulator from lithium battery
on CPU
13.Apply AC power to the control panel by placing the external circuit breaker to the ON position.
Do NOT connect batteries until AC power is checked (see next step).
14.Check AC power.Section 3.15.1 “Checking AC Power”
15.Connect the batteries using interconnect cable as described in power supply manual.
16.Install the dress panels, doors and
covers.
17.Program the control panel.Programming Manual.
18.Field test the system.Section 5 “Testing the System”
Auxiliary power supply manuals and/or battery charger manuals
Note: If using multiple power supplies with one set of batteries, refer to
main power supply manual for connection requirements.
Section 3.5.1 “Memory-Backup Battery”
CAB-3/CAB-4 Series Cabinet Installation Document
18NFS-3030 Installation PN 51330:C 10/28/2003
Mounting a CabinetSection 3 Installation
3.3 Mounting a Cabinet
This section provides instructions for mounting the CAB-4 Series backbox to a wall. Follow these
guidelines when mounting the backbox:
• Locate the backbox so that the top edge is 66 inches (1.6764 m) above the surface of the finished
floor.
• Allow sufficient clearance around cabinet for door to swing freely. (See Section 2.4 “System
Cabinets”.)
• Use the four holes in the back surface of the backbox to provide secure mounting (See Figure 4).
• Mount the backbox on a surface that is in a clean, dry, vibration-free area.
CAUTION: Unless you are familiar with the placement of components within this backbox, only
!
use the knockout locations provided for conduit entry.
Follow the instructions below.
1.Mark and pre-drill holes for the top two keyhole mounting bolts.
2.Select and punch open the appropriate knock-outs. (For selection guidelines, see Section 3.16 “UL
Power-limited Wiring Requirements”.)
3.Using the keyholes, mount the backbox over the two screws.
4.Mark the location for the two lower holes, remove the backbox and drill the mounting holes.
5.Mount the backbox over the top two screws, then install the remaining fasteners. Tighten all
fasteners securely.
6.Feed wires through appropriate knockouts.
7.Install CPU and other components according to this section, before installing hinges and door (see
CAB-3/CAB-4 Series Cabinet Installation Document).
Figure 4 Backbox-Mounting Holes and Chassis-Mounting Studs
CAB-4 Series backbox,
D-size (four-row)
CAB-4 Series backbox,
A-size (one-row)
Keyholes
2 places
Mounting holes
Chassis-
mounting
studs
(2 per row of
backbox)
2 places
Chassis-
mounting
studs
(2 per row of
backbox)
CAB4cabinetmountingholes.cdr
NFS-3030 Installation PN 51330:C 10/28/200319
Section 3 InstallationLaying Out Equipment in Cabinet and Chassis
3.4 Laying Out Equipment in Cabinet and Chassis
The NFS-3030 allows for flexible system
design. Follow these guidelines when
deciding where to locate equipment in the
backbox. There are four basic positions
Four positions
Figure 5 Chassis CHS-M3
on chassis
CHS-M3
12 34
available on a chassis; the number of layers
that can be mounted in each position depends
on the chassis model and the module size.
The CPU mounts in chassis CHS-M3 in the
top row of the cabinet. The CPU and its
optional display occupy the left half of the
chassis (positions 1 and 2, see Figure 5). If
NCA is used, it may be door-mounted in front
of a displayless CPU (see the NCA manual for
details & restrictions).
Positions 3 and 4 of CHS-M3 can hold up to
Positions 1 and 2:
CPU
Positions 3 and 4:
Four layers of equipment
four layers of equipment including
annunciators, panel circuit modules, and option boards. See Figure 6 for possible configurations of
these four layers.
The BMP-1 Blank Module Plate covers unused positions and also provides a location to door-mount
some option boards (see BMP-1 Product Installation Drawing for details).
Figure 6 Configuring Equipment in Chassis (Side View):
Positions 3 and 4 of CHS-M3, All 4 Positions of CHS-4N
CHS-M3.cdr
Layers 1&2&3 mounted to
PEM studs on chassis
Layer 4 mounted to
PEM studs and tab-slot
*Note: If CHS-4N is used, door-mounting is only for use with
ACM-24AT and ACM-48A series annunciators.
Layers 1&2&3 mounted to
PEM studs on chassis
Layer 4 door-mounted*
Second, third, and fourth rows of equipment use any chassis compatible with CAB-4 series backboxes,
such as CHS-4N (shipped as part of CHS-4MB) or CHS-4L. Refer to the CAB-3/CAB-4 Series Cabinet Installation Document for a complete list. Some equipment (such as the NCA and annunciators) can be
door-mounted; refer to your equipment’s documentation for instructions.
Panel circuit modules include ICM-4RK, CRM-4RK, IZM-4RK, VCM-4RK, DCM-4RK and their
expanders. See Section 3.7 “Attaching Panel Circuit Modules”; for VCM-4RK and DCM-4RK, see the
Voice Alarm System Manual. Option boards include LCM-320, LEM-320, NCM-W/F, TM-4, and DPI232; see Section 3.6 “Attaching Option Boards”. The documentation shipped with your equipment may
also contain device-specific instructions.
Layers 1&2 mounted to
PEM studs on chassis
Layer 4 mounted to PEM
studs and tab-slot; Layer 3
suspended from Layer 4
Layers 1&2 mounted to
PEM studs on chassis
CHS-M3-options.cdr
Layer 4 mounted to PEM
studs and tab-slot; Layer 3
suspended from Layer 4
Note: It is recommended that system design take into consideration the UL requirements for minimum
20NFS-3030 Installation PN 51330:C 10/28/2003
Attaching the CPU & ChassisSection 3 Installation
separation of power-limited and non-power-limited wiring; for example, having all non-power-limited
circuits grouped in one area of the cabinet (see Section 3.16 “UL Power-limited Wiring Requirements”
and your power supply manual).
3.5 Attaching the CPU & Chassis
Mount CPU into positions 1 and 2 of CHS-M3 as follows; equipment may be mounted to the chassis
before or after the chassis is mounted in the backbox. Some equipment may be door-mounted directly in
front of the CPU; see Section 3.4 “Laying Out Equipment in Cabinet and Chassis” and the manual
shipped with the other device.
1.Attach four stand-offs to chassis as shown in Figure 7.
CPU-3030D (with keypad/display) requires the longer stand-offs: 1.5 inch (38.1 mm);
CPU-3030ND (without keypad/display) requires the shorter stand-offs: 0.25 inch (6.35 mm)
2.Slide circuit-board tabs into slots on chassis as shown in Figure 7.
3.Place the board over the stand-offs so that mounting holes line up with those on the chassis. Secure
all stand-offs with screws provided.
CAUTION: It is critical that all mounting holes of the NFS-3030 are secured with a screw or
!
stand-off to insure continuity of Earth Ground.
Figure 7 Standoffs on Chassis CHS-M3
CPU standoffs at
Positions 1 and 2:
1 inch (25.4 mm)
Chassis-mounting slots
CPU-3030ND
(without keypad/display)
CPU-3030D
(with keypad/display)
Note for CPU-3030D: Due to the difficulty of reaching under the keypad, it may be convenient to
remove the insulator from the lithium memory-backup battery at this time. See Section 3.5.1 “MemoryBackup Battery”.
Mounting Chassis in Backbox
Align chassis-mounting slots with chassis-mounting studs (see Figure 4 and Figure 7 for locations).
Secure with nut & lock-washer provided with chassis.
CHS-M3.cdr
NFS-3030 Installation PN 51330:C 10/28/200321
Loading...
+ 47 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.