While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system—typically made up of
smoke detectors, heat detectors, manual pull st ati ons, audib le
warning devices, and a fire alarm control panel with remote
notification capability—can provi de early warn ing of a develop
ing fire. Such a system, however, does not assure protection
against property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the
recommendations of the current edition of the National Fire
Protection Association S tandard 72 (NFPA 72), manufacturer's
recommendations, State and local codes, and the recommen
dations contained in the Guides for Proper Use o f System
Smoke Detectors, which are made available at no charge to all
installing dealers. These documents can be found at http://
www.systemsensor.com/html/applicat.html. A study by the
Federal Emergency Management Agency (an agency of the
United States government) indicated that smoke detectors
may not go off in as many as 35% of all fires. While fire al arm
systems are designed to provide early warning against fire,
they do not guarantee warning or protection against fire. A fire
alarm system may not provide timely or adequate warning, or
simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behi nd walls, on
roofs, or on the other side of closed doors. Smoke detectors
also may not sense a fire on another level or floor of a building.
A second-floor detector, for example, may not sense a firstfloor or basement fire.
Particles of combustion or “smoke” from a developing fire
may not reach the sensing chambers of smoke detectors
because:
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow.
• Smoke particles may become “cold,” stratify, and not reach
the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air
outlets.
• Smoke particles may be drawn into air returns before
reaching the detector.
The amount of “smoke” present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm at
various levels of smoke density. If such density levels are not
created by a developing fire at the location of detectors, the
detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing
limitations. Detectors that have photoelectronic sensing
chambers tend to detect smoldering fires better than flaming
fires, which have little visible smoke. Detectors that have ion
izing-type sensing chambers tend to detect fast-flaming fires
better than smoldering fires. Because fires d evelop in dif ferent
ways and are often unpredictable in their growth, neither type
of detector is necessarily best and a given type of detector
may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and violent
explosions (caused by escaping gas, improper storage of
flammable materials, etc.).
Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors incre ases at a predete r
mined rate or reaches a predetermined level. Rate-of-rise
heat detectors may be subject to reduced sensitivity over t ime.
For this reason, the rate-of-rise feature of each detector
should be tested at least once per year by a qualified fire pro
tection specialist. Heat detectors are designed to protect
property, not life.
IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by the sys
tem for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so
located, a developing fire may damage the alarm system, crip
pling its ability to report a fire.
Audible warning devices such as bells may not alert people
if these devices are located on the other side of closed or
partly open doors or are located on another floor of a building .
Any warning device may fail to alert people with a disability or
those who have recently consumed drugs, alcohol or medica
-
tion. Please note that:
• Strobes can, under certain circumstances, cause seizures
in people with conditions such as epilep sy.
• Studies have shown that certain people, even when they
hear a fire alarm signal, do not respond or comprehend the
meaning of the signal. It is the property owner's responsi
bility to conduct fire drills and other training exercise to
make people aware of fire alarm signals and instruct them
on the proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can
cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical
power. If AC power fails, the system will operate from st and by
batteries only for a specified time and only if the batteries have
been properly maintained and replaced regularly.
Equipment used in the system may not be technically compatible with the control panel. It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a
premise to a central monitoring station may be out of service
or temporarily disabled. For added protection against tele
phone line failure, backup radio transmission systems are recommended.
The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in
excellent working order, ongoing maintenance is required per
the manufacturer's recommendations, and UL and NFPA stan
dards. At a minimum, the requirements of NFPA 72 shall be
followed. Environments with large amounts of dust, dirt or
high air velocity require more frequent maintenance. A main
tenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled
monthly or as required by National and/or local fire codes and
should be performed by authorized professional fire alarm
installers only. Adequate written records of all inspections
should be kept.
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be
connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associ
ated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is
energized. Do not attempt to install, service, or operate this
unit until manuals are read and understood.
CAUTION - System Re-acceptance Test after Software
Changes: To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any pro
gramming operation or change in site-specific software. Reacceptance testing is required after any change, addition or
deletion of system components, or after any modification,
repair or adjustment to system hardware or wiring. All compo
nents, circuits, system operations, or sof tware functions known
to be affected by a change must be 100% tested. In addit ion,
to ensure that other operations are not inadvertently affected,
at least 10% of initiating devices that are not directly affected
by the change, up to a maximum of 50 devices, must also be
tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49º
C/32-120º F and at a relative humidity 93% ± 2% RH (non
condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful
life of the system's standby batteries and the electronic com
ponents may be adversely affected by extreme temperature
ranges and humidity. Therefore, it is recommended that this
system and its peripherals be installed in an environment with
a normal room temperature of 15-27º C/60-80º F.
Verify that wire sizes are adequate for all initia ting and indicating device loops. Most devices cannot tol erate more than a
10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subject ed to light
ning induced transients. Although no system is completely
immune from lightning transients and interference, proper
grounding will reduce susceptibility. Overhead or outside aerial
wiring is not recommended, due to an increased susceptibility
to nearby lightning strikes. Consult with the Technical Ser
vices Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or
inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure. When possible, make
all cable entries from the sides or rear. Before making modifi
cations, verify that they will not interfere with battery, transformer, or printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Overtightening may damage threads, resulting in reduced terminal
contact pressure and difficulty wit h screw terminal removal.
This system contains static-sensitive components.
Always ground yourself with a proper wrist strap before han
dling any circuits so that static charges are removed from the
body. Use static suppressive packaging to protect electronic
assemblies removed from the unit.
Follow the instructions in the inst al lati on, opera ting, and pr ogramming manuals. These instructions must be followed to
avoid damage to the control panel and associated equipment.
FACP operation and rel iability depend upon prop er inst allatio n.
Precau-D1-9-2005
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual may
cause interference to radio communications. It has been
tested and found to comply with the limits for class A
computing devices pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when devices are
operated in a commercial environment. Operation of this
equipment in a residential area is likely to cause interference, in which case the user will be required to correct
the interference at his or her own expense.
Canadian Requirements
This digital apparatus does not exce ed the Class A limit s
for radiation noise emissions from digital apparatus set
out in the Radio Interference Regulations of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits
radioelectriques depassant les limites applicables aux
appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edict e p ar l e
ministere des Communications du Canada.
HARSH™, NIS™, and NOTI•FIRE•NET™ are all trademarks; and Acclimate® Plus, FlashScan®, NION®, NOTIFIER®, ONYX®, ONYXWorks®, UniNet®,
VeriFire®, and VIEW® are all registered trademarks of Honeywell International Inc.HARSH™, NIS™, and NOTI•FIRE•NET™ are all trademarks; and
Acclimate® Plus, FlashScan®, NION®, NOTIFIER®, ONYX®, ONYXWorks®, UniNet®, VeriFire®, and VIEW® are all registered trademarks of Honeywell
International Inc. Echelon® is a registered trademark and LonWorks™ is a trademark of Echelon Corporation. ARCNET® is a registered trademark of
Datapoint Corporation. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation.
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make
frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest
features, we strongly recommend that you download the most current version of software for each product prior to
commissioning any system. Contact T echnical Support with any questions about software and the appropriate version for
a specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about
our online Help or printed manuals, you can email us.
Please include the following information:
•Product name and version number (if applicable)
•Printed manual or online Help
•Topic Title (for online Help)
•Page number (for printed manual)
•Brief description of content you think should be improved or corrected
•Your suggestion for how to correct /improve documentation
Send email messages to:
FireSystems.TechPubs@honeywell.com
Please note this email address is for documentation feedback only. If you have any technical issues, please contact
Technical Services.
Section 1: General Information................................................................................................8
1.1: UL 864 Compliance.......................................................................................................................................8
1.2: About This Manual........................................................................................................................................8
1.2.1: Cautions and Warnings........................................................................................................................8
1.2.4: Shortcuts to Operating Functions......................................................................................................10
1.3: Introduction to the Control Panel ................................................................................................................10
Section 2: Use of the Controls...............................................................................................11
2.2: System Status Indicator LEDs.............................................................. .. .....................................................11
2.3: Control Keys................................................................................................................................................12
2.3.2: Signal Silence....................................................................................................................................13
2.3.3: System Reset .....................................................................................................................................13
3.2: Normal Mode of Operation .........................................................................................................................16
3.3: Fire Alarm Mode of Operation....................................................................................................................17
3.3.1: How the Control Panel Indicates a Fire Alarm..................................................................................17
3.3.2: How to Respond to a Fire Alarm.......................................................................................................17
3.3.3: Interpreting Fire Alarm Type Codes .................................................................................................18
3.4: System Trouble Mode of Operation ............................................................................................................19
3.4.1: How the Control Panel Indicates a System Trouble..........................................................................19
3.4.2: How to Respond to a System Trouble...............................................................................................20
3.5: Security Alarm Mode of Operation.............................................................................................................21
3.5.1: How the Control Panel Indicates a Security Alarm...........................................................................21
3.5.2: How to Respond to a Security Alarm................................................................................................22
3.5.3: Interpreting Security Type Codes......................................................................................................22
3.6: Active Supervisory Signal Mode of Operation ...........................................................................................22
3.6.1: How the Control Panel Indicates an Active Supervisory ..................................................................22
3.6.2: How to Respond to an Active Supervisory .......................................................................................23
3.6.3: How to Interpret Supervisory Type Codes........................................................................................24
3.7: Pre-Alarm Warning Mode of Operation......................................................................................................24
3.7.1: How the Control Panel Indicates a Pre-Alarm Warning ...................................................................24
3.7.2: How to Respond to a Pre-Alarm Warning.........................................................................................25
3.8: Disabled Points Mode of Operation ............................................................................................................26
3.9: Non-Alarm Mode of Operation ...................................................................................................................26
3.9.1: Purpose of Non-Alarm Points............................................................................................................26
3.9.2: How the Control Panel Indicates an Active Fire Control..................................................................27
3.9.3: How the Control Panel Indicates an Active Non-Fire Point .............................................................27
3.10: CO Alarm Mode of Operation...................................................................................................................27
3.10.1: How the Control Panel Indicates a CO Alarm ................................................................................27
3.10.2: How to Respond to a CO Alarm......................................................................................................28
3.10.3: Interpreting CO Alarm/Supervisory Type Codes............................................................................28
3.11: Active Trouble Monitor Mode of Operation..............................................................................................29
3.11.1: How the Control Panel Indicates an Active Trouble Monitor .........................................................29
3.11.2: How to Respond to an Active Trouble Monitor..............................................................................29
3.12: Output Circuit Trouble Mode of Operation...............................................................................................30
4.2: What is Read Status?........................ .................................. .................................. ........................................34
A.2: Releasing Zones (R0-R9)............................................................................................................................49
A.2.1: Purpose of Releasing Zones..............................................................................................................49
A.2.2: How to View Releasing Zone Selections .........................................................................................50
A.2.3: How Releasing Zones Operate .........................................................................................................50
A.3: Time, Date, and Holiday Functions............................................................................................................52
C.1: General Description.....................................................................................................................................60
C.3: Using the CRT-2 for Read Status ................................................................................................................62
C.3.4: Display Devices in Alarm or Trouble...............................................................................................63
C.3.5: Display All Programmed Points .......................................................................................................64
C.3.6: Step-through History .........................................................................................................................64
C.3.7: View All History...............................................................................................................................64
C.3.8: Step-through Alarm History .............................................................................................................64
C.3.9: View All Alarm History....................................................................................................................64
C.4: Using the CRT-2 for Alter Status ................................................................................................................65
C.4.6: Clear the Entire History Buffer................................. .. ......................................................................67
C.4.7: Set the Pre-Alarm for Alert or Action...............................................................................................67
Appendix D: Point and System Troubles Lists....................................................................68
D.1: Point (Device) Troubles ..............................................................................................................................68
D.2: System Troubles..........................................................................................................................................69
This product has been certified to comply with the requirements in the Standard for Control Units
and Accessories for Fire Alarm Systems, UL 864 9th Edition.
1.2 About This Manual
1.2.1 Cautions and Warnings
This manual contains cautions and warnings to alert the reader as follows:
CAUTION:
Information about procedures that could cause programming errors, runtime errors, or equipment
damage.
WARNING:
Indicates information about procedures that could cause irreversible damage to the control panel,
irreversible loss of programming data or personal injury.
1.2.2 Typographic Conventions
This manual uses the following typographic conventions as listed in below:
When you seeSpecifiesExample
text in small capsthe text as it appears in the
LCD display or on the control
panel
text in quotesa reference to a section or a
LCD menu screen
bold textIn body text, a number or
character that you enter
italic texta specific documentNFS2-640 Installation Manual
a graphic of the keyIn a graphic, a key as it
appears on the control panel
Table 1.1 Typographic Conventions in this Manual
NOTE: In this manual, the term NFS2-640 is used to refer to the NFS2-640 and NFS2-640E
unless otherwise noted.
MARCHTIME is a selection that appears in the
LCD display; or Press the
“Read Status”; specifies the Read S tatus section
or menu screen
Press 1; means to press the number “1” on the
keypad
The table below provides a list of documents referenced in this manual, as well as documents for
selected other compatible devices. The document series chart (DOC-NOT) provides the current
document revision. A copy of this document is included in every shipment.
Compatible Conventional Devices (Non-addressable)Document Number
Device Compatibility Document15378
Fire Alarm Control Panel (FACP) and Main Power Supply InstallationDocument Number
NFS2-640 Installation, Operations, and Programming Manuals52741, 52742, 52743
DVC and DAA Digital Audio Series Manual52411
DAA Digital Audio Amplifier Product Installation Document52410
SLC Wiring Manual51253
Note: For individual SLC Devices, refer to the SLC Wiring Manual
Off-line Programming UtilityDocument Number
VeriFire® Tools CD help file
Veri•Fire Medium Systems Help File
Cabinets & ChassisDocument Number
CAB-3/CAB-4 Series Cabinet Installation Document15330
Battery/Peripherals Enclosure Installation Document50295
Power Supplies, Auxiliary Power Supplies & Battery ChargersDocument Number
T o the left of each program function, you’ll find a keypad shortcut, which contains a
series of keypad entries required to access the program function. All shortcuts start
with the control panel in normal operation.
For example, the keypad shortcut to the left, shows how to enter the Read Status
function with the control panel in normal operation, as well as how to exit the
function.
1.3 Introduction to the Control Panel
The NFS2-640 is a modular, intelligent Fire Alarm Control Panel (F ACP) with features su itable for
most applications. Following is a list of operating features available.
•Alarm Verification selection, to reduce unwanted alarms, for intell igent detector points
•Positive Alarm Sequence (PAS) and Presignal per NFPA 72
•Silence Inhibit timer and Auto Silence timer for Notification Appliance Circuits (NACs)
•March time/temporal code for Notification Appliance Circuits (NACs)
•Programmable Signal Silence, System Reset, and Alarm Activate functions through monitor
modules
•Automatic time-of-day and day-of-week control functions, with holiday option
•Intelligent Sensing with nine field-adjustable Pre-Alarm levels with programmable
Control-By-Event (CBE)
•Operate automatic smoke or heat detector sounder base on action Pre-Alarm level, with
general evacuation on alarm level
•Security alarm point option with separate audible signal code
•Centralized voice paging and audible alarm signaling options
•Programmable Control-By-Event control of outputs from individual alarm or supervisory
addressable devices
•Networks with other FACPs and equipment for large applications.
You can also press this key to display multiple alarms or troubles. If more than one alarm or trouble
exists, the control panel displays the next alarm or trouble for 3 seconds (or until you press the
ACKNOWLEDGE/SCROLLDISPLAYkey), then displays the next alarm or trouble.
NOTE: If Local Control is set to “0” (No Control), the FACP will not respond to ACKNOWLEDGE,
and the piezo will not sound.
2.3.2 Signal Silence
Use the SIGNALSILENCE key to silence the panel sounder and turn off all audio and visual devices
connected to Notification Appliance Circuits. When pressed, the control panel does the following:
•Turns off the panel sounder
•Turns off all silenceable output circuits
•Lights the SIGNALSSILENCED LED
•Sends a SIGNALSSILENCEDmessage to the History buffer and installed printers, CRT-2
terminals, and FDU-80 annunciators
Partial Signal Silence
When some active outputs are silenced and others remain constant, the SIGNALSSILENCED LED
will flash.
NOTE: If Local Control is set to “0” (No Control) or “2” (Partial Control), the FACP will not
respond to SIGNALSILENCE.
2.3.3 System Reset
Use the SYSTEMRESET key to reset the control panel. When pressed, the control panel does the
following:
•Clears ALL active inputs
•Interrupts resettable power
•Sends a “System Reset” message to the History buffer, and installed printers, CRT-2 terminals,
and FDU-80 annunciators
•Decouples from Noti•Fire•Net, if connected, for 60 seconds to allow Cooperative Control By
Event (CCBE) to clear.
If any alarm or trouble exists after you press the SYSTEMRESET key, all NACs, contr ol output s, and
panel audio and visual indicators will reactivate.
NOTE: Trouble conditions will not clear and re-report upon reset.
NOTE: If Local Control is set to “0” (No Control), the FACP will not respond to SYSTEMRESET.
2.3.4 Drill
Use the DRILL key to manually activate all silenceable outputs and Notification Appliance Circuits.
To prevent accidental activation, you must press the
control panel does the following:
This section contains instructions for operating the control panel. Listed below are the topics
detailed in this section:
SectionRefer to Page
3.2, "Normal Mode of Operation"page 16
3.3, "Fire Alarm Mode of Operation"page 17
3.4, "System Trouble Mode of Operation"page 19
3.5, "Security Alarm Mode of Operation"page 21
3.6, "Active Supervisory Signal Mode of Operation"page 22
3.7, "Pre-Alarm Warning Mode of Operation"page 24
3.8, "Disabled Points Mode of Operation"page 26
3.9, "Non-Alarm Mode of Operation"page 26
3.10, "CO Alarm Mode of Operation"page 27
3.11, "Active Trouble Monitor Mode of Operation"page 29
3.11, "Active Trouble Monitor Mode of Operation"page 29
3.12, "Output Circuit Trouble Mode of Operation"page 30
3.13, "Operation of Special System Timers"page 32
3.14, "Waterflow Circuit Operation"page 33
3.15, "Style 6 and Style 7 Operation"page 33
This manual also contains information on operating the control panel in the appendixes, listed as
follows:
•Appendix A, “Special Zone Operation”, on page 49
•Appendix B, “Intelligent Detector Functions”, on page 58
•Appendix C, “Remote Terminal Access”, on page 60
•Appendix D, “Point and System Troubles Lists”, on page 68
WARNING:
When used for CO2 releasing applications, observe proper precautions as stated in NFPA 12. Do not
enter the protected space unless physical lockout and other safety procedures are fully completed.
Do not use software disable functions in the panel as lockout.
3.2 Normal Mode of Operation
The system operates in Normal mode when no alarms or troubles exist. In Normal mode, the
control panel displays a System Normal message as follows
•Sends an Alarm message to the LCD display, remote annunciators, History buffer, installed
printers, and CRT-2s.
•Latches the control panel in alarm. (You can not return the control panel to normal operation
until you correct the alarm condition and reset the control panel)
•Initiates any Control-By-Event actions
•Starts timers (such as Silence Inhibit, Auto Silence)
•Activates the general alarm zone (Z00)
3.3.2 How to Respond to a Fire Alarm
If the control panel indicates a fire alarm, you can do the following:
•To silence only the panel sounder:
Press the ACKNOWLEDGE/SCROLLDISPLAY key. The local sounder will silence and the FIRE
ALARM LED will change from flashing to steady.
The control panel will send an acknowledge message to the LCD display, remote annunciators,
history buffer, installed printers, and CRT-2s.
Operation of the Control PanelFire Alarm Mode of Operation
Status banner
Time and date of the
Alarm Silenced
SIGNALS SILENCED
03:12P 041508 Tue
•To silence the panel sounder and any activated outputs that are programmed as silenceable:
Press the SIGNALSILENCE key . The FIREALARM LED and SIGNALSSILENCED LED light steady.
The control panel sends an Signal Silenced message to the remote annunciators, history buffer,
installed printers, and CRT-2s. The figure below shows a sample Alarm Silenced message.
Figure 3.3 Sample Alarm Silenced Message
1.Check the Alarm message for the location and type of trouble.
2.Correct the condition causing the alarm.
3.When you finish correcting the alarm condition, press the SYSTEMRESET key to return the
control panel to normal operation (indicated by the “System Normal” message). The control
panel sends a “System Normal” message to the LCD display, History buffer and installed
printers, FDU-80 annunciators, and CRT-2s.
3.3.3 Interpreting Fire Alarm Type Codes
The Type Code that displays in the Alarm message indicates the function of the point that initiates
the fire alarm. For example, a monitor module with a
PULLSTATION Type Code means that the
monitor module connects to a manual pull station. The table below lists the Type Codes that can
Type Code
appear in an alarm message:
Latching
(Y/N)
PurposeWhat it does
Monitor Modules
BlankYIndicates activation of a device with no descriptionLights FIREALARM LED and activates CBE
HEAT DETECTYIndicates activation of a conventional heat detectorLights FIREALARM LED and activates CBE
MONITORYIndicates activation of an alarm-monitoring deviceLights FIREALARM LED and activates CBE
PULL STATIONYIndicates activation of a manual fire-alarm-activating
device, such as a pull station.
RF MON MODULYIndicates activation of a wireless alarm-monitoring device Lights FIREALARM LED and activates CBE
RF PULL STAYIndicates activation of a wireless manual fire-alarm-
activating device, such as a pull station
SMOKE CONVENYIndicates activation of a conventional smoke detector
attached to an FZM-1
SMOKE DETECTYIndicates activation of a conventional smoke detector
attached to an FZM-1
WATERFLOWYIndicates activation a waterflow alarm switchLights FIREALARM LED and activates CBE
EVACUATE SWNPerforms Drill function.Activates all silenceable outputs
MAN. RELEASEYIndicates activation of a monitor module programmed to a
releasing zone to perform a releasing function.
MANREL DELAYYIndicates activation of a monitor module programmed for
a release output
SECOND SHOTNProvides second activation of releasing zone after soak
timer has expired.
CO MONITOR*YIndicates activation of a CO conventional detectorActivates CBE, does not light an indicator
System Trouble Mode of OperationOperation of the Control Panel
Type Code
SMOKE(ION)YIndicates activation of an ion smoke detectorLights FIREALARM LED and activates CBE
SMOKE(DUCT I)YIndicates activation of a duct ion smoke detectorLights FIREALARM LED and activates CBE
SMOKE(PHOTO)YIndicates activation of a photo smoke detectorLights FIREALARM LED and activates CBE
RF_PHOTOYIndicates activation of a wireless photoelectric smoke
SMOKE(DUCTP)YIndicates activation of a duct photo smoke detectorLights FIREALARM LED and activates CBE
SMOKE(HARSH)*YIndicates activation of a HARSH smoke detectorLights FIREALARM LED and activates CBE
SMOKE(LASER)YIndicates activation of a laser smoke detectorLights FIREALARM LED and activates CBE
SMOKE(DUCTL)YIndicates activation of a duct laser smoke detectorLights FIREALARM LED and activates CBE
SMOKE(BEAM)YIndica tes activation of a beam smoke detectorLights FIREALARM LED and activates CBE
SMOKE(DUCTL)YIndicates activation of a duct laser smoke detectorLights FIREALARM LED and activates CBE
AIR REFYIndicates activation of a laser air reference detector. Lights FIREALARM LED and activates CBE
HEATYIndicates activation of a 190oF intelligent thermal detector Lights FIREALARM LED and activates CBE
HEAT+YIndicates activation of a 190oF adjustable threshold
HEAT(ANALOG)Y135oF intelligent thermal sensorLights FIREALARM LED and activates CBE
HEAT (ROR)Y15oF per minute rate-of-rise detectorLights FIREALARM LED and activates CBE
SMOKE ACCLIMYIndicates activation of detector (Acclimate Plus™, FSC-
SMOKE (ACCL+)YIndicates activation of detector (Acclimate Plus™, FSC-
SMOKE MULTI*YMultisensor smoke detectorLights FIREALARM LED and activates CBE
PHOTO/CO*YIndicates activation of the Photo, Heat, or CO element of a
PHOTO/CO (P SUP)*YIndicates activation of the Photo, Heat or CO element of a
PHOTO/CO (C SUP)*YIndicates activation of the Photo, Heat or CO element of a
*FlashScan only
Latching
(Y/N)
detector
intelligent thermal detector
851 IntelliQuad), without freeze warning
851 IntelliQuad), with freeze warning
detector.
detector.
detector.
PurposeWhat it does
Lights FIREALARM LED and activates CBE
Lights FIREALARM LED and activates CBE
Lights FIREALARM LED and activates CBE
Lights FIREALARM LED and activates CBE
Lights FIREALARM LED for photo and heat,
no LED will light for a CO alarm. Photo and
heat will activate CBE, CO alarm activates
special function zone FC and sixth CBE
zone only (sixth CBE zone programmable
via VeriFire Tools)
Lights FIREALARM LED for heat, no LED will
light for a CO alarm, supervisory LED will
light for photo alarm, heat and photo will
activate CBE, CO alarm activates special
function zone FC and sixth CBE zone only
(sixth CBE zone programmable via VeriFire
Tools)
Lights FIREALARM LED for heat and photo
alarms, will light supervisory LED for CO
alarm, photo and heat alarms will activate
CBE, CO alarm will activate sixth CBE
zone only (sixth CBE zone programmable
via VeriFire Tools)
Table 3.1 Fire Alarm Type Codes (2 of 2)
3.4 System Trouble Mode of Operation
3.4.1 How the Control Panel Indicates a System Trouble
The system goes into system trouble when the control panel detects an electrical fault. If no fire
alarms exist, the control panel does the following:
•Displays a Type Code that indicates the type of device with a trouble.
•Displays TROUBL in the status banner on the LCD display as well as the type of trouble and
information specific to the device, as shown in
Figure 3.4 below.
•Sends a Trouble message to the LCD display, remote annunciators, history buffer, installed
printers, and CRT-2s.
NOTE: If a fire alarm exists when a trouble exists, the SYSTEMTROUBLE LED lights, but the Alarm
message appears in the LCD display.
Typical Trouble message that appears on the LCD display:
Figure 3.4 Sample Trouble Message
3.4.2 How to Respond to a System Trouble
If the control panel indicates a trouble, you can do the following:
1.Press the ACKNOWLEDGE/SCROLLDISPLAY key to silence the panel sounder and switch the
SYSTEMTROUBLE LED from flashing to steady—regardless of the number of troubles, alarms,
security and supervisory signals.
NOTE: Pressing the SIGNALSILENCE key when only troubles exist, gives the same result as
pressing the ACKNOWLEDGE/SCROLLDISPLAY key. The SIGNALSSILENCED LED does not light unless
an alarm exists in the system.
2.The control panel sends an Acknowledge message to the remote annunciators, history buffer,
installed printers, and CRT-2s.
Figure 3.5 Sample Acknowledge Message
3.Check the trouble message for the location and type of trouble.
Figure 3.6 Sample Trouble Messages on CRT-2 or Printer
4.Correct the condition causing the trouble. If the trouble clears, the control panel sends a Clear
Trouble message to the History buffer and installed printers FDU-80 annunciators, and
CRT-2s.
If all troubles clear and no supervisory signals or fire alarms exist, the control panel does the
following:
Security Alarm Mode of OperationOperation of the Control Panel
ACTIVE SECURITY INTENSIVE CARE UNIT
EASTERN WING Z004 03:17P 041508 2M147
Status Banner
Type Code
Custom descriptor for
this device location
Device address
Time and date of trouble
Zone
•Returns to Normal operation (indicated by the “System Normal” message)
•Sends a “System Normal” message to the LCD display, History buffer and installed printers,
FDU-80 annunciators, and CRT-2s
•Restores troubles automatically - even if troubles are not acknowledged
If multiple trouble conditions exist in the system, the LCD and optional CRT-2 and FDU-80s
automatically step through each trouble every 3 seconds in the following order:
1.Alarms, in order of address
2.Supervisory, in order of address
3.Troubles, in order of address
Press the ACKNOWLEDGE/SCROLLDISPLAY key and the display stops on the current trouble event
for 1 minute, then begins to automatically step through remaining troubles. To manually step
through remaining troubles, press the
ACKNOWLEDGE/SCROLLDISPLAY key.
Refer to Appendix D, “Point and System Troubles Lists”, on page 68 for explanations of troubles
that appear on the display.
3.5 Security Alarm Mode of Operation
3.5.1 How the Control Panel Indicates a Security Alarm
The system goes into Security mode when a monitor module point programmed with a Security
Type Code activates. If no fire alarm exists, the control panel does the following:
•Produces a warbling audible tone
•Turns on the Security relay (TB5)
•Flashes the SECURITY LED (blue)
•Displays a Type Code that indicates the type of security alarm being generated
•Displays ACTIVE in the status banner on the control panel, along with information specific to
the device
•Sends a Security message to the LCD display, remote annunciators, history buffer, installed
printers, and CRT-2s.
•Sends a Security message to the proprietary receiver via the network, if applicable.
NOTE: If a fire alarm exists, and there are silenced alarms (the SIGNALSSILENCED LED is
lighted), a Security alarm will resound the panel sounder.
A Typical security message that appears on LCD display:
Operation of the Control PanelActive Supervisory Signal Mode of Operation
3.5.2 How to Respond to a Security Alarm
A Security Type Code latches the control panel. To return the control panel to normal operation,
you must correct the condition causing the security condition, then reset the control panel. If the
control panel indicates a security alarm, take the following action:
NOTE: If a fire alarm exists, and there are silenced alarms (the SIGNALSSILENCED LED is
lighted), a Security alarm will resound the panel sounder.
1.Press the ACKNOWLEDGE/SCROLL display key to silence the panel sounder and switch the
SECURITY LED from flashing to steady—regardless of the number of troubles, alarms,
supervisory, and security signals. The control panel sends a Security message to the remote
annunciators, history buffer, installed printers, and CRT-2s.
2.Correct the condition that activated the Security point.
3.When you finish correcting the Security condition, press the SYSTEMRESET key to return the
control panel to normal operation (indicated by the “System Normal” message). The control
panel sends a “System Normal” message to the LCD display, remote annunciators, history
buffer, installed printers, and CRT-2s.
3.5.3 Interpreting Security Type Codes
The Type Code that displays in the security alarm message indicates the type of security alarm
being generated by the monitor module that initiates the alarm. For example, a monitor module
with a Type Code of
AREAMONITOR indicates an intruder in a protected premises area. The table
below lists the Type Codes that can appear in a security alarm message.
Monitor Modules
Type Code
AREA MONITORYMonitors area surveillance equipment, such
SECURITYYMonitors security switches for tamperingLights SECURITY LED, activates CBE
SYS MONITORYMonitors critical equipment for securityLights SECURITY LED, activates CBE
Latching
(Y/N)
PurposeWhat it does
Lights SECURITY LED, activates CBE
as motion detectors
Table 3.2 Security Type Codes
3.6 Active Supervisory Signal Mode of Operation
3.6.1 How the Control Panel Indicates an Active Supervisory
The system goes into Supervisory mode when a monitor module point programmed with a
Supervisory type code activates. When a Supervisory point activates, the control panel does the
following:
•Produces a warbling audible tone
•Turns on the Supervisory relay (TB5)
•Flashes the SUPERVISORY LED (yellow)
•Displays one of the Type Codes listed in Table 3.3.
•Displays ACTIVE in the status banner on the control panel, along with information specific to
the device
Active Supervisory Signal Mode of OperationOperation of the Control Panel
ACTIVE TAMPER INTENSIVE CARE UNIT
EASTERN WING Z004 03:19P 041508 2M147
Status Banner
Type Code
Custom descriptor for
this device location
Device address
Time and date of trouble
Zone
Extended 12 character
custom label
•Sends a Supervisory message to the LCD display, remote annunciators, history buffer, installed
printers, and CRT-2s.
NOTE: If a fire alarm exists, and there are silenced alarms (the SIGNALSSILENCED LED is
lighted), a Supervisory alarm will resound the panel sounder.
A Typical Supervisory message that appears on LCD display:
Figure 3.8 Sample Supervisory Signal Message
3.6.2 How to Respond to an Active Supervisory
If a Latching Supervisory Type Code Displays
Some Supervisory Type Codes latch the control panel (Refer to Table 3.3 for a list of these type
codes). To return the control panel to normal operation, you must correct the condition causing the
supervisory condition, then reset the control panel. Take the following action:
NOTE: If a fire alarm exists, and there are silenced alarms (the SIGNALSSILENCED LED is
lighted), a Supervisory alarm will resound the panel sounder.
1.Press the ACKNOWLEDGE/SCROLL DISPLAY key to silence the panel sounder and switch the
SUPERVISORY LED from flashing to steady—regardless of the number of troubles, alarms, and
supervisory signals. The control panel sends a Supervisory message to the remote
annunciators, history buffer, installed printers, and CRT-2s.
2.Correct the condition that activated the supervisory point.
3.When you finish correcting the latching supervisory condition, press the SYSTEMRESET key to
return the control panel to normal operation (indicated by the “System Normal” message). The
control panel sends a “System Normal” message to the LCD display, remote annunciators,
history buffer, installed printers, and CRT-2s.
If Non-latching Type Code Displays
Some Supervisory Type Codes do not latch the control panel. (Refer to Table 3.3 for a list of these
type codes). The control panel automatically returns to normal operation, when you correct the
condition that activates the supervisory point. If the control panel indicates a non-latching
supervisory point, take the following action:
NOTE: If a fire alarm exists, and there are silenced alarms (the SIGNALSSILENCED LED is
lighted), a Supervisory alarm will resound the panel sounder.
1.Press the ACKNOWLEDGE/SCROLLDISPLAY key to silence the panel sounder and switch the
SUPERVISORY LED from flashing to steady—regardless of the number of troubles, alarms, and
supervisory signals. The control panel sends a Supervisory message to the remote
annunciators, history buffer, installed printers, and CRT-2s.
2.Correct the condition that activated the supervisory point.