Notifier NDM-100P User Manual

Monitor Modules
NMM-100(A) (Type H)
6999cov.jpg
NMM-100(A), NMM-100P(A), NZM-100(A), and NDM-100(A) for FireWarden Series Panels
General
NMM-100(A) is a standard-sized module (typically mounts to a 4" [10.16 cm] square box) that supervises either a Style D (Class A) or Style B (Class B) circuit of dry-contact input devices.
NMM-100P(A) is a miniature monitor module a mere 1.3" (3.302 cm) H x 2.75" (6.985 cm) W x 0.5" (1.270 cm) D that supervises a Style B (Class B) circuit of dry-contact input devices. Its compact design allows the NMM-100P(A) to be mounted in a single-gang box behind the device it monitors.
NZM-100(A) is a standard-sized module that monitors and supervises compatible two-wire, 24 volt, smoke detectors on a Style D (Class A) or Style B (Class B) circuit.
NDM-100(A) is a standard-sized dual monitor module that monitors and supervises two independent two-wire Style B (Class B) dry-contact initiating device circuits (IDCs) at two separate, consecutive addresses in intelligent, two-wire systems.
NMM-100(A) Monitor Module
• Built-in type identification automatically identifies this device as a monitor module to the control panel.
• Powered directly by two-wire SLC loop. No additional power required.
• High noise (EMF/RFI) immunity.
• SEMS screws with clamping plates for ease of wiring.
• Direct Decade entry of address: 01 – 99 on FireWarden­100-2, 01 – 50 on FireWarden-50.
• LED flashes during normal operation and latches on steady to indicate alarm.
The NMM-100(A) Monitor Module is intended for use in intelli­gent, two-wire systems, where the individual address of each module is selected using the built-in rotary switches. It pro­vides either a two-wire or four-wire fault-tolerant Initiating Device Circuit (IDC) for normally-open-contact fire alarm and supervisory devices. The module has a panel-controlled LED indicator.
NMM-100(A) APPLICATIONS
Use to monitor a zone of four-wire smoke detectors, manual fire alarm pull stations, waterflow devices, or other normally­open dry-contact alarm activation devices. May also be used to monitor normally-open supervisory devices with special supervisory indication at the control panel. Monitored circuit may be wired as an NFPA Style B (Class B) or Style D (Class A) Initiating Device Circuit. A 47K ohm End-of-Line Resistor (provided) terminates the Style B circuit. No resistor is required for supervision of the Style D circuit.
DN-6999:C
Intelligent Addressable Devices
NMM-100(A) OPERATION
Each NMM-100(A) uses one of the available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/nor­mal/short) of its Initiating Device Circuit (IDC). A flashing LED indicates that the module is in communication with the control panel. The LED latches steady on alarm (subject to current limitations on the loop).
NMM-100(A) SPECIFICATIONS
Nominal operating voltage: 15 to 32 VDC.
Maximum current draw: 5.0 mA (LED on).
Average operating current: 350 μA (LED flashing), 1 com-
munication every 5 seconds, 47k EOL.
Maximum IDC wiring resistance: 40 ohms.
EOL resistance: 47K ohms.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x
2.125" (5.398 cm) deep box.
DN-6999:C • 10/06/2010 — Page 1 of 4
NMM-100P(A) Mini Monitor Module
6720m101.wmf
• Built-in type identification automatically identifies this device as a monitor module to the panel.
• Powered directly by two-wire SLC loop. No additional power required.
• High noise (EMF/RFI) immunity.
• Tinned, stripped leads for ease of wiring.
• Direct Decade entry of address: 01 – 99 on FireWarden­100-2, 01 – 50 on FireWarden-50.
Dimensions: 1.3" (3.302 cm) high x 2.75" (6.985 cm) wide x
0.65" (1.651 cm) deep.
Wire length: 6" (15.24 cm) minimum.
NZM-100(A) Interface Module
• Supports compatible two-wire smoke detectors.
• Supervises IDC wiring and connection of external power source.
• High noise (EMF/RFI) immunity.
• SEMS screws with clamping plates for ease of wiring.
• Direct Decade entry of address:, 01 – 99 on FireWarden­100-2, 01 – 50 on FireWarden-50.
• LED flashes during normal operation.
• LED latches steady to indicate alarm on command from control panel.
The NZM-100(A) Interface Module is intended for use in intelli­gent, addressable systems, where the individual address of each module is selected using built-in rotary switches. This module allows intelligent panels to interface and monitor two­wire conventional smoke detectors. It transmits the status (nor­mal, open, or alarm) of one full zone of conventional detectors back to the control panel. All two-wire detectors being moni­tored must be UL compatible with the module.
NZM-100(A) APPLICATIONS
Use the NZM-100(A) to monitor a zone of two-wire smoke detectors. The monitored circuit may be wired as an NFPA
The NMM-100P(A) Mini Monitor Module can be installed in a single-gang junction directly behind the monitored unit. Its small size and light weight allow it to be installed without rigid mounting. The NMM-100P(A) is intended for use in intelligent, two-wire systems where the individual address of each module is selected using rotary switches. It provides a two-wire initiat­ing device circuit for normally-open-contact fire alarm and security devices. NMM-100P(A)
NMM-100P(A) APPLICATIONS
Use to monitor a single device or a zone of four-wire smoke detectors, manual fire alarm pull stations, waterflow devices, or other normally-open dry-contact devices. May also be used to monitor normally-open supervisory devices with special super­visory indication at the control panel. Monitored circuit/device is wired as an NFPA Style B (Class B) Initiating Device Circuit. A 47K ohm End-of-Line Resistor (provided) terminates the cir­cuit.
NMM-100P(A) OPERATION
Each NMM-100P(A) uses one of the available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/nor­mal/short) of its Initiating Device Circuit (IDC).
NMM-100P(A) SPECIFICATIONS
Nominal operating voltage: 15 to 32 VDC.
Average operating current: 350 μA, 1 communication every 5 seconds, 47k EOL; 600 μA Max. (Communicating, IDC Shorted).
Maximum IDC wiring resistance: 40 ohms.
Maximum IDC Voltage: 11 Volts.
Maximum IDC Current: 400 μA.
EOL resistance: 47K ohms.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% noncondensing.
Style B (Class B) or Style D (Class A) Initiating Device Circuit. A 3.9 K ohm End-of-Line Resistor (provided) terminates the end of the Style B or D (class B or A) circuit (maximum IDC loop resistance is 25 ohms). Install ELR across terminals 8 and 9 for Style D application.
NZM-100(A) OPERATION
Each NZM-100(A) uses one of the available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/nor­mal/short) of its Initiating Device Circuit (IDC). A flashing LED indicates that the module is in communication with the control panel. The LED latches steady on alarm (subject to current limitations on the loop).
NZM-100(A) SPECIFICATIONS
Nominal operating voltage: 15 to 32 VDC.
Maximum current draw: 5.1 mA (LED on).
Maximum IDC wiring resistance: 25 ohms.
Average operating current: 300 μA, 1 communication and 1
LED flash every 5 seconds, 3.9k eol.
EOL resistance: 3.9K ohms.
External supply voltage (between Terminals T3 and T4):
DC voltage: 24 volts power limited. Ripple voltage: 0.1 Vrms maximum. Current: 90 mA per module maximum.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x
2.125" (5.398 cm) deep box.
Page 2 of 4 — DN-6999:C • 10/06/2010