Notifier NCM-W, NCM-F Installation Documentation

12 Clintonville Road Northford, CT 06472-1653 USA www.notifier.com
NCM Installation Document
Network Communications Module NCM-W, NCM-F
PN 51533:A1 03/27/03 ECN 03-171
1 Product Overview
The Network Communications Module (NCM) provides a means for connecting specific Notifier fire alarm control products to NOTI•FIRE•NET™. There are two types of NCMs available: NCM-W for connecting nodes with twisted-pair wire, and NCM-F for connecting nodes with fiber-optic cable.
1.1 The Network Communications Module for Wire (NCM-W)
Ground Fault Detection Switches and Network End-of-Line Termination Resistor Switches
Diagnostic LEDs
Not used
EF B TERM B
EF A TERM A
SW101
SW103
SW102
SW100
ON OFF
LED101 LED100
B HI
A HI
LED6 LED7
RCDA RCDB
LED4 LED2
STATA STATB
LED3 LED5
RECONPULSE1
LED1 LED8
RESET POWER
LCMATERM
A
OFF
ON
SW1
SW2
Figure 1 NCM-W
Channel A & B
ON OFF
J3 J2
NUP1
NUP2
LCM ALCM B
Connections
Network Connection Ports (NUP)
NCM-w.cdr
• Supports twisted-pair wire medium.
• NFPA Style 4 (Class B) operation or NFPA Style 7 (Class A) operation.
• Two programmable data thresholds.
• Transformer coupling provides electrical isolation between nodes.
• Pluggable terminal wiring with strain relief.
• Pluggable service connector (feeds signal directly through) in the event that power must be removed from a node.
• 312.5 Kbaud transmission rate.
• Data is regenerated at each node.
• Two network ports to allow simultaneous connection to fire alarm control panel and to programming computer
• Enables software and database upload/download over NOTI•FIRE•NET™.
• Refer to the
NOTI•FIRE•NET™
Version 4.0 and Higher) for wiring length and threshold information.
1.2 The Network Communications Module for Fiber (NCM-F)
Diagnostic LEDs
Not used
Channel A & B Connections
Network Connection Ports (NUP)
NCM-f.cdr
Figure 2 NCM-F
• Supports fiber-optic medium.
• NFPA Style 4 (Class B) or Style 7 (Class A) operation.
• Data is immune to all environmental noise.
• Optical isolation prevents ground loops.
NOTI•FIRE•NET™ fiber optic medium.
• Fiber type:
• 62.5/125 micrometers (multimode, 8 dB limit)
• 50/125 micrometers (multimode, 4.2 dB limit)
• Wavelength (1): 820 nanometers. (Use standard 850 nm fiber.)
• Connectors: ST® Style (ST® is a registered trademark of AT & T) .
• 312.5 Kbaud transmission rate.
• Data is regenerated at each node.
• Two network ports to allow simultaneous connection to fire alarm control panel and to programming computer.
• Enables software and database upload/download over NOTI•FIRE•NET™.
Manual (Network
NCM Installation PN 51533:A1 03/27/03
2 Installing the NCM
2.1 Interconnecting the NCM-W
When wiring consecutive NCM-W boards, note that wiring may enter or exit at Port A or Port B as shown in Figure 4. NCM-W port-to-port wiring is not polarity sensitive. The use of Port A or Port B is arbitrary. An NCM-W may be connected to any of the following devices:
• MIB-W
• MIB-WF
• NAM-232W
• NCM-W (in another panel)
• NCS-W network connection
•RPT-W
•RPT-WF
For information regarding these devices, refer to the documentation listed in Table 4 “Supplemental Documentation”.
From last node,
Port A
B
A
To next node,
Port B
B
A
EF B TERM B
SW101
EF A TERM A
SW103
SW102
ON OFF
SW100
ON OFF
EF B TERM B
SW101
SW102
EF A TERM A
SW103
SW100
ON OFF
ON OFF
ote: Wiring from the NCM-W that is installed outside the building:
Cannot exceed 1000m (3280 ft.). Must be in conduit and is to be buried in a trench separate from any power lines. Cannot cross any power lines.
Figure 3 The NCM-W
TB100-1 CH-A (+) Channel-A Driver/Receiver
TB100-2 CH-A (-) Channel-A Driver/Receiver
TB100-3 CH-B (+) Channel-B Driver/Receiver
TB100-4 CH-B (-) Channel-B Driver/Receiver
TB100-5 Earth Ground
Tab le 1 NOTI•FIRE•NET™ Connections: NCM-W
Switch Functions: Ground Fault Detection and Line Termination
The NCM-W provides two sets of switches to simplify network setup; in Figure 4 all are in the “off” position.
• Enable ground fault detection by setting switches “on”: SW103 for Channel A, and SW101 for Channel B.
EF B T ERM B
SW101
SW102
EF A TERM A
ON OFF
SW103
NCM-w-connex.cdr
SW100
ON OFF
• Activate on-board end-of-line resistors by setting switches “on”: SW100 for Channel A; SW102 for Channel B.
Figure 4 NCM-W Switches
Note: Correct configuration depends on your network design; refer to the
NOTI•FIRE•NET™
Manual (Network Version 4.0 and Higher).
2 NCM Installation PN 51533:A1 03/27/03
ncm-w-switches.cdr
2.2 Interconnecting the NCM-F
When connecting consecutive nodes/repeaters, note that fiber cable must exit one board on transmit (TX) and enter the next node/repeater on receive (RX). Also, note that the fiber-optic pair (RX, TX) from port A of one Node/Repeater may be connected to either Port A or Port B of another node/repeater (refer to Figure 5). An NCM-F may be connected to any of the following devices:
• MIB-F
• MIB-WF
• NAM-232F
• Another NCM-F
• Network connection for NCS-F
•RPT-F
•RPT-WF
For information regarding these devices, refer to the NAM-232 and Repeater manuals listed in Table 4 “Supplemental Documentation”.
Note: See the
NOTI•FIRE•NET™
optic cable attenuation.
Manual (Network Version 4.0 and Higher) for maximum fiber-
RXRX
J202
J201
J203
RxB TxATxB RxA
Channel BChannel
J200
A
TXTX
J203
RxB TxATxB RxA
Channel
RXRX
J202
J201
Channel
B
A
Figure 5 NCM-F Connection
J200 CH A Transmit
J201 CH A Receive
J202 CH B Transmit
J203 CH B Receive
Table 2 NOTI•FIRE•NET™ Connections: NCM-F
TXTX
J200
NCM-f-connex.cdr
2.3 Mixing Wire & Fiber on One Network
In some networks, it may be necessary to mix twisted-pair wire and fiber-optic cable. There are two solutions for this situation.
1. In any network, an RPT-WF may be used as an interface between wire and fiber.
2. In a network that uses an AFP1010 or AM2020, a MIB-WF may also be used as the interface
between wire and fiber.
See 1.2 “The Network Communications Module for Fiber (NCM-F)” for requirements and restrictions on the use of fiber optic cable. See the Higher) for a discussion of all compatible configurations.
NCM Installation PN 51533:A1 03/27/03 3
NOTI•FIRE•NET™
Manual (Network Version 4.0 and
3 Diagnostic Indicators
The NCM has LEDs that serve as diagnostic indicators to help in troubleshooting and system connection. Refer to Table 3 for a list of diagnostic indicators and their descriptions. Refer to Figure 6 for location of the diagnostic indicators.
A HI (NCM-W only)
RCD A
STATA
RECON
RESET
B HI
A HI
RCDA RCDB
STATB
STATA
RECON PULSE1
RESET POWER
NCM-LEDS.cdr
B HI (NCM-W only)
RCD B
STATB
PULSE1
POWER
Figure 6 Diagnostic Indicator Locations
LED Indicator LED Color LED Description
A HI (NCM-W only)
B HI (NCM-W only)
RCD A Green Illuminates when the NCM is receiving data from
RCD B Green Illuminates when the NCM is receiving data from
STATA Yellow Illuminates when the NCM has not received valid data from
Green Illuminates to indicate the NCM-W Port A is set for high threshold.
Green Illuminates to indicate the NCM-W Port B is set for high threshold.
NOTI•FIRE•NET™ on Port A.
NOTI•FIRE•NET™ on Port B.
NOTI•FIRE•NET™ on Port A for at least 16 seconds.
STATB Yellow Illuminates when the NCM has not received valid data from
NOTI•FIRE•NET™ on Port B for at least 16 seconds.
RECON Yellow Illuminates when a reconfiguration on NOTI•FIRE•NET™ is in
progress.
PULSE1 Green Illuminates when the NCM is transmitting data to
NOTI•FIRE•NET™.
RESET Yellow Illuminates when the microcontroller fails.
POWER Green Illuminates when +5 VDC is available
Table 3 Diagnostic Indicator Functions and Colors
4 NCM Installation PN 51533:A1 03/27/03
4 Door-Mounting
Both NCM-W and NCM-F can be installed in any panel circuit module position; see your control panel installation manual. Additionally, the NCM-W can be door-mounted on the ADP-4B Dress Panel on a single-space blank plate (BMP-1) for mounting in a CAB-4 Series cabinet.
Note: The module cannot be mounted in the ADP-4B Dress Panel when a front slot of the CHS-4 or CHS-4N is occupied, or when either of the two front right positions of the CHS-M2 is occupied. Always be certain there is enough clearance to close the cabinet door when this installation is used.
Single-space blank plate
Mount a single-space blank plate onto the ADP-4B Dress Panel.
ADP4-door-module.cdr
Fasten module to the plate with four screws (included).
5 Supplemental Documentation
The table below provides a list of document sources (manuals) containing additional information regarding the NCM and products that it can connect to. The NOTIFIER document (DOC-NOT) chart provides the current document revision.
For information on… Refer to… Part No.
Networking NOTI•FIRE•NET™ Manual (for Network Version 4.0 and Higher)
Onyx NCS Network Control Station (for Network Version 4.0 and Higher) NCS Network Control Station (for Network Version 4.0) NFS-640 Installation
Operations
Programming NCA Network Control Annunciator Media Interface Board (MIB) Manual NAM-232 Network Adaptor Module RPT - W/WF/F Repeaters for NOTI•FIRE•NET™
Off-line Programming Utility VeriFire™ Tools CD on-line help file VeriFire-TCD
Compatible Devices Device Compatibility Document 15378
Cabinets & Chassis CAB-3/CAB-4 Series Installation Document
BMP-1 Product Installation Document
Also see your panel’s Installation Manual
Table 4 Supplemental Documentation
51584 51658 51585 51332 51333 51334 51482 50255 50038 50256
15330 51119
Note: For module mounting instructions, refer to the documentation for your control panel
NCM Installation PN 51533:A1 03/27/03 5