Notifier NC-100R User Manual

NC-100(A)
NC-100(A)
7000cov.JPG
Control Module for FireWarden Series Panels
General
The NC-100(A) Addressable Control Module provides NOTI­FIER’s FireWarden Series intelligent control panels a super­vised Class B (Style Y) of Class A (Style Z) circuit for Notification Appliances (horns, strobes, etc.). Addressability allows the NC-100(A) to be activated, either manually or through panel programming, on a select (zone or area of cov­erage) basis.
Features
• Built-in type identification automatically identifies these devices to the control panel.
• Internal circuitry powered directly by two-wire SLC loop. The NC-100(A) module requires power (for horns, strobes, etc.).
• Integral LED “blinks” when communicating, and turns on steady when activated.
• High noise immunity (EMF/RFI).
• The NC-100(A) may be used to switch 24-volt NAC power.
• Wide viewing angle of LED.
• SEMS screws with clamping plates for wiring ease.
• Direct Decade entry of address: 01 – 99 with FireWarden­100-2(C), or 01-50 with the FireWarden-50(C).
Applications
The NC-100(A) is used to switch 24 VDC audible/visual power.
Construction
• The face plate is made of off-white heat-resistant plastic.
• Controls include two rotary switches for direct-dial entry of address setting.
• The NC-100(A) is configured for a single Class B (Style Y) or Class A (Style Z) Notification Appliance Circuit.
Operation
Each NC-100(A) uses one of the module addresses on a SLC loop. It responds to regular polls from the control panel and reports its type and status, including the open/normal/short status of its Notification Appliance Circuit (NAC). The LED blinks with each poll received. On command, it activates its internal relay. The NC-100(A) supervises Class B (Style Y) or Class A (Style Z) notification or control circuits.
Upon code command from the panel, the NC-100(A) will dis­connect the supervision and connect the external power sup­ply in the proper polarity across the load device. The disconnection of the supervision provides a positive indication to the panel that the control relay actually turned ON. The external power supply is always relay-isolated from the com­munication loop so that a trouble condition on the external power supply will never interfere with the rest of the system.
Rotary switches set a unique address for each module. The address may be set before or after mounting. The built-in TYPE CODE (not settable) will identify the module to the con­trol panel.
dn-7000:a2 • A1-360
Addressable
Specifications
Normal operating voltage: 15 to 32 VDC.
Maximum SLC current draw: 6.5 mA (LED on).
Average operating current: 350 μA (LED flashing).
External supply voltage: maximum 80 volts (RMS or DC).
Drain on external supply: 2 mA maximum (using internal
EOL relay).
EOL resistance: 47K ohms.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% non-condensing.
Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x
2.125" (5.398 cm) deep box.
Agency Listings and Approvals
In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult fac­tory for latest listing status.
•FM approved
UL/ULC Listed: file S635.
CSFM approved: file 7300-0028:230.
MEA approved: file 72-01-E Vol. 2.
dn-7000:a2 • 06/17/10 — Page 1 of 2
Made in the U.S. A.
Contact Ratings
Current
Rating
3 A 30 VDC Resistive Non-Coded
2 A 30 VDC Resistive Coded
.9 A 110 VDC Resistive Non-Coded
.9 A 125 VDC Resistive Non-Coded
.5 A 30 VDC
1 A 30 VDC
.3 A 125 VAC
1.5 A 25 VAC
.7 A 70.7 VAC
2 A 25 VAC
Maximum
Vol tag e
Load
Description
Inductive (L/R=5ms)
Inductive (L/R=2ms)
Inductive (PF=0.35)
Inductive (PF=0.35) Non-Coded
Inductive (PF=0.35) Non-Coded
Inductive (PF=0.35) Non-Coded
Application
Coded
Coded
Non-Coded
Product Line Information
NC-100: Intelligent addressable control module.
NC-100(A): Intelligent addressable control module, ULC listed
version.
SMB500: Optional surface-mount backbox.
CB500: Optional control module barrier, required by UL for
separating power-limited and non-power-limited wiring in the same junction box as NC-100(A).
NOTE: For installation instructions, see document I56-2592-001 and refer to the SLC Wiring Manual, document 52304. The NC­100R(A) relay module, previously on this data sheet, is now on DN-60383.
Page 2 of 2 — dn-7000:a2 • 06/17/10
NOTIFIER® is a registered trademark of Honeywell International Inc. ©2010 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Loading...