Notifier NAM-232 User Manual

Network Adaptor Module
www.PDF-Zoo.com
NAM-232
Document 50038 12/29/99 Revision:
PN 50038:F ECN 99-521
F
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system–typically made up of smoke detectors, heat detectors, manual pull stations, audible warn­ing devices, and a fire alarm control with remote notification capability–can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detec­tors be located throughout a protected premise following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guide for Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. A study by the Federal Emer­gency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are de­signed to provide early warning against fire, they do not guar­antee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a build­ing. A second-floor detector, for example, may not sense a first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire may not reach the sensing chambers of smoke detectors be­cause:
• Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not reach the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air outlets.
• Smoke detectors may be drawn into air returns before reaching the detector.
The amount of "smoke" present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ion­izing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in differ­ent ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detec­tor may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of flammable materials, etc.).
Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a prede­termined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire pro­tection specialist.
Heat detectors are designed to protect
property, not life.
IMPORTANT!
Smoke detectors must be installed in the
same room as the control panel and in rooms used by the sys­tem for the connection of alarm transmission wiring, communi­cations, signaling, and/or power.
cated, a developing fire may damage the alarm system, crip­pling its ability to report a fire.
Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol or medica­tion. Please note that:
Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.
Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property owner's responsibil­ity to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals.
In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.
Equipment used in the system may not be technically com­patible with the control. It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against tele­phone line failure, backup radio transmission systems are rec­ommended.
The most common cause of fire alarm malfunction is inade­quate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA stan­dards. At a minimum, the requirements of Chapter 7 of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent mainte­nance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled monthly or as required by National and/ or local fire codes and should be performed by authorized pro­fessional fire alarm installers only. Adequate written records of all inspections should be kept.
If detectors are not so lo-
www.PDF-Zoo.com
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING -
nected to the fire alarm control panel.
of power before servicing. Control unit and associated equip­ment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood.
CAUTION -
Changes.
must be tested in accordance with NFPA 72 Chapter 7 after any programming operation or change in site-specific soft­ware. Reacceptance testing is required after any change, ad­dition or deletion of system components, or after any modifica­tion, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software func­tions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvert­ently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 de­vices, must also be tested and proper system operation veri­fied.
This system meets NFPA requirements for operation at 0-49° C/32-120° F condensing) at 30° C/86° F. However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and all peripherals be installed in an environment with a nomi­nal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.
Several different sources of power can be con-
Disconnect all sources
System Reacceptance Test after Software
To ensure proper system operation, this product
and at a relative humidity of 85% RH (non-
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to light­ning-induced transients. Although no system is completely immune from lightning transients and interferences, proper grounding will reduce susceptibility.
Overhead or outside aerial wiring is not recommended, due to an increased sus­ceptibility to nearby lightning strikes.
cal Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or in­serting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifi­cations, verify that they will not interfere with battery, trans­former, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
Though designed to last many years, system components can fail at any time. This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are re­moved from the body. Use static-suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation by authorized personnel.
Consult with the Techni-
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at his own expense.
www.PDF-Zoo.com
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.
Table of Contents
Section 1 General ...................................................................................................................6
1.1 Related Documentation.......................................................................................................................6
Table 1.1 Related Documentation ..................................................................................................6
1.2 Product Features..................................................................................................................................7
1.3 Installation...........................................................................................................................................7
Figure 1.1 Simplified Local Network Connection to AFP-200 ....................................................7
Figure 1.2 Simplified Remote Network Connection to AFP-200 .................................................7
Figure 1.3 Simplified Local Network Connection to AFP-300/AFP-400 .....................................8
Figure 1.4 Simplified Remote Network Connection to AM2020/AFP1010 .................................8
1.4 Product Description.............................................................................................................................8
1.5 Trouble Conditions/CCBE Messages For AFP-200............................................................................8
1.6 Trouble Conditions/CCBE Messages for AFP-300/AFP-400...........................................................10
1.7 Limitations of the AM2020/AFP1010 with a (NAM-232)...............................................................11
1.8 Trouble Conditions/Messages for AM2020/AFP1010......................................................................11
1.9 Diagnostic Indicators.........................................................................................................................12
Table 1.1 Identifying Indicators ...................................................................................................12
1.10 Configuration Switches...................................................................................................................13
Table 1.2 Configuration Switches ................................................................................................13
Figure 1.5 Network Adaptor Module-Wire (NAM-232W) .........................................................14
Figure 1.6 Network Adaptor Module-Fiber (NAM-232F) ..........................................................15
Section 2 Installing the NAM-232 .......................................................................................16
2.1 Installing the NAM-232 in an AFP-200 Cabinet..............................................................................16
Figure 2.1 Removing the AFP-200 Motherboard to Mount the NAM-232 ................................16
Figure 2.2 Mounting the NAM-232 Without Removing the AFP-200 Cabinet .........................17
2.2 Powering the NAM-232 From the AFP-200.....................................................................................17
Table 2.1 Powering From the AFP-200 .......................................................................................17
Figure 2.3 Powering the NAM-232 From the AFP-200 .............................................................18
2.3 Installing the NAM-232 in the AFP-300/AFP-400...........................................................................18
2.4 Powering the NAM-232 From the MPS-400 Power Supply.............................................................18
Table 2.1 Powering From the MPS-400 .......................................................................................18
Figure 2.4 Powering the NAM-232 From the MPS-400 .............................................................19
2.5 Installing the NAM-232 in an ICA-4/4L Chassis..............................................................................19
Figure 2.5 Mounting the NAM-232 in an ICA-4/4L Chassis .....................................................19
2.6 Installing the NAM-232 in a CHS-4 Chassis....................................................................................20
Figure 2.6 Mounting the NAM-232 in the CHS-4 Chassis .........................................................20
2.7 Powering the NAM-232 From the MPS-24A or MPS-24AE Main Power Supply ..........................20
Table 2.1 Powering From the MPS-24A or MPS-24AE ..............................................................20
2.8 NAM-232 Connections .....................................................................................................................21
Figure 2.7 NAM-232W to NAM-232W ......................................................................................21
Figure 2.8 NAM-232W to RPT-W Connections .........................................................................21
Figure 2.9 NAM-232W to RPT-WF Connections ......................................................................22
Figure 2.10 NAM-232W to MIB-W ...........................................................................................22
Figure 2.11 NAM-232W to MIB-WF Connections ....................................................................23
Figure 2.12 NAM-232F to NAM-232F Connections ..................................................................23
Figure 2.13 NAM-232F to RPT-F ...............................................................................................24
Figure 2.14 NAM-232F to RPT-WF Connections ......................................................................24
Figure 2.15 NAM-232F to MIB-F ..............................................................................................25
Figure 2.16 NAM-232F to MIB-WF Connections 2......................................................................5
2.9 Connecting the NAM-232 to an AFP-200.........................................................................................26
Table 2.1 EIA-232 Serial Connections .........................................................................................26
Figure 2.17 Connecting the EIA-232 Interface to the AFP-200 .................................................26
2.10 Connecting the NAM-232 to an AFP-300/AFP-400.......................................................................26
Table 2.1 EIA-232 Serial Connections .........................................................................................27
Figure 2.18 Connecting the EIA-232 Interface to the AFP-300/AFP-400 ..................................27
NAM-232 50038:F 12/29/99
www.PDF-Zoo.com
4
Table of Contents
2.11 Connecting an AM2020/AFP1010 Through TPI-232 Modems to a NAM-232.............................27
Section 3 AFP-200 Programming Requirements ..............................................................28
3.1 NOTI•FIRE•NET™ Channel Threshold Programming....................................................................28
3.2 Node Address Programming.............................................................................................................28
3.3 CCBE Zone Programming................................................................................................................29
3.4 CCBE Drill Programming.................................................................................................................29
3.5 Additional Programming Requirements............................................................................................30
Section 4 AFP-300/AFP-400 Programming Requirements ..............................................31
4.1 AFP-300/AFP-400 (LocT)................................................................................................................31
4.2 NOTI•FIRE•NET™ Channel Threshold Programming....................................................................31
4.3 Node Address Programming.............................................................................................................32
4.4 Special ACS Offset............................................................................................................................32
4.5 CCBE Zone Programming................................................................................................................32
Figure 4.1 Verifire™ Version 3.0 System Parameter Screen .....................................................33
Figure 4.2 CCBE Zone Programming Example ..........................................................................33
4.6 CCBE Drill Programming.................................................................................................................33
Figure 4.3 CCBE Drill Programming Example ..........................................................................34
4.7 Additional Programming Requirements............................................................................................34
Section 5 Programming .......................................................................................................35
5.1 AM2020/AFP1010 Programming Requirements..............................................................................35
Section 6 AFP-200, AFP-300/AFP-400 Message Translations .........................................36
Verifire™ is a trademark of NOTIFIER, 1996.
NOTI•FIRE•NET™ is a trademark of NOTIFIER, 1994
5
www.PDF-Zoo.com
NAM-232 50038:F 12/29/99
General
The Network Adaptor Module NAM-232 functions as an interface between the AFP-200, AFP­300/AFP-400, or the AM2020/AFP1010 Fire Alarm Control Panels (FACPs) and the NOTIFIER fire alarm local area network, following AFP-200, AFP-300/AFP-400 or AM2020/AFP1010 part numbers:
AFP-200, Software Part Number #AFP2M3.0
Display Interface Assembly for AM2020 (DIA-2020), Part Number #DIA2M3.0
Central Processing Unit for AM2020 (CPU-2020), Part Number #CPU M3.0
Display Interface Assembly for AFP1010 (DIA-1010), Part Number #DIA1M3.0
Central Processing Unit for AFP1010 (CPU-2), Part Number #CPU1M3.0
AFP-300/AFP-400, Software Part Number #AFP4R3.0
1.1 Related Documentation
To obtain a complete understanding of specific features within the network, or to become familiar with network functions in general, refer to the documentation listed in Table 1.1 or use Verifire™. Verifire™ is Windows® based, and provides an of f-line programming and test utility which reduces installation programming time. The NOTIFIER Document Revision Chart provides the current document revis ion.
Section 1 General
NOTI•FIRE•NET™
. The NAM-232 is compatible with the
Windows® is a registered trademark of Microsoft.
Related Documentation
Title Number Title Number
AM2020/AFP1010 Fire Alarm Control Panel 15088 Annunciator Control System 15842 Liquid Crystal Display (LCD-80) 15037 Lamp Driver Modules (LDM) 15885 Network Control Station (NCS) 51095 Voice Alarm Multiplex 15889 Intelligent Network Annunciator (INA) 15092 The XP Series Transponder System 15888 Universal Zone Coder Installation (UZC-256) 15216 Network Adaptor Module (NAM-232) 50038 Product Installation Document (CCM-1) 15328 The UDACT Universal Digital Alarm
Communicator/Transmitter
Product Installation Document (MPS-TR) 15331 Video Graphics Annunciator System (VGAS)
Installation Manual
Analog Fire Panel (AFP-300/AFP-400) 50253/
50259/
50260 Notifier Device Compatibility Document 15378 Media Interface Board (MIB) 50255 Analog Fire Panel (AFP-200) 15511 Repeater (RPT) 50256 ACT-2 Audio Coupling Transformer 51118 Network Interface Board (NIB-96) 15666 Telephone/Panel Interface (TPI-232) 50372 Smoke Control Manual 15712 CHG-120 Battery Charger 50641 AM2020/AFP1010 Operator Instructions 15337 MMX-2 Installation Instructions M500-03-00 Canadian Requirements for the AM2020/
AFP1010 APS-6R Auxiliary Power Supply 50702 VEC 25/50 Voice Evacuation Control Panel 50686 RM-1 Series Microphones 51138 NBG-12LX Pull Station 51093 XP5 Series Transponders 50786
15631 Automatic Fire Alarm Warden Station Series
FCPS-24/FCPS-24E Field Charger/Power Supply Installation, Operation and Application Manual
NOTI•FIRE•NET™
Product Installation Drawing
50050
50251
50059
50257
50705
6 NAM-232 50038:F 12/29/99
www.PDF-Zoo.com
Table 1.1 Related Documentation
Product Features
1.2 Product Features
The NAM-232 is available in either a wire or a fiber version. The following features are included with the NAM-232W:
Connects AFP-200, AFP-300/AFP-400 or AM2020/AFP1010 Fire Alarm Panels to
NOTI•FIRE•NET™
Supports two channels of twisted pair wire medium
National Fire Protection Association (NFP A) Style 4 (Class B) or Style 7 (Class A) operation
Selectable earth fault detection per channel
Provides electrical isolation between nodes
Diagnostic indicators
Selectable data thresholds per channel (high or low)
Built-in repeater function
The following features are included with the NAM-232F:
Connects AFP-200, AFP-300/AFP-400 or AM2020/AFP1010 Fire Alarm Panels to
NOTI•FIRE•NET™
Supports two channels of fiber optic cable medium
NFPA Style 4 (Class B) or Style 7 (Class A) operation
Diagnostic indicators
Built-in repeater function
Fiber type: 62.5/125 micrometers multi-mode
Wavelength (l): 820 nanometers (use 850 nanometer fiber optic cable)
Connectors: ST® Style
Data is immune to all environmental noise
Optical isolation prevents ground loops
ST® is a registered trademark of AT&T.
General
1.3 Installation
The NAM-232 may be installed locally or remotely. Refer to Figure 1.1 through Figure 1.4 for simplified block diagrams of each type of installation.
NOTI•FIRE•NET™
NOTI•FIRE•NET™
NAM-232 50038:F 12/29/99 7
www.PDF-Zoo.com
NAM-232
Figure 1.1 Simplified Local Network Connection to AFP-200
NAM-232
Figure 1.2 Simplified Remote Network Connection to AFP-200
TPI-232
Modem
TPI-232
Modem
AFP-200
Fire Alarm
Control Panel
AFP-200
Fire Alarm
Control Panel
General
Product Description
NOTI•FIRE•NET™
Figure 1.3 Simplified Local Network Connection to AFP-300/AFP-400
NOTI•FIRE•NET™
NAM-232
Figure 1.4 Simplified Remote Network Conn ection to AM2020/AFP1010
1.4 Product Description
The following features are supported by the NAM-232:
Acknowledge
transmits signals to the INA/NCS for network operator acknowledgment. This function is inoperative if an INA/NCS is not connected, or if the network is fragmented so that the INA/ NCS is disconnected from the NAM-232.
Signal Silence
— FACP may be reset locally or from an INA/NCS.
Reset Network Resound
another fire alarm signal is generated by any network node.
NAM-232
TPI-232
Modem
TPI-232
Modem
AFP-300/400
Fire Alarm
Control Panel
AM2020/AFP-1010
Fire Alarm
Control Panel
—The NAM-232 automatically acknowledges events at the local panel and
— FACP may be silenced locally, or from an INA/NCS.
— All previously silenced devices on the FACP are reactivated when
— Local AFP-200/AFP-300/AFP-400 drill function. An optional network AFP-200/
Drill
AFP-300/AFP-400 drill function permits the dri ll switch on any AFP-200/AFP-300/AFP-400 to activate all other networked AFP-200/AFP-300/AFP-400 drill outputs.
CCBE Zone
—The Cooperativ e Co ntrol By Ev ent (CCBE) zone fun ction co nsists of zones 01 through 45 on an AFP-200 or zones 1 through 99 on an AFP-300/AFP-400, which may be programmed to activate when a zone on another
CCBE Drill
—The Cooperative Control By Event (CCBE) drill function on an AFP-200/
NOTI•FIRE•NET™
AFP-300/AFP-400 may be programmed to activate when a zone on another
NOTI•FIRE•NET™
node is active.
1.5 Trouble Conditions/CCBE Messages For AFP-200
The following paragraphs describe the trouble conditions and messages which may display at various times.
1. This message:
TROUBL IN SYSTEM
NETWORK FAILURE
05:16P WED 04/15/00
will be displayed on the AFP-200 when a break exists in one or more of the following connections and the FACP is configured with a non-zero node address:
node is active.
EIA-232 transmit line from the AFP-200 to the NAM-232.
EIA-232 receive line from the NAM-232 to the AFP-200.
If TPI-232 is used, may indicate loss of carrier on the leased lines.
8 NAM-232 50038:F 12/29/99
www.PDF-Zoo.com
Trouble Conditions/CCBE Messages For AFP-200
General
Transmit/receive connection on the NAM-232W to/from A or Port B.
Receive connection from
2. One of these messages (only when the NAM-232 has been configured for NFPA Style 7 operation or dual port monitoring):
TROUBL IN SYSTEM
NETWORK FAIL PORT A
05:16P WED 04/15/00
will be displayed on the AFP-200 when a break exists in the following connection:
Transmit/recei ve c onnection from B, respectively.
Receive connection from respectively.
3. This message:
NOTI•FIRE•NET™
NOTI•FIRE•NET™
NOTI•FIRE•NET™
ACTIVE BY NETWORK
ZONE NUMBER NN
05:16P WED 04/15/00
(both Port A and Port B) to the NAM-232F.
TROUBL IN SYSTEM
NETWORK FAIL PORT B
05:16P WED 04/15/00
to the NAM-232F on Port A or Port B,
NOTI•FIRE•NET™
to the NAM-23 2W on Port A or Port
on both Port
where NN is a zone number (01 trough 45); will be displayed on the AFP-200 whenever a local zone is activated by CCBE.
4. This message:
MANUAL EVACUATE
05:16P WED 04/15/00
will be displayed on the AFP-200 whenever the drill function is activated by CCBE or via the front keyboard.
5. If the AFP-200 recognizes that the connected NAM-232 has a different node address, the following message will be displayed:
TROUBL IN SYSTEM
NAM CCBE PROG LOST
05:16P WED 04/15/00
Both the AFP-200 and the NAM-232 store the network node address. Ordinarily, these numbers match since they are programmed simultaneously. However, if later a NAM-232 with a different node number is connected to the AFP-200, the CCBE equations and threshold settings associated with the AFP-200 node address will not be available. When it is used with an AFP-200, the NAM-232 stores CCBE and threshold data which is accessed by a node address. To prevent improper network operation, the N AM-2 32 will erase all CCBE information when connected to an AFP-200 that has a different node address. Use care to ensure that the NAM-232 is not separated from the matching AFP-200 panel during service and maintenance operations.
To clear the mis-match trouble message, first program the AFP-200 to a new (undesired) node number. Then program the AFP-200 to the actual (desired) node number and enter the CCBE data.
NAM-232 50038:F 12/29/99 9
www.PDF-Zoo.com
General
Trouble Conditions/CCBE Messages for AFP-300/AFP-400
1.6 Trouble Conditions/CCBE Messages for AFP-300/AFP-400
The following paragraphs describe the trouble conditions and messages which may display at various times.
1. This message:
TROUBL IN SYSTEM NETWORK FAILURE
05:16P WED 04/15/00
will be displayed on the AFP-300/AFP-400 when a break exists in one or more of the following connections and the FACP is configured with a non-zero node address:
EIA-232 transmit line from the AFP-300/AFP-400 to the NAM-232.
EIA-232 receive line from the NAM-232 to the AFP-300/AFP-400.
If TPI-232 is used, may indicate loss of carrier on the leased lines.
Transmit/receive connection on the NAM-232W to/from A or Port B.
Receive connection from
2. One of these messages (only when the NAM-232 has been configured for NFPA Style 7 operation or dual port monitoring):
TROUBL IN SYSTEM NETWORK FAIL PORT A
TROUBL IN SYSTEM NETWORK FAIL PORT B
will be displayed on the AFP-300/AFP-400 when a break exists in the following connection:
Transmit/receive connection from B, respectively.
Receive connection from respectively.
3. This message:
ON SOFTWARE ZONE << ZONE LABEL >>
NOTI•FIRE•NET™
NOTI•FIRE•NET™
NOTI•FIRE•NET™
(both Port A and Port B) to the NAM-232F.
05:16P WED 04/15/00
05:16P WED 04/15/00
to the NAM-232F on Port A or Port B,
NOTI•FIRE•NET™
to the NAM-232 on Port A or Port
on both Port
where NN is a zone number (01 through 99 ), Nnnn is a node num ber (1 through 249), and Zzzz is a network zone number (1-240); will be displayed on the AFP-300/AFP-400 whenever a local zone is activated by CCBE.
4. This message:
will be displayed on the AFP-300/AFP-400 whenever the drill function is activated by CCBE or via the front keypad.
10 NAM-232 50038:F 12/29/99
www.PDF-Zoo.com
N
nnnZzzz
MANUAL EVACUATE
ZNN
05:16P WED 04/15/00
Limitations of the AM2020/AFP1010 with a (NAM-232)
1.7 Limitations of the AM2020/AFP1010 with a (NAM-232)
The AM2020/AFP1010 occupies a single node address on the network. This configuration has limited capability. Functions are limited to the display of signals at an INA or NCS, network acknowledge, signal silence, and reset functions. Other features such as cooperative-control-by­event, read status, alter status, etc. are not supported in this configuration.
1.8 Trouble Conditions/Messages for AM2020/AFP1010
The following paragraphs describe the trouble conditions and messages which may display at various times on the AM2020/AFP1010.
1. This message:
TROUBL NAM COMMUNICATIONS FAULT
02:56P 09/10/00 TC9
will be displayed on the AM2020/AFP1010 when a break exists in one or more of the following connections and the FACP is configured with a non-zero address:
EIA-232 transmit or receive line between the AM2020/AFP1010 and a TPI-232 modem.
EIA-232 transmit or receive line between the NAM-232 and a TPI-232 modem.
General
The telephone line connection between two TPI-232 modems.
Transmit/receive connection on the NAM-232W to/from
Receive connection from
2. These messages (only when the NAM-232 has been configured for NFPA Style 7 operation or dual port monitoring):
TROUBL NETWORK COMMUNICATION LINK FAI
will be displayed on the AM2020/AFP1010 when a break exists in one or more of the following connections:
Transmit/receive connection from or Port B.
Receive connection from
NOTI•FIRE•NET™
TROUBL NETWORK COMMUNICATION LINK FAI
PORT A 02:56P 09/10/00 TDA
PORT B 02:56P 09/10/00 TDA
NOTI•FIRE•NET™
NOTI•FIRE•NET™
(both Port A and Port B) to the NAM-232F.
to the NAM-232F on either Port A or Port B.
NOTI•FIRE•NET™
to the NAM-232W on either Port A
.
L
L
NAM-232 50038:F 12/29/99 11
www.PDF-Zoo.com
General
1.9 Diagnostic Indicators
The NAM-232 has diagnostic indicators which aid in troubleshooting and assist the installer in connecting the system. Refer to Table 1.2 for a list of diagnostic indicators and their descriptions.
Indicator Color Description
RECON Yellow This LED should remain off at all times when the network is
STA TB Yello w Illu minates when the N AM-23 2 is not recei ving v al id data from
RCVDB Green Illuminates when the NAM-232 is receiving data from
B HI Green Illuminates to indicate the NAM-232W Channel B is set for
A HI Green Illuminates to indicate the NAM-232W Channel A is set for
Diagnostic Indicators
LED
operating properly. If it illuminates periodically, check the network media and thre sholds using the MET-1 (Media Evaluation Tool).
NOTI•FIRE•NET™
NOTI•FIRE•NET™
high threshold (N/A on NAM-232F).
high threshold (N/A on NAM-232F).
on Port B.
on Channel B.
RCVDA Green Illuminates when the NAM-232 is receiving data from
NOTI•FIRE•NET™
STA TA Yellow Illumina tes when the NAM-232 is not receiving v alid data from
NOTI•FIRE•NET™
PULSE Green Illuminates when the NAM-232 is transmitting data to
NOTI•FIRE•NET™
TROUBLE Yellow Indicates that the NAM-232 is not functioning. TXD Green Indicates when the NAM-232 is transmitting data to the FACP. RXD Green Ind i cates when the NAM-232 is receiving data from the FACP.
on Channel A.
on Port A.
Table 1.2 Identifying Indicators
12 NAM-232 50038:F 12/29/99
www.PDF-Zoo.com
Loading...
+ 28 hidden pages