N-MPS and NFW-MPS
Conventional Series
Manual Stations
General
The Notifier MPS Conventional Series manual stations provide
reporting for the NFS-320C, NFS2-640, and NFS2-3030 fire
alarm control panels; NFW-MPS series manual stations provide
reporting for FireWarden series panels. These high quality, die
cast metal manual stations include screw terminal connections,
and integrated break-glass rod. The alarm contact for the manual station is rated for 1A, 24VDC. The contacts are gold plated
to avoid the risk of corrosion.
The MPS Series manual stations are available as single or twostage for conventional systems. Models N-MPS-SC/SCC are
single-stage manual stations. Models N-MPS-2C/2CC (twostage models) are similar to the N-MPS-SC (single-stage models) except they contain an additional 2nd Stage normally open
key-switch. A 2nd stage key is supplied with each unit to activate
the 2nd Stage key-switch.
All models are available with screw terminal connectors and a
hex key for reset. Two-stage models also include a key-switch
and 2 keys. All conventional models mount on a single gang
box or on a single gang box with a plaster ring.
For surface mounting, use Notifier surface back-box MPS-BB
with all conventional manual stations.
Canadian DN-5497:C1
Conventional Initiating Devices
Operation
The Notifier MPS Series manual stations are operated by pulling
the handle on the front of the station. To reset the manual station, open the manual station with the hex key (provided) and
place the handle in the normal upright position. Replace the
break-glass rod, and close the manual station front cover.
The N-MPS two-stage models include a key switch which is
located above the handle. Operation of the key-switch, when
connected to a separate alarm initiating circuit, will activate the
second stage of a two-stage alarm signaling system.
To reset the second stage activation, return the key-switch to the
original position before resetting the fire alarm control panel.
Models provided with an ancillary contact for mag-lock release,
will simultaneously release the locally connected mag-lock upon
pulling the handle on the front of the manual station.
Features
• Constructed of high quality die-cast metal
• Highly visible red enamel finish
• English and French lettering
• Single action pull lever design
• Optional dual action lever kit
• Integrated break-glass
• Hex key resettable
• Screw terminal connectors
• Optional ancillary contact for local mag-lock release
• Single-stage and two-stage models
• Key-switch activation for second stage
• Surface or semi-flush mounting
• All conventional models mount on a standard single-gang
electrical box or a surface metal back-box
Architectural/Engineering
Specifications
The manual station is the Notifier N-MPS series. Operating
instructions appear in English and French lettering. The unit is
constructed of high quality die cast metal and finished in red
enamel paint to be easily identified. When the handle is pulled,
the manual station initiates an immediate operation of the alarm
detection circuit. In addition, those manual stations installed in a
two-stage system are equipped with a key-switch designed to
operate the second stage alarm initiating circuit. Manual stations
shall have the option of an ancillary contact for local mag-lock
release. Manual stations are listed with Underwriters Laboratories Canada (ULC). Manual stations are required to be installed
to the current Canadian Electrical Code and the current CAN/
ULC – S524 (Standard for the installation of Fire Alarm Systems) and comply with CAN/ULC-S528, (Manual Stations for
Fire Alarm Systems, Including Accessories). Manual stations
must be installed within the limits defined by the national/local
requirements. Final acceptance is subject to the local authority
having jurisdiction.
Manual stations are provided with a hex key–operated reset lock
to reset the device after the manual station has been operated
and to allow access for testing. The stations are designed so
that after an actual emergency operation the stations cannot be
restored to normal operation without the use of the supplied hex
key. The manual stations are provided with an integrated breakglass feature.
The addition of the dual action adapter cover (MPS-LP) requires
the operator to first lift the cover and then pull the handle of the
manual station.
All conventional models mount on a single-gang box or on a single-gang box with a plaster ring.
For surface mounting, use Notifier surface back-box MPS-BB
for conventional manual stations.
Canadian DN-5497:C1 • 06/22/2010 — Page 1 of 2
Agency Listings and Approvals
• ULC listed: S7568
Specifications
ALL CONVENTIONAL MODELS
Maximum Applied Voltage: 32 VDC
Supply Voltage Nominal: 24 VDC
Average Current Consumption: 400uA, Single stage ver-
sions, 550 uA Two stage versions
Maximum Current Consumption: 550 uA Single stage versions, 1100 uA Two stage versions
Operating Temperature Range: 0°C to 49°C
Humidity: 10 to 93% noncondensing
Dimensions: 121mm (H) x 82mm (W) x55mm (D)
Weight: 499 Grams Single stage version, 567 Grams Two stage
version
ALL MODELS WITH ANCILLARY CONTACTS
Ancillary Contact Ratings:
• 30 VAC 6 amps Resistive, 6 amps Inductive
• 30 VDC 6 amps Resistive, 3 amps Inductive
NOTE: All models are for use indoors in a dry location.
Product Line Information
CONVENTIONAL MANUAL STATIONS
N-MPS-SC: Conventional single-stage manual station, English/
French lettering.
N-MPS-SCCF: Conventional single-stage manual station.
Form-C alarm and ancillary contacts included. English/French
lettering.
N-MPS-SCB: Conventional single-stage manual station. Blue in
color. English/French lettering.
N-MPS-2C: Conventional two-stage manual station. English/
French lettering.
N-MPS-2CC: Conventional two-stage manual station. Form-C
alarm and ancillary contacts included. English/French lettering.
For addressable manual stations, see DN-60629.
ACCESSORIES
MPS-LP: Lift/pull dual action adapter cover for use with the
MPS Series manual stations. English/French lettering.
RMS-TP3: Mounting plate for semi-flush mounting addressable
manual stations to a 4" square electrical box, red.
RMS-TP1: Mounting plate for semi-flush mounting addressable
manual stations to a two-gang electrical box, red.
MPS-BB: Surface back-box, for use with conventional
models123.83mm(H) x 82.5mm(W) x 44.5mm(D) 4.88"(H) x
3.25"(W) x 1.75"(D).
MPS-ER: Extension ring for addressable models using existing
single-gang electrical boxes.
RMS-GR/10: Replacement break-glass rods. Package of 10.
PS-AWRC-029: Replacement Hex Key
MPS-KEY: Replacement 2nd Stage Key
Notifier® is a registered trademark of Honeywell International Inc.
©2010 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
This document is not intended to be used for
installation purposes. We try to keep our
product information up-to-date and accurate. We
cannot cover all specific applications or anticipate
all requirements. All specifications are subject to
Page 2 of 2 — Canadian DN-5497:C1 • 06/22/2010
change without notice.
For more information, contact Notifier.
(888) 289-1114
10 Whitmore Road
Woodbridge, Ontario L4L 7Z4
www.notifier.com