Notifier Mini-Horns MHW User Manual

SpectrAlert® Advance Mini-Horns
MHR/MHW
General
The SpectrAlert® Advance series of mini-horn sounders are designed to simplify installation to provide primary and sec­ondary signaling for fire and security applications.
The MHR and MHW mini-horns operate at 12 and 24 volts and are ideal for hotel, motel or residential fire system applications, where a smaller notification device is desired. The mini-horns offer high and low volume settings, and temporal or non-tem­poral tones. The horns can be mounted to single gang back boxes for aesthetically sensitive applications. Synchronization is also provided when using the MDL3R, MDL3W module or any Notifier panel with the System Sensor sync protocol.
The MHR and MHW mini-horns can operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave recti­fied, unfiltered power supply. They are listed to Underwriter’s Laboratories.
dn-60341:a1
Audio/Visual Devices
Features
• Standard UL 464 for fire protective signaling systems.
• 12 and 24V operation.
• High and low volume settings.
• Temporal and non-temporal tones.
• Mounts to a single-gang backbox.
• Compatible with MDL sync module.
• Mechanically and electrically compatible with PA400 series Mini-Alert™ sounders.
Specifications
PHYSICAL SPECIALIZATIONS
Dimensions: 4.6”L x 2.9”W x .45”D.
Weight: 2.67 oz.
Operating Temperature Range: 0°C to 49°C
Mounting: Surface: Deep single-gang backbox (2-3/4” deep);
Flush: Standard 4” x 4” back box.
ELECTRICAL SPECIFICATIONS
Input Terminals: 12 to 18 AWG
Nominal Voltage: Regulated 12DC/FWR or 24DC/FWR
Operating Voltage: 8-33
Operating Voltage with MDL3R/W: 9-33
(32°F to 120°F)
60296pho1.jpg
Listings and Approvals
These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in progress. Consult factory for listing status.
UL Listed: S4011
MEA: 7-07-E
CSFM: 7135-1653:196
FM Approved: 3028007
Ordering Information
.
MHR: Mini-Horn; Red.
MHW: Mini-Horn; White.
Architectural/Engineering Specifications
Mini-horns shall be a System Sensor Model MHR or MHW capable of operating at nominal 12 or 24VDC and shall mount to a single gang back box. Mini-horns shall be listed to Under­writer’s Laboratories Standard UL464 for fire protective signal­ing systems. Mini-horns shall operate between 32 and 120 degrees Fahrenheit from a regulated DC, or full-wave rectified, unfiltered power supply. When used with the Sync•Circuit™ Module, 12-volt rated notification appliance circuit outputs shall operate between nine and 17.5 volts; 24-volt rated notifi­cation appliance circuit outputs shall operate between 17 and 33 volts.
dn-60341:a1 • 2/9/10 — Page 1 of 2
UL Sound Output and Current Draw Data
SOUNDER OUTPUT (dBA)
Switch
Position
1 Temporal High 68 67 71 70 78 76
2 Temporal Low 66 65 69 68 76 75
3 Non-temporal High 72 71 75 74 80 79
4 Non-temporal Low 70 69 73 72 78 77
SOUNDER CURRENT DRAW (mA RMS)
Sound
Pattern
Volu m e
8-17.5
VDC
8-17.5 VFWR
Switch Position Sound Pattern Volume
1TemporalHigh12 10 17 15
2 Temporal Low 1091413
3 Non-temporal High 22 17 29 25
4 Non-temporal Low 17 13 21 19
Nominal
12 VDC
Nominal
12 VFWR
16-33
VDC
8-17.5 V 16-33 V
DC FWR DC FWR
16-33
VFWR
Page 2 of 2 — dn-60341:a1 • 2/9/10
SpectrAlert® is a registered trademark and Mini-Alert™ is a trademark of Honeywell International Inc. ©2010 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Made in the U.S. A.
Loading...