Notifier IFS-2600 Maintenance Manual

Page 1
IFS-2600
Fire Indicator Panel
OPERATION, INSTALLATION &
PROGRAMMING MANUAL
DOC-01-009 ECN11-0012
19/04
/2011Rev:
1.02
Page 2
Documentation Feedback
Your feedback helps us keep our documentation up to date and accurate. If you have any comments or suggestions about our printed manuals you can email us.
Please include the following information:
Product name and version number (if applicable) Manual part number and revision (found on the front cover) Page number Brief description of the content you think should be improved or corrected Your suggestion for how to correct/improve documentation
Send email messages to:
techpubs@notifier.com.au
Please note this email address is for documentation feedback only. If you have any technical issues, please contact your nearest branch for technical support.
Page 3
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before
servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood.
Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning induced transients. Although no system is completely immune from lightning transients and interference, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries
from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, or printed circuit board location.
Do not over tighten screw terminals. Over tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
This system contains static-sensitive components. Always ground yourself with a
proper wrist strap before handling any circuits so that
Static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. These
instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation.
This equipment must be correctly programmed and installed to suit the specific application.
Please ensure correct operational parameters are set prior to commissioning. If further details on programming options are required, please consult the programming manual or contact our helpful technical support personnel.
EMC WARNING:
This equipment may radiate radio frequency energy. It may also be affected by radio frequency energy and, if not installed and operated in accordance with the manufacturer’s instructions, may cause interference to radio communications. It has been tested and found to comply with the Class A radiated and conducted EMI requirements of AS/NZS CISPR 22:2009 (including Amendments 1 & 2) as well as the EMI susceptibility requirements of Clause C3.5 in AS4428.0:1997.
Radio communication devices should not be used in the vicinity of fire panels or associated ancillary devices and systems.
This is a Class A product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures.
Page 4
IFS-2600 Fire Indicator Panel Section 1
About this Manual
DOC-01-009
Table of Contents
Section 1 - About this Manual................................................................1
1.1. Notes, Cautions and Warnings..................................................................... 1
Section 2 - System Overview...................................................................2
2.1. Overview..................................................................................................... 2
2.2. Features...................................................................................................... 2
2.3. System Description...................................................................................... 3
2.4. Internal Buzzer............................................................................................. 3
2.5. LCD Display................................................................................................. 4
2.6. Keypad........................................................................................................ 5
Section 3 - Operation ...............................................................................7
3.1. Suggested Alarm Procedure........................................................................ 7
3.2. Fire Fighter Functions.................................................................................. 7
3.3. Global Operator Functions........................................................................... 8
3.4. Zone Operator Function..............................................................................11
3.5. Standard Outputs........................................................................................14
3.6. Relay Expansion Boards.............................................................................15
3.7. Printer Output.............................................................................................15
Section 4 - Installation ...........................................................................16
4.1. Compatible Detectors .................................................................................16
4.2. Specification...............................................................................................17
4.3. Overview of IFS-2600 System Equipment...................................................20
4.4. Power Supply .............................................................................................21
4.4.1 Power Supply Ratings & Settings for NI-2017-01 & NI-2025-01 Boards......21
4.4.2. Power Supply Ratings & Settings for IFS-2005 & IFS-2006 Boards ............ 23
4.4.3. Battery Type and Capacities...................................................................... 25
4.5. Technical Description..................................................................................26
4.6. Placing Into Operation.................................................................................33
Section 5 - Programming........................................................................36
5.1. Program Mode............................................................................................36
5.2. Zone Options & Programming.....................................................................39
5.2.1. Zone Options............................................................................................. 39
5.2.2. Zone Programming....................................................................................40
5.3. Relay Options & Programming....................................................................42
5.3.1. Relay Options............................................................................................ 42
5.3.2. Relay Programming...................................................................................44
Page 5
IFS-2600 Fire Indicator Panel Section 1
About this Manual
DOC-01-009
5.4. Global Options & Programming...................................................................46
5.5. Print Programming Data..............................................................................48
Section 6 Appendix.................................................................................49
6.1. Appendix A.................................................................................................49
6.2. Appendix B.................................................................................................50
6.3. Appendix C.................................................................................................52
6.4. Technical Drawings.....................................................................................59
6.4.1. System Sensor Conventional Detector Connection Diagram ...................... 59
6.4.2. Hochiki Conventional Detector Connection Diagram................................... 60
6.4.3. Ancillary Connection Diagram.................................................................... 61
6.4.4. ASE Connection Diagram ......................................................................... 62
6.4.5. MIMIC Connection Diagram....................................................................... 63
6.4.6. Dual Fan Connection Diagram................................................................... 64
6.4.7. Exhaust Fan Connection Diagram..............................................................65
6.4.8. Supply Fan Connection Diagram................................................................66
6.4.9. Smoke Spill Fan Connection Diagram........................................................ 67
6.4.10. 10W EVAC Connection Diagram................................................................ 68
Page 6
IFS-2600 Fire Indicator Panel Section 1
About this Manual
DOC-01-009 1
Section 1 - About this Manual
1.1. Notes, Cautions and Warnings
This manual contains notes, cautions and warnings to alert the reader as follows:
NOTE: Supplement information for a topic such as tips and references.
CAUTION: Information about procedures that could cause programming errors, runtime
errors, or equipment damage.
WARNING: Indicates information about procedures that could cause irreversible equipment damage, irreversible loss of programming data or personal injury.
Page 7
IFS-2600 Fire Indicator Panel Section 2 System Overview
DOC-01-009 2
Section 2 - System Overview
2.1. Overview
The overall intent of a fire protection system is to provide warning should smoke or a fire be detected. The systems can be configured to alert occupants of the building, advise fire brigades and take necessary action to either extinguish the fire and/or stop the fire from spreading. The fire indicator panel is an essential part of a building fire protection systems, it must therefore be properly and carefully installed, configured and maintained.
2.2. Features
The IFS-2600 Fire Indicator Panel (FIP) has many custom designed components along with microprocessor and circuitry, ensuring greater reliability and suppression from external sources.
The FIP uses both a liquid crystal display and conventional LED displays for fast and accurate display of system status and changing events.
A custom designed membrane keypad is used together with the liquid crystal display and LED indicators to provide fast, efficient and simple modes of operation. The keypad also provides the required flexibility for the programming of many user configurable options of this FIP. The FIP can be configured on-site without the need of expensive programmers or components. These configured options are retained by the FIP even if the power is totally disconnected.
A serial printer can also be connected if required. The printer can be used to output programming information for ease of modification,for safekeeping and to assist in the commissioning of the installation.
The IFS-2600 uses serial chain mimic outputs which significantly saves time and costs of cabling to mimic panels.
A door holder power supply is incorporated into the system for the release of smoke and fire doors on alarm (Optional transformer may be used).
IFS-2600 is available in a standard 8-zone configuration and can be upwards expandable to its fully
expanded state as required. IFS-2600 in its fully expanded state can;
• Monitor 64 detection zones
• Control 64 optional "mapped" relay outputs
• Output to a serial printer
• Output serially to a mimic panel (Max seven panels)
• Control up to 30 door holders
• Interface as required to any Australian Fire Brigade
IFS-2600 has been designed to be functional, flexible and reliable whilst maintaining a user-friendly environment.
Page 8
IFS-2600 Fire Indicator Panel Section 2 System Overview
DOC-01-009 3
2.3. System Description
The basic IFS-2600 Fire Indicator Panel (FIP) consists of
Quantity
Description
1
Wall Mounting Cabinet with Manual Call Point
1
Main Control Board (Located on inside of inner door) – CPU – NI-2004-01
1
Main Termination Board (Located in rear of panel enclosure) – NI-2025-01
1
NPS Brick Power Supply(2.6A/5.6A/11.7A)
1
Power Supply Interface Board (PSI) – NI-2017-01
For Older IFS-2600 Panels,
1
Mains Transformer
1
Main Control Board (Located on inside of inner door) – CPU – IFS-2004
1
Power Supply PCB fitted to Main Termination Board – IFS-2005
1
Power Supply Interface Board (PSI) – IFS-2006
Optional equipment that may be found fitted to the IFS-2600 FIP
Maximum
Quantity
Description
2
Batteries 12V
7
Zone Expansion Board (8 Zone)
4
Display Expansion Board (16 Zone)
8
Relay Expansion Board
For Older IFS-2600 Panels,
1
Door Holder Power Supply Transformer
Table 2-1, IFS-2600 Panel Components
IFS-2600 requires the basic equipment as listed above to function. The microprocessor and other sensitive electronic components are located on the Main Processor Board, located on the inner panel that can be easily removed during installation to allow improved terminal access.
Power supplies and I/O's are located on the main Termination Board. Terminated to this board, at a minimum, should be the NPS brick power supply, batteries, bell and at least one AZF circuit.
With the cabinet outer door closed, the viewing window allows a clear view of the keypad, LCD and LED's.
2.4. Internal Buzzer
A buzzer is located on the main termination board to provide an audible alert to persons in the near vicinity of the FIP of a fault or a zone has gone into alarm. This buzzer sound can be activated or heard by hitting any key on the keypad.
The buzzer is also used for "audio-feedback" during keypad operation; one short beep as any key is depressed verifies the key operation.
One long beep (approx 2 seconds) indicates that an incorrect entry has been made.
Two consecutive short beeps verify entry into a different mode, i.e. "ALARM TEST MODE", "ISOLATE MODE" etc.
Page 9
IFS-2600 Fire Indicator Panel Section 2 System Overview
DOC-01-009 4
2.5. LCD Display
In addition to the LED's a 16-character x 2-line liquid crystal display is provided to indicate system status, changing events and programming information. Any keystroke or event will actuate the backlighting on the display for better readability in dark areas. The backlighting will automatically turn off in 30 seconds if no further keys are pressed.
The primary task of the LCD is for programming and subsequent configuration of the fire indicator panel. The LCD is also used to indicate the current mode of operation, e.g. "ISOLATE MODE", "ALARM TEST MODE" etc. The LCD is also used as a prompt for user entries e.g. "ENTER ZONE #".
When the panel is in the normal mode of operation, the LCD displays and constantly updates the current zone status including the total number of;
ZonesIn Alarm – A=00ZonesIn Fault – F=00ZonesIsolated – I=00Current DateCurrent Time (As per the settings)
Page 10
IFS-2600 Fire Indicator Panel Section 2 System Overview
DOC-01-009 5
2.6. Keypad
The custom-designed 30 key membrane keypad is the users interface to accessing all zone and global functions of the IFS-2600.These 30 keys consist of;
Figure 2-1, IFS-2600 Keypad
1. Five Specialised single-stroke Fire Fighters Keys
2. Four Zone function keys
3. Twelve Keys for Numeric Entry
4. Five Global function keys
5. Four Programming Keys
Operations and functions of these keys are explained in Section 3
Fire Fighter’s
Keys
Zone Function
Keys
Numeric
Keys
Global Function
Keys
Programming
Keys
EXT BELL ISOLATE ALARM TEST
0 – 9 Keys
ENT Key ALL Key
AUTO TEST PREVIOUS
WARN SYS ISOLATE
FAULT TEST ACF ISOLATE NEXT
ACK ISOLATE ACF RESET SELECT RESET RESET WALK TEST EXIT
ISOLATE BATT TEST
FIRE FIGHTER
S FACILITY
BELLS WARNING SYSTEM
ACF
1 2 3
4 5
6 7 8
Page 11
IFS-2600 Fire Indicator Panel Section 2 System Overview
DOC-01-009 6
Qty Descriptor Colour Function Buzzer
1 MAINS ON Green Illuminates when there is AC supply to the panel. 1
BATTERY FAULT
Yellow
Illuminates if the battery fails a battery test. Illuminates if batteries are disconnected >30 seconds. Illuminates if batteries are short circuit >30 seconds.
Yes
1 PSU FAULT Yellow
Illuminates if the power supply is outside the manufacturers range. (Also if power supply is disconnected)
Yes
1
CHARGER FAULT
Yellow
Illuminates if the battery charger is outside the recommended float charge voltage.
Yes
1
COMMON FAULT
Yellow
Illuminates if there is Any fault;
Any un-isolated zone is in open circuit fault. ACF output is open or short circuit Bell output is open or short circuit Warning System output is open or short circuit Power Supply Fault including Battery or Charger MAF Isolate Input is Open Circuit Configuration Fault
Yes
1 ACF ACT Red Illuminates if the ACF output has been activated. 1 ACF FLT Yellow Illuminates if the ancillary circuit is open or short circuit. Yes
1 ACF ISO Yellow
Illuminates if the ancillary output has been manually
isolated. 1 Bell ACT Red Illuminates when the bell output has been energised. 1 Bell FLT Yellow Illuminates if the bell circuit is open or short circuit. Yes 1 Bell ISO Yellow Illuminates if the bell output has been manually isolated.
1
Warning System ACT
Red
Illuminates if the Warning System output has been
energised. 1
Warning System FLT
Yellow
Illuminates if the Warning System circuitis open or short
circuit.
Yes
1
Warning System ISO
Yellow
Illuminates if the Warning System has been manually
isolated.
8
ALARM LEDS
Red
This LED will flash if its corresponding zone goes into
alarm. It will remain flashing until it is Acknowledged at
which time it will go steady and remain on until the alarm is
reset. If the zone is programmed as a time delay type, a
steady LED indicates the “pre-alarm” condition. If the zone
is isolated and in alarm it will also be steady.
Yes
8 FAULT LEDS Yellow
This LED illuminates if it's corresponding zone goes into
fault. It will remain on until the fault is removed.
Yes
8
ISOLATE LEDS
Yellow
This LED illuminates if its corresponding zone is isolated. It
will remain on until the zone is de-isolated.
Table 2-2, Key Pad Description
Page 12
IFS-2600 Fire Indicator Panel Section 3 Operation
DOC-01-009 7
Section 3 - Operation
3.1. Suggested Alarm Procedure
The following is a suggested alarm procedure for use by building fire officers or duty wardens. The fire indicator panel is designed for use by qualified fire fighters and it is strongly recommended that the fire panel not be operated in an emergency situation by anyone other than suitably qualified fire fighters.
Do not open fire indicator panel door or press any buttons until fire officers arriveDeterminelocation of the fire by inspecting the label beside any lit red zone alarm LEDs on the
Panel (Location -> number).
Visually inspect area at a safe distance for actual fire or false alarm.Notifyfire-monitoring station of either result.Perform evacuation and extinguishing operations as required.IF a FIRE, direct fire fighters to the fire indicator panel and cause of alarm as they arrive.IF a FALSE ALARM, advise maintenance technicians to determine and rectify cause.Record all events in logbook.
3.2. Fire Fighter Functions
Fire Fighter Functions are those specifically used by the Fire Brigade on attendance. Following is an explanation of their operation and the keystrokes required to perform the function required. These keys are located at the top of the keypad marked “FIREFIGHTER’S FACILITY” and bordered in red.
The purpose of the internal buzzer is to alert people of a new event on the panel, and a new potential fire danger. Once the fire's location has been determined, the fire-fighter may wish to silence the internal buzzer without having to totally reset the alarm.
When the buzzer is operating, pressing the "ACK" key once will silence it, however the External Alarm Bell will continue to sound. If a subsequent alarm arises, the buzzer will be reactivated and a second ACK operation will be required to silence it.
When an alarm is acknowledged, the Alarm LED will stop flashing and light continuously.
RESET
RESET
The reset function momentarily disconnects power and resets all alarm parameters for the zone(s) that have been acknowledged. This returns the zone back to its "normal" state. The reset key only operates on zones with acknowledged alarms.
NOTE:
A suitably qualified fire officer should perform the above procedure. These are suggested procedures only, and if specific fire proceduresare available or issued, they must prevail.
ACKNOWLEDGE
ACK
Page 13
IFS-2600 Fire Indicator Panel Section 3 Operation
DOC-01-009 8
ISOLATE
ISOLATE
The isolate function prevents the transmission of alarms or faults from the zones to the master alarm facility. The isolate key only operates on zones with acknowledged alarms.
BELL ISOLATE
EXT BELL ISOL
Pressing the "EXT BELL ISOLATE" key will isolate the bells. The "Ext Bells Isolate" LED will illuminate and the bells will not sound until the bells are de-isolated. Pressing "EXT BELL ISOLATE" a second time will de-isolate the bell.
WARN SYS ISOLATE
WARN SYS ISOL
Pressing the "WARN SYS ISOLATE" key will isolate the warning system. The "Warn Sys Isolate" LED will illuminate and the warning system will not operate in the event of an alarm.
Pressing "WARN SYS ISOLATE" a second time will de-isolate the warning system.
3.3. Global Operator Functions
Global functions are those relating to the overall system and are not specific to particular zones. Following is an explanation of their operation and the keystrokes required to perform the function.
BATTERY TEST
BATT TEST
For NI-2025-01 & NI-2017-01 Boards:
Press BTST/RST button located on the PSI board to start the Battery test. Once this key is pressed a Yellow light illuminates next to the B.TST location on PSI board. This yellow light automatically turns off after one hour, indicating the end of Battery test.
To manually turn off the Battery test, press the same button once again. Yellow light turns off, indicating the end of battery test.
NOTE:
Battery test button on keypad will not function.
Page 14
IFS-2600 Fire Indicator Panel Section 3 Operation
DOC-01-009 9
For IFS-2005 & IFS-2006 Boards:
This function tests the performance of the batteries fitted to the system. Pressing this button will initiate a battery test as specified in AS4428. The test will temporarily disconnect the batteries from the panel and apply load on the batteries for 15 seconds.
The result of the test will be displayed on the LED's. If the "Battery Fault" LED is on, only a successful battery test will turn the LED off. The pressing of any key during the test period will abort the battery test and return the system back to normal mode.
This function will perform a fixed automatic test procedure to the panel. This mode cannot be selected if any zone(s) is in alarm. Auto test will perform the following test functions;
1. Displays firmware revision REV-6
2. Turnon ALL LEDs for 0.5 seconds
3. Test LCD Backlighting
4. Test Panel memory(E2ROM & RAM)
5. Test LCD
6. Isolate all alarm zones
7. Fault test all alarm zones
8. Alarm test all alarm zones
9. Test buzzer (Beeps twice)
WALK TEST MODE
WALK TEST
This function will place the panel into "walk test" mode. Walk test mode is used for the on-site testing of detector zones. This mode cannot be selected if any zone(s) are in alarm.
When WALK TEST button is pressed, panel will be automatically placed in walk test mode, which is acknowledged by two buzzer beeps and LCD displays “WALK TEST MODE, PRESS ANY KEY TO EXIT”.
Selecting any key from the keypad triggers the buzzer to beep twice and activates the BELL relay leading BELL ACT LED to blink thrice.
NOTE:
Battery test function is disabled when the panel is in alarm condition.
AUTO TEST MODE
AUTO TEST
NOTE:
Pressing of any key during "AUTO TEST" will abort the tests and return the system back to normal mode once the current test is complete.
During "AUTO TEST", all zones are treated as zone type #1 (standard latching type with 2 Second delay). Once AUTO TEST has finished, all zones will be reset and returned back to their previously configured types.
Page 15
IFS-2600 Fire Indicator Panel Section 3 Operation
DOC-01-009 10
For the duration of walk test mode, all zones are changed to output configuration #2 (indicate and ring bells only) and all zones are set to type #1 (standard latching, 2 second).
If the bells are not required to ring during walk test, simply press the "EXT BELL ISOLATE" key once. The EXT BELL ISOLATE LED will illuminate to verify that the bells have been isolated.
Any alarm signal from detectors will be received by the panel on its appropriate zone. The panel will beep to acknowledge receipt of the alarm and indicate the alarm by illuminating the appropriate alarm LED for 4 seconds (the bells will also ring for a 3 second period unless previously isolated).
The zone and detector will then be automatically reset for 15 seconds. If the optional printer is connected, the alarm will be printed out as it is received. This can eliminate the
need for a second serviceman to record zone numbers during walk test and the printout can be retained for verification at a later date.
Pressing any key will terminate the walk test mode and return the panel back to normal operation, restoring all zone types and output configurations also ensuring that bell and ancillary outputs are de­isolated. The bells will give three pulses of 1 second each to warn any testers still in the building that walk test mode has been terminated.
Failure to receive any alarms or keystrokes within a 15 minutes period will result in the panel automatically exiting walk test mode and returning back to normal as follows:
1. Bell outputs to be de-isolated.
2. Ancillary outputs to be de-isolated.
3. Bell will sound 3 times, each of 1-second duration.
4. Exit from walk test mode.
5. Zone types and output configurations restored
ACF ISOLATE
ACF ISOL
Pressing the "ACF ISOLATE" key will isolate the ACF (Ancillary output) and the Door Holder Output. The ACF isolated LED will illuminate and the output will not operate until de-isolated. Pressing "ACF ISOLATE" for a second time will de-isolate the output.
If the ancillary output has already been tripped and is programmed as latching, isolating the ACF will not affect the existing ancillary output. If the ACF is isolated prior to the alarm, it will prevent the ancillary output from tripping. This does not apply to the Door Holder output.
ACF RESET
ACF RESET
Resetting of the ancillary output (ACF) is only required if the ancillary output was programmed as latching.
The ancillary alarm will remain latched until manually reset. Pressing the "ACF RESET" button will extinguish the 'ACF Activated' LED and de-energise the ancillary output. Pressing "ACF RESET" when the ACF is not tripped will have no effect.
Page 16
IFS-2600 Fire Indicator Panel Section 3 Operation
DOC-01-009 11
3.4. Zone Operator Function
Zone functions are those relating specifically to the detection zones. Following is an explanation of their operation and the keystrokes required to perform the function required.
ALARM TEST
ALARM TEST # ENT
The alarm test function momentarily disconnects the detector lines of the zone(s) under test and simulates a detector going into alarm, therefore testing the zone(s) alarm detection capability.
A resistive load equal to worst case alarm condition is placed on the zone for a period of 120 seconds and then removed. If the zone being tested is not a latching type, the alarm will reset automatically once the load is removed. Acknowledging and resetting the alarm will terminate an alarm test.
Once the zone has alarmed, all outputs are initiated (as programmed) similar to a real alarm. The zone may be isolated prior to an alarm test if desired; this will prevent any outputs from operating.
‘#’ in the above key sequence is the zone number, which can be selected using Numeric keys on the keypad.
If only one zone is to be tested, use the appropriate number. Alternatively the "ALL" button can be used to simultaneously test all zones.
To perform an alarm test:
1. Press the "ALARM TEST" button once; the buzzer will give 2 short beeps to indicate that alarm test mode has been entered
2. The LCD display will read "ALARM TEST MODE, ENTER ZONE No"
3. Now enter the zone number Individual zone ("#") 1 - 64 or select “ALL” key
4. Press "ENT"
If a correct entry is made, alarm testing on the zone commences immediately. However remember there is a 2 second transient delay on all zones. It will therefore take approximately 2 seconds before the zone registers an alarm (this could be longer, depending on zone type).
LED’s on the respective selected zone(s) will start blinking with a continuous buzzer sound and a red LED light is illuminated next to BT INH location on PSI board.
Pressing ACK acknowledge key stops the buzzer sound and blinking LED automatically turns into continuous lighting.
Pressing RESET key automatically brings panel to its normal condition. A long beep will signify an incorrect entry and will revert back to normal operating mode. The "ALARM
TEST" button will need to be pressed again to re-enter alarm test mode.
NOTE:
This LED is for new IFS-2600 termination boards(NI-2025-01) only.
Page 17
IFS-2600 Fire Indicator Panel Section 3 Operation
DOC-01-009 12
FAULT TEST
FAULT TEST # ENTER
The fault test function momentarily disconnects the detection zone(s) under test and simulates the worst­case condition for fault.
A resistor load equal to worst case fault is placed on the zone continuously for 5 seconds then the zone is returned back to its normal condition.
If several zones are being tested consecutively and are being entered at a rate faster than the 5-second fault timer, the fault timeout will occur 5 seconds after the last entry was completed.
Once the zone has registered a fault, all outputs relating to that zone are initiated similar to a real fault. The zone may be isolated prior to a fault test if desired. This will prevent any outputs from operating. ‘#’ in the above key sequence is the zone number. If only one zone is to be tested, use the appropriate zone number. Alternatively the "ALL" button can be
used to simultaneously test all zones. To perform a fault test on a particularzone or on all zones:
1. Press the "FAULT TEST" button once. The buzzer will give 2 short beeps to indicate that fault test mode has been entered.
2. The LCD display will read "FAULT TEST MODE, ENTER ZONE No.".
3. Enter the zone number ("#") 1-64 or “all”.
4. Press "ENTER".
If a correct entry is made, fault testing on the selected zone(s) commences with a long beep of about 10­15 seconds and an illuminatedfault LED next to the selected zone(s).
A long beep will signify an incorrect entry and the panel will revert back to normal operating mode. The "FAULT TEST" button will need to be pressed again to re-enter fault test mode.
ISOLATE
ISOLATE # ENTER
The isolate function prevents the transmission of alarms or faults from the zones, to the master alarm facility.
‘#’ in the above key sequence is the zone number. If only one zone is to be isolated, use the appropriate zone number. Alternatively the "ALL" button can be
used to simultaneously isolate all zones.
To isolate a particular zone or all zones:
1. Press the "ISOLATE" button. The buzzer will give 2 short beeps to indicate that isolate mode has been entered.
2. TheLCD display will read "ALARM ISOL. MODE, ENTER ZONE No.".
3. Enter the zone number ("#") 1-64 or “all”.
4. Press "ENTER".
A long beep will signify an incorrect entry and will revert back to normal operating mode. The "ISOLATE" button will need to be pressed again to re-enter isolatemode.
Page 18
IFS-2600 Fire Indicator Panel Section 3 Operation
DOC-01-009 13
If a correct entry is made, the zone is immediately isolated. If the zone is already in alarm, all of its alarm outputs are isolated and indicators remain visible.
If the "ALL" function is performed, all zones will be isolated, regardless of their previous state. Performing the "ALL" function for a second time will de-isolate all zones.
RESET
RESET # ENTER
The reset function momentarily disconnects power, and resets all alarm parameters for the zone(s) being reset. This returns the zone back to its "normal" state.
‘#’ in the above key sequence is the zone number. If only one zone is to be reset, type in the zone number. Alternatively the "ALL" button can be used to
simultaneously reset all zones. To perform a reset on a particular zone or on all zones:
1. Press the "RESET" button. The buzzer will give 2 short beeps to indicate that reset mode has been entered.
2. The LCD display will read "ALARM RESET MODE, ENTER ZONE NO".
3. Enter the zone number ("#") 1-64 or “all”.
4. Press "ENTER".
A long beep will signify an incorrect entry and will revert back to normal operating mode. The "RESET" button will need to be pressed again to re-enter reset mode.
If a correct entry is made, resetting of the zone begins immediately. Any alarm indication will be removed immediately; also resetting the zone(s) programmed outputs.
NOTE:
If the Zone is still active after the RESETfunction, it will automatically revert back to
alarm mode.
Page 19
IFS-2600 Fire Indicator Panel Section 3 Operation
DOC-01-009 14
3.5. Standard Outputs
Output Type Description
Standby
Change over relay contact
Normally energised relay: Will de- energise if system volts fall below 21V. This usually means AC has failed and batteries are getting low. I.e. panel is about to shut down.
Brigade Alarm #1
Change over relay contact
Normally de-energised relay: Will energise if requested by the zone output configuration of the non- isolated zone(s) in alarm. (Programmable)
Brigade Alarm #2
Change over relay contact
Normally de-energised relay: Will energise if requested by the zone output configuration of the non- isolated zone(s) in alarm. (Programmable)
Fault
Change over relay contact
Normally energised relay: Will de-energise if a common fault is registered.
Mains Fail (NV)
Change over relay contact
Normally energised relay: Will de-energise if the AC fails
Isolate
Change over relay contact
Normally de-energised relay: Will energise if any zones are isolated.
General Alarm 1
Change over relay contacts
Normally de-energised relay: Will energise if requested by the zone output configuration of the non-isolated zone(s) in alarm. (Non-Programmable)
General Alarm 2
Change over relay contacts
Normally de-energised relay: Will energise if requested by the zone output configuration of the non-isolated zone(s) in alarm. (Non-Programmable)
Bell
Monitored 24 VDC Output 1A Fused
Normally de-energised: Output will energise if requested by the zone output configuration of the non-isolated zone(s) in alarm. Will remain energised until alarm is reset or warning system is isolated.
Warning System
Monitored 24 VDC Output 1A Fused
Normally De-energised: Output, will energise if requested by the zone output configuration of the non- isolated zone(s) in alarm.
Ancillary (ACF)
24 VDC Output 1A Fused
If ancillary is set as non-latch: Ancillary will remain energised until alarm(s) is reset. If ancillary is set as latching: Ancillary will remain energised until ancillary is manually reset from the keypad. Even if the zone has been reset.
Door Holder
24 VDC Output up to 3A
Normally energised 24VDC output: Will de-energise on general alarm. NOTE: This output is isolated through the ACF Isolate Function.
Auxiliary Power
24 VDC Continuous
Power output for use with ancillaries (500mA maximum).
Mimic Outputs
Serial four wire mimic outputs
This output mimics the status of all alarm zones fitted on the panel to a remote mimic panel in the building.
Table 3-1, Standard Outputs
NOTE:
Normally energised (fail safe) relayMonitored circuit, EOL resistor or load is required.
Page 20
IFS-2600 Fire Indicator Panel Section 3 Operation
DOC-01-009 15
3.6. Relay Expansion Boards
The maximum number of boards that can be fitted is eight (i.e.: 64 relays). Each board contains 8 change-over relay outputs. Relays can be programmed to simulate:
BrigadeAlarm Relay #1 BrigadeAlarm Relay #2 Fault Relay MainsFail Relay Isolate Relay General Alarm Relays Bell Output Ancillary Output Door Holder Output Door Switch Reset
or can be used to
3.7. Printer Output
Located on the main termination board, a portable serial printer may be connected to the DB9 serial port provided.
Most standard IBM compatible serial printers are suitable for this operation, which uses hardware handshaking and will be enabled automatically.
AND MAP”
“OR MAP” “MAP FAULT” “MAP ISOLATE” “MAP ISO/FLT”
Up to 5 zones in Alarm Up to 5 zones in Alarm Up to 5 zones in Fault Up to 5 zones in Isolate Up to 5 zones in Fault or Isolate
Page 21
IFS-2600 Fire Indicator Panel Section 4 Installation
DOC-01-009 16
Section 4 - Installation
4.1. Compatible Detectors
Make
Model
Type
Model Number
System Sensor Thermal Type A 5451AUS System Sensor Thermal Type A 51A51 System Sensor Thermal Type B 4451AUS System Sensor Thermal Type B 51B51 System Sensor Thermal Type B Sealed 885WP-B System Sensor Thermal Type C 51C51 System Sensor Thermal Fixed TEMP 63
o
5151AUS
System Sensor Thermal ROR 63
o
5151RAUS
System Sensor Thermal Fixed TEMP 90
o
5151HAUS
System Sensor Thermal ROR 90
o
5151HRAUS
System Sensor Smoke Photo-Optical 2151AUS System Sensor Smoke Photo-Optical 2151BAUS System Sensor Smoke Ionisation 1151AUS System Sensor Smoke Beam BEAM1224(S) System Sensor Smoke Duct DH-100LP System Sensor Smoke Photo-Duct D2
Apollo Thermal Type A Series 60 Apollo Thermal Type B Series 60 Apollo Thermal Type C Series 60 Apollo Thermal Type D Series 60 Apollo Smoke Ionisation Series 60 Apollo Smoke Photo Optical Series 60
Hochiki Thermal Type A DCA-B-60R MkV Hochiki Thermal Type A DCC-A Hochiki Thermal Type A DCD-A Hochiki Thermal Type B DFE-60B Hochiki Thermal Type B DFJ-60B Hochiki Thermal Type C DCA-B-90R Mk1 Hochiki Thermal Type C DCC-C Hochiki Thermal Type C DCD-C Hochiki Thermal Type D DFE-90D Hochiki Thermal Type D FDJ-90D Hochiki Thermal Cool Room Type B sealed DFG-60BLKJ Hochiki Smoke Ionisation SIH-AM Hochiki Smoke Ionisation SIJ-ASN Hochiki Smoke Photo Optical SLK-A Hochiki Smoke Photo Optical SLR-AS
Olsen Thermal Type A T56B-T6A Olsen Thermal Type B T56B-T6B Olsen Thermal Type C T56B-T6C Olsen Thermal Type D T56B-T6D Olsen Smoke Ionisation C24B Olsen Smoke Photo Optical P24B
Panelect Thermal Type A PFS-A Panelect Thermal Type B PFS-B Panelect Thermal Type C PFS-C
Page 22
IFS-2600 Fire Indicator Panel Section 4 Installation
DOC-01-009 17
Panelect Thermal Type D PFS-D Panelect Smoke Ionisation PFS-I Panelect Smoke Ionisation PFS-I , MkII Panelect Smoke Photo Optical PFS-P Panelect Smoke Photo Optical PFS-P, MkII
Table 4-1, Compatible Detectors
4.2. Specification
General
Approvals:
Australian Standard AS4428.1 1998 Approval No AFP-1553 C-Tick Approval No. N1336
Environmental Limits:
-10 Deg.C to +55 Deg.C Dry heat. +40 Deg.C @ 93% Relative Humidity.
Specification for IFS-2600 in CAB650/CAB900:
Cabinet Zinc Sealed Steel 1.2mm, Powder Coated, Hinged Inner & Outer
Door Outside Dimensions Refer to Figure 4-1 & Figure 4-2 for dimensions Fuses
(NI-2025-01 & NI-2017-01 Boards)
Warning System Fuse F2
M205 1A
Bell Fuse F4
M205 1A
ACF Fuse F6
M205 1A
AUX Fuse F8
M205 1A Slow Blow Door Holder Fuse F10 M205 3A AZF Circuits Current Limited 40mA
E.O.L Resistor on AZFs, monitored outputs, Bells, Warning system, ACF
4K7 Ohms
Page 23
IFS-2600 Fire Indicator Panel Section 4 Installation
DOC-01-009 18
Specification for IFS-2608 & IFS-2624:
Cabinet Zinc Sealed Steel 1.6mm, Powder Coated
Hinged Inner & Outer Door
Outside Dimensions 2608 (8 zones) 394mm H x 390mm W x 180mm D*
2624 (24 zones) 750mm H x 390mm W x 180mm D* *Note: the depth quoted is including the door and break glass.
Fuses (IFS-2005 & IFS-2006
Boards)
Panel Supply Fuse F1 M205 5A Battery Charger Fuse F2 M205 3A Battery Protection Fuse F3 Polyfuse 3A External Supply Fuse F4 M205 7A Door Holder Fuse F5 M205 3A Aux Power Output Fuse F6 M205 1A Slow Blow Bell Fuse F7 M205 1A Warning System Fuse F8 M205 1A ACF Fuse F9 M205 1A AZF Circuits Current Limited 40mA
E.O.L Resistor on AZFs, monitored outputs, Bells, Warning system, ACF
4K7 Ohms
Table 4-2, IFS-2600 Panel Configuration
Page 24
IFS-2600 Fire Indicator Panel Section 4 Installation
DOC-01-009 19
CAB 650 Mechanical Dimensions:
Figure 4-1, CAB650 Dimensions
CAB 900 Mechanical Dimensions:
Figure 4-2, CAB900 Dimensions
Page 25
IFS-2600 Fire Indicator Panel Section 4 Installation
DOC-01-009 20
4.3. Overview of IFS-2600 System Equipment
NI-2025-01
DISP
PCB816
MIMICPANEL
12VBATTERY 12VBATTERY
+ +
-
-
MAINPROCESSOR BOARD
MAINTERMINATION BOARD
SERIALPRINTER
POWERSUPPLYUNIT
240V ISOL
S/W
MAINSSUPPLY
240V AC
NI-2004-01
RELAY BOARD
IFS803
RELAY BOARD IFS803
RELAY BOARD IFS803
ZONE
EXP
PCB804
ZONE
EXP
PCB804
POWER
NI-2017-01
ZONE
INPUTS
1-8
ZONE
INPUTS
9-16
ZONE
INPUTS
32-40
8RELAY OUTPUTS
1-8
8RELAY OUTPUTS
9-16
8RELAY
32-40
MAX 8PCB803
OUTPUTS
CABLEC3
CABLE C5
CABLEC1
CABLE C3
CABLEC3
4CORECABLE
4CORECABLE
CABLEC8
MAX 120M
ZONEDISPLAYS1-8
IN
IN
IN OUT
OUT
OUT
OUT
LAPTOP
P/N130
16ZONE
DISP
PCB816
IFS810 MIMICDRV P/N2201 IFS811B INDBRD P/N2202
IFS812DISPLAYBRD P/N2122
DB-9 FEMALE
(1FOR EACH8 ZONES)
OUTPUTS
8ZONE
LAST DISPLAYCANBE8/16 OTHERSMUSTBE16ZONE
CABLE C9
CABLE C32
PCB1125
BELL/ACF
3CORECABLE
SUPPLY BOARD
RX, TX,GND
TX,CTS, GND
FORDETAILS, REFERTO POWERSUPPLYSECTION
ASEBRACKETS CODERED #10115
ROMTEK #10117 TYCO #10116
RELAY BOARDCABLES 6WIRE
C1 60mm #130 C3 230mm #125 C6 2000mm #1860 C7 630mm #1861 C9 11000mm #1863
UPGRADE KITS
8WAYRELAYBRD P/N1469 8ZONEUPGRADE P/N 8056 16ZONEUPGRADE P/N 8053
Page 26
IFS-2600 Fire Indicator Panel Section 4 Installation
DOC-01-009 21
4.4. Power Supply
IFS-2600 Panels use two kinds of power supply with different set of boards.
Power Supply (Brick power supply – NPS-2/NPS-5/NPS-11):
This type of power supply is used in new IFS-2600 panels in conjunction with NI-2025-01 and NI-2017-01 boards to provide external & internal power supply to the panel. (Refer to Section 4.4.1 for more details)
Power Supply (240V/30V AC TRANSFORMER):
This type of power supply is used in older IFS-2600 panels in conjunction with IFS-2005 and IFS-2006 boards to control & power the panel (Refer to Section 4.4.2 more details)
4.4.1 Power Supply Ratings & Settings for NI-2017-01 & NI-2025-01 Boards
Brick Power Supply with NI-2025-01 Termination Board and NI-2017-01 Power Supply Interface:
This supply performs a dual function; to power panel and to charge the batteries. The supply is monitored by an NI-2017-01 interface board, which performs all the monitoring and testing functions required to meet AS4428.5
Battery testing is automatic and user intervention is not required. Three models are available with output ratings of 2.6A, 5.6A, and 11.7A.
Figure 4-3, Power Supply Unit schematics
MAINPROCESSORBOARD
NI-2004-01
ZONE DISPLAYS1-8
MAIN TERMINATIONBOARD NI-2025-01
POWERSUPPLYINTERFACE NI-2017-01
27V SupplyIn
J5
J2
27V
0VPOWERSUPPLYUNIT
ACTIVE NEUTRAL
EARTH
240V AC MAINSIN
Page 27
IFS-2600 Fire Indicator Panel Section 4 Installation
DOC-01-009 22
Power Supplies NPS-2, NPS-5, NPS-11
AC Operational Voltage
NPS-2 AC 100-240V; 50/60Hz; 1.3A NPS-5 AC 100-240V; 50/60Hz; 2.5A NPS-11 AC 100-240V; 50/60Hz; 5A
Output Current @ 27.3V (Max)
NPS-2 2.6 Amp NPS-5 5.6 Amp
NPS-11 11.7 Amp Output Voltage 27.3 VDC Output Ripple 200 mV Mains Fail Within 30 secondsof Mains Failure Charger Fault Below 26.9V or Above 27.7V
Battery Fault
Within 30 seconds of Battery disconnection or when Battery voltage
drops below 24V during a battery test
Battery Test
Automatic. One Hour of quiescent panel load every 6.65± 4 days.
NOTE: The battery fault is latched until a successful battery test is
performed.
Table 4-3, Power Supply Settings
DIP Switch Settings on Power Supply Interface (PSI)
Dip Switches on PSI (NI-2017-01) board SW1.1, SW1.2, SW1.3 & SW1.4 should always be set to OFF position for automatic mode.
Figure 4-4, DIP Switch settings on PSI
Page 28
IFS-2600 Fire Indicator Panel Section 4 Installation
DOC-01-009 23
4.4.2. Power Supply Ratings & Settings for IFS-2005 & IFS-2006 Boards
Figure 4-5, Power Supply Schematics (IFS-2004, IFS-2005 & IFS-2006 Boards)
IFS -2005
12V BATTERY 12VBATTERY
+ +
-
-
MAINPROCESSORBOARD
MAINTERMINATION BOARD
240V/30V AC
100 VA
TRANSFORMER
2600/DHTX
100 VA
TRANSFORMER
240V ISOL S/W
MAINS SUPPLY
240 V AC
IFS -2004
POWER
IFS -2006
ZONE DISPLAYS1-8
PANEL
POWER
D/HOLDER POWER
OPTION
SUPPLY BOARD
ACTIVE NEUTRAL EARTH
Important Note:
After a power failure, the battery will only reconnect to the charger if the battery voltage is above approximately 20V ± 2V.
A battery fault will be generated in the event that the battery does not automatically reconnect. This is to ensure that a faulty or dead flat battery (due to an extended power failure) does not bring the entire system down.
In order to reconnect a flat battery, it is necessary to disconnect the battery from the panel and charge it externally. The battery should be thoroughly tested before returning it to service.
In the event that an external charger is not available, the battery may be trickle charged above 22V via a 30 ohm, 5W resistor connected between the 24v Aux Output and the battery positive terminal. A 1N4004
Diode (Notifier part number #286) or similar should also be fitted in series with the resistor to stop the
battery from pulling down the main panel voltage. Trickle charging the battery by this method may take several hours to bring it up to the minimum level.
The battery can then be reconnected to the panel for charging via the internal battery charger. It is important that the voltage on the battery be monitored to ensure that it is charging. The battery should then be left for 24 hours and then fully tested to ensure that no damage has occurred due to the deep discharge.
Page 29
IFS-2600 Fire Indicator Panel Section 4 Installation
DOC-01-009 24
Panel Power Supply
With batteries disconnected and no alarms present, measure voltage across the 0V and MAIN test points on the 2006 power supply board and, if necessary, adjust the multi-turn potentiometer VR2 until voltage is
26.5V 0.05V (26.45V – 26.55V). Current limiting is fixed and field adjustment is not possible.
AC Input 30 VAC +10% - 15% Output Current 3.0 AMPS Output Voltage 26.5 VDC Current Limit 3.0 AMPS Output Ripple 50 mV
Battery Charger
With batteries disconnected and no alarms present, measure voltage across the 0V and CHARG test points on the 2006 power supply board and, if necessary, adjust the multi-turn potentiometer VR1 until voltage is 27.3V 0.05V (27.25V– 27.35V).
Current limiting is factory preset and field adjustment is not required.
AC Input 30 VAC +10% -15% Output Current 1.5 AMPS Output Voltage 27.3 VDC Current Limit 1.5 AMPS Output Ripple 200 mV
External Power Supply (if fitted)
With batteries disconnected and no alarms present, measure voltage across Remote Input terminals on IFS-2005 and adjust the voltage on the external power supply until the voltage is 26.5V 0.5V (26.0V –
27.0V). Note: This voltage is not critical for the operation of the IFS-2600 panel, but the voltage must not go outside the limits as specified for the field ancillariesthat it powers.
This supply is used in addition to the internal power supply for large systems. Its primary function is to power any additional ancillary loads of the FIP up to 7 amps. This supply meets the requirements of AS4428.5.
IFS-2006 – JP1 External PS Monitoring
When using external power supply, JP1 link on IFS2006E must be fitted to enable external PSU monitoring.
Power Supply Comparator Reference Voltage TP10
With the panel in the quiescent mode, measure voltage between system 0V and TP10. Adjust multi-turn potentiometer VR3 until voltage is 7.0V 1% (6.93V – 7.07V).
Non Adjustable Test Points
TP8 = 5.0 VDC 5% 5VDCPOWER SUPPLY TP5 = 12.0 VDC 5% 12VDC POWER SUPPLY
If these test point voltages are not correct, please return the main termination board to the factory for repair.
Page 30
IFS-2600 Fire Indicator Panel Section 4 Installation
DOC-01-009 25
Important Notes: This applies to IFS-2005/IFS-2006 Boards without ECN09-034 modification!!
When using external power supply, JP1 link on IFS2006E must be fitted to enable external PSU monitoring.
If this supply is used to power a NI-2008 gas module, the following additional components are required to ensure a break free change over from the mains supply to the panel battery in case of mains fail condition.
1. A 6A4 or P600G rectifier diode (Notifier part number #266) is to be installed in series with the external
+27V output of the IFS-2600 termination board.
2. A 3300µF 50V Electrolytic Capacitor (Notifier part number #1248) should be installed across the +27V and 0V of the ancillary device.
4.4.3. Battery Type and Capacities
In general, any Sealed Lead Acid (SLA) Battery, or Wet Lead Acid Battery designed for stationary use is compatible with the IFS-2600 Fire Indicator Panel. Automotive batteries must not be used. The use of Nickel Cadmium batteries is not recommended.
Table 4-4, Battery Capacities
Manufacturer
Type
Number
Voltage
Capacity (Ah)
Qty Required
Olympic Batteries SLA CJ12-7 12 7 2 Olympic Batteries SLA CJ12-12 12 12 2 Olympic Batteries SLA CJ12-18 12 18 2 Olympic Batteries SLA CJ12-26 12 26 2 Olympic Batteries SLA CJ12-33 12 33 2 Olympic Batteries SLA CJ12-40 12 40 2 Olympic Batteries SLA CJ12-85 12 85 2 Olympic Batteries SLA CJ12-100 12 100 2
CAUTION:
Risk of explosion if battery is replaced by an incorrect type. Dispose of used batteries according to Manufacturer Instructions
AC
INPUT
24V
0V
-+
24V
0V
REMOTE
OUTPUT
REMOTE
INPUT
BATT
INPUT
EXTERNAL
POWER
SUPPLY
OUTPUT
NI-2008 GAS
SUPPRESSION
MODULE
3300uF
6A4
Page 31
IFS-2600 Fire Indicator Panel Section 4 Installation
DOC-01-009 26
4.5. Technical Description
General
The IFS-2600 in its most basic form comprises of three boards, the main control board, the main termination board and the power supply board.
The main control board contains the Microprocessor, EPROM, RAM and E2ROM. The main control board also has the liquid crystal display and keypad attached. All of the "delicate" electronics have been placed on this board. The main control board complete with the inner door is easily removed during installation to avoid damage and allow greater access to the field terminals.
The main termination board contains one power supply for 5V logic, and connectors for a Power Supply and Battery Charger daughter board, the first eight zones, all common outputs and the printer interface. All charger settings, fuses etc are located on this board. The Power Supply and Battery Charger board contains two switch mode regulators, 26.5V for the panel power & 27.3V for the battery charger.
Up to seven (7) zone expansion boards can be added to the system to increase its detection capability. These boards contain the same electronics as on the main termination board for zone scanning. Addressing is by a jumper that selects which group of eight zones the board refers to.
Up to four (4) zone indicator boards can also be added. These boards will display the status of the zone expansion boards fitted.
Up to eight (8) relay boards can be added. These boards contain 8 change-over relay contacts, each rated at 1 amp. These boards require no addressing, as they work on a serial data chain. Output 1 is the closest output to the main board.
Transient Suppression
The IFS-2600's transient protection comprises of Dual Transorb input traps, inductive paths on incoming PCB tracks, circuit board planes and metal oxide varistors on outputs. These devices are all self-resetting.
Current Consumption
Zones
Fitted
Quiescent
Current
Quiescent + 2 AZF'S in alarm +1A of Bell
+1 Amp ACF
8 150 mA 2.23 AMPS 16 250 mA 2.33 AMPS 24 350 mA 2.43 AMPS 32 450 mA 2.53 AMPS 40 550 mA 2.63 AMPS 48 650 mA 2.73 AMPS 56 750 mA 2.83 AMPS 64 850 mA 2.93 AMPS
Table 4-5, Current Consumption
NOTE:
Each installation would require individual battery calculations to be performedfor load Capacity and power supply capacity.
Each IFS-717 relay board can add 370 mA current per board (when in alarm).
Page 32
IFS-2600 Fire Indicator Panel Section 4 Installation
DOC-01-009 27
AZF Description
The AZF's on the IFS-2600 are monitored and scanned by custom thick film hybrids. These hybrid IC's significantly reduce the possibility of false alarms and improve product efficiency and reliability.
The total Alarm Zone loop resistance is the sum of the end of line resistor (EOLR 4K7) plus all the parallel connected detector loads.
AZF Supervisory Current
The supervisory current flows through the external terminal AZF+ through the field cable and to the end of line resistor (EOLR), returning to the panel at AZF- terminal. Parallel connected, across the 2-wire pair field cable, are a number of the previously listed detectors. During the quiescent state there is essentially an open circuit across the + and - terminals of the detector base. The maximum number of detectors that can be installed on each AZF is dependent on the type of detector and is listed in the IFS-2600 ActivFire
®
listing. In an alarm state, a 560-ohm resistor is connected across the detector base causing additional loop current
to flow. This is sensed by the AZF to produce an alarm output. Removal of the E.O.L. resistor (in a non alarm state) or the interruption of the supervisory current will produce a fault signal in the AZF.
As described above, the level of current is used to define the status of the alarm zone: -
I = 3.5 mA and below FAULT I = 4.0 - 5.0mA at 24V QUIESCENT I = 16 mA to 40 mA (current limited) ALARM
The zone current is used by the hybrid IC to determine the condition of the zone as above. This information is then transferred to the microprocessor for processing.
Overload Protection
Note: Refer to SpecificationsSection 4.2 for details.
Zone Overload Self Reset
If a zone is overloaded by an accidental short to earth on an AZF circuit, the zone will automatically shut down and produce a fault. Once this happens the panel will automatically recheck the zone every 60 seconds and once the overload is removed, restore power and the fault will clear.
Page 33
IFS-2600 Fire Indicator Panel Section 4 Installation
DOC-01-009 28
Manual Call Point (MCP)
For IFS-2005 Boards:
Panel MCP connection is achieved by wiring from the zone, to the MCP, to the MCP loop then out to the field with the EOL across the last detector. The MCP is the first device on the circuit and both fault and alarm conditions will be indicated.
Figure 4-6, Manual Call Point (MCP) for IFS-2005/2006 Boards
For NI-2025-01 Boards:
In case of these boards, MCP connections are achieved by wiring from MCP Loop (+ & -) terminals on main termination board to the terminals (3 & 4) on MCP. The MCP loop is in parallel with Zone 1 and no EOL is required.
Figure 4-7, MCP connection for NI-2025-01/2017-01
Page 34
IFS-2600 Fire Indicator Panel Section 4 Installation
DOC-01-009 29
IFS-2600 MIMIC
MIMIC Outputs:
A mimic output is standard on all IFS-2600 panels. This output mimics the status of all alarm zones fitted on the panel to a remote mimic panel in the building.
The four (4) wire serial mimic decoder board can be connected to the panel by using a 4-core cable. 4 conductors are used, 24VDC, 0V, data, & clock connecting directly to their respective terminals at the panel and the mimic.
The decoder boards contain up to 64 alarm LED indicators, 64 fault LED indicators, a sounder, sounder mute, lamp test facility and conventional mimic outputs at the rear of the board for interfacing to conventional mimic panels or driving auxiliary relay outputs up to a maximum of 20mA.
MIMIC
Panel
Specification
Maximum Number of Mimics
7
Cable used for Connection
0.75mm, 4-core for Power & Serial Data Connections
Maximum Length of Cable
120 Metres
Printer Output
The printer port is designed to be used during testing and commissioning of the panel. The serial printer will report alarms and faults together with the date and time of the event. The printer can also be used during “walk test” mode to produce a history of the test and can also be used to print current programming configuration.
A DB9 plug male is provided at the top of the main termination board. This communication port will communicate with an IBM compatible serial printer (ASCII printer) with the following settings.
Baud Rate 1200 bps Data Bits 8 Stop Bits 1 Parity None Handshaking DTR
Cabling to the printer requires a 4-core telephone style cable with a maximum length of 10 metres. A DB9 socket is required at the panel end. The printer end is dependent on the type of printer used but is usually a male DB25. Connection is as follows. A 5-core cable can be used for both comms and printer functions
IFS-2600 END
P
rinter
END
DB9 FEMALE
DB25 MALE
DB9 MALE
2 RX (only for programming) 2 3 3 TX 3 2 5 GND 7 5 7 RTS ( do not use) (5) (8) 8 CTS ( only for printer) 4 7
Table 4-6, Cable connection
NOTE:
Refer to IFS-2600 Equipment Overview (Section 4.3) & MIMIC Connection Diagram (Section 6.4.5) for more details about connecting a mimic to the standard IFS-2600 panel.
Page 35
IFS-2600 Fire Indicator Panel Section 4 Installation
DOC-01-009 30
Programming By Computer
Programming of the zones, relays, global functions and time can be set with the DOS based program “2600/SW” using the printer port (Cannot be used with Windows XP).
After the cable is installed, the program can be run and the menu will prompt for the available functions.
Alarm Threshold Comparator TP7 (For IFS-2005 & IFS-2006 Boards Only)
With the panel in the quiescent mode, measure and take note of the INTERNAL 24V DC POWER SUPPLY as above.
Measure the voltage between system 0V and TP7. Adjust multi-turn potentiometer VR4, and adjust until the voltage is as per the following table.
Rail Voltage
3.3V Setting
Range
20.6 2.833 2.80 to 2.86
21.0 2.888 2.86 to 2.92
21.5 2.956 2.93 to 2.99
22.0 3.025 2.99 to 3.06
22.5 3.094 3.06 to 3.12
23.0 3.163 3.13 to 3.19
23.5 3.231 3.20 to 3.26
24.0 3.300 3.27 to 3.33
24.5 3.369 3.34 to 3.40
25.0 3.438 3.40 to 3.47
25.5 3.506 3.47 to 3.54
26.0 3.575 3.54 to 3.61
26.5 3.644 3.61 to 3.68
27.0 3.713 3.68 to 3.75
27.5 3.781 3.74 to 3.82
27.6 3.795 3.76 to 3.83
28.0 3.850 3.81 to 3.89
Table 4-7, Voltage Adjustments (Alarm)
2600
Figure 4-8, Programming Options
Page 36
IFS-2600 Fire Indicator Panel Section 4 Installation
DOC-01-009 31
Fault Threshold Comparator TP6 (For IFS-2005 & IFS-2006 Boards Only)
With the panel in the quiescent mode, measure and take note of the INTERNAL 24V DC POWER SUPPLY as above.
Measure the voltage between system 0V and TP6. Adjust multi-turn potentiometer VR1, and adjust until the voltage is as per the following table.
Rail
Voltage
0.6V
S
etting
Range
20.6 0.600 0.59 to 0.61
21.0 0.612 0.61 to 0.62
21.5 0.626 0.62 to 0.63
22.0 0.641 0.63 to 0.65
22.5 0.655 0.65 to 0.66
23.0 0.670 0.66 to 0.68
23.5 0.684 0.68 to 0.69
24.0 0.699 0.69 to 0.71
24.5 0.714 0.71 to 0.72
25.0 0.728 0.72 to 0.74
25.5 0.743 0.74 to 0.75
26.0 0.757 0.75 to 0.76
26.5 0.772 0.76 to 0.78
27.0 0.786 0.78 to 0.79
27.5 0.801 0.79 to 0.81
27.6 0.804 0.80 to 0.81
28.0 0.816 0.81 to 0.82
Table 4-8, Voltage Adjustments (Fault)
Configuration Jumpers
IFS-2004 - JP3 CPU Default
Holding a short across these pins for 5 seconds during start-up causes the panel to reset to standard factory defaults. The panel will give 4 beeps after reset, to acknowledge default on start-up.
IFS-2004 - JP4 CPU Program Disable
When fitted, jumper between these pins to inhibit program changes.
IFS-2004 - JP5 CPU Reset
With panel operating, a momentary short acrossthese pins will cause a CPU restart.
IFS-2005 & NI-2025-01 – JP2 DOOR HOLDER BYPASS
If zoned door holder outputs are required and is to be done external to the main termination board, then the main door holder release needs to be disabled. Fitting a link across JP2 on IFS2005 PCB does this.
NOTE:
Door holder output is only enabled if optional door holder transformer is fitted. SW1 must be linked on IFS-2004 CPU board prior to Version 6 Firmware.
Page 37
IFS-2600 Fire Indicator Panel Section 4 Installation
DOC-01-009 32
IFS804 - JP1-7 Zone Board Addressing
Jumper JP1 to JP7 on zone expansion board IFS-804 selects the addressing for the zones. Place jumper in link position for the appropriate 8 zones to which the expansion board applies
Figure 4-9, Zone addressing
Page 38
IFS-2600 Fire Indicator Panel Section 4 Installation
DOC-01-009 33
4.6. Placing Into Operation
Suitably qualified technicians must install the panel. The following check procedures are recommended after every installation and prior to initial power-up.
A thorough visual inspection should be made to every aspect of the fire panel. This includes loose wire, metal filings, loose circuit boards,loose cabling, damage in transit etc.
All problems must be rectified immediately as they could cause incorrect operation or permanent damage to the equipment.
Equipment as Fitted
QTY Description Code
1 MAIN CONTROL BOARD NI-2004-01 1 MAIN TERMINATION BOARD NI-2025-01
1 MAIN POWER SUPPLY INTERFACE NI-2017-01
Table 4-9, Equipment fitted
Initial Checklist
System general appearance good Cabinet colour and condition good Cabinet Lock – Can be opened with L003 key All circuit boards firmly fastened Manual call point fitted & functional Viewing window clear and firmly secured Cable entries adequately sealed 240VAC mains cabling is correctly terminated All earthing secured All ribbon cables firmly secured All operationalzones adequately identified All fuses correct value and fitted properly All othermodules securely fitted AS 4428 Manufactured & Tested label affixed
You are now ready to power up the IFS-2600 Fire Indicator Panel.
NOTE:
Additional Equipment may depend on required configuration.
Page 39
IFS-2600 Fire Indicator Panel Section 4 Installation
DOC-01-009 34
Power up Checklist
Ensure batteries are disconnected Turn mains switch to "on" The "mains on" LED should light Allow 15 seconds for the panel to perform its start up tests Connect batteries Pulsing Heartbeat on the Termination Board (For new Board only)
Functional Tests
Primary ac supplyvoltage: 200 or 220 or 240vac +10% as required Charger output voltage without batteries: 27.3v dc Keypad functional Perform auto test
LED’s all functional LCD backlight functional LCD Screen (Display) functional Zone fault detection
Zone alarm detection Internal Buzzer operating MCP loop wired to zone number 1(For new Board it is connected to +VE & -VE) Test auxiliary power output Test bell output Test warning system output Test ACF output Test door holder output (optional) Test bell output supervision Test warning system output supervision Test ACF output supervision Test brigade alarm relay #1 Test brigade alarm relay #2 Test standby relay (normally energised) Test fault relay (normally energised) Test mains fail relay Test isolate relay Test general alarm relays (2) Test relay boards (if fitted) Test open collector output boards (if fitted) Press battery test button on Termination Board BTST/RST twice (For NI-2025-01 &
NI-2017-01 boards only)
If batteries are flat, allow 24hrs to charge and then re-test
Page 40
IFS-2600 Fire Indicator Panel Section 4 Installation
DOC-01-009 35
Fault Record
FAULT CORRECTION DATE
TESTS SATISFACTORILY COMPLETED.
TESTED BY _______________________________
SIGNATURE _______________________________
DATE OF TEST ____________________________
If all faults have been rectified and all tests are completed satisfactorily, the IFS-2600 fire indicator panel is now ready for operation.
Page 41
IFS-2600 Fire Indicator Panel Section 5
Programming
DOC-01-009 36
Section 5 - Programming
5.1. Program Mode
Press the following buttons in order shown to enter programming mode.
PREVIOUS
NEXT
SELECT
EXIT
ENTER
Programming Mode
The liquid crystal display will display all messages and prompts required to program the IFS-2600 Panel. Only the "PREVIOUS","NEXT","SELECT","EXIT" AND "ENTER" keys are used in programming mode. All
other keys will give an error beep and should be ignored. Alarm detection is not affected during the programming function but you must exit programming mode if
any other panel functionsare to be performed including acknowledge and reset of alarms.
EXIT
SAVE CHANGES
YES NO
Programming Hierarchy
ZONES RELAY
GLOBAL PRINT
Zones
TYPE
OUTPUT
STD LATCHING INDICATE STANDARD LATCHING AVF I BELL NON LATCH IB GENERAL NON LATCH 20S IBG ACF OUT TIME DELAY 10S IBGA BRIGADE 1 TIME DELAY 20S IBGA BRIGADE 2 TIME DELAY 30S IBGA BRIGADE 1 & 2 TIME DELAY 40S TIME DELAY 50S TIME DELAY 60S
NOTE:
Refer to appendices for detailed explanation of functions.
Page 42
IFS-2600 Fire Indicator Panel Section 5
Programming
DOC-01-009 37
Relays
TYPE
MAPPING
ISOLATE RELAY ANCILLARY OUTPUT (ACF) BRIGADE RELAY #1 BRIGADE RELAY #2 FAULT RELAY MAINS FAIL RELAY GENERAL ALARM RELAY BELL OUTPUT DOOR HOLDER RELAY MAP - AND (00)(00)(00)(00)(00) MAP - OR (00)(00)(00)(00)(00) MAP - FAULT (00)(00)(00)(00)(00) MAP – ISOLATE (00)(00)(00)(00)(00) MAP – ISOLATE / FAULT (00)(00)(00)(00)(00) DOOR SWITCH RESET
Global
ACF
AVF
RELAY
TIME
NON-LATCHING ND DISABLED MAP RELAY (XX) >>> (DD) / (MM) / (YY) LATCHING ND 2 MINUTES FROM ZONE XX (HH) : (MM) NON-LATCHING NE 3 MINUTES LATCHING NE 4 MINUTES
5 MINUTES
ND: = NORMALLY DE-ENERGISED NE: = NORMALLY ENERGISED
Print
PRINT
PRINTS OUT CURRENT CONFIGURATION
Main Menu
(ZONES) RELAYS
GLOBAL PRINT
Use the "NEXT" & "PREVIOUS" keys to scroll through "ZONES" "RELAYS" "GLOBAL" "PRINT" and wrap around. Once the desired option has been highlighted, pressing the "SELECT" button will select it.
Pressing "EXIT" at this stage will exit programming mode.
Page 43
IFS-2600 Fire Indicator Panel Section 5
Programming
DOC-01-009 38
EXIT Programming Mode
SAVE CHANGES YES (NO)
Use the "NEXT" & "PREVIOUS" keys to scroll through "YES" & "NO". Once the desired option has been highlighted, pressing the "SELECT" button will select it.
Highlighting "YES" and pressing "SELECT" will write all changes made to the system memory (E2ROM) and the panel will then restart.
Highlighting "NO" and pressing "SELECT" will ignore any changes made to the programming and exit back to normal panel operation without restarting.
WARNING!!
The above action causes the panel to drop any door holders / air-conditioning if connected.
NOTE:
This does not apply to saving changes to the time. Changes to time are saved immediately the select key is pressed when in the time adjustment menu.
Page 44
IFS-2600 Fire Indicator Panel Section 5
Programming
DOC-01-009 39
5.2. Zone Options & Programming
5.2.1. Zone Options
Description of Alarm Zone Types
Different zone types can be selected using the programming mode. Each zone can be selected as any one of the following:
Type
Description
Input Delay
1 Standard Latching 2 seconds 2 Standard Latching 2 seconds with AVF 3 Non Latching 2 seconds 4 Non Latching 20 seconds 5 Time Delay 10 seconds 6 Time Delay 20 seconds 7 Time Delay 30 seconds 8 Time Delay 40 seconds 9 Time Delay 50 seconds 10 Time Delay 60 seconds
Latching Type
Once an alarm condition is received from the detector, the alarm zone will start a timer, if after 2 seconds the detector is still activated the alarm zone will register an alarm condition. Indicators will illuminate and alarm functions are initiated immediately, unless zone is set as AVF - refer Appendix C.
The alarm zone will remain in alarm until manually reset. A reset is performed by interrupting the power to the detector for 0.5 seconds and returning the alarm zone
back to its quiescent state. If an alarm is still present in the detector area, the detector will re-activate and the 2-second timer will be re-initiated.
Non – Latching Type
A temporary actuation device (e.g. Flow Switch) is usually connected to this type of alarm zone. Once a signal has been received CONTINUOUSLY for 2 seconds or 20 seconds (dependant on programming) an alarm will be registered causing the alarm LED to flash and alarm functions will be performed as programmed.
The alarm group will remain in alarm until the actuating device no longer reports a signal. When actuating device signal is clear, the alarm is cleared, causing the zone to power down for 0.5 seconds and return back to normal state.
Time Delay AZF
The time delay AZF zone can be preset to any one of 6 time delays in the initial setup. This type of zone is used for AS1668 smoke detection zones. Zone timing etc is as per AS1668-1991.
Example: Timer #1 = 60 seconds Once the first alarm is received, the alarm LED is turned on steady; this indicates "PARTIAL ALARM" condition.
The detector is then reset (by removing its power for 0.5 seconds) and a timer is also started for 60 seconds (TIMER#1). Another timer of 10 seconds (TIMER#2) is also started. The zone must respond again within these 10 seconds (TIMER#2) to register another alarm.
Failure to receive another alarm within this 10-second period will return the zone back to its normal state immediately and extinguish the alarm LED.
Page 45
IFS-2600 Fire Indicator Panel Section 5
Programming
DOC-01-009 40
If an alarm is received, the detector is reset again and TIMER#2 is also reset.
This monitoring continues until the 60-second timer (TIMER#1) has elapsed and then the NEXT alarm signal will trip the zone into "FULL ALARM". This is the stage at which all mapped relays, bells etc. will operate.
When "FULL ALARM" condition is reached, a third timer (TIMER#3) of 70 seconds is started. This timer is used to prevent "hunting" of air conditioning fans as specified in AS1668.
TIMER#2 is kept operating and alarm signals are still to be received as per previous. Alarm signals are required continually to keep the zone in "FULL ALARM". Each time another alarm is received Timer#3 is restarted (i.e. 70 seconds). Failure to comply with TIMER#2 will result in the zone being returned back to its NORMAL state once TIMER#3 has elapsed.
Zone Output Configurations
Once a zone has alarmed, its output functions are as programmed to one of the following output types.
Refer to technical specification for descriptionsof output types. The zone can also be programmed to operate one (1) or more relay contacts through the use of the relay
mapping output feature.
5.2.2. Zone Programming
Select ZONE #
SELECT ZONE #
(ALL)
Use the "NEXT" & "PREVIOUS" keys to scroll through "ALL" "1" "2" "3"
ZONE Selected
ZONE # ALL
(TYPE) OUTPUT
Use the "NEXT" & "PREVIOUS" keys to scroll through "TYPE" & "OUTPUT". Once the desired option has been highlighted, pressing the "SELECT" button will select it. Pressing "EXIT" at this stage will return "SELECT ZONE #".
Type
Output Description
1 Indicate Only 2 Indicate, Bell 3 Indicate, Bell, General Alarm 4 Indicate, Bell, General Alarm, Ancillary 5 Indicate, Bell, General Alarm, Ancillary, Brigade Relay #1 6 Indicate, Bell, General Alarm, Ancillary Brigade Relay #2 7 Indicate, Bell, General Alarm, Ancillary, Brigade Relay #1, & Brigade Relay #2
NOTE:
A function of “BELL” also operated the WARNING SYSTEM.
Page 46
IFS-2600 Fire Indicator Panel Section 5
Programming
DOC-01-009 41
ZONE Type
ZONE # ALL TYPE
STD LATCHING
Use the "NEXT" & "PREVIOUS" keys to scroll through
Once the desired option has been highlighted, pressing the "SELECT" button will select it. Making a selection or pressing "EXIT" will return to zone selected.
A function of “BELL” also operates the WARNING SYSTEM.
ZONE Output Configuration
ZONE #ALL OUTPUT
IBGA BRIG 1&2
Use the "NEXT" & "PREVIOUS" keys to scroll through:
INDICATE I BELL IB GENERAL IBG ACF OUT IBGA BRIGADE 1 IBGA BRIGADE 2 IBGA BRIG 1&2
Once the desired option has been highlighted, pressing the "SELECT" button will select it. Pressing "EXIT" at this stage will return to "Zone Selected"
A function of “BELL” also operates the WARNING SYSTEM.
STD LATCHING STD LATCHING AVF NON LATCH NON LATCH 20S TIME DELAY 10S TIME DELAY 20S TIME DELAY 30S TIME DELAY 40S TIME DELAY 50S TIME DELAY 60S
NOTE:
The option previously set is displayed in brackets and is the first to be displayed.
Previously set options will not be displayed if "ALL" is selected.
NOTE:
The option previously set is displayed in brackets and is the first to be displayed.
Previously set options will not be displayed if "ALL" is selected.
Page 47
IFS-2600 Fire Indicator Panel Section 5
Programming
DOC-01-009 42
5.3. Relay Options & Programming
5.3.1. Relay Options
Optional Relays can be programmed to simulate:
Isolate Relay ACF Output Brigade Relay #1 Brigade Relay #2 Fault Relay Mains Fail Relay General Alarm Relay Bell Output Door Holder Relay Door Switch Reset
Or Can Be Used To:
"MAP AND" Up to 5 Zones in Alarm "MAP OR" Up to 5 Zones in Alarm “MAP FAULT” Up to 5 Zones in Fault “MAP ISOLATE” Up to 5 Zones in Isolate “MAP ISO/FAULT” Up to 5 Zones in Isolate/Fault
Relay Output Mapping
A total of 64 expansion relays can be fitted to the IFS-2600. Each relay can be individually programmed to mimic any of the following;
Standard Outputs which may be mimicked:
ANCILLARY OUTPUT (ACF) BRIGADE ALARM RELAY #1 BRIGADE ALARM RELAY #2 *
FAULT RELAY (NORMALLY ENERGISED)
*
MAINS FAIL RELAY (NV) (NORMALLY ENERGISED) ISOLATE RELAY GENERAL ALARM RELAYS BELL OUTPUT DOOR SWITCH RESET DOOR HOLDER RELAY FAULT/ISOLATE
When mapping to a normally energised relay, take care to ensure that connections take into account the normally energised state of the relay. Alternatively, the expansion relay(s) can be mapped to provide customised logic to suit specific installations:
Page 48
IFS-2600 Fire Indicator Panel Section 5
Programming
DOC-01-009 43
AND Mapping
AND MAPPING allows the relay output to be programmed for a combination of up to 5 zones, and only after they ‘ALL’ go into alarm, will the relay operate.
AND MAPPING is useful for applications which have special shutdowns, multiple risk Gas Facilities etc.
OR Mapping
OR MAPPING works similarly. This function will cause the relay to operate if any one of up to five (5) zones go into alarm, the relay will operate.
If the relay map options are set as "01" "02" "03" "00" "00", zones 1 or 2 or 3 in alarm will cause the relay to operate.
OR MAPPING is useful for applications which have special shutdowns, zoned mimic outputs etc.
FAULT Mapping
FAULT MAPPING works the same as OR mapping of alarm except it relates to the fault flag on each zone instead of the alarm flag. This function will cause the relay to operate if any one of up to five (5) zones go into fault.
If the relay map options are set as "01" "02" "03" "00" "00", then zones 1 or 2 or 3 going into fault, will cause the relay to operate.
FAULT/ISOLATE Mapping
FAULT/ISOLATE MAPPING works the same as OR mapping of alarm except it relates to the fault/isolate flag on each zone instead of the alarm flag. This function will cause the relay to operate if any one of up to five (5) zones go into fault/put in isolate.
If the relay map options are set as "01" "02" "03" "00" "00", then zones 1 or 2 or 3 going into fault/ (or are manually put in isolate) will cause the relay to operate.
ISOLATE Mapping
ISOLATE MAPPING works the same as or mapping of alarm except it relates to the isolate flag on each zone instead of the alarm flag. This function will cause the relay to operate if any one of up to five zones is put in isolate.
If the relay map options are set as "01" "02" "03" "00" "00", then zones 1 or 2 or 3, if put in isolate will cause the relay to operate.
Default Settings
ACF OUTPUT NON-LATCHING, NORMALLY DE-ENERGISED ALARM VERIFICATION (AVF) 3 MINUTES TIME 1/1/11 11:11 ZONE TYPES STANDARD LATCH 2S ZONE OUTPUT CONFIG I-B-G-A-BR1 & BR2 RELAY MAPPING MAP -OR-, MAPPING = 1 TO 1
IE: RELAY 1 = ZONE 1, RELAY 2 = ZONE 2.............
The IFS-2600 PANEL is self-configuring on power-up therefore it is not necessary to program the number of relay boards.
Zone expansion boards fitted must have the correct jumper selected.
Page 49
IFS-2600 Fire Indicator Panel Section 5
Programming
DOC-01-009 44
5.3.2. Relay Programming
Select RELAY #
SELECT RELAY#
(ALL)
Use the "NEXT" & "PREVIOUS" keys to scroll through "ALL" "1" "2" "3” Up to 64 and then wrap around. Once the desired relay number has been selected, pressing the "SELECT" button will select it. Pressing "EXIT" at this stage will return to main menu.
RELAY Selected
RELAY #ALL
(TYPE) MAPPING
Use the "NEXT" & "PREVIOUS" keys to scroll through "TYPE" & "MAPPING". Once the desired option has been highlighted, pressing the "SELECT" button will select it. Pressing "EXIT" at this stage will return to "Select Relay #".
RELAY Type
RELAY #ALL TYPE
(GENERAL)
Use the "NEXT" & "PREVIOUS" keys to scroll through:
ISOLATE ANCILLARY BRIGADE 1 BRIGADE 2 FAULT MAINS FAIL GENERAL BELL DOOR HOLDER MAP -AND­MAP -OR­MAP –FAULT­MAP –ISOLATE­MAP -ISOLATE/FLT­DOOR SWITCH RESET
Once the desired option has been highlighted, pressing the "SELECT" button will select it. Making a selection or pressing "EXIT" will return to "Relay Selected".
NOTE:
The option previously set is displayed in brackets and is the first to be displayed.
Previously set options will not be displayed if "ALL" is selected.
Page 50
IFS-2600 Fire Indicator Panel Section 5
Programming
DOC-01-009 45
RELAY Mapping
RELAY #1 MAP
(00) 00 00 00 00
** Relay mapping can only be selected if the relay is set as a MAP type. These 5 entry fields represent the zone numbers that the relay is to be mapped to and will be activated
from. Use the "NEXT" and "PREVIOUS" keys to increment/decrementthe zone number within the brackets. Use the "ENTER" key to move to the next field. Fields may be changed as required and set by
pressing "SELECT". Any fields left as (00) will be ignored. Pressing "EXIT" at this stage will return to "RELAY # ".
NOTE:
The option previously set is displayed in brackets and is the first to be displayed.
Previously set options will not be displayed if "ALL" is selected.
Page 51
IFS-2600 Fire Indicator Panel Section 5
Programming
DOC-01-009 46
5.4. Global Options & Programming
There are four global options that can be programmed:
(ACF) AVF
RELAY TIME
Use the "NEXT","PREVIOUS" & "SELECT" keys to select. Pressing "EXIT" will return to "Main Menu".
Ancillary Control Facility (ACF)
ACF OUTPUT
(NON-LATCH ND)
The ancillary trip is used for the shutting down of air conditioning and other systems in the event of a fire. Global Programmable Options:
Ancillary Trip (ACF)
1 LATCHING NORMALLY DE-ENERGISED 2 NON-LATCHING NORMALLY DE-ENERGISED 3 LATCHING NORMALLY ENERGISED 4 NON-LATCHING NORMALLY ENERGISED
The ancillary trip can be programmed as latching or non- latching depending on the application. It call also be programmed as normally energised or normally de-energised.
If a zone is programmed to operate the ancillary trip, an alarm condition will energise the ancillary trip until the alarm is removed (if non-latching), or until the alarm is removed and the ACF is manually reset via the keypad (latching).
Use the "NEXT" & "PREVIOUS" keys to scroll through:
LATCHING ND
NON-LATCH NE
LATCHING NE
ND = Normally De-energised i.e.: Output is not energised until an alarm occurs. NE = Normally energised i.e.: Output is energised and then is de-energised once an alarm occurs
NOTE:
The option previously set is displayed in brackets and is the first to be displayed.
Page 52
IFS-2600 Fire Indicator Panel Section 5
Programming
DOC-01-009 47
Alarm Verification Facility (AVF)
Alarm verification (AVF) is a facility used to minimise false alarms. AVF only applies to the zones programmed for the AVF function.
Global Programmable Options:
A
larm Verification
1
DISABLED
2
2 MINUTES
3
3 MINUTES
4
4 MINUTES
5
5 MINUTES
Operation is as follows: If a zone is programmed as AVF and it registers an alarm, no alarm functions are performed, if it is the first
AVF zone in alarm. This zone and all other zones programmed as AVF zones are reset by shutting down power to their
detectors for 12 seconds, the power is then restored and the zones are re- enabled. The alarm verification zones are now in "alert" mode. Any AVF zone going into alarm within the pre-
selected timeout period (2,3,4,5 minutes) will then cause an immediate alarm condition with all the programmed output functions being initiated.
If no alarm is received within this period, the AVF zones are removed from the "alert" mode and returned to normal. A further alarm will re-initiate the reset sequence etc.
Other zones are unaffected by the actions of AVF zones. They will all function as normal, regardless of AVF zone status.
If the timeout period is disabled, the alarm will transmit instantly thus making the AVF non-functional.
AVF TIMEOUT
(3 MINUTES)
Use the "NEXT" & "PREVIOUS" keys to scroll through:
DISABLED 2 MINUTES 3 MINUTES 4 MINUTES 5 MINUTES
RELAY (Global Relay Unity MAP)
MAP RELAY (XX) >>
FROM ZONE (XX)
NOTE:
The option previously set is displayed in brackets and is the first to be displayed.
Page 53
IFS-2600 Fire Indicator Panel Section 5
Programming
DOC-01-009 48
Use the "NEXT" & "PREVIOUS" keys to change the first relay to start from, together with the matching zone. Use the “ENTER” key to toggle between the two and press “SELECT” once finalised. “Exit” will abort unity map.
This function will start programming relays starting from the relay number specified in a 1 to 1 configuration with zones starting from the first zone number specified.
Example 1: if the above table was to look like this:
MAP RELAY (10) >>
FROM ZONE (01)
Then relay #10 would be set as MAP OR with its mapping as (01) 00 00 00 00, relay #11 would be set as MAP OR with it’s mapping set as (02) 00 00 00 00 and so on all the way up to relay #64. Relays number 1-through 9 remains unaffected by this function.
Example 2: if the above table was to look like this:
MAP RELAY (01) >>
FROM ZONE (09)
Then relay #1 would be set as MAP OR with its mapping as (09) 00 00 00 00, relay #2 would be set as MAP OR with it’s mapping set as (10) 00 00 00 00 and so on all the way up to relay #64.
Date & Time
The current DATE & TIME will be displayed as DD/MM/YY (in 24h format) Use the PREVIOUS” & NEXT” keys to increment or decrement the number highlighted by brackets. The ENTER key will move to the next field. When finished, the SELECT key must be pushed to store the date/time.
5.5. Print Programming Data
Prints the programming data currently stored in RAM, including all changes made (they may have not yet been written to the E2ROM).
Output is printed directly onto the serial printer if fitted.
NOTE:
In example 2, zone number 64 is reached and there are still more relays to go. (i.e. we are only at relay #56) the programming stops at this point and any relays not yet programmed will be left in their previous programmed mode and are unaffected by this function.
NOTE:
The Date/Time data is saved when the Select key is pushed.
DO NOT select “Save Changes “Y” as this will restart (and drop any door holders / air­conditioning if connected).
Page 54
IFS-2600 Fire Indicator Panel Section 6 Appendix
DOC-01-009 49
Section 6 Appendix
6.1. Appendix A
Glossary of Terms
AS-4428.1
Australian standard for; ­Automatic Fire Detection and Alarm Systems Control and Indicating Equipment.
AS-4428.5
Australian standard for; ­Automatic Fire Detection and Alarm Systems Power Supply Units.
AS-1670.1
Australian standard for; ­Automatic Fire Detection and Alarm Systems System Design Installation and Commissioning.
AS-1668.1 Australian standardfor; -
SAA Mechanical Ventilation and Air Conditioning Fire Precautions in Buildings with Air­handling Systems.
AZF Alarm Zone Facility (zone) MAF Master Alarm Facility
ACF Ancillary Control Facility AVF Alarm Verification Facility ISOL Isolate FLT Fault ZONE Alarm Zone Facility DET Detector LED Light Emitting Diode LCD Liquid Crystal Display A/C Air Conditioning AC Alternating Current DC Direct Current V Voltage A Amps FIP Fire Indicator Panel N/L Non Latching TD Time Delay STD Standard SBY Standby BR1 Brigade Relay 1 BR2 Brigade Relay 2 NV AC Fail Relay GEN General Alarm Contacts D/H Door Holder RLY Relay
Page 55
IFS-2600 Fire Indicator Panel Section 6 Appendix
DOC-01-009 50
6.2. Appendix B
Summary of Terminations & Cautions
MCP LOOP
Used for the looping of the manual call point to a particular zone chosen for indication. This is achieved by wiring from the zone, to the MCP, to the MCP loop then out to the field with the EOL across the last detector. The MCP is the first device on the circuit and both fault and alarm conditions will be indicated. (Refer to Section 4.5 for more details.)
DETECTION ZONES
Refer to list of compatible actuation devices for detectors which may be used (Table 4-1). Any other hard contact device may be used on these detection zones. An end of line resistor (E.O.L) of 4K7 ohms is required.
RELAY OUTPUTS
Relay outputs are voltage free change over contacts rated at 24VDC 1Amp (resistive). DO NOT attempt to switch 240VAC with these relay contacts.
BELL OUTPUTS
This output is fused at 1 Amp and can drive up to 10 NIFS bells as specified. Output is also monitored and if no bells are connected an EOL resistor (4K7 ohms)is required across the output terminals.
ACF OUTPUTS
This output is fused at 1 Amp. Output is also monitored and if no ancillary devices are connected, an EOL resistor (4K7 ohms) is required acrossthe output terminals.
WARNING SYSTEM
Connection to the warning systems such as “Occupant Warning System” or “electronic sounders”.
DOOR HOLDER OUTPUTS
When a door holder transformer is fitted to the panel, this output becomes functional. Output is rated at 3 Amps maximum and can power up to 30 NIFS style door holders continuously. (Nom. 80mA each). Output is separately fused at 3A (FS-1). Jumper JP3 if fitted will disable this output, i.e. 24V DC output all the time. The Door Holder Output can be isolated using the ACF Isolate function.
AUXILIARY POWER & MIMIC POWER (For IFS-2005 & IFS-2006 Boards only)
A total auxiliary power draw of 500mA is available from the auxiliary power and mimic power terminals. This output is fused at 1 Amp (FS-3) and is battery backed.
MAF ISOL & TRANSPONDER 0V
A 0V signal is switched back from the transponder test switch and is used for indication purposes at the FIP. This will indicate as MAF ISOLATED and initiate a common fault. It can also used for an external device to indicate a fault.
NOTE:
Relay contacts shown at Terminals (NC, C, NO) are for the Relay in a De-energised State.
Page 56
IFS-2600 Fire Indicator Panel Section 6 Appendix
DOC-01-009 51
MIMIC DATA & CLOCK
These outputs together with the mimic power terminals are used to serially communicate with the mimic panels when fitted. EOL resistor is not required on these lines. (Refer to Section 4.5 for more details.)
AC INPUT (For IFS-2005 & IFS-2006 Boards only)
Mains step down transformer output (30VAC) is connected at these terminals. DO NOT connect 240VAC to these terminals. (Refer to Section 4.4.2 for more details).
BATTERY
The 24V batteries are connected at these terminals. Reverse polarity will cause serious and permanent damage to the equipment.
DOOR HOLDER INPUT
Terminate the door holder AC transformer at these terminals. 24 VAC is the only acceptable power source at this point. DO NOT connect 240VAC at this point.
OUTPUT RELAYS
STANDBY (N) Normally energised, drops out when power supply (or battery supply) is below
specified voltage.
BRIGADE1 Brigade 1, defaults as energising on any alarm zone, programmable.
BRIGADE2 Brigade 2, defaults as energising on any alarm zone, programmable.
FAULT (N) Normally energised, drops out on any fault unless that function is isolated.
AC-FAIL (N) Normally energised, drops out if the mains power is lost.
ISOLATE Energised if any zone is isolated.
GENERAL1 Energised if any zone goes into alarm
GENERAL2 Energised if any zone goes into alarm
NOTE:
Firmware must be Version 6 or above for mimic operation.
Page 57
IFS-2600 Fire Indicator Panel Section 6 Appendix
DOC-01-009 52
6.3. Appendix C
IFS-2600 Programmed Options
Global System Parameters Date: / /
Latch ND Non-Latch ND Latch NE Non-Latch NE
ACF Output
Disabled 2 min 3 min 4 min 5 min
Alarm Verification (AVF)
Notes:
Programmed by
Place an "X" in the appropriate box = Default
Page 58
IFS-2600 Fire Indicator Panel Section 6 Appendix
DOC-01-009 53
ZONE TYPE PROGRAMMING
Date:
/ /
12345678910AZF
No.
STD
STD
N/L
N/L
T/D
T/D
T/D
T/D
T/D
T/D2SAVF2S20S
10S
20S
30S
40S
50S
60S
1 2
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
Place an "X" in the appropriate box = Default
Page 59
IFS-2600 Fire Indicator Panel Section 6 Appendix
DOC-01-009 54
12345678910AZF No.
STD
STD
N/L
N/L
T/D
T/D
T/D
T/D
T/D
T/D2SAVF2S20S
10S
20S
30S
40S
50S
60S
33 34
35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64
Place an "X" in the appropriate box = Default
Page 60
IFS-2600 Fire Indicator Panel Section 6 Appendix
DOC-01-009 55
ZONE OUTPUT PROGRAMMING Date: / /
AZF
No.
INDICATE
IB-GENERAL
IBG-ACF
IBGA
-BR1
IBGA
-
BR2
IBGA
-
BR1&BR2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
Place an "X" in the appropriate box = Default
Page 61
IFS-2600 Fire Indicator Panel Section 6 Appendix
DOC-01-009 56
AZF No.
INDICATE
IB-GENERAL
IBG-ACF
IBGA
-BR1
IBGA
-BR2
IBGA
-
BR1&BR2
33
34353637383940414243444546474849505152535455565758596061626364
Place an "X" in the appropriate box = Default
Page 62
IFS-2600 Fire Indicator Panel Section 6 Appendix
DOC-01-009 57
RELAY OUTPUT MAPPING Date: / /
MAPPING
RLY
ISO
ACF
BR1
BR2
FLT
MAINS
FAIL
GEN
BELL
D/H
ANDORFLT
ISO
ISO/
FLT
DO
-ORRE
-
SET
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
Place an "X" in the appropriate box = Default
Page 63
IFS-2600 Fire Indicator Panel Section 6 Appendix
DOC-01-009 58
MAPPING
RLY ISO ACF BR1 BR2 FLT MAINS
FAIL
GEN BELL D/H AND OR FLT ISO ISO/
FLT
DO-ORRE-
SET
33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64
Page 64
IFS-2600 Fire Indicator Panel
Technical Drawings
DOC-01-009 59
6.4.Technical Drawings
6.4.1. System Sensor Conventional Detector Connection Diagram
1
1
2
2
3
3
4
4
D D
C C
B B
A A
Rev
Size
Drg. No.
Title
Sheet:
Drawn/ Traced
Engineer Design
Approved ThisDrawing mustnot be usedfor Construction
unlesssignedas approved
7 Columbia Court, Norwest Business Park Baulkham Hills NSW 2153 AUSTRALIA Tel Fax Email: support@inertia.com.au
A4
No.
Revision- revise on CAD. Do not amendby hand Eng. App. Date
Copyright
Thisdocument is& shall remainthe propertyof
NotifierInertia FireSystems
Unauthoriseduseof this documentin anyway is prohibited.
Drawing File No.
C
O
61 2 9894 1444 61 2 9899 4156
=DocumentFullPathAndName
Of:
+
-
TO PANEL
BASE B401
DET A DET B
-D
+D
+R
RIP
1
2
3
4
5
1
2
3
4
5
EOL
4K7
+
-
TO PANEL
EOL
4K7
DET B
-D
+D
+R
RIP
1
2
3
4
5
BASE B401R
1
2
3
4
5
BASE B401R
BASE B
1
2
3
4
5
PROBE
SEALED
PROBE
SEALED
PROBE B
BASE A
PROBE A
SEALED DETECTOR CONNECTION DIAGRAM
CONVENTIONAL DETECTOR CONNECTION DIAGRAM
+R
+D
-D
470R
+R
+D
-D
Not current limited (3-24 V)
Current limited 10 mA
Common Return
BASE B401
REMOTE INDICATOR
SS-DET
A
SYSTEM SENSOR CONVENTIONALDETECTOR CONNECTION DIAGRAM
1 1 I PERRY IPERRY
I PERRY
( NORMAL HEAD NOT CONNECTED )
+
-
TOPANEL
BASEB401
DETA DETB
-D
+D
+R
RIP
1
2
3
4
5
1
2
3
4
5
EOL
4K7
+
-
TOPANEL
EOL
4K7
DETB
-D
+D
+R
RIP
1
2
3
4
5
BASEB401R
1
2
3
4
5
BASEB401R
BASEB
1
2
3
4
5
PROBE
SEALED
PROBE
SEALED
PROBEB
BASEA
PROBEA
SEALEDDETECTORCONNECTIONDIAGRAM
CONVENTIONALDETECTORCONNECTIONDIAGRAM
BASEB401
(NORMALHEADNOT CONNECTED)
Page 65
IFS-2600 Fire Indicator Panel
Technical Drawings
DOC-01-009 60
6.4.2. Hochiki Conventional Detector Connection Diagram
1
1
2
2
3
3
4
4
D D
C C
B B
A A
Rev
Size
Drg. No.
Title
Sheet:
Drawn/ Traced
Engineer Design
Approved ThisDrawing must notbe used for Construction
unlesssigned asapproved
7 Columbia Court, Norwest Business Park Baulkham Hills NSW 2153
AUSTRALIA Tel Fax Email: support@inertia.com.au
A4
No.
Revision- revise on CAD. Do not amend by hand Eng. App. Date
Copyright
Thisdocument is &shall remainthe propertyof
NotifierInertia Fire Systems
Unauthorised useof this documentin anyway is prohibited.
Drawing File No.
C
O
61 2 9894 1444 61 2 9899 4156
=DocumentFullPathAndName
Of:
+
-
TO PANEL
1
2
3
4
5
67
DET A
-D
+D
+R
RIP
1
2
3
4
5
67
DET B
-D
+D
+R
RIP
EOL
4K7
1
2
3
4
5
67
DET C
+
-
TO PANEL
CONNECTION FOR DFG-60BLKJ SEALED DETECTOR
DET A
-D
+D
+R
RIP
-D
+D
+R
RIP
EOL
4K7
L CS
DET B
L CS
DET C
L CS
RED
BLUE
WHITE
CONNECTION FOR STANDARD DETECTORS AND BASES
+R
+D
-D
470R
+R
+D
-D
Not current limited (3-24 V)
Current limited 10 mA
Common Return
REMOTE INDICATOR
HOC-DET
A
HOCHIKI CONVENTIONAL DETECTOR CONNECTION DIAGRAM
1 1 I PERRY I PERRY
I PERRY
Page 66
IFS-2600 Fire Indicator Panel
Technical Drawings
DOC-01-009 61
6.4.3. Ancillary Connection Diagram
IFS- 2600TYPICAL
Page 67
IFS-2600 Fire Indicator Panel
Technical Drawings
DOC-01-009 62
6.4.4. ASE Connection Diagram
1
1
2
2
3
3
4
4
D D
C C
B B
A A
Rev
Size
Drg. No.
Title
Sheet:
Drawn/ Traced
Engineer Design
Approved ThisDrawing must notbe used for Construction
unlesssigned asapproved
7 Columbia Court, Norwest Business Park Baulkham Hills NSW 2153
AUSTRALIA Tel Fax Email: support@inertia.com.au
A4
No. Revision - revise on CAD. Do not amendby hand Eng. App. Date
Copyright
Thisdocument is& shall
remainthe propertyof
NotifierInertia FireSystems
Unauthorised useof this documentin anyway is prohibited.
Drawing File No.
C
O
61 2 9894 1444 61 2 9899 4156
=DocumentFullPathAndName
Of:
2600
STANDBY
N/C
COM
N/O
BRIGADE 1
COM
BRIGADE 2
N/C
COM
N/O
FAULT
N/O
N/O N/C
+24
0V
AUX
N
IFS2600
N/C
N/O
AC-FAIL
N/C
COM
N/C
COM
ISOLATE
COM
N/O
ASE CONNECTION
26-ASE
A
1 1 22/8/05 I.P.
ASE
POWER
BRACKET
TYCO #10116
CODE RED #10115 ROMTEK 10117
AC FAIL
BR1
FAULT
ISOLATE
ASE
PCB2004
TERMINATION
N
N
N
N
Page 68
IFS-2600 Fire Indicator Panel
Technical Drawings
DOC-01-009 63
6.4.5. MIMIC Connection Diagram
1
1
2
2
3
3
4
4
D D
C C
B B
A A
Rev
Size
Drg. No.
Title
Sheet:
Drawn/ Traced
Engineer Design
Approved This Drawingmust notbe used for Construction
unlesssigned as approved
7 Columbia Court, NorwestBusiness Park BaulkhamHills NSW 2153 AUSTRALIA Tel Fax Email: support@inertia.com.au
A4
No.
Revision- reviseon CAD. Do not amend by hand Eng. App. Date
Copyright
Thisdocument is &shall remainthe propertyof
NotifierInertia FireSystems
Unauthoriseduseof this documentin any wayis prohibited.
Drawing File No.
C
O
61 2 9894 1444 61 2 9899 4156
=DocumentFullPathAndName
Of:
A
1 1 2/2/04 G.W.
ZONES 1-8 ZONES 9-16
PCB810
PCB811
PCB812 PCB812
PCB812
ZONES 17-24
SERIAL BUS
MIM/26/KIT
MIM/EXT/26 MIM/EXT/26
MIM/26/KIT
1-8 9-16 17-24 25-32
33-40 41-48 49-56 57-64
Max 120 Meters
26-MIM-CON
N/O
BELL
0V +24
TP 0V
ACF
0V +24
HOLD
0V
+24
AUX
MAF ISO
DOOR
DATA
CLK
DOOR
INPUT
WARN
0V +24
MIMIC
+
-
HOLD
DATA
CLK
+24
0V
FOR 8 ZONES
FOR EXTRA ZONES
STANDARD SIZES 8, 24 AND 64 ZONES
4/0.75mmcable
POWER AND SIGNAL RETURN
FITTED WITH IFS2600 MIMIC DRIVER
IFS2600 TERMINATION BOARD
Page 69
IFS-2600 Fire Indicator Panel
Technical Drawings
DOC-01-009 64
6.4.6. Dual Fan Connection Diagram
1
1
2
2
3
3
4
4
D D
C C
B B
A A
Rev
Size
Drg.
No.
Title
Sheet:
Drawn/ Traced
Engineer Design
Approved ThisDrawing must notbe used for Construction
unlesssigned as approved
7 Columbia Court, Norwest Business Park Baulkham Hills NSW 2153 AUSTRALIA Tel Fax Email: support@inertia.com.au
A4
No.
Revision- revise on CAD. Do not amend by hand Eng. App. Date
Copyright
Thisdocument is & shall
remainthe propertyof
NotifierInertia FireSystems
Unauthoriseduseof this documentin any wayis prohibited.
DrawingFile No.
C
O
61 2 9894 1444 61 2 9899 4156
=DocumentFullPathAndName
Of:
OFF
AUTO
ON
RUN
STOP
FAULT
+24 0V START1
START2
STOP1
STOP2
CONTROL
PCB1102
+24
START
+24
START
STOP
RUN
STOP
FLT
STOP
RUN
STOP
FLT
INDICATION
FAN 1
FAN 1
COMMON +VE
FAN 2
FAN 2
FRONT PANEL CONTROL
CONTROL
INDICATION
COMMON +VE
RUN
STOP
FAULT
FIREPANEL
FIELDWIRING
START STOP
* NOTE
THE MECHANICAL SERVICES BOARD MUST BE CONFIGURED TO HAVE THE STOP RELAY TO TAKE PRECEDENCE OVER THE START RELAY
19/8/05 I PERRY
A
DUAL FAN (GENERAL)
2600-DUAL FAN
FAN TERMINATION BOARD
AUX +24 AUX 0V
AUX POWER
CONTROL
LINK SW1 A & B TO SW2 A, B
REMOVE SW2
FAN RUNNING FAN STOPPED AND POWER AVAILABLE FAN FAULT OR NO POWER AVAILABLE
FAN RUNNING FAN STOPPED AND POWER AVAILABLE FAN FAULT OR NO POWER AVAILABLE
OFF
AUTO
ON
FOR SINGLE CONTROL
*NOTE
FAN 1 START RELAY
FAN 2 START RELAY
FAN 1 STOP RELAY
FAN 2 STOP RELAY
RIBBON CABLE
1 1
START STOP
Page 70
IFS-2600 Fire Indicator Panel
Technical Drawings
DOC-01-009 65
6.4.7. Exhaust Fan Connection Diagram
1
1
2
2
3
3
4
4
D D
C C
B B
A A
Rev
Size
Drg. No.
Title
Sheet:
Drawn/ Traced
Engineer Design
Approved ThisDrawing must notbe used for Construction
unlesssigned asapproved
7 Columbia Court, Norwest Business Park Baulkham Hills NSW 2153 AUSTRALIA Tel Fax Email: support@inertia.com.au
A4
No.
Revision- revise on CAD. Do not amend by hand Eng. App. Date
Copyright
Thisdocument is &shall remainthe propertyof
NotifierInertia Fire Systems
Unauthoriseduse ofthis documentin any wayis prohibited.
Drawing File No.
C
O
61 2 9894 1444 61 2 9899 4156
=DocumentFullPathAndName
Of:
OFF
AUTO
ON
RUN
STOP
FAULT
+24 0V START1 STOP1
CONTROL
PCB1128
+24
START
STOP
RUN
STOP
FLT
INDICATION
FAN 1
COMMON +VE
FRONT PANEL CONTROL
FIREPANEL
FIELDWIRING
START STOP
* NOTE
THE MECHANICAL SERVICES BOARD MUST BE CONFIGURED TO HAVE THE STOP RELAY TO TAKE PRECEDENCE OVER THE START RELAY
19/8/05 I PERRY
A
EXHAUST FAN (TYPICAL)
2600-EXH
FAN TERMINATION BOARD
AUX +24 AUX 0V
AUX POWER
CONTROL
FAN RUNNING FAN STOPPED AND POWER AVAILABLE FAN FAULT OR NO POWER AVAILABLE
RIBBON CABLE
1 1
+24
0v
FIRE TRIP
ACF
PCB1125
-
+
IN
OUT
LOAD
-
+
-
+
D1 R1
FROM FIP
RELAY
* NOTE
EITHER THE MAPPING ABOVE MAY BE USED TO STOP THE EXHAUST FAN OR THE GENERAL ACF TRIP BELOW, BUT NOT BOTH.
USE OF THE FIRE TRIP RELAY BELOW REQUIRES THAT THE MSSB STOPS THE FAN.
FAN STOP RELAY
(MAPPED TO ACF FOR
GENERALOR ZONED)
Page 71
IFS-2600 Fire Indicator Panel
Technical Drawings
DOC-01-009 66
6.4.8. Supply Fan Connection Diagram
1
1
2
2
3
3
4
4
D D
C C
B B
A A
Rev
Size
Drg. No.
Title
Sheet:
Drawn/ Traced
Engineer Design
Approved ThisDrawing must notbe used for Construction
unlesssigned as approved
7 Columbia Court, Norwest Business Park Baulkham Hills NSW 2153 AUSTRALIA Tel Fax Email: support@inertia.com.au
A4
No.
Revision- revise on CAD. Do not amend by hand Eng. App. Date
Copyright
Thisdocument is &shall remainthe propertyof
NotifierInertia Fire Systems
Unauthoriseduse ofthis documentin any wayis prohibited.
Drawing File No.
C
O
61 2 9894 1444 61 2 9899 4156
=DocumentFullPathAndName
Of:
OFF
AUTO
ON
RUN
STOP
FAULT
+24 0V START1 STOP1
CONTROL
PCB1128
+24
START
STOP
RUN
STOP
FLT
INDICATION
FAN 1
COMMON +VE
FRONT PANEL CONTROL
FIREPANEL
FIELDWIRING
START STOP
* NOTE
THE MECHANICAL SERVICES BOARD MUST BE CONFIGURED TO HAVE THE STOP RELAY TO TAKE PRECEDENCE OVER THE START RELAY
19/8/05 I PERRY
A
SUPPLY AIR FAN (TYPICAL)
2600-SAF
FAN TERMINATION BOARD
AUX +24 AUX 0V
AUX POWER
CONTROL
FAN RUNNING FAN STOPPED AND POWER AVAILABLE FAN FAULT OR NO POWER AVAILABLE
FAN START RELAY
RIBBON CABLE
1 1
(MAPPEDTO ACF FOR
GENERAL OR ZONED)
+24
0v
FIRE TRIP
ACF
PCB1125
-
+
IN
OUT
LOAD
-
+
-
+
D1 R1
FROM FIP
RELAY
* NOTE
EITHER THE MAPPING ABOVE MAY BE USED TO START THE SAF OR THE GENERAL ACF TRIP BELOW, BUT NOT BOTH.
USE OF THE FIRE TRIP RELAY BELOW REQUIRES THAT THE MSSB STARTS THE FAN.
FAN STOP RELAY (MAPPEDTO AIR INTAKE SMOKE DETECTOR)
Page 72
IFS-2600 Fire Indicator Panel
Technical Drawings
DOC-01-009 67
6.4.9. Smoke Spill Fan Connection Diagram
1
1
2
2
3
3
4
4
D D
C C
B B
A A
Rev
Size
Drg.
No.
Title
Sheet:
Drawn/ Traced
Engineer Design
Approved ThisDrawing must notbe used for Construction
unlesssigned asapproved
7 Columbia Court, Norwest Business Park Baulkham Hills NSW 2153
AUSTRALIA Tel Fax Email: support@inertia.com.au
A4
No.
Revision- revise on CAD. Do not amend by hand Eng. App. Date
Copyright
Thisdocument is &shall remainthe propertyof
NotifierInertia Fire Systems
Unauthoriseduse ofthis documentin any wayis prohibited.
Drawing File No.
C
O
61 2 9894 1444 61 2 9899 4156
=DocumentFullPathAndName
Of:
OFF
AUTO
ON
RUN
STOP
FAULT
+24 0V START1 STOP1
CONTROL
PCB1128
+24
START
STOP
RUN
STOP
FLT
INDICATION
FAN 1
COMMON +VE
FRONT PANEL CONTROL
FIREPANEL
FIELDWIRING
START STOP
* NOTE
THE MECHANICAL SERVICES BOARD MUST BE CONFIGURED TO HAVE THE STOP RELAY TO TAKE PRECEDENCE OVER THE START RELAY
19/8/05 I PERRY
A
SMOKE SPILL FAN (TYPICAL)
2600-SSF
FAN TERMINATION BOARD
AUX +24 AUX 0V
AUX POWER
CONTROL
FAN RUNNING FAN STOPPED AND POWER AVAILABLE FAN FAULT OR NO POWER AVAILABLE
FAN START RELAY
RIBBON CABLE
1 1
(MAPPEDTO ACF FOR
GENERAL OR ZONED)
+24
0v
FIRE TRIP
ACF
PCB1125
-
+
IN
OUT
LOAD
-
+
-
+
D1 R1
FROM FIP
RELAY
* NOTE
EITHER THE MAPPING ABOVE MAY BE USED TO START THE SSF OR THE GENERAL ACF TRIP BELOW, BUT NOT BOTH.
USE OF THE FIRE TRIP RELAY BELOW REQUIRES THAT THE MSSB STARTS THE FAN.
Page 73
IFS-2600 Fire Indicator Panel
Technical Drawings
DOC-01-009 68
6.4.10. 10W EVAC Connection Diagram
1
1
2
2
3
3
4
4
D D
C C
B B
A A
Rev
Size
Drg. No.
Title
Sheet:
Drawn/ Traced
Engineer Design
Approved ThisDrawing must notbe used for Construction
unlesssigned asapproved
7 Columbia Court, Norwest Business Park Baulkham Hills NSW 2153
AUSTRALIA Tel Fax Email: support@inertia.com.au
A4
No.
Revision- revise on CAD. Do not amend by hand Eng. App. Date
Copyright
Thisdocument is &shall remainthe propertyof
NotifierInertia Fire Systems
Unauthorised useof this documentin anyway is prohibited.
DrawingFile No.
C
O
61 2 9894 1444 61 2 9899 4156
=DocumentFullPathAndName
Of:
+24
WARN
0V
REMOTE
REMOTE
OUTPUT
INPUT
+24V0V+24V
0V
EXTERNAL
POWER
MONITORJP1
AC INPUT
BATT
LINK JP1
+24 0V
AUX
+24V
0V
+24V COM
FAULT
ALERT OUT
EVAC OUT
ALARM
BGM EN
EVAC IN
ALERT IN
PTT
0V
PA+
PA -
BGM +
BGM -
VOLPA
+24
GND
COM
LINE +
10W EVAC
PCB 908
SHIELDED
BGM INPUT
1V P-P
BGM ENABLE
FRONT PANEL EVAC CONTROL
EOL
47K 5%
SPEAKERSWITH 100V LINETRANSFORMERS AND ISOLATION CAPACITORS
( ENABLEDON
CLOSURE)
SHIELDED
WHITE RED
BLACK/SHIELD BLUE
MICROPHONE
WITHPTT
4K7 5%
IFS-2600 10 WATT CONNECTIONDIAGRAM
1 1
I PERRYI PERRY
I PERRY
2600-10W
A
IFS2600 TERMINATION BOARD
NOTE: TO SLAVETWO AMPLIFIERS
TOGETHER,REMOVE THE IFS903 BOARDFROM THE SLAVE AMPLIFIER AND CONNECTJP1 ON THE MASTERTO JP2ON THE SLAVE.
THEMICROPHONEAND BGM
MUSTONLYBE CONNECTED TO THEMASTERAMPLIFIER.
CONNECTPIN 4, P12 ON MASTER
TO PIN4P12 ON SLAVE.
JP2JP1
SOUND
Page 74
NOTES
Page 75
NOTES
Page 76
New South Wales (Head Office) 9 Columbia Way Baulkham Hills NSW 2153
ph +61 (02 9899-4155 fax +61 (0)2 9899-4156
Queensland 24 Potts Street East Brisbane, QLD 4169
ph +61 (0)7 3391 5777 fax +61 (0)7 3391 5800
Victoria 32 Lambert Street Richmond, VIC 3121
ph +61 (0)3 9421 5552 fax +61 (0)3 9421 5553
Western Australia Unit 4, 283 Camboon Road Malaga WA 6090
ph +61 (0)8 9270 6555 fax +61 (0)8 9270 6556
New Zealand 264 Mt Eden Road Auckland
ph +64 (0)9 623 5050 fax +64 (0)9 623 5060
Loading...