Notifier ID50, ID60 Operating Manual

ID50/60
operating manual
997-264-000-8, Issue 8 January 2007
ID50 Series Panel - Operating Manual
Contents
January 2007
Contents
1 Introduction 1
1.1 Associated Documents 1
1.2 The ID50 / ID60 Series Panel 1
1.2.1 Device T ype Abbreviations 2
1.3 Cleaning 2
2 Panel Controls and Indicators 3
2.1 Controls 3
2.2 Indicators 4
3 Automatic Alarms - What to do 5
3.1 Fire 5
3.1.1 Fire in Delayed Mode 7
3.2 Pre-alarm 8
3.3 Fault 9
3.2.1 Power Fail 10
3.3 Plant Alarm 11
4 Operator Actions at Panel 12
4.1 Introduction 12
4.1.1 Liquid Crystal Display 12
4.1.2 Internal Buzzer 13
4.1.3 Access Codes 13
4.1.4 Keyswitch 14
4.2 MUTE BUZZER Pushbutton 14
4.3 EXTEND DELAY Pushbutton 14
4.4 END DELA YS/EVA CU ATE Pushbutton 15
4.5 SILENCE/RESOUND Pushbutton 16
4.6 RESET Pushbutton 17
4.7 Numeric Keys 18
4.7.1 Cancellation/T ermination Button 18
4.7.2 Level 2 Options Menu Button 18
4.8 Level 2 Option Menus 19
4.9 TEST - User Option 20
4.9.1 LEDs - User Option 21
4.9.2 LCD - User Option 21
4.9.3 Zones - User Option 22
4.9.4 Auto High Test - User Option 24
4.9.5 Outputs - User Option 25
ID50 Series Panel - Operating Manual
Contents
ii997-264-000-8, Issue 8
January 2007
4.9.6 Buzzer - User Option 27
4.9.7 Keyboard - User Option 27
4.10 DISABLE / ENABLE - User Option 28
4.10.1 Zones - User Option 28
4.10.2 Outputs - User Option 31
4.10.3 Day Mode - User Option 32
4.10.4 Delays - User Option 33
4.11 CLOCK - User Option 34
4.11.1 Time - User Option 35
4.11.2 Date - User Option 36
4.12 VIEW MODE - User Option 37
4.12.1 Log - User Option 3 8
4.12.2 Devices - User Option 39
4.12.3 Faults - User Option 40
4.12.4 Input Events - User Option 41
4.12.5 Disabled - User Option 42
4.12.6 Alarm Count - User Option 42
4.12.7 Voltages - User Option 43
4.12.8 Version - User Option 44
4.13 Commissioning 44
4.14 Print 44
Appendix 1 - Log Book A1-1 Appendix 2 - Maintenance A2-1 Appendix 3 - ID60 Single Loop Panel
Differences A3-1
ID50 Series Panel - Operating Manual
Contents
iii 997-264-000-8, Issue 8
January 2007
ID50 Series Panel
ID50 Series Panel
ID50 Series Panel - Operating Manual
Introduction
1 997-264-000-8, Issue 8
January 2007
1 Introduction
This manual contains operating instructions for the ID50 and ID60 Series Fire Detection Panels. Differences between the ID50 and ID60 panels are given in Appendix 3.
Users of this manual are assumed to be working with a panel that has already been installed and configured appropriately for the area under its supervision.
1.1 Associated Documents
This manual does not describe the installation or configuration procedures of the panel. For information on these topics, refer to the ID50 Series
Panel - Installation, Commissioning and Configuration Manual (Ref. 997-263-000-X).
1.2 The ID50/ ID60 Series Panel
The panel, as supplied by NOTIFIER, is a 1-loop, 16-zone Analogue Addressable Panel. The single loop has the capacity for up to 99 analogue sensors plus up to 99 modules and, in some installations, panels may also be connected to repeaters using the RS485 Communications Link.
All the control and operation functions described in this manual can be carried out using the pushbuttons on the front of the panel.
A keyswitch is provided which, when set to the right, has the same effect as entering an access 2 passcode. Set it to the centre to cancel out of all menus and return to the Status: NORMAL display. This indicates access level 2 is de-selected.
ID50 Series Panel - Operating Manual
Introduction
2997-234-000-8, Issue 8
January 2007
1.2.1 Device Type Abbreviations
Throughout this manual the panel may refer to devices by an abbreviated name. The following table lists the device type abbreviation and its description.
Abbreviation Type Description
AUX Plant Warning Input AVR* Advanced VIEW™ Reference* AVS* Advanced VIEW™ Sensor* CTE Monitored (Relay Type) Output (VdS) CTL Monitored (Relay Type) Output ESE Extinguishant System Output (VdS) ESM Extinguishant System ESO Monitored Extinguishing System Output EST Extinguishant Monitor System Trigger ION Ionisation Smoke Detector IRL Immediate Release Input MCP† Manual Call Point† MLT Advanced Multi Sensor MNS Monitor module (no short-circuit) MON Fire Alarm Monitor Input MRL Manual Release Input OPT Optical/Photo-electric Smoke Detector OPX Optiplex Multi-sensor RLE Unmonitored (Relay Type) or O/C Outputs (VdS) RLY Unmonitored (Relay Type) or O/C Outputs SDR Monitored (Sounder Type) Output SM4* SMART Multi-criteria Sensor* TMP Temperature Detector TxD Monitored Transmission Routing Output ZMX Conventional Detector Input
Note: Devices marked ‘*’ are supported by the ID60
Panel only. The Device marked ‘†’ is also
available as ‘DKM’ - not used in this application (provided to be compatible with VdS requirements).
1.3 Cleaning
The panel case may be cleaned periodically by wiping with a soft, damp lint-free cloth.
Do not use solvents.
ID50 Series Panel - Operating Manual
Panel Controls & Indicators
3 997-264-000-8, Issue 8
January 2007
2 Panel Controls and Indicators
The panel’s controls and indicators are used to operate the overall system and display the panel status. The panel has five function pushbuttons, twelve numeric/cursor keys and thirty-two zonal LED indicators, two ‘FIRE’ indicators and fourteen system status LED indicators.
An access level 2 keyswitch is provided to enable the operation of panel controls and access to user menus without entering a passcode via the numeric keypad.
2.1 Controls
The pushbuttons are listed below, together with references to the relevant sections of the manual:
Function Pushbuttons
MUTE BUZZER - (Section 4.2).
EXTEND DELA Y - (Section 4.3).
END DELA Y/EVACUATE
1
- (Section 4.4)
SILENCE/RESOUND - (Section 4.5).
RESET - (Section 4.6).
1
Also configurable as Transmission Device (TD) Enable/Disable.
Numeric/Cursor Keys
Numeric/Cursor keys - (Section 4.7).
Keyswitch
Turn the keyswitch to enable level 2 access. The keyswitch provides an alternative to entering the level 2 access code via the numeric keys. See Section 4.1.3 and Section 4.1.4.
ID50 Series Panel - Operating Manual
Panel Controls & Indicators
4997-264-000-8, Issue 8
January 2007
2.2 Indicators
The panel status indicators comprise three groups: a. Zone S t atus LED indicators.
b. Panel/System LED indicators. c. Visible/Audible indicators.
Zone Status LED Indicators
ZONE FIRE - these LEDs indicate affected zone(s).
ZONE FAULT/DISABLE/TEST - these LEDs indicate
affected zone(s).
Panel/System LED Indicators
FIRE - these LEDs indicate a fire condition.
Other System Status LEDs:
FAULT indicates a fault has been
detected by the panel.
DISABLEMENT indicates the presence of a
manually-configured
disablement. TEST indicates a test is in progress. DELAY ACTIVE indicates delays are active. FIRE OUTPUT ACTIVEindicates fire outputs have
been operated. PRE-ALARM
1
indicates a pre-alarm
condition exists. POWER indicates status of power
supply. SYSTEM FAULT indicates the CPU has reset
or a system fault has occurred. EARTH FAULT indicates an earth fault has
occurred. PLANT ALARM
2
indicates a fault or warning
from a plant-monitoring device. FIRE CONTROL O/P: F AUL T/DISABLED
indicates a fire control output
fault or disablement. FIRE OUTPUT: FAULT/DISABLED
indicates a fire output fault or
disablement SOUNDER: FAUL T/DISABLED
indicates a sounder circuit
fault or disablement POWER SUPPLY FAULT
indicates an unsatisfactory
power supply to the panel.
1
This LED is also configurable as SO UND ER S SIL EN CED .
2
This LED can be configured as: FAULT O/P: FAUL T/ DISABLED.
Visible/Audible Indicators
Liquid Crystal Display (LCD) - (Section 4.1.1).
Internal Buzzer - (Section 4.1.2).
ID50 Series Panel - Operating Manual
Automatic Alarms - What to do
5 997-264-000-8, Issue 8
January 2007
3 Automatic Alarms - What to do
Before any automatic alarms have been sounded the panel only operates in display mode (quiescent state). The user must then turn the keyswitch to the right or enter a Level 2 access code to enable the panel’s pushbuttons.
Only one alarm condition can be displayed at a time on the LCD. If fire alarms, faults and/or warning conditions
(Plant Alarm) are present on the panel at the same time, they are displayed in the following priority order:
a. Fire Alarms. b. Pre-alarms c. Faults. d. Warnings. The alarm condition is registered in a log.
The user must then enter a Level 2 access code, or turn the keyswitch to the right, to enable the panel’s pushbuttons. When the Level 2 access code is active,
the ‘2/8’ buttons can be used to scroll through the alarms and the ‘4’ button will display the first alarm.
3.1 Fire
Automatic panel actions:
If the system detects a fire alarm, the panel always does the following automatically:
a. Operates the internal (high-pitched) buzzer . b. Illuminates the red FIRE LEDs, and the numbered
red ZONE FIRE LED.
c. Displays information on the LCD regarding the fire
condition. The information includes device address and device location (see example below).
FIRE 02 / 05 Z01 M12 MCP 11:59 MAIN BUILDING BASEMENT ROOM 23
Note: If a delay is configured DELAYED is displayed on
the top line of the LCD. When a delay is active the DELAY ACTIVE LED illuminates and the remaining time before the first day mode delay expires is displayed every 5 secs. The LED only extinguishes when the delay period has expired.
d. Operates the sounders and output modules according
to the panel’s Control-by-Event (CBE) Rules (configured during the Commissioning stage).
ALARM
CONDITION
ZONE
NUMBER
DEVICE
ADDRESS
ZONE TEXT
TIME OF LOGGED
ALARM CONDITION
DISPLAYED
ALARM
CONDITION
LOGGED
ALARM
CONDITIONS
DEVICE
TYPE
DEVICE
TEXT
ID50 Series Panel - Operating Manual
Automatic Alarms - What to do
6997-264-000-8, Issue 8
January 2007
Recommended operator actions:
Note: In the recommended operator actions described below
only MUTE BUZZER and END DELAY are select able at Access Level 1. The operation of EXTEND DELAY , EV ACUATE, SILENCE, RESOUND and RESET must only be possible at access Level 2, in accordance with the requirements of EN54:Part 2.
1 Operate the MUTE BUZZER pushbutton to silence
the panel’s internal buzzer .
2 Follow prescribed instructions for evacuation of
premises, notification of Fire Brigade and investigation of source of fire.
3 If additional sounder operations are required to
achieve a complete and immediate evacuation of the premises, press the END DELAY /EVACUATE pushbutton (needs access level 2). This will cause the internal buzzer to resound, so press the MUTE BUZZER pushbutton to silence.
4 When more than one fire Alarm condition is present,
it is possible to manually scroll through all logged Fire Alarm conditions using the ‘2/8’ arrows.
Note: With multiple alarms, the LCD displays the first
alarm event.
5 When evacuation of the premises is achieved, or at
the direction of an authorised person, the Alarm Sounders may be silenced by pressing the SILENCE / RESOUND pushbutton.
Note: The SOUNDERS SILENCED LED illuminates if
this option was configured during panel commissioning. The default function for this LED is PRE-ALARM.
6 To re-start the sounders, press the
SILENCE / RESOUND pushbutton. Y ou must wait at least 10 seconds after having originally silenced the sounders before resounding them. If the SOUNDERS SILENCED LED option was configured during commissioning to illuminate, this will now extinguish.
7 When the cause of the alarm has been removed and
call points and input devices have been locally reset, the system may be returned to ‘Status: NORMAL ’* by pressing the RESET pushbutton.
* Unless the Site name menu was edited during
commissioning - refer to Section 4.1.1 Liquid crystal Display.
3
4
7
Status: NORMAL
Sat 01/12/2001 00:00:00
5
6
1
EN54-2: 7.6.1, 7.8, 8.7.1,
9.1.2
Ensure EN54 compliance
for access to controls.
ID50 Series Panel - Operating Manual
Automatic Alarms - What to do
7 997-264-000-8, Issue 8
January 2007
1a
2
3
3.1.1 Fire in Delayed Mode
The DeIayed Mode introduces a delay between an alarm being detected and the sounders and output modules activating. Depending upon the panel configuration, this may be a single delay or a 2-stage delay (an initial brief delay which may be extended by pressing EXTEND DELA Y to allow an investigation). The delay is initiated i f the panel enters an alarm condition during Delayed Mode.
Note: For any configured delays, pressing EXTEND
DELA Y cancels the initial response time and initiates the fire investigation period. Activation of an MCP will also cancel any configured delay period. The maximum time for the primary initial response time is 300 secs; the TOTAL time for both periods is 600 secs. The delay period can only be configured at Level 3 by the Commissioning Engineer.
The delayed mode status is indicated on the LCD as below:
1a When the panel enters a fire condition the delay
countdown is started and the internal buzzer sounds. The buzzer can be silenced by pressing the MUTE BUZZER pushbutton. The LCD displays the alarm information on the top line; this alternates for 1 sec every 5 secs with the time remaining before the shortest day mode delay expires.
1b If the 2-stage delay is configured, pressing the
EXTEND DELAY pushbutton during the primary delay initiates the fire investigation period.
Note: If configured to do so, the DISABLEMENT LED is
illuminated (not default) from the initiation of the primary delay and extinguishes at the end of the primary delay period or fire investigation period.
2 If the delay time elapses, a full alarm condition is
entered (the configured fire outputs are activated). To cancel the delay , operate the END DELA Y/EVACUA TE pushbutton; the full alarm condition is entered and the internal buzzer sounds (it can be silenced by pressing the MUTE BUZZER pushbutton).
Note: A Fire alarm in a different zone to the first alarm
will also cancel the delay .
3 When the cause of the alarm has been cleared, press
the RESET pushbutton to return to the ‘Status: NORMAL’ message.
EN54-2: 7.11 (c)
Total time for configured
delays MUST NOT
exceed 600 seconds.
Status: NORMAL
Sat 01/12/2001 00:00:00
1b
Status: DELAYED
Sat 01/12/2001 00:00:00
FIRE 02 / 05 DELAYED: 050 MAIN BUILDING FIRST FLOOR ROOM 36
FIRE 02 / 05 Z01 S16 ION 11:59 MAIN BUILDING FIRST FLOOR ROOM 36
ID50 Series Panel - Operating Manual
Automatic Alarms - What to do
8997-264-000-8, Issue 8
January 2007
3.2 Pre-alarm
When one or more input devices signal to the panel a reading higher than normal but not yet at the FIRE level, this is a PRE-ALARM condition.
Automatic panel actions
a. Intermittent operation of the internal buzzer (one
second ON, one second OFF).
b. Operation of the appropriate ZONE FAUL T/DISABLE/
TEST LED and yellow PRE-ALARM LED.
c. Displays information on the LCD regarding the pre-
alarm condition.
d. Operation of any assigned outputs in response to a
general pre-alarm condition at the panel (refer to
Section 5.7 Control-by-Event Rules).
Recommended operator actions:
1 Operate the MUTE buzzer pushbutton to silence the
panel’s internal buzzer .
2 Check condition of sensor indicated and check area
for possible fire. If the cause cannot be determined notify authorised servicing company .
Status: FAULT 01/02 14:55 PRE-ALARM
ID50 Series Panel - Operating Manual
Automatic Alarms - What to do
9 997-264-000-8, Issue 8
January 2007
3.3 Fault
Automatic panel actions:
If a fault occurs, the panel automatically does the following:
a. Operates the internal buzzer (2 sec. on, 1 sec. off). b. Flashes the appropriate FAULT LEDs, including
numbered ZONE FAULT/ DISABLE / TEST LED(s) if appropriate.
c. Operates any control outputs which are associated in
the Control-by-Event Rules with fault events.
Recommended operator actions:
1 A fault message typically displays information as
follows (not all items apply to all types of fault): a. Fault condition. b. Fault number currently displayed. c. Total number of faults logged. d. A text message describing the fault. e. Zone Number. f. Device Address. g. Device Type. h. Time fault was logged.
Depending upon the fault message, either: i If the fault message relates to a specific loop device,
investigate whether the cause of the fault is immediately apparent and can be corrected.
Note: Press the ‘6’ button to view additional zone text
information. To return to the fault message press any numeric/cursor key (if no key is pressed within ten [10] seconds the display automatically returns to the fault message).
ii. If the fault message relates to a system fault condition,
as displayed below, note the full description of the fault and notify the authorised servicing company .
Note: Items e, f, and g are not applicable.
F AULT 01 / 03 Z01 M12 MCP 14:55 NO REPLY FROM DEVICE >
ABC D E F G H
FAULT 01 / 03 Z01 : M12 MCP 14:55 < - - - Zone Te xt - - - > < - - - Device Text - - - >
FAULT 01 / 03 14:55 EARTH FAULT
ABC
D
H
6
ID50 Series Panel - Operating Manual
Automatic Alarms - What to do
10997-264-000-8, Issue 8
January 2007
2 If a service contact number has been entered during
panel commissioning, the LCD alternates between the fault message(s) and the following:
Note: Press the MUTE BUZZER pushbutton to silence
the panel’s internal buzzer .
3 When the cause of the fault has been cleared, press
the RESET pushbutton.
3.3.1 Power Fail
1 The loss of a power supply causes the panel to enter
a Power Fail condition. The POWER SUPPL Y F AUL T and general FAULT LEDs illuminate and the internal
buzzer operates. The LCD displays: a. Fault condition. b. Fault number currently displayed. c. Total number of faults logged. d. Time fault was logged. e. A text message describing the fault.
A battery fault is shown on the LCD as follows:
2 If a service contact number has been configured, the
LCD alternates between the power fault message and
the service contact number. Note: Press the MUTE BUZZER pushbutton to silence
the panel’s internal buzzer .
3 When the cause of the fault has been cleared, press
the RESET pushbutton.
If both the AC and
Battery power fail, the
indicators and LCD are
non-operational.
FAULT 01 / 02 14:55 NO MAINS SUPPLY
FAULT 01 / 03 14:55 For Service Contact ***** ******
ABCD
E
FAULT 01 / 02 14:55 BATTERIES MISSING
ABCD
E
Status: NORMAL
Sat 01/12/2001 00:00:00
Status: NORMAL
Sat 01/12/2001 00:00:00
ID50 Series Panel - Operating Manual
Automatic Alarms - What to do
11 997-264-000-8, Issue 8
January 2007
Status: NORMAL
Sat 01/12/2001 00:00:00
3.4 Plant Alarm
A Plant Alarm indication is the default configuration setting
for ID50 Series fire control panels. In this configuration,
the panel operates as follows:
A Plant Alarm message is displayed if the panel detects
a non-fire input (AUX) configured in zones 17 to 32. When
a non-fire event occurs the Plant Alarm LED is illuminated
(except for Hold Switch and Abort Switch AUX inputs)
and the LCD displays the following information:
a. Plant Alarm condition. b. Alarm number currently displayed. c. Number of alarms. d. Zone number. e. Device address. f. Device type. g. Time of logged message. h. Zonal and device text (if any).
When the cause of the alarm has been cleared, the
message will automatically be removed from the LCD
and the LED extinguished. The panel returns to quiescent
mode.
3.5 Fault Output: Fault /Disabled (Optional)
If the panel has been configured to indicate the status of
the Fault Output relay circuit, a message is displayed if a
Fault Output relay circuit fault condition is detected or if it
has been disabled.
Note: An output device configured to a Fault CBE rule
remains active if disabled from a source other than the panel Fault Output relay disable function.
PLANT 01 / 01 Z21 M12 MCP 14:55 < - - - Zone Te xt - - - > < - - - Device Text - - - >
ABCDEF
GH
ID50 Series Panel - Operating Manual
Operator Actions at Panel
12997-264-000-8, Issue 8
January 2007
4 Operator Actions at Panel
4.1 Introduction
Operator actions at the panel require the correct pushbutton and access code entry. The LCD and the user pushbuttons located on the panel allow the following actions to be carried out:
a. Mute the panel buzzer. b. Extend Delays. c. Panel reset. d. End Delays / Evacuate (terminate delays to outputs,
if delay is active and activate sounders).
e. Silence and resound the alarms. f. Menu navigation and alphanumeric key entry. g. Operator-controlled tests. h. Disable and enable of zones, outputs or delays. i. Set the clock and date. j. View: log, devices, faults, input events, disablements,
voltages and versions.
Note: Maintenance alarm count is also available but this
is an ID60 feature available at access level 3 only.
All actions are access-controlled either through turning the panel keyswitch to the right, or by entering a Level 2 access code (see Section 4.1.3 Access Codes).
4.1.1 Liquid Crystal Display
The Liquid Crystal Display (LCD) provides 80 characters of alphanumeric information on a 2 line display. The LCD is backlit to assist viewing under dim ambient light conditions.
System Normal Display
When in a quiescent state the LCD shows the ‘Status: NORMAL’ message on line 1 and the day, date and time on line 2. The message will be different if the Site Name menu was edited during commissioning.
The user options are accessed via a menu structure, which in turn is accessed from the ‘Status: NORMAL’ message (see opposite).
If the ‘Status: NORMAL’ message is not present, press the ‘4’ button repeatedly until it is displayed (this terminates access Level 2). Alternatively , turn the keyswitch to the right
and and then back to normal to exit all user menus. Menus will revert to the panel status display automatically five minutes
after the last key press. Press the ‘ ’ button to toggle between the menus and top level display .
Note: To exit the Level 3 Commissioning menu press the
numeric ‘7’ button.
* The Commissioning Menu is ONLY
available with a Level 3 passcode
1 : TEST
2 : DISABLE/ENABLE
3 : CLOCK
4 : VIEW MODE
6 : PRINT
5 : COMMISSIONING
SYSTEM NORMAL
Status: NORMAL
Sat 01/12/2001 00:00:00
ID50 Series Panel - Operating Manual
Operator Actions at Panel
13 997-264-000-8, Issue 8
January 2007
4.1.2 Internal Buzzer
The panel has an internal buzzer which gives a local
warning when any of the following is detected:
a. Fire condition.
b. Pre-alarm condition.
c. Fault condition.
4.1.3 Access Codes
With the exception of the Loop Booster Output T est option,
the actions described in this manual require access Level 2,
which is invoked either by turning the keyswitch or by entry
of an access code. The access code is a sequence of
numbers configured in the panel during commissioning. The
panel has two levels of access codes:7 Level 2 and Level
3. Level 3 is required for testing the loop booster output and
for panel configuration and commissioning procedures.
The panel has a maximum of ten (10) Level 2 access
codes, each defined by the user identification number
[U0 - U9] in the top left-hand corner. Entering a Level 2
access code allows access to all functional controls and
some system operation parameters. (Operating the
keyswitch to enter Level 2 always displays ‘[U9]’).
Note: When the panel is at Level 3, [S1] is displayed in
place of the user identification number.
1 Press the ‘ ’ button at the ‘Status: NORMAL’
message to prompt for a Level 2/3 access code, as shown below:
2 Press and hold the ‘
0..9
’ button while pressing the
appropriate 4 digit Level 2 access code. ‘*’ will appear on the LCD as the numbers are entered.
3 Press the ‘5’ button to confirm the entered code.
The Level 2 Options are then displayed.
4 The procedure to cancel Level 2 (and thus prevent
any other person accessing Level 2 options) is given in Section 4.1.1).
Note: If an incorrect access code is entered, the following
is displayed:
Press the ‘4’ button or wait for approximately one minute to return to the ‘Status: NORMAL ’ message.
ACCESS TO MENUS RESTRICTED
Enter Level 2/3 Passcode: . . . . < : BackSp
[U0] 1:Test 2:Disable/Enable 3:Clock
4:View Mode 5:Commission
ERROR - INCORRECT PASSCODE ! ! !
ACCESS TO MENUS RESTRICTED Enter Level 2/3 Passcode:
* * * *
< : BackSp
Throughout this manual a
U accompanied by a
number represents a Level
2 access code.
5
1
2,3
Operations within this
manual require Level 2
access (code or keyswitch),
although a Level 3 access
code may be entered.
ID50 Series Panel - Operating Manual
Operator Actions at Panel
14997-264-000-8, Issue 8
January 2007
4.1.4 Keyswitch
The panel is fitted with a keyswitch which provides an alternative to the Level 2 access code. If the keyswitch is in the enabled position, it overrides the requirement for a Level 2 access code. Therefore, if an alarm condition occurs the keyswitch enables the immediate operation of the control keys.
With the keyswitch in the enabled position the Level 2 menus are accessible by pressing the ‘ ’ button.
4.2 MUTE BUZZER Pushbutton
Operating the MUTE BUZZER pushbutton when an alarm or fault has occurred, silences the internal buzzer. If the Primary Delay is active during an alarm condition this pushbutton will also terminate this delay and start the Extend Delay time.
The internal buzzer remains silent until the system is RESET or the panel detects another alarm condition.
4.3 EXTEND DELAY Pushbutton
With the occurrence of an alarm and with the Primary Delay active, pressing the EXTEND DELAY pushbutton cancels the initial response time and initiates the fire investigation period (refer to Section 3.1.1 Fire in Delayed Mode). The DELAY ACTIVE LED remains illuminated until the delay timer expires.
[U0] 1:Test 2:Disable/Enable 3:Clock
4:View Mode 5:Commission
ID50 Series Panel - Operating Manual
Operator Actions at Panel
15 997-264-000-8, Issue 8
January 2007
OPERATOR 01 / 05 14:55 EVACUATE
4.4 END DELAY / EVACUATE Pushbutton
The END DELAY/EVACUATE pushbutton is used to
initiate the Evacuate procedure. If this pushbutton is
operated while a delay is active, all delays are cancelled
and all sounders designated in the pre-configured
Evacuate rule are activated.
Fire Alarm Condition
Providing the pushbuttons have been enabled for Level
1 operation and delays are active the following occurs:
1 Press the END DELAY/EVACUATE pushbutton. The
following is typically displayed:
2 No further action is needed until it is required to silence
the sounders, in which case the SILENCE/RESOUND pushbutton should be pressed, see Section 4.5,
Silence / Resound pushbutton.
Note: If the pushbuttons are enabled to operate at
Level 2, enter the Level 2 passcode in the manner described in the RESET pushbutton procedure (Section 4.6).
No Alarm Condition
In quiescent mode, pressing the END DELA Y/EVACUA TE
pushbutton immediately sounds the internal buzzer,
operates all outputs configured in accordance with the
CBE rules (configured at time system was commissioned)
and the LCD displays the ‘EV ACUATE’ message.
OPERATOR 01 / 01 14:55 EVACUATE
ID50 Series Panel - Operating Manual
Operator Actions at Panel
16997-264-000-8, Issue 8
January 2007
4.5 SILENCE / RESOUND Pushbutton
The term ‘silence’ as used throughout this manual, describes a temporary state the panel enters whenever the SILENCE / RESOUND pushbutton is pressed to stop the sounders operating. While the panel is in this state, a new fire alarm, operating the SILENCE / RESOUND pushbutton again or operation of the END DELAY/ EVACUATE pushbutton, will re-sound all previously silenced sounders.
You can suspend all sounder output delays and silence all sounder outputs which are operating as a result of a FIRE alarm or an EVACUATE operation. Provided that the pushbuttons have been enabled for Level 1 operation and delays are active, proceed as follows:
1 Press the SILENCE / RESOUND pushbutton. The
following are not switched off by this operation: a. The internal FIRE buzzer. b. Any output modules configured in the CBE Rules
during commissioning NOT to be silenced by the SILENCE / RESOUND pushbutton.
2 To start the sounders again in the same pattern as
they were previously operating and reactivate any programmed delays, press the SILENCE / RESOUND pushbutton.
3 The panel may have been configured, during
commissioning, to illuminate the SOUNDERS SILENCED LED when the SILENCE/RESOUND pushbutton is pressed (non-default selection). Pressing the SILENCE / RESOUND pushbutton again to operate the sounders, the SOUNDERS SILENCED LED extinguishes.
Note: If the pushbuttons are enabled to operate at
Level 2, enter the Level 2 passcode in the manner described in the RESET pushbutton procedure (Section 4.6).
1
2
3
ID50 Series Panel - Operating Manual
Operator Actions at Panel
17 997-264-000-8, Issue 8
January 2007
CONTROL KEY LOCKED - ACCESS REQUIRED
Enter Level 2/3 Passcode: . . . . < : BackSp
CONTROL KEY LOCKED - ACCESS REQUIRED Enter Level 2/3 Passcode:
* * * *
< : BackSp
5
4.6 RESET Pushbutton
The RESET pushbutton is used to clear all non-quiescent
conditions and return the panel to a normal quiescent
condition. Provided that the control keys have been
enabled for Level 1 operation, the following occurs:
a. All FIRE and FAULT lamps are switched off.
b. All sounders cease to operate.
c. The system status returns to NORMAL provided that
no operator actions are being carried out.
If the pushbuttons are enabled to operate at Level 2, follow
the procedure below:
1 Press the RESET pushbutton. The LCD displays the
following:
2 Either turn the keyswitch, or enter an appropriate Level
2 access code and confirm using the ‘5’ button.
If Alarm(s), and/or Fault(s) conditions are still present
when RESET is operated, the condition will be reported
as if it were a completely new event with appropriate
annunciation.
ID50 Series Panel - Operating Manual
Operator Actions at Panel
18997-264-000-8, Issue 8
January 2007
4.7 Numeric Keys
When using any numeric key, each operation is confirmed by a sharp audible bleep.
At Access Level 1, the numeric buttons have NO function until an alarm condition occurs. The alarm condition
enables the ‘2’ and ‘8’ buttons, allowing the user to view each alarm in turn.
At Access Level 2 the ‘2/8’ function remains identical to the Level 1 function. The ‘4’ (cancel), ‘5’ (confirm), ‘6’ (go to next option) buttons are enabled. Numeric entry (used in conjunction with the ‘
0..9
’ [shift] button) is
also enabled.
a. Use the ‘2’ and ‘8’ buttons to scroll through fire
alarms, fault conditions, and warning conditions or to
view the ‘More’ menu list when available.
b. Press the ‘5’ button to confirm an option. c. Press the ‘
0..9
’ (Shift) button to enable number entry.
Following the input of a number (approx. 1 sec later)
a second audible bleep indicates that number entry is
no longer enabled.
4.7.1 Cancellation/Termination Button
T o cancel or terminate configuration data entry , press the ‘4’ button. The LCD returns to the previous menu.
To cancel access rights, press the ‘4’ button until the ‘Status: NORMAL ’ message is displayed.
4.7.2 Level 2 Options Menu Button
Operating the ‘ ’ button enables the Level 2 menu and prompts for the entry of an appropriate access code, as
described in Section 4.1.3 Access Codes. Pressing the menu button toggles between the panel
status and user menus.
Press and hold the ‘
0..9
(Shift) pushbutton while
entering numbers.
0..9
4
ID50 Series Panel - Operating Manual
Operator Actions at Panel
19 997-264-000-8, Issue 8
January 2007
Notes:
1. Level 3 Configuration Menus are described in 997-263-000-X, ID50 Series Panel Installation, Commissioning & Configuration Manual, Section 5 Configuration.
2. With a fire alarm active the panel status
display will override the user menu 5 secs after the last key press.
4.8 Level 2 Option Menus
The following Level 2 Option Menus are available after a correct Level 2 access code has been input or the keyswitch has been operated.
The menu map at left shows an overview of the Level 2 menus. The Commissioning menu is shown inverted to indicate that a Level 3 access is required.
ID50 Series Panel - Operating Manual
Operator Actions at Panel
20997-264-000-8, Issue 8
January 2007
4.9 TEST - User Option
The following tests are available at Access Level 2 from the Test - User Option menu:
a. LEDs. b. LCD. c. Zones. d. Auto High Test. e. Outputs. f. Buzzer. g. Keyboard. To start the TEST - User Option:
1 At the ‘Status:NORMAL’ message, press the ‘
button. The LCD prompts for a Level 2/3 access code. (To cancel, press ‘4’).
Note: Entering an incorrect access code causes the LCD
to display the ‘ERROR - INCORRECT P ASSCODE ! ! !’ message, then an automatic return to the access code prompt.
2 Either turn the keyswitch or, using the numeric keypad,
enter the correct Level 2 access code and confirm using the ‘5’ button. The User Option menu is
displayed with the user number ([U0] to [U9]) in the top left-hand corner.
Extinguishing System - T esting SLC de vice outputs.
T o prevent inadvertant operation of the direction and release valves during testing, zones containing the associated SLC devices MUST FIRST be put into TEST mode. Also, where a zone test is manually activated using an input module, extinguishant bottles MUST FIRST be disconnected to prevent unauthorized extinguishant discharge.
Note: A manual release reset will not stop the
extinguishant discharge because of a physical link between the direction valve inputs and outputs.
ACCESS TO MENUS RESTRICTED
Enter Level 2/3 Passcode: . . . . < : BackSp
[U0] 1 : T est 2 : Disable/Enable 3 : Clock
4 : View Mode 5 : Commission
ID50 Series Panel - Operating Manual
Operator Actions at Panel
21 997-264-000-8, Issue 8
January 2007
4.9.1 LEDs - User Option
This option, selected from the T est menu, illuminates each LED in turn. T o test the p anel LEDs, enter access Level 2 and follow the procedure below:
1 Using the numeric keypad, press ‘1’ to display the
TEST menu.
2 To test LEDs, press the ‘1’ button on the numeric
keypad.
3 Each of the panel LEDs illuminates in turn while the
LCD flashes the message shown below. When all LEDs have been tested, press the ‘4’ button to
cancel and return to the Test menu.
4.9.2 LCD - User Option
The LCD Option, selected from the Test menu, tests the LCD by displaying each upper case character in turn. To test the LCD, enter access Level 2 and follow the procedure below.
1 Using the numeric keypad, press ‘1’ to display the
TEST menu.
2 T o test the LCD, press the ‘2’ button on the numeric
keypad.
3 Each character is then displayed in turn on the LCD.
When all characters have been displayed, press the ‘4’ button to cancel and return to the Test Menu.
[U0] 1 : T est 2 : Disable/Enable 3 : Clock
4 : View Mode 5 : Commission
TESTING LEDs ! ! !
[U0] 1 : T est 2 : Disable/Enable 3 : Clock
4 : View Mode 5 : Commission
AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA
BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB
ZZZZZZZZZZZZZZZZZZZZZZZZZZZZZZZZZZZZZZZZ ZZZZZZZZZZZZZZZZZZZZZZZZZZZZZZZZZZZZZZZZ
1
1
1
2
[U0 Test] 1:LEDs 2:LCD 3:Zones
4:Auto High T est 5:Outputs : More
[U0 Test] 1:LEDs 2:LCD 3:Zones
4:Auto High T est 5:Outputs : More
ID50 Series Panel - Operating Manual
Operator Actions at Panel
22997-264-000-8, Issue 8
January 2007
4.9.3 Zones - User Option
The Test Zones option, selected from the Test Menu, allows the user to perform a walk test on one zone at a time.
During the walk test the TEST and relevant ZONE FAUL T/DISABLE/TEST LEDs are illuminated, indicating that the system and zone is in TEST mode. To perform a walk test, at the TEST menu:
1 Press the ‘3’ button on the numeric keypad to select
the walk test procedure.
2 The LCD displays the T est Zones menu. Select either
the Ring Sounders or No Sounders walk test:
a. Using the numeric keypad press ‘1’ to display the
Ring Sounders menu as below. In this mode the sounders will ring for a few seconds when a device is tested, then reset automatically.
i Use the ‘2/8’ buttons to select the zone to be
tested. Press the ‘5’ button to confirm the zone number.
ii The LCD prompts for confirmation. Press the ‘5’
button to start the walk test for this zone. Repeat steps i and ii for any further zones to be tested. Test the devices (see Checking the Devices overleaf).
iii Press the ‘4’ button to exit the Ring Sounders menu
and return to the Zones menu.
b. To walk test devices on a specific zone without
activating the sounders, press ‘2’ on the numeric keypad to select the ‘No Sounders’ option. The walk
test procedure is otherwise the same as given above for ‘Ring Sounders’.
[U0 Zones] 1: Ring Sounders 2:No Sounders 3:View/Stop Test : More
[WALK TEST (Sounders)] Select Zone:01
: Start : Change <:Exit
[WALK TEST (Sounders)] Select Zone: 01 Press to Confirm <:Cancel
[WALK TEST (Sounders)] Select Zone: 01
: Start : Change <:Exit
3
52 8
1
2
or
[U0 Test] 1:LEDs 2:LCD 3:Zones
4:Auto High Test 5:Outputs : More
ID50 Series Panel - Operating Manual
Operator Actions at Panel
23 997-264-000-8, Issue 8
January 2007
3 To end the walk test: a.
For a specified zone: at the Test Zones menu, press the ‘
3
’ button on the numeric keypad to select the
View/S top Test menu:
i Use the ‘2/8’ buttons to select the zone, then press
the ‘5’ button to confirm the zone number.
ii Press the ‘5’ button to stop the walk test for the
selected zone. If no other walk tests are active, the following is displayed:
iii Press the ‘4’ button to exit the W alk Test menu and
return to the Test Zones menu.
b. For all zones: from the ‘ : More’ option (‘2/8’)
press the ‘4’ button on the numeric keypad to select the Stop All menu:
4 To exit the Test Zones menu, press the ‘4’ button.
Continue pressing this button until the required menu or the ‘Status: NORMAL ’ message is displayed.
Checking the Devices
Use the following methods to check devices during a walk test: i. Test sensors by applying smoke or heat as
appropriate, or by operating the device’s internal test switch by means of a magnet.
ii. Test Manual Call Point s by using a test key. For each device, the panel will record the event in the
log, sound its internal buzzer , illuminate the appropriate ZONE FIRE LED and turn on the LED at the device that initiated the alarm.
Note: A maximum of ten devices’ LEDs can be illuminated
during the test. Further device testing functions normally in all other respects. LEDs will not light again until after the removal of the walk test condition and manually resetting the panel.
[STOP WALK TEST] Select Zone: 01
: Stop : Change <:Exit
[STOP WALK TEST] Select Zone: 01 Press to Confirm <:Cancel
The system has no walk test zones active
<:Exit
[U0 Zones] 1: Ring Sounders 2:No Sounders 3:View/Stop Test : More
[U0 Zones] 4: Stop All
: More
Stop all Zones in Walk Test ? Press to Confirm <:Cancel
52
8
or
2
8
5
4
ID50 Series Panel - Operating Manual
Operator Actions at Panel
24997-264-000-8, Issue 8
January 2007
After a few seconds, the panel will automatically return to Test Mode and the device LED will be turned off. The panel is then ready to test the next device.
Note: Up to one minute must be allowed for smoke
sensors to clear.
If a fire alarm signal is received from a zone other than those being tested, all sounder output and relay output circuits will activate as configured for a zone in alarm. The sounders will continue to ring until silenced from the panel.
4.9.4 Auto High Test - User Option
The Auto High Test, if configured during commissioning, automatically polls and tests all devices on the loop at a specified time of day. This test takes about 70-80 seconds to complete. To run the test manually:
1 From the T est Menu, using the numeric keypad press
the ‘4’ button to select the Auto High Test.
2 When the LCD displays the start Auto High Test
message, press the ‘5’ button to start the test.
3 The LCD displays the message shown below, then
re-displays the Test Menu.
4 If a fault occurs while the Auto High Test is active the
LCD displays a fault message (example given below):
Press the ‘6’ button to display additional zonal and device text information. Press the ‘4’ button to return
to the Test menu. Clear the fault and repeat the test.
Manually start automatic high test ? Press to confirm <:Cancel
F AULT 01 / 03 Z01 M12 MCP 14:55 DEVICE F AILED AUTO HIGH TEST >
Automatic high test started ! ! !
4
5
[U0 Test] 1:LEDs 2:LCD 3:Zones
4:Auto High Test 5:Outputs : More
ID50 Series Panel - Operating Manual
Operator Actions at Panel
25 997-264-000-8, Issue 8
January 2007
4.9.5 Outputs - User Option
The Test Outputs option, accessed from the T est Menu, tests the panel’s internal sounder and relay circuits and the Signalling Line Circuit (SLC) loop outputs. To perform this test:
Test Internal Outputs
1 From the Test Menu, press the ‘5’ button on the
numeric keypad to select the Outputs option.
2 Press the ‘1’ button on the numeric keypad to display
the Internal Test menu.
3 Use the ‘2/8’ buttons to select the internal output
required for testing and press the ‘5’ button to start the test. The LCD then displays the following:
4 Check that the output operates. T o stop the test, press
the ‘4’ button. Press the ‘4’ button again to return to the Test Outputs menu.
Test SLC Outputs
1 From the Outputs menu, press the ‘2’ button on the
numeric keypad to display the SLC Output Test menu:
2 Use the ‘2/8’ buttons to select the output required
for testing and press the ‘5’ button to start the test. The LCD then displays the following:
3 Check that the output operates. T o stop the test, press
the ‘4’ button. Press the ‘4’ button again to return to the Test Outputs menu.
[Internal Test] B:01 SDR
: Start : Change Output <:Exit
[U0 Outputs] 1:Internal 2:SLC
3: Loop P ower
[Internal Test] B:01 SDR Output test in progress <:Stop
[SLC Test] M:nn SDR
: Start : Change Output <:Exit
[SLC Test] M:nn SDR Output test in progress <:Stop
[U0 Test] 1:LEDs 2:LCD 3:Zones
4:Auto High T est 5:Outputs : More
[U0 Outputs] 1:Internal 2:SLC
3: Loop P ower
ID50 Series Panel - Operating Manual
Operator Actions at Panel
26997-264-000-8, Issue 8
January 2007
[U0 Outputs] 1:Internal 2:SLC
3:Loop Power
COMMISSION MODE ACCESS Enter Level 3 passcode - < BackSp
To perform a Loop Booster output test an access level 3 passcode ( is required.
[LBM Test] Loop : Both Sides 0%
: Start : Change<:Exit
Test Loop Booster Outputs
A number of tests are available to satisfactorily test the operation of the Loop Booster Modules (LBMs) during alarm conditions. The tests are designed so that the power delivered to the loop by the panel can be switched off from either end, or each LBM in turn can be prevented from being turned on. The tests are designed, when combined with a walk-test, to check that:
a. The panel operates all loop-powered devices correctly
with the LBM(s) with one source of loop power isolated.
b. All loop-powered outputs operate correctly with any individual
LBM disabled or with the loop only powered from one end.
1 Press the ‘3’ button on the numeric keypad to select
the Loop Booster test procedure. With the panel currently at access level 2, the following warning is displayed prompting for entry of access level 3 passcode:
2 Having entered the access level 3 passcode, press
the ‘5’ button to start the test.
3 Before the test starts a 0% percentage indication of the
equipment under test is displayed on the top line. As the test progresses, the percentage value increases to 100% as to indicate that all loop-powered devices under test are operating correctly. This percentage value may go down if a device starts reporting incorrectly or becomes de-activated.
4 Press the ‘2/8’ pushbuttons to select the other Loop
Booster options: ‘In Only’ or ‘Out Only’
5 To perform a loop test without loop booster support
you can turn off individual LBMs while testing that loop­powered sounders are still able to operate correctly .
6 Press the 4’ button to cancel the test and return to
the Test Menu.
Note: If the test is not cancelled manually, it is cancelled
automatically 4 hours after the last panel keystroke.
[LBM Test] Loop : Both Sides 0%
: Start : Change<:Exit
[LBM Test] Loop : Out Only 0%
: Start : Change<:Exit
[LBM T est] Loop : In Only 0%
: Start : Change<:Exit
[LBM Test] M nn : Inactive 0%
: Start : Change<:Exit
Select ‘Both Sides’ to test loop­powered sounders only (LBMs are not turned on).
Select ‘In Only’ to perform test with loop powered only from the ‘Loop Out’ end.
Select ‘Out Only’ to perform test with loop powered only from the ‘Loop In’ end.
ID50 Series Panel - Operating Manual
Operator Actions at Panel
27 997-264-000-8, Issue 8
January 2007
Press ALL keys to exit . . . 0 . . 9 0 MENU 1 2 3 4 5 6 7 8 9 A B C D E
4.9.7 Keyboard - User Option
This option allows the panel keyboard to be functionally tested.
1 Using the numeric keypad, press ’1’ to display the
TEST menu.
2 Press the ‘2/8’ pushbuttons to display the next
screen options. To test the keyboard, press the ‘7’ button on the numeric keypad.
3 The following screen is displayed. Press each panel
pushbutton in turn. When a pushbutton is pressed, the corresponding display entry is replaced by an equivalent number of asterisk (*) characters. The five pushbuttons are represented by A to E, where A is the top button. Once all pushbuttons have been pressed the display will return to the test menu. The keyboard test will automatically abort after one minute if no key is pressed.
[U0] 1 : Test 2 : Disable/Enable 3 : Clock
4 : View Mode 5 : Commission 6:Print
The standard function of the
control keys is suppressed
while this test is active.
Normal function resumes
upon test completion.
7
[U0 Test] 6:Buzzer 7:Keyboard
: More
1
4.9.6 Buzzer - User Option
The Buzzer User Option, selected from the Test Menu, tests the internal buzzer . Proceed as follows:
1 Using the numeric keypad, press ’1’ to display the
TEST menu.
2 Press the ‘2/8’ pushbuttons to display the next
screen options. To test the buzzer, press the ‘6’ button on the numeric keypad.
3 The buzzer sounds with a 2:1 mark:space ratio and
the LCD flashes the message below. Press the ‘4’ button to cancel the test and return to the Test Menu.
[U0] 1 : T est 2 : Disable/Enable 3 : Clock
4 : View Mode 5 : Commission
[U0 Test] 6:Buzzer 7:Keyboard
: More
1
TESTING BUZZER ! ! !
6
ID50 Series Panel - Operating Manual
Operator Actions at Panel
28997-264-000-8, Issue 8
January 2007
[U0 Disable/Enable] 1:Zone 2:Outputs
3:Day Mode 4:Delays
[Disable/Enable] Zone _ _ Enter Zone Number < : Cancel
1
4.10 DISABLE / ENABLE - User Option
This option allows the user to disable or enable (depending on their current state) the following parts of the system:
a. Zone (Device or Full Zone). b. Outputs. c. Day Mode. d. Delays. T o display the DISABLE/ENABLE menu:
1 At the ‘Status: NORMAL’ message, press the ‘
button. The LCD prompts for a Level 2/3 access code.
2 Either turn the keyswitch or, using the numeric keypad,
enter the correct Level 2 access code and confirm using the ‘5’ button to display the menu. The LCD
displays the user number ([U0] to [U9]) in the top left­hand corner.
Note: An incorrect access code causes the LCD to
display the ‘ERROR - INCORRECT PASSCODE’ message. After one minute the LCD returns to the ‘Status: NORMAL’ message.
3 Using the numeric keypad, press the ‘2’ button to
display the DISABLE / ENABLE menu.
4.10.1 Zone - User Option
This option allows the user to disable/enable a full zone or part of a zone (selected devices). T o perform this operation:
1 Using the numeric keypad, press the ‘1’ button to
select the Disable/Enable Zone option.
2 The LCD displays the Zone option and prompts for a
zone number. Enter the zone number (one or two digits entered via the numeric keypad). Press the ‘5’ to
confirm the zone number.
[U0] 1 : Test 2 : Disable/Enable 3 : Clock
4 : View Mode 5 : Commission
[U0 Disable/Enable] 1:Zone 2:Outputs
3:Day Mode 4:Delays
2
ACCESS TO MENUS RESTRICTED
Enter Level 2/3 Passcode: . . . . < : BackSp
ID50 Series Panel - Operating Manual
Operator Actions at Panel
29 997-264-000-8, Issue 8
January 2007
3 The LCD then displays the current state of the zone
(Fully enabled, Fully disabled or Part disabled) and prompts for selection of Full Zone or Devices in zone:
Note: Press the ‘2/8’ buttons to step to the previous/
next zone and confirm using the ‘5’ button.
4 To disable:
a. A Full Zone - Press the ‘1’ button on the numeric
keypad to select the Full Zone option, and the ‘5’ button to confirm.
The DISABLEMENT and relevant ZONE FAULT/ DISABLE/TEST LEDs illuminate, indicating that the selected zone(s) are now disabled. The LCD returns to the Disable/Enable menu.
To enable a Full Zone:
The DISABLEMENT and relevant ZONE FAULT/ DISABLE/TEST LEDs extinguish.
b. A Partial Zone - Press the ‘2’ button on the numeric
keypad to select the Device in Zone option:
5 To select individual devices use the ‘2/8’ buttons
to display the required device(s). Confirm selection of each by pressing the ‘5’ button.
[Disable/Enable] Zone 0 1 (Fully enabled) 1:Full Zone 2:Device in Zone : More
[Disable/Enable] Zone 0 1 Disable fully ? Press to Confirm <:Cancel
[Disable/Enable] Zone 0 1 Fully disabled 1:Full Zone 2:Device in Zone : More
[Disable/Enable] Zone 0 1 Enable fully ? Press to Confirm <:Cancel
[Disable/Enable] Zone 0 1 Fully enabled 1:Full Zone 2:Device in Zone : More
5
5
1
5
1
[Disable/Enable] Zone 0 1 Part disabled 1:Full Zone 2:Device in Zone : More
[Enable] Zone 0 1 - Enable S02 ? Press to confirm <:Cancel
[Disable] Zone 0 1 - Disable S01 ? Press to confirm <:Cancel
[Disable] Zone 0 1 - Disable M99 ? Press to confirm <:Cancel
5
2
8
2
ID50 Series Panel - Operating Manual
Operator Actions at Panel
30997-264-000-8, Issue 8
January 2007
Repeat until all devices are in the required state (either disabled or enabled). The DISABLEMENT LED remains illuminated if one or more devices are disabled. It is extinguished when all devices have been enabled.
The relevant ZONE FAULT/DISABLE/TEST LED is illuminated when all devices in that zone have been disabled. Disablement of ALL devices is confirmed by the ‘Fully Disabled’ LCD message.
6 Press the ‘4’ button to return to the Disable/Enable
menu.
ID50 Series Panel - Operating Manual
Operator Actions at Panel
31 997-264-000-8, Issue 8
January 2007
4.10.2 Outputs - User Option
The Outputs option allows the user to disable or enable all sounders, the extinguishant system (if fitted), and relay and control outputs.
To Disable/Enable these outputs, proceed as follows:
1 Using the numeric keypad, press the ‘2’ pushbutton
to display the Disable/Enable Outputs menu:
2 Press the appropriate numbered button on the
numeric keypad to display one of the following: a. Press the ‘1’ button to disable/enable all
sounders.
b. Press the ‘2’ button to disable/enable all
transmission device outputs.
c. Press the ‘2’ button to disable/enable all
Extinguishant System outputs.
d. Press the ‘3’ button to disable/enable all Fault
relay outputs.
e. Press the ‘5’ button to disable/enable ‘other’
(relays and control) outputs.
3 Press the ‘5’ button to confirm the selected
operation. The LCD automatically returns to the Disable/Enable menu.
When outputs are disabled, the general DISABLEMENT LED and, if applicable, the FIRE CONTROL O/P: F AULT/ DISABLED, FIRE OUTPUT : F AUL T/DISABLED and/or SOUNDERS: FAUL T/DISABLED LEDs illuminate. If the Extinguishant System is disabled, only the DISABLEMENT LED will illuminate.
[U0 Disable/Enable] 1:Zone 2:Outputs
3:Day Mode 4:Delays
Disable ALL Sounder Outputs Press to confirm <:Cancel
Disable ALL Extinguishant System Outputs Press to confirm <:Cancel
1
5
3
2
2
[U0 Disable/Enable] 3:Ext. Systems
4:Fault Relays 5:Other s :More
[U0 Disable/Enable] 1:Sounder s
2:T ransmission Device Outputs :More
Disable ALL T ransmission Device Outputs Press to confirm <:Cancel
4
5
Disable ALL Relay and CTL Outputs Press to confirm <:Cancel
Disable ALL Fault Relay Outputs Press to confirm <:Cancel
ID50 Series Panel - Operating Manual
Operator Actions at Panel
32997-264-000-8, Issue 8
January 2007
4.10.3 Day Mode - User Option
If Day Mode is enabled during panel commissioning, this option allows the user to activate/deactivate Day Mode delays during the set Day Mode time period. This has no effect on any sensor sensitivity changes that may have been configured during commissioning. Any sensor sensitivity changes will automatically occur at the set Day Mode period start and end times.
To Disable / Enable Day Mode, proceed as follows:
1 From the Disable / Enable menu, press the ‘3’ button
to display the following:
2 Press the ‘5’ button to confirm the requested
operation. The LCD automatically returns to the Disable / Enable menu.
If Delays have been configured the DELAY ACTIVE LED illuminates when Day Mode is started.
3 To end Day Mode, repeat step s 1 and 2 (the display is
as shown below):
The DELAY ACTIVE LED will extinguish when the Day Mode operation has been ended, either when day mode is turned off or when the timer has timed out. No delays are active.
Note: If Day Mode is NOT cancelled manually, Day Mode
delays are automatically deactivated at the end of the set time period.
[U0 Disable/Enable] 1:Zone 2:Outputs
3:Day Mode 4:Delays
Start Day Mode Press to confirm <:Cancel
[U0 Disable/Enable] 1:Zone 2:Outputs
3:Day Mode 4:Delays
End Day Mode Press to confirm <:Cancel
3
5
The FIRE CONTROL O/P: F A ULT/DISABLED, FIRE OUTPUT: FAULT/DISABLED and the SOUNDERS DISABLED LEDs extinguish when the corresponding outputs have been enabled. The DISABLEMENT LED will only extinguish when ALL disablements have been enabled.
[U0 Disable/Enable] 1:Zone 2:Outputs
3:Day Mode 4:Delays
5
ID50 Series Panel - Operating Manual
Operator Actions at Panel
33 997-264-000-8, Issue 8
January 2007
4.10.4 Delays - User Option
The Disable / Enable Delays option allows the user to cancel or initiate the Delays function of the panel, which is configured during commissioning (refer to 997-263
ID50 Series Panel Installation, Commissioning and Configuration Manual, Sections 5.5.5.4 Primary/ Extend Delay Timers and 5.7.8 CBE Zones).
To Disable / Enable Delays:
1 Using the numeric keypad, press the ‘4’ button to
select the Disable/Enable Delays option:
2 At the prompt, press the ‘5’ button to confirm the
Delays operation. If delays are disabled, the LCD prompts to enable delays, and vice versa.
When the delays are disabled, the DELAY ACTIVE LED is extinguished. When the delays are enabled, the LED is illuminated.
If a Day Mode time period is configured, the CBE Rule delays will activate when Day Mode is started either:
a. Using the Disable / Enable menu, or b. When Digital / ÜE Input 1 is operated (if this input
is configured during commissioning for Day Mode Start).
These delays will be deactivated when Day Mode is ended, either automatically at the end of the configured Day Mode period, or by one of the following:
a. Using the Disable / Enable menu, b. When the Digital / ÜE Input 1 is operated, c. Delays are disabled using the Disable / Enable
menu.
[U0 Disable/Enable] 1:Zone 2:Outputs
3:Day Mode 4:Delays
Disable Delays Press to confirm <:Cancel
[U0 Disable/Enable] 1:Zone 2:Outputs
3:Day Mode 4:Delays
5
4
ID50 Series Panel - Operating Manual
Operator Actions at Panel
34997-264-000-8, Issue 8
January 2007
4.11 Clock - User Option
The CLOCK User Option allows the user to enter or edit the following:
a. Time. b. Date. To edit the CLOCK - User Option:
1 At the ‘Status: NORMAL’ message, press the ‘
button. The LCD prompts for a Level 2/3 access code.
Note: If an incorrect access code is entered, the LCD
displays an ‘ERROR - INCORRECT P ASSCODE ! ! !’. After one minute the LCD returns to the ‘St atus: NORMAL’ message.
2 Either turn the keyswitch or, using the numeric keypad,
enter the correct Level 2 access code and confirm using the ‘5’ button. The Level 2 menu is displayed
with the user number ([U0] to [U9]) in the top left-hand corner.
3 Press the ‘3’ button on the numeric keypad to select
the Clock menu.
ACCESS TO MENUS RESTRICTED
Enter Level 2/3 Passcode: . . . . < : BackSp
[U0] 1 : T est 2 : Disable/Enable 3 : Clock
4 : View Mode 5 : Commission
[U0 Clock] 1 : Time 2 : Date
5
3
ID50 Series Panel - Operating Manual
Operator Actions at Panel
35 997-264-000-8, Issue 8
January 2007
4.11.1 Time - User Option
The Time User Option allows the user to enter or edit the current time displayed on the LCD. To edit the time, proceed as follows:
1 Press the ‘1’ pushbutton on the numeric keypad to
select the Time option.
2 The LCD displays the Enter New Time prompt. Using
the numeric keypad, enter the numbers directly. All digits are automatically entered into position from left to right on the display .
After entering the last digit, press the ‘5’ to confirm and return to the CLOCK menu.
Note: The entered time must be in the 24-hour clock
format (e.g. for 07:1 1 pm, enter 1911).
If an invalid time is entered, the LCD displays an error message and then re-displays the Clock menu.
[U0 Clock] 1 : Time 2 : Date
ENTER NEW TIME (format hh : mm)
- - : - - <:Cancel
ENTER NEW TIME (format hh : mm) 19 : 11 <:Cancel
[U0 Clock] 1 : Time 2 : Date
ENTER NEW TIME (format hh : mm) 91 : 11 <:Cancel
Invalid Value Entered !
[U0 Clock] 1 : Time 2 : Date
1
1
1
1
1
1
5
51
9
9
ID50 Series Panel - Operating Manual
Operator Actions at Panel
36997-264-000-8, Issue 8
January 2007
4.11.2 Date - User Option
The Date User Option allows the user to enter or edit the current date displayed on the LCD. To enter or edit the date, proceed as follows:
1 Using the numeric keypad, press the ‘2’ button to
select the Date option.
2 The LCD prompts for entry of a new date. Using the
numeric keypad, enter the numbers directly . All digits are automatically entered into position from left to right on the display .
After entering the last digit press the ‘5’ to confirm and return to the Clock menu.
Note: The date MUST be entered in the same format as
indicated on the LCD. Only date entries between 2000 and 2063 are valid.
If an invalid date is entered, for example 222222 - 22/22/22, the LCD displays an error message and then re-displays the Clock menu.
[U0 Clock] 1 : Time 2 : Date
ENTER NEW DATE (format dd/mm/yy)
- -/- -/- - <:Cancel
Invalid Value Entered !
ENTER NEW DATE (format dd/mm/yy) 12/12/00 <:Cancel
[U0 Clock] 1 : Time 2 : Date
ENTER NEW DATE (format dd/mm/yy) 22/22/22 <:Cancel
[U0 Clock] 1 : Time 2 : Date
1 1
5
2
2 2 0 0
5
2 22
2
2
2
ID50 Series Panel - Operating Manual
Operator Actions at Panel
37 997-264-000-8, Issue 8
January 2007
4.12 View Mode - User Option
The VIEW MODE User Option allows the user to view the following system parameters:
a. Log b. Devices on the loop c. Faults d. Input Events e. Disablements on the loop f. Maintenance Log (ID60 only - requires access level 3) g. Alarm Count h. Voltages i. Version (system and loop software).
To display the View Mode menu:
1 From the ‘Status: NORMAL’ message, press the ‘
button. The LCD prompts for a Level 2/3 access code.
Note: If an incorrect access code is entered, the LCD
displays ‘ERROR - INCORRECT P ASSCODE ! ! !’. After one minute the LCD returns to the ‘Status: NORMAL’ message.
2 Either turn the keyswitch or, using the numeric keypad,
enter the correct Level 2 access code and confirm using the ‘5’ button. The Level 2 menu is displayed with the
user number ([U0] to [U9]) in the top left-hand corner .
3 Using the numeric keypad, press the ‘4’ button to
select the View Mode menu:
4 Press the ‘2/8’ buttons to display further menu
options:
* ID60 panels only
ACCESS TO MENUS RESTRICTED
Enter Level 2/3 Passcode: . . . . < : BackSp
5
4
[U0] 1 : T est 2 : Disable/Enable 3 : Clock
4 : View Mode 5 : Commission
[U0 View] 1: Log 2: Devices 3: Faults
4: Input Events 5: Disabled : More
[U0 View] 6: Maint.* 7: Alarm Count
8: V oltages 9: V ersion : More
82
or
ID50 Series Panel - Operating Manual
Operator Actions at Panel
38997-264-000-8, Issue 8
January 2007
4.12.1 Log - User Option
The Log User Option allows the user to view all logged events, one at a time. To display the Log, from the VIEW Mode menu:
1 On the numeric keypad, press the ‘1’ pushbutton to
select the Log option.
2 The LCD automatically displays the last recorded
event. Viewing commences from this point; press the ‘2/8’ buttons to scroll through the Log entries.
Example Log entries are given below:
Note: Press the ‘6’ button to view additional zone text
information. T o return to the previous display press any numeric/cursor key. Alternatively, if no key is pressed within ten (10) seconds the LCD returns to the View Log display automatically .
3 Press the ‘4’ pushbutton to return to the View Mode
menu.
[U0 View] 1:Log 2:Devices 3:Faults 4:Input Events 5:Disabled : More
[LOG 002/512] M12 MCP 12/12/00 14:55 DEVICE ADDED >
[LOG 001/512] 12/12/00 11:48 CPU FAULT >
[LOG 002/512] M12 MCP 12/12/00 14:55 ZONE10 >
1
6
2
8
ID50 Series Panel - Operating Manual
Operator Actions at Panel
39 997-264-000-8, Issue 8
January 2007
4.12.2 Devices - User Option
The Devices User Option allows the user to observe all loop devices in turn. T o view Devices, from the View Mode menu:
1 On the numeric keypad, press the ‘2’ button to select
the Devices display .The LCD displays the last-viewed sensor address:
2 Press the ‘2/8’ buttons to scroll through device
address entries until the desired sensor is displayed.
3 Press the 6’ button to view additional device
information.
Note: Three percentage values are displayed [this is the
device’s alarm level status, e.g. 100% (default) is equivalent to alarm]. The value on the left is the current alarm status level. The other percentage values are historical; the previous two alarm status percentages are displayed, the one on the left being the more recent.
4 Press the ‘4’ button to return to the View Mode
menu.
AWACSTM Devices (ID60 only)
The ID60 panel allows the configuration of all sensor types, except HEAT sensors, to use the AW ACSTM multi­sensing algorithm. For these devices an additional screen is available which displays the current percentage values for alarm and pre-alarm.
[U0 View] 1:Log 2:Devices 3:Faults 4:Input Events 5:Disabled : More
[U0 Sensor 02 - OPT] >: Next : More PW1:286 2:283 3:285 4:1003 5:0292 <:Exit
[U0 Sensor 03 - OPT] >: Next : More PW1:286 2:283 3:285 4:1003 5:0292 <:Exit
Device
Type
Device
Address
Pulse Width
Time Periods
2
2
8
[U0 Sensor nn - OPT] >: Next : More Level 050% -
〉〉
〉〉
050% -
〉〉
〉〉
050%
[U0 Sensor nn - AAA] >: Next : More PW1:286 2:283 3:285 4:1003 5:0292 <:Exit
[U0 Sensor nn - A VS] >: Next : More AW A CS - Alarm: 000%, Prealarm: 000%
ID50 Series Panel - Operating Manual
Operator Actions at Panel
40997-264-000-8, Issue 8
January 2007
4.12.3 Faults - User Option
This menu option allows the user to view active faults while the normal active fault display has been overridden by a higher priority display (alarms). T o view Fault s, from the View Mode menu:
1 On the numeric keypad, press the ‘3’ button to select
the Faults display .
2 The LCD automatically displays the last recorded
event first. Viewing commences from this point. Press the ‘2/8’ buttons to scroll through the faults.
Note: Press the ‘6’ button to view additional zone text
information. To return to the fault message press any numeric/cursor key. Alternatively, if no key is pressed within ten (10) seconds the display reverts to the fault message. Example fault displays are given below:
a. Fault condition b. Fault currently displayed. c. Total number of faults
logged. d. Text description of fault. e. Zone Number. f. Device Address. g. Device Type. h. Time fault was logged.
Note: If no faults are recorded on the system, the
following message is displayed:
3 Press the ‘4’ button to return to the View Mode
menu.
[U0 View] 1:Log 2:Devices 3:Faults
4:Input Events 5:Disabled : More
F AULT 01 / 03 Z01 M12 MCP 14:55 < - - - Zone Te xt - - - > < - - - Device Text - - - >
FAULT 01 / 03 Z01 S23 TMP 14:55 NO REPLY FROM DEVICE >
The system has NO faults present
<:Exit
FAULT 01 / 03 Z01 M12 MCP 14:55 NO REPLY FROM DEVICE >
ABC DE F G H
2
8
6
3
ID50 Series Panel - Operating Manual
Operator Actions at Panel
41 997-264-000-8, Issue 8
January 2007
4.12.4 Input Events - User Option
The Input Events menu option allows the user to view active input events/plant alarms while the normal active input events/plant alarms display has been overridden by a higher priority display (alarms). T o view Plant Alarms, from the VIEW Mode menu:
1 Using the numeric keypad, press the ‘4’ button to
select the Input Events display .
2 The LCD automatically displays either:
a. The first input event, or
b. The ‘No Warnings message’, if there are no current
input events recorded on the system.
3 If a number of input events are present, press the
‘2/8’ buttons to scroll through the entries:
a. Plant Alarm condition
b. Alarm currently displayed.
c. Number of alarms.
d. Zone Number.
e. Device Address.
f. Device Type.
g. Time alarm was logged.
h. Zonal and Device text
(if any).
Note: Plant alarms for Hold Switch and Abort Switch
inputs are entered as AUX events in the Fault list. These input events are not processed by any CBE rules.
4 Press the ‘4’ button to return to the View Mode
menu.
[U0 View] 1:Log 2:Devices 3:Faults
4:Input Events 5:Disabled : More
PLANT 01 / 10 Z21 M12 AUX 14:55 < - - - Zone Te xt - - - > < - - - Device Text - - - >
The system has NO warnings present
<:Exit
PLANT 01 / 10 Z21 M12 AUX 14:55 < - - - Zone Te xt - - - > < - - - Device Text - - - >
ABCDEFG
H
PLANT 02 / 10 Z17 M05 MON 15:05 < - - - Zone Te xt - - - > < - - - Device Text - - - >
2
8
4
ID50 Series Panel - Operating Manual
Operator Actions at Panel
42997-264-000-8, Issue 8
January 2007
4.12.5 Disabled - User Option
The Disablement User Option allows the user to view all current loop-based input disablements recorded on the system. T o view each disablement in turn, from the VIEW Mode menu:
1 Using the numeric keypad, press the ‘5’ button to
select the Disablements display .
2 The LCD automatically displays either:
a. The zone disablements, or
b. The NO disablements message, if no current
Disablements are present on the system.
3 If more than one disablement is present, press the
‘2/8’ buttons to scroll through the Disablement entries (see examples below):
a. Condition, b. Disablement currently
displayed, c. Active disablements, d. Zone number, e. Device address, f. Device type, g. Zonal and device text
(if any).
4 Press the ‘4’ button to return to the View Mode
menu.
4.12.6 Alarm Count - User Option
The Alarm Count User Option allows the user to view the number of times the panel has entered alarm condition since manufacture. To view the Alarm Count, from the VIEW Mode menu:
1 Using the numeric keypad, press the ‘6’ button to
select the Alarm Count display.
* ID60 panels only
2 The LCD displays the Alarm Count. Press the ‘4’
button to return to the View Mode menu.
[U0 View] 1:Log 2:Devices 3:Faults
4:Input Events 5:Disabled : More
DISABLEMENT 01 / 01 Z01 S02 TMP < - - - Zone Text - - - > < - - - Device Text - - - >
There are no loop devices disabled
<:Exit
ABCDEFG
DISABLEMENT 01 / 09 Z01 S02 TMP < - - - Zone Te xt - - - > < - - - Device Text - - - >
DISABLEMENT 01 / 09 Z01 S03 TMP < - - - Zone Te xt - - - > < - - - Device Text - - - >
Current Alarm Count is 12
<:Exit
5
2
8
6
[U0 View] 6: Maint.* 7: Alarm Count
8: V oltages 9: Ver sion : More
ID50 Series Panel - Operating Manual
Operator Actions at Panel
43 997-264-000-8, Issue 8
January 2007
4.12.7 Voltages - User Option
The Voltages User Option allows the user to view the Voltages of various parts of the system. To view these Volt ages, from the V iew Mode menu:
1 Using the numeric keypad, press the ‘7’ button to
select the Volt ages menu.
* ID60 Panels only .
2 The Battery Volts window is automatically displayed.
Press the ‘2/8’ buttons to display the previous/next system voltage.
Note: The voltage displayed for each system should be
within a given range.
a. Mains supply present: a battery voltage value greater
than 15V means that batteries are connected; battery voltage is low if greater than 15V but less than 18.9V .
No mains supply present: a value of less than 22V means an imminent deep discharge; a value less than 21V indicates deep discharge of the batteries.
b. An Earth Fault is indicated when the displayed value
is less than 175 or greater than 450.
c. A Sounder is open circuit if the displayed value is
below 75, or short circuit if above 250.
d. A mains failure is detected when the AC voltage drops
below 193Vac. This fault will remain until the AC voltage rises above 205V ac.
e. The Charger is faulty if a value less than 24V is
displayed.
3 Press the ‘4’ button to cancel and return to the View
Mode menu.
[U0 VOLTS] BATTERY VOLTS = 27.0
: Select <:Cancel
[U0 ANALOGUE] EARTH = 271
: Select <:Cancel
[U0 ANALOGUE] SOUNDER 1 = 164
: Select <:Cancel
[U0 ANALOGUE] SOUNDER 2 = 164
: Select <:Cancel
[U0 ANALOGUE] SOUNDER 3 = 164
: Select <:Cancel
[U0 ANALOGUE] SOUNDER 4 = 164
: Select <:Cancel
[U0 VOLTS] AC POWER = 237
: Select <:Cancel
[U0 VOLTS] CHARGER = 27.2
: Select <:Cancel
7
2
8
[U0 View] 6: Maint.* 7: Alarm Count
8: V oltages 9: V ersion : More
ID50 Series Panel - Operating Manual
Operator Actions at Panel
44997-264-000-8, Issue 8
January 2007
4.12.8 Version - User Option
The Version User Option allows the user to view the System and Loop part numbers and revision levels used in the system. To view the Versions, from the View Mode menu:
1 Using the numeric keypad, press the ‘8’ button to
select the Versions display.
* ID60 panel only 2 The LCD automatically displays the following. Press
the ‘4’ button to cancel and return to the View Mode menu.
4.13 Commissioning
The Commissioning User Option is available to Level 3 users only (i.e. the Level 3 access code must be entered). The Commissioning menu allows the engineer to configure the system in preparation for handover.
For details concerning commissioning and configuring the system, refer to 997-263, ID50 Series Panel -
Installation, Commissioning & Configuration Manual, Sections 4 and 5.
4.14 Print
The RS232 Protocol option has to be set to ‘Printer’ for this option to become available. If available, the panel’s event log and disablements can be printed using an external printer or displayed on a terminal or saved as a file on a PC connected to the RS232 port.
To print the event log:
1 From the top level menu, press the ‘6’ button to select
the Print option. The following options are displayed:
1
ID60 option only.
2 Press the ‘1’ pushbutton to select the Print Log
option.
Part Number
Revision Level
[U0 VERSION] System : nnn-nnn-nnn n.nn
Loop : nnn-nnn n.nn
8
[U0] 1 : Test 2 : Disable/Enable 3 : Clock
4 : View Mode 5 : Commission 6: Print
[U0 PRINT] 1 : Log 2 : Disablements
3 : Maintenance
1
[U0 PRINT LOG] 1 : All 2 : Fire 3 : Fault
4 : Pre-Alarm 5 : Test 6: Disablement
6
1
[U0 View] 6: Maint.* 7: Alarm Count
8: V oltages 9: Ver sion : More
ID50 Series Panel - Operating Manual
Operator Actions at Panel
45 997-264-000-8, Issue 8
January 2007
3 Select the appropriate print option from the Log menu
using the appropriate numeric key . Y ou are prompted to enter the dates of the event log period you wish to print. Use the numeric keypad to enter the dates, press
the ‘5’ to confirm the date entered. If you make a mistake, edit the date using the ‘4’ button and then press the ‘5’ button.
4 The display now changes to indicate that printing is
taking place as follows:
5 If the event log is being printed to a PC, the data can
be saved as a .csv (comma separated values Excel) file for archiving purposes.
Note: The ID5x/6x Series offline configuration tool has
an option (under the T ools menu) to allow event or device data to be retrieved from the panel and saved on the PC.
6 To print the disablements, press the ‘2’ button at
the Print screen:
7 Select the appropriate option using the numeric
keypad. If disabled device data is available the print screen changes to advise that printing is taking place. For example, if option 2 Zone is selected the following information is displayed:
8 To print the maintenance log (ID60 only), press the
‘3’ button. The display changes to indicate that
printing is in progress, as below:
Note: The Maintenance log can hold up to 100 log
entries. Newer entries replace the oldest in the log.
9 Press the 4’ button to cancel printing and return to
the Print menu.
Where no history exists
for a selected print
option, the option will
not be selectable.
Enter date rang,e (dd/mm/yy)
-- /-- / -- to -- /-- /-- : All <: Cancel
Printing Event Log < : Stop
[U0 PRINT DISABLEMENTS] 1 : Device
2 : Zone 3 : Outputs
2
Printing Maintenance Log
Printing Zone Disablements < : Stop
ID50 Series Panel - Operating Manual
Appendix 1 - Log Book
A1 - 1 997-264-000-8, Issue 8
January 2007
Appendix 1 - Log Book
In accordance with EN54 part 14, it is the user’s responsibility to maintain a log book and to record all events resulting from or affecting the system. The log book should be kept in a place accessible to authorised persons (preferably near the control panel).
One or more identifiable individuals should be appointed to oversee or carry out all entries in the log book. The names of these persons (and any changes of responsible person) should be recorded.
All events should be properly recorded (events include real and false fire alarms, faults, pre-alarm warnings, tests, temporary disconnections and service visits). A brief note of any work carried out or outstanding should be made.
Sample pages of the log book are provided here and can be photocopied to produce a log book that conforms to EN54-14. The sample below is for the reference data (eg the name of the responsible person), while the sample on the next page is for the entry of event data.
REFERENCE DATA
Name and address-----------------------------------------------------------------------------------------------­Responsible person-----------------------------------------------------------------------------------------------
---------------------------------------------------------------------- Date --------------------------------------
---------------------------------------------------------------------- Date --------------------------------------
---------------------------------------------------------------------- Date --------------------------------------
---------------------------------------------------------------------- Date --------------------------------------
---------------------------------------------------------------------- Date --------------------------------------
---------------------------------------------------------------------- Date --------------------------------------
---------------------------------------------------------------------- Date --------------------------------------
---------------------------------------------------------------------- Date --------------------------------------
---------------------------------------------------------------------- Date --------------------------------------
---------------------------------------------------------------------- Date -------------------------------------­This system was installed by ----------------------------------------------------------------------------------­and is maintained under contract by
---------------------------------------------------------------------- until --------------------------------------­Telephone number --------------------------------------------­should be contacted if service is required
ID50 Series Panel - Operating Manual
Appendix 1 - Log Book
A1 - 2997-264-000-8, Issue 8
January 2007
Date Time Event Action Required Date Completed Initials
Event Data
ID50 Series Panel - Operating Manual
Appendix 1 - Log Book
A1 - 3 997-264-000-8, Issue 8
January 2007
Date Time Event Action Required Date Completed Initials
Event Data
ID50 Series Panel - Operating Manual
Appendix 1 - Log Book
A1 - 4997-264-000-8, Issue 8
January 2007
Date Time Event Action Required Date Completed Initials
Event Data
ID50 Series Panel - Operating Manual
Appendix 2 - Maintenance
A2 - 1 997-264-000-8, Issue 8
January 2007
Appendix 2 - Maintenance
Create a log book (see Appendix 1) in accordance with the recommendations of EN54 Part 14. This log book should be used and maintained for recording events as described below.
A2.1 Routine Testing
In order to ensure that the system is fully operational, and to comply with the requirements of EN54 Part 14 and BS 5839 Part 1: 1988, the following routine attention is recommended:
Daily - Check the panel to ascertain that it indicates normal operation. If any fault is indicated check that it has been recorded in the log book and that the appropriate actions have been taken, e.g. informing the maintaining company.
Weekly - Test at least one sensor or call point to confirm the operation of the panel and the audible alarms. Test a different zone each week and, if possible, a different device. Keep a record of the device and zone tested each week. Record and report any malfunction.
Quarterly - The responsible person should ensure that every three months the system is checked by a competent person who shall:
Check the log book entries and any action taken. Check the standby batteries and the charger voltage. Test at least one device in each zone to check the panel
functions. Check the operation of the audible alarm and any link to
a remote manned centre, Central Station, etc. Carry out a visual inspection of the installation to check
for alterations or obstructions and issue a certificate of testing.
Annually - The responsible person should ensure that, in addition to the quarterly checks, each device on the system is tested and that a visual inspection is made of the cable fittings and equipment.
A2.2 Batteries
As a minimum, replace the batteries every four years. The battery units should always be disposed of in
accordance with the battery manufacturer’s recommendations and local regulations.
A2.3 Cleaning
The panel may be cleaned periodically by wiping with a soft, damp lint-free cloth. Do not use any solvents.
ID50 Series Panel - Operating Manual
Appendix 3 - ID60 Differences
A3 - 1 997-264-000-8, Issue 8
January 2007
Appendix 3
ID60 Single Loop Panel Differences
The ID60 Panel differs from the ID50 Panel in that it supports Very Intelligent Early Warning (VIEWTM) and SMART 4 multi-criteria sensors. This appendix describes differences to the user operations required by the ID60 Panel.
VIEWTM Sensor
Each VIEWTM sensor has to be calibrated on first operation with the panel. If a VIEWTM sensor is removed and cleaned, or replaced with a new one, wait at least 30 secs after removal before replacing it.
Calibration is carried out automatically for each sensor approximately 60 secs after the sensor is installed on a panel which is already operating normally .
During this initial period (which is required to allow the VIEWTM sensor to stabilise) the sensor must not be exposed to smoke or any other abnormal conditions, otherwise the panel may report a sensor fault.
SMART 4 Sensor No user procedures are required with this sensor.
However, a new advisory message is logged whenever a SMART 4 device approaches the end of the useful life of the CO sensor element (approximately 6 months before the sensor needs a complete replacement). A new print option is available with the ID60 that allows printing of the maintenance log. It is still possible to print the maintenance log even if it contains no entries. The print out will confirm that the maintenance log is empty .
Following replacement,
VIEWTM sensors remain
inoperable for 60 seconds
while calibrating.
Charles Avenue Burgess Hill W. Sussex RH15 9UF
T: +44 (0) 1444 230 300 F: +44 (0) 1444 230 888 E: sales@notifierfiresystems.co.uk www.notifierfiresystems.co.uk
local distributor
Every care has been taken in the preparation of this document but no liability can be accepted for the use of the information therein. Design features may be changed or amended without prior notice.
Quality Systems Certificate No. 154
Assessed to ISO9001
L
O
S
S
P
R
E
V
E
N
T
I
O
N
C
E
R
T
I
F
I
C
A
T
I
O
N
B
O
A
R
D
007
Loading...