July 18, 2005 DN-6935 • H-202
FSP-851 and FSP-851T
Intelligent Plug-in Photoelectric
Smoke Detectors with FlashScan®
Section: Intelligent/Addressable Devices
GENERAL
NOTIFIER 851 Series intelligent plug-in smoke detectors with integral communication provide features that surpass conventional
detectors. Detector sensitivity can be programmed in the control
panel software. Sensitivity is continuously monitored and reported to the panel. Point ID capability allows each detector’s
address to be set with decade address switches, providing exact detector locations for selective maintenance when chamber contamination reaches an unacceptable level. The FSP-
851 photoelectric detector’s unique optical sensing chamber
is engineered to sense smoke produced by a wide range of
combustion sources. Dual electronic thermistors add 135°F
(57°C) fixed-temperature thermal sensing on the FSP-851T.
FSP-851 and FSP-851T detectors are compatible with all
NOTIFIER intelligent Fire Alarm Control Panels (FACPs).
FlashScan®
tocol developed by NOTIFIER Engineering that greatly enhances the speed of communication between analog intelligent
devices and certain NOTIFIER systems. Intelligent devices communicate in a grouped fashion. If one of the devices within the
group has new information, the panel’s CPU stops the group
poll and concentrates on single points. The net effect is response
speed
(U.S. Patent 5,539,389)
greater than five times
is a communication pro-
that of earlier designs.
S1115
MARYLAND
State Fire Marshal
U.S. Coast Guard
161.002/23/3
161.002/27/3
161.002/42/1
Certif. # 2004081801000017 (FSP-851T)
Certif. # 2004081801000016 (FSP-851)
FEATURES
• Sleek, low-profile design.
• Addressable-analog communication.
• Stable communication technique with noise immunity.
• Low standby current.
• Two-wire SLC connection.
• FlashScan® (NFS-640, NFS-3030) and classic CLIP system (AFP100, AFP-200, AFP-300, AFP-400, NFS-640, AFP1010, AM2020,
and NFS-3030) compatible.
• Rotary, decimal addressing (1 – 99 on current classic systems, 1 – 159 on FlashScan® systems).
• Optional remote, single-gang LED accessory (RA400Z).
• Dual LED design provides 360° viewing angle.
• Visible bicolor LEDs blink green every time the detector is
addressed, and illuminate steady red on alarm.
• Remote test feature from the panel.
• Walk test with address display (an address of 121 will blink
the detector LED: 12-
• Built-in functional test switch activated by external magnet.
• Built-in tamper-resistant feature.
• Sealed against back pressure.
• Constructed of off-white Bayblend®, designed to commercial standards, and offers an attractive appearance.
• 94-5V plastic flammability rating.
• SEMS screws for wiring of the separate base.
• Optional relay, isolator, or sounder bases.
• Listed to UL 268.
• Backward-compatible.
(pause)
-1)
(FlashScan® systems only)
SPECIFICATIONS
Size: 2.1" (5.3 cm) high x 4.1" (10.4 cm) diameter installed in
B501 base, 6.1" (15.5 cm) diameter installed in B710LP base.
Shipping weight: 5.2 oz. (147 g).
This document is not intended to be used for installation purposes. We try to keep our
product information up-to-date and accurate. We cannot cover all specific applications
or anticipate all requirements. All specifications are subject to change without notice.
For more information, contact NOTIFIER. Phone: (203) 484-7161 FAX: (203) 484-7118
6934pho1.jpg
FSP-851 with
B710LP base
6935pho1.jpg
FSP-851T with
B710LP base
Operating temperature:
FSP-851T:
nal for FSP-851T at 45°F +/– 10°F (7.22°C +/– 5.54°C).
UL-Listed velocity range: 0 – 4000 ft./min. (1219.2 m/min.),
.
suitable for installation in ducts.
Relative humidity: 10% – 93% noncondensing.
Thermal ratings: fixed-temperature setpoint 135°F (57°C).
DETECTOR SPACING and APPLICATIONS:
NOTIFIER recommends spacing detectors in compliance with
NFPA 72. In low airflow applications with smooth ceilings, space
detectors 30 feet (9.144 m) for ceiling heights 10 feet (3.048 m)
and higher. For specific information regarding detector spacing,
placement, and special applications, refer to NFPA 72.
Smoke Detector Application Guide,
able at systemsensor.com.
FSP-851 and FSP-851T are Listed for use in ducts, but they
NOT
are
FlashScan® NOTIFIER® and System Sensor® are registered trademarks of Honeywell International INC.
Bayblend® is a registered trademark of Bayer Corporation.
MEA
225-02-E
CS915
(FSP-851A,
FSP-851TA)
California
State Fire
Marshal
7272-0028:206
Permit # 2122
BSMI
CI313066760036
(AFP-200)
(AFP1010/AM2020)
(NFS-640)
CCCF
03/60011
0°C to 38°C (32°F to 100°F). Low-temperature sig-
FSP-851:
Listed for use inside duct smoke detector housings.
0°C to 49°C (32°F to 120°F);
System
document A05-1003, is avail-
12 Clintonville Road, Northford, Connecticut 06472
DN-6935 • 07/18/05 — Page 1 of 2

See
Duct Application Smoke Detectors Guide
1004, available at systemsensor.com, for details on pendantmount applications.
, document A05-
ELECTRICAL SPECIFICATIONS:
Voltage range: 15 - 32 volts DC peak.
Standby current (max. avg.): 250 µA @ 24 VDC (with no com-
munication enabled); 360 µA @ 24 VDC (one communication
every 5 seconds with LED enabled).
LED current (max.): 6.5 mA @ 24 VDC (“ON”).
BASES AVAILABLE:
B710LP: 6.1" (15.5 cm) diameter.
B501: 4.1" (10.4 cm) diameter.
B501BH or B501BHT: Sounder base assembly. Includes B501
base.
B224RB Relay Base:
mm²).
Relay type:
tive; 0.3 A @ 110 VDC inductive; 1.0 A @ 30 VDC inductive.
Dimensions:
B224BI Isolator Base:
(3.048 cm).
6.2" (15.748 cm) x 1.2" (3.048 cm).
Maximum:
Screw terminals:
Form-C.
Rating:
Dimensions:
25 devices between isolator bases.
up to 14 AWG (2.0
2.0 A @ 30 VDC resis-
6.2" (15.748 cm) x 1.2"
INSTALLATION
FSP-851 plug-in detectors use a separate base to simplify installation, service, and maintenance. A special tool allows maintenance personnel to plug in and remove detectors without using a ladder.
Mount base on an electrical backbox which is at least 1.5" (3.81
cm) deep. Suitable mounting base boxes include:
• 4.0" (10.16 cm) square box.
• 3.5" (8.89 cm) or 4.0" (10.16 cm) octagonal box.
• Single-gang box
•
With B501BH or B501BHT base,
square box.
•
With B224RB or B224BI base,
nal box, or a 4.0" (10.16 cm) octagonal or square box.
NOTES: 1) Because of the inherent supervision provided by the
SLC loop, end-of-line resistors are not required. Wiring “T-taps”
or branches are permitted for Style 4 (Class “B”) wiring. 2) When
using relay or sounder bases, consult data sheet DN-2243
(ISO-X) for device limitations between isolator modules and isolator bases.
(except relay or isolator base)
use a 4.0" (10.16 cm)
use a 3.5" (8.89 cm) octago-
.
PRODUCT LINE INFORMATION
NOTE: “A” suffix indicates ULC Listed model.
FSP-851: Low-profile intelligent photoelectric sensor. Must be
mounted to one of the bases listed below.
FSP-851A: Same as FSP-851 but with ULC Listing.
FSP-851T: Same as FSP-851 but includes a built-in 135°F
(57°C) fixed-temperature thermal device.
FSP-851TA: Same as FSP-851T but with ULC Listing.
Bases:
B710LPBP: Standard U.S. low-profile base, pkg. of 10.
B710LPA: Standard U.S. low-profile base, ULC Listing.
B501BP: Standard European flangeless base, pkg. of 10.
B501A: Standard European flangeless base, ULC Listing.
B501BH(A): Sounder base, includes B501(A) base above.
B501BHT(A): Same as B501BH(A), but includes temporal sounder.
B224RB(A): Intelligent relay base.
B224BI(A): Intelligent isolator base. Isolates SLC from loop shorts.
Accessories:
F110: Retrofit replacement flange for BX-501 base. Converts BX501 base for use with FlashScan® detectors.
RA400Z(A): Remote LED annunciator. 3 – 32 VDC. Fits U.S. singlegang electrical box.
Supported by B710LP(A) and B501(A) bases
only.
SMK400: Surface mounting kit provides for entry of surface
wiring conduit.
RMK400: Recessed mounting kit.
For use with B501(A) base only.
For use with B501(A) base
only.
SMB600: Surface mounting kit for use with B710LP(A).
BCK-200B: Black detector covers, box of 10.
M02-04-01: Test magnet.
M02-09-00: Test magnet with telescope stick.
XR2B: Detector removal tool. Allows installation and/or removal
of FlashScan® Series detector heads from base in high ceiling
installations.
T55-127-000: Detector removal tool without pole.
XP-4: Extension pole for XR2B. Comes in three 5-ft. sections.
Detector Guards:
NOTE: Some guards listed below may not be applicable to FSP models.
SDG-773: Smoke detector guard; cover is 7.0" (17.78 cm)
square x 3.0" (7.62 cm) deep.
This guard is mechanically compatible with FSP-751. It is UL-compatibility listed with the FSP851 (file UL S5515).
STI 9601: Low-profile, flush-mount smoke detector guard, wire.*
STI 9602: Low-profile, surface-mount, smoke detector guard,
wire.*
STI 9609: High-profile, flush-mount, smoke detector guard, wire.*
STI 9605: High-profile, surface-mount, smoke detector guard,
wire.*
STI 9604: Flush-mount heat detector guard, wire.*
STI 9610: Surface-mount heat detector guard, wire.*
*For dimensions and additional information on STI Steel Web Stoppers, see data sheet DN-4936.
STI-8200-SS: Flush-mount stainless steel smoke detector guard
(compatibility pending)
STI-8230-SS: Surface-mount stainless steel smoke detector
(compatibility pending)
guard
.
.
WIRING DIAGRAM
6833addr.wmf
address dial on
back of detector
Page 2 of 2 — DN-6935 • 07/18/05
4762wir1.tif