FSC-851(A) IntelliQuad™
Advanced Multi-Criteria Detector
with four unique sensing elements
General
This latest addition to Notifier’s Advanced Detection line
combines four complementary technologies into one device to
convey accurate fire sensing information for locations where
absolute certainty is required.
It is designed for use with Notifier’s ONYX series fire alarm
control panels (FACPs).
Features
• Unique ability to detect all four major elements of a fire
• Highest nuisance alarm immunity
• Advanced algorithms interpret and respond to the multiple
inputs
• Six levels of sensitivity
• CO sensing for fastest response to slow developing, smoldering fires
• Fully integrated infrared sensing to support the fire alarm
decision
• Automatic drift compensation of smoke sensor and CO cell
• Superior EMI protection
• Twin LED indicators providing 360° visibility
• LEDs can be panel controlled to blink, latch on, latch off
• Built-in test switch
This plug-in fire detector combines four separate sensing
elements in one unit:
1. Electrochemical cell technology that monitors carbon
monoxide (CO) produced by smoldering fires
2. Infrared (IR) sensing that measures ambient light levels
and flame signatures
3. Photo-electric smoke detection
4. Thermal detection for temperature monitoring
The integration of continual monitoring for all four major
elements of a fire has enabled Notifier to create a detector that
responds more quickly to an actual fire with the highest
immunity to nuisances. This advanced multi-criteria detector
operates at a high immunity level, changing to become very
sensitive to identify those that should be ignored, reducing
false alarms.
Its on-board intelligence runs advanced algorithms that
dynamically adjust detection parameters to respond to the
inputs from the sensors, enabling instant response as ambient
conditions change.
The program changes sensor thresholds, sensor gain, time,
delays, combinations, sampling rates, and averaging rates. If
any sensor fails, the detector automatically adjusts the
sensitivity of the remaining sensors. It also recognizes a fault
condition.
The CO cell has an expected lifetime of approximately six
years. It is not a field replaceable component. An internal
timer signals the control panel to indicate the approach of the
CO cell’s end of life. Upon expiration, you should contact the
system supplier to arrange for replacement of the unit.
Detection is not compromised when the CO cell expires. The
algorithms automatically adjust to properly weight the inputs
from the photo-electric, heat, and IR sensors.
DN-60412:B
Intelligent / Addressable Devices
NOTE: The CO cell is specifically deployed as a component of
smoke detection in this device. This device is not listed for applications in which standalone CO detection is required for life safety.
The IR light sensor recognizes specific situations such as
welding and makes adjustments rapidly to further reduce the
potential for nuisance alarms. The thermal detection function
uses thermistor technology with a software-corrected linear
temperature response to offer exceptional nuisance alarm
immunity and excellent fire detection.
Product Line Information
FSC-851: IntelliQuad Advanced Multi-Criteria Detector
FSC-851A: ULC-listed version
Accessories
B710LP: Flanged mounting base. 6.1” (15.5 cm) diameter.
B710LPA: Flanged mounting base, ULC Listed.
B710LPBP: Flanged mounting base. (Pack of 10)
B200S: Intelligent sounder base, capable of producing a
variety of tone patterns including ANSI Temporal 3.
Compatible with System Sensor sychronization protocol.
B200SA: Intelligent sounder base, capable of producing a
variety of tone patterns including ANSI Temporal 3.
Compatible with System Sensor sychronization protocol, ULClisted.
B200SR: Intelligent sounder base, Temporal 3 or Continuous
tone.
B200SRA: Intelligent sounder base, Temporal 3 or Continuous
tone, ULC-listed.
B224RB: Relay base Screw terminals: up to 14 AWG (2.0
mm²). Relay type: Form-C. Rating: 2.0 A @ 30 VDC resistive;
0.3 A @ 110 VDC inductive; 1.0 A @ 30 VDC inductive.
Dimensions: 6.2" (15.748 cm) x 1.2" (3.048 cm)..
B224RBA: Relay base, ULC Listed.
DN-60412:B • 08/25/2010 — Page 1 of 2
B224BI: Isolator base. Dimensions: 6.2" (15.748 cm) x 1.2"
4.0"
(10.16 cm)
2.4"
(6.096 cm)
60412dia.wmf
(3.048 cm). Maximum: 25 devices between isolator bases.
B224BIA: Isolator base, ULC Listed.
Listings and Approvals
• UL Listed: S911
• ULC Listed: S1115 (FSC-851A)
• FM Approved
• CSFM: 7272-0028:0255
Specifications
GENERAL SPECIFICATIONS
Size: Height: 2.4" (6.1 cm), Diameter: 4.0" (10.16 cm)
Shipping Weight: 4.6 ounces
Color: Ivory
Operating Humidity Range: 10 to 93% relative humidity
(non-condensing)
Application Temperature Range: 32°F to 100°F (0°C to
38°C)
ELECTRICAL SPECIFICATIONS
Operating Voltage Range: 15 to 32VDC
Maximum Standby Current: 200μA at 24VDC (no
communications)
Maximum Alarm Current (LED on): 7mA at 24VDC
SENSITIVITY SETTINGS & SUGGESTED APPLICATION
Level 1: 1% per foot (30.48 cm) of smoke. Very clean
environments - Laboratories.
Level 2: 2% per foot (30.48 cm) of smoke. Clean
environments - Offices.
Level 3: 3% per foot (30.48 cm) of smoke. Moderately clean
environments - Hotel Room, Dorm Room.
Level 4: 3% per foot (30.48 cm) of smoke with different
algorithm processing and weighting of sensor elements. Hotel
rooms near a shower, Boiler Rooms.
Level 5: 4% per foot (30.48 cm) of smoke. Equipment rooms,
Kitchens, Paint Shops.
Level 6: Thermal alarm at 135°F (57°C).
NOTE: Once the CO cell has reached the end of life, any device
set to Level 3 or Level 4 will default to Level 5 and Level 5 will drop
to 3%. The following sensitivities apply to devices with expired CO
cells:
Level 1: 1% per foot (30.48 cm) of smoke. Very clean
environments - Laboratories.
Level 2: 2% per foot (30.48 cm) of smoke. Clean
environments - Offices.
Level 5: 3% per foot (30.48 cm) of smoke. Moderately clean
environments - Hotel Room, Dorm Room.
Level 6: Thermal alarm at 135°F (57°C).
FSC-851 IntelliQuad
Advanced Multi-Criteria Detector
Notifier®, System Sensor®, and FlashScan® are registered trademarks
and IntelliQuad™ is a trademark of Honeywell International Inc.
©2010 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
Page 2 of 2 — DN-60412:B • 08/25/2010
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.