Notifier FRM User Manual

FCM-1(A) & FRM-1(A)
FCM-1(A)
7000cov.JPG
Series
Control and Relay Modules
General
FCM-1(A) Control Module: The FCM-1(A) Addressable Con­trol Module provides Notifier intelligent fire alarm control pan­els a circuit for Notification Appliances (horns, strobes, speakers, etc.). Addressability allows the FCM-1(A) to be acti­vated, either manually or through panel programming, on a select (zone or area of coverage) basis.
FRM-1(A) Relay Module: The FRM-1(A) Addressable Relay Module provides the system with a dry-contact output for acti­vating a variety of auxiliary devices, such as fans, dampers, control equipment, etc. Addressability allows the dry contact to be activated, either manually or through panel programming, on a select basis.
FlashScan® (U.S. Patent 5,539,389) is a communication pro­tocol developed by NOTIFIER Engineering that greatly enhances the speed of communication between analog intelli­gent devices. Intelligent devices communicate in a grouped fashion. If one of the devices within the group has new infor­mation, the panel CPU stops the group poll and concentrates on single points. The net effect is response speed greater than five times that of other designs.
DN-6724:B3
Intelligent / Addressable Devices
Features
• Built-in type identification automatically identifies these devices to the control panel.
• Internal circuitry and relay powered directly by two-wire SLC loop. The FCM-1(A) module requires power (for horns, strobes, etc.), or audio (for speakers).
• Integral LED “blinks” green each time a communication is received from the control panel and turns on in steady red when activated.
• LED blink may be deselected globally (affects all devices).
• High noise immunity (EMF/RFI).
• The FCM-1(A) may be used to switch 24-volt NAC power, audio (up to 70.7 Vrms).
• Wide viewing angle of LED.
• SEMS screws with clamping plates for wiring ease.
• Direct-dial entry of address 01– 159 for FlashScan loops, 01 – 99 for CLIP mode loops.
• Speaker, and audible/visual applications may be wired for Class B or A (Style Y or Z).
Applications
The FCM-1(A) is used to switch 24 VDC audible/visual power, high-level audio (speakers). The FRM-1(A) may be pro­grammed to operate dry contacts for applications such as door holders or Air Handling Unit shutdown, and to reset four-wire smoke detector power.
NOTE:
Refer to the SLC Manual (PN 51253) for details regarding releasing applications with the FCM-1(A). Refer to the FCM-1-REL datasheet (DN-60390) for new FlashScan® releasing applications.
Construction
• The face plate is made of off-white heat-resistant plastic.
• Controls include two rotary switches for direct-dial entry of
address (01-159).
• The FCM-1(A) is configured for a single Class B (Style Y) or Class A (Style Z) Notification Appliance Circuit.
• The FRM-1(A) provides two Form-C dry contacts that switch together.
Operation
Each FCM-1(A) or FRM-1(A) uses one of 159 possible module addresses on a SLC loop (99 on CLIP loops). It responds to regular polls from the control panel and reports its type and status, including the open/normal/short status of its Notifica­tion Appliance Circuit (NAC). The LED blinks with each poll received. On command, it activates its internal relay. The FCM-1(A) supervises Class B (Style Y) or Class A (Style Z) notification or control circuits.
Upon code command from the panel, the FCM-1(A) will dis­connect the supervision and connect the external power sup­ply in the proper polarity across the load device. The disconnection of the supervision provides a positive indication to the panel that the control relay actually turned ON. The external power supply is always relay isolated from the com­munication loop so that a trouble condition on the external power supply will never interfere with the rest of the system.
Rotary switches set a unique address for each module. The address may be set before or after mounting. The built-in TYPE CODE (not settable) will identify the module to the con­trol panel, so as to differentiate between a module and a sen­sor address.
Specifications for FCM-1(A)
Normal operating voltage: 15 to 32 VDC.
Maximum current draw: 6.5 mA (LED on).
Average operating current: 350 μA direct poll, 375 μA group
poll with LED flashing, 485 μA Max. (LED flashing, NAC shorted.)
DN-6724:B3 • 2/17/2011 — Page 1 of 2
Made in the U.S. A.
Maximum NAC Line Loss: 4 VDC.
External supply voltage (between Terminals T10 and T11): Maximum (NAC): Regulated 24 VDC; Maximum
(Speakers): 70.7 V RMS, 50W.
Drain on external supply: 1.7 mA maximum using 24 VDC supply; 2.2 mA Maximum using 80 VRMS supply.
Max NAC Current Ratings: For class B wiring system, the current rating is 3A; For class A wiring system, the current rat­ing is 2A.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% non-condensing.
Dimensions: 4.5" (114.3 mm) high x 4" (101.6 mm) wide x
1.25" (31.75 mm) deep. Mounts to a 4" (101.6 mm) square x
2.125" (53.975 mm) deep box.
Accessories: SMB500 Electrical Box; CB500 Barrier
Specifications for FRM-1(A)
Normal operating voltage: 15 to 32 VDC.
Maximum current draw: 6.5 mA (LED on).
Average operating current: 230 μA direct poll; 255 μA group
poll.
EOL resistance: not used.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% non-condensing.
Dimensions: 4.5" (114.3 mm) high x 4" (101.6 mm) wide x
1.25" (31.75 mm) deep. Mounts to a 4" (101.6 mm) square x
2.125" (53.975 mm) deep box.
Accessories: SMB500 Electrical Box; CB500 Barrier
Agency Listings and Approvals
In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult fac­tory for latest listing status.
UL: S635
ULC: S3705 (A version only)
• FM Approved
CSFM: 7300-0028:0219
MEA: 14-00-E
FDNY: COA #6067, #6065
Contact Ratings for FRM-1(A)
Current
Rating
3 A 30 VDC Resistive Non-Coded
2 A 30 VDC Resistive Coded
.9 A 110 VDC Resistive Non-Coded
.9 A 125 VDC Resistive Non-Coded
.5 A 30 VDC
1 A 30 VDC
.3 A 125 VAC
1.5 A 25 VAC
.7 A 70.7 VAC
2 A 25 VAC
NOTE: Maximum (Speakers): 70.7 V RMS, 50 W
Maximum
Voltage
Load
Description
Inductive (L/R=5ms)
Inductive (L/R=2ms)
Inductive (PF=0.35)
Inductive (PF=0.35) Non-Coded
Inductive (PF=0.35) Non-Coded
Inductive (PF=0.35) Non-Coded
Application
Coded
Coded
Non-Coded
Product Line Information
NOTE: “A” suffix indicates ULC Listed model.
FCM-1(A): Intelligent Addressable Control Module.
FRM-1(A): Intelligent Addressable Relay Module.
A2143-20: Capacitor, required for Class A (Style Z) operation
of speakers.
SMB500: Optional Surface-Mount Backbox.
CB500: Control Module Barrier — required by UL for separat-
ing power-limited and non-power limited wiring in the same junction box as FCM-1(A).
NOTE: For installation instructions, see the following documents:
FCM-1(A) Installation document I56-1169.
FRM-1(A) Installation document I56-3502.
Notifier SLC Wiring Manual, document 51253.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
Page 2 of 2 — DN-6724:B3 • 2/17/2011
Notifier® and FlashScan® are registered trademarks of Honeywell International Inc. ©2011 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
www.notifier.com
Loading...