Notifier FDU-80 User Manual

FDU-80
80 Character Liquid Crystal Display
General
The FDU-80 is a compact, cost-effective, 80-character, backlit LCD remote Fire Annunciator for use with the NOTIFIER Fire­Warden-100-2, NFS2-640, and NFS-320 Fire Alarm Control Panels (FACPs). The FDU-80 mimics the display of the control panel and displays complete system point status information.
Up to 32 FDU-80s may be connected onto the EIA-485 termi­nal port of each FACP. The FDU-80 requires no programming, which saves time during system commissioning.
Features
• 80-character Liquid Crystal Display.
• Mimics all display information from the host panel.
• Control switches for System Acknowledge, Signal Silence, Drill and Reset with enable key.
• System status LEDs for Power, Alarm, Trouble, Supervisory and Alarm Silenced.
• No programming necessary — FDU-80 connects to the ter­minal porton the FACP.
• Displays device type identifiers, individual point alarm, trou­ble or supervisory, zone and custom alpha labels.
• Time-and-date display field.
• Aesthetically pleasing design.
• May be powered from the host FACP or by remote power supply (requires 24 VDC).
• Up to 32 FDU-80 annunciators per FACP.
• Plug-in terminal blocks for ease of installation and service.
• Can be remotely located up to 6,000 feet (1828.8 m) from the FACP.
• Local piezo sounder with alarm and trouble resound.
• Semi-flush mounts to 2.188" (5.556 cm) minimum deep, three-gang electrical box (NOTIFIER PN 10103) or three­gangable electrical switchbox.
• Surface-mounts to NOTIFIER PN SBB-3 surface backbox.
Operation
The FDU-80 annunciator provides the FACP with point annun­ciation with full display text on an 80-character LCD display. The FDU-80 also provides an array of LEDs to indicate system status, and includes control switches for remote control of criti­cal system functions.
The FDU-80 provides the FACP with up to 32 remote serially connected annunciators. All field-wiring terminations on the FDU-80 use removable, compression-type terminal blocks for ease of wiring and circuit testing.
Communication between the FACP and the annunciators is accomplished over an EIA-485 serial interface, which greatly reduces wire and installation cost over traditional systems.
DN-6820:B • D-123
Annunciators
6820fdu8.jpg
Ordering Information
FDU-80: 80 character, backlit, LCD Fire Annunciator with con­trol switches for remote control of system functions, and key­switch lock.
FDU-80C: ULC-listed version; see DN-60573 for details.
10103: Three-gang electrical box, minimum 2.188" (5.556 cm)
deep, for semi-flush mount applications.
SBB-3: Three-gang surface backbox for surface-mount appli­cations.
Agency Listings And Approvals
These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status.
UL Listed: S635
MEA Listed: 245-00-E
• FDNY: COA#6038
• CSFM: 7120-0028:209
• FM Approved
NOTE: For ULC-listed version, see DN-60573.
Installation
The FDU-80 can be semi-flush mounted to a 2.188" (5.556 cm) minimum deep, three-gang electrical box or three-gang­able electrical switchboxes. Alternately, an SBB-3 surface backbox is available for surface-mount applications.
DN-6820:B • 05/17/2010 — Page 1 of 2
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
Page 2 of 2 — DN-6820:B • 05/17/2010
NOTIFIER® is a registered trademark of Honeywell International Inc. ©2010 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
www.notifier.com
Made in the U.S. A.
Loading...