INSTALLATION AND MAINTENANCE INSTRUCTIONS
9
8
7
6
5
4
3
2
1
0
TENS
ONES
ADDRESS
LOOP
0
7
8
6
5 
4 
3
2
1
9
10
11
12
13
14
15
0
2
4
6
8
0
1
2
3
4
9
8
7
6
5
0
T
E
N
S
O
N
E
S
AD
D
R
E
S
S
LO
O
P
8
6
4
2
0
9
8
7
6
5
4
3 
2 
1
10
11
12
13
14
15
FDM-1 Dual Monitor Module
Specications
Normal Operating Voltage:          15 to 32 VDC 
Maximum Current Draw:           5.7 mA (LED on) 
Average Operating Current:          750µA (LED ashing) 
EOL Resistance:                  47K Ohms 
Maximum IDC wiring resistance:      1,500 Ohms 
Temperature Range:               32˚F to 120˚F (0˚C to 49˚C) 
Humidity:                      10% to 93% Noncondensing 
Dimensions:                     4 
Accessories:                     SMB500 Electrical Box
Before Installing
This information is included as a quick reference installation 
guide. Refer to the control panel installation manual for detailed 
system information. If the modules will be installed in an existing 
operational system, inform the operator and local authority that 
the system will be temporarily out of service. Disconnect power to 
the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this 
equipment.
General Description
The Dual Monitor Module is intended for use in intelligent, two 
wire systems. It provides two independent 2-wire initiating device 
circuits (IDC), at two separate, consecutive addresses. It is capable 
of monitoring normally open contact re alarm and supervisory 
devices, or either normally open or normally closed security devices. The module has a single panel controlled red LED.
Compatibility Requirements
To ensure proper operation, this module shall be connected to a 
compatible Notier system control panel (list available from Noti-
er).
Mounting
Mounts directly to 4” square electrical boxes (see Figure 2A). The 
box must have a minimum depth of 2
trical boxes (SMB500) are available from Notier.
Wiring
NOTE:  All wiring must conform to applicable local codes, or-
dinances, and regulations. This module is intended for 
power limited wiring only.
1. Install module wiring in accordance with the job drawings and 
appropriate wiring diagrams.
2. Set the address on the module per job drawings.
     Note: Some panels support extended addressing. In order 
   to set the module above address 99 on compatible systems, 
   carefully remove the stop on the upper rotary switch with  
   thumb in the direction shown in Figure 1.
   Note: Monitor module L (using terminals 6 and 7) re-
sponds at the address set on the code switches. Monitor 
module H (using terminals 8 and 9) will automatically respond at the next higher address. For example, if the code 
switches are set to 76, module L will respond at address 76 
and module H will respond at address 77. Use caution to 
N500-75-00                                               1                                               I56-1463-02
Technical Manuals Online! - http://www.tech-man.com
1
/2″ H x 4″ W x 11/4″ D (Mounts to a 4″ square by 21/8″ deep box.)
1
/8”. Surface mounted elec-
12 Clintonville Rd
 Northford, CT 06472-1653
(203) 484-7161
avoid duplicate addressing of modules on the system.
3.  Secure module to electrical box (supplied by installer), as 
shown in Figure 2A.
Figure 1. Removing 
Rotary Switch Stop:
A78-2318-13
Figure 2A. Module mounting:
Figure 2B: 
A78-2611-19
A78-2610-14
 

0
7
8
6
5 
4 
3
2
1
9
10
11 
12 
13
14
15
FROM PANEL OR
(+)
(—)
TO NEXT
(+)
(—)
DEVICE
(+)
(—)
MONITOR
CONNECT MODULES TO LISTED COMPATIBLE
32 VDC MAX.
SHIELDED-TWISTED PAIR
IS RECOMMENDED
NOTIFIER CONTROL PANELS ONLY
PREVIOUS DEVICE
COMMUNICATION LINE
MONITOR A (TERMINALS 6 & 7) RESPONDS AT ADDRESS 
SET ON CODE SWITCHES. MONITOR B (TERMINALS 8 & 9) 
RESPONDS AT NEXT HIGHER ADDRESS.
ANY NUMBER OF UL LISTED CONTACT CLOSURE
DEVICES MAY BE USED. DO NOT MIX FIRE
ALARM INITIATING, SUPERVISORY, OR SECURITY
 DEVICES ON THE SAME INITIATING DEVICE CIRCUIT.
INSTALL CONTACT CLOSURE DEVICES PER
MANUFACTURER’S INSTALLATION INSTRUCTIONS.
47 K EOL 
RESISTOR 
ELR-47K
MODULE
47 K EOL 
RESISTOR 
ELR-47K
H
L
9
8
7
6
5
4
3
2
1
0
TENS
ONES
ADDRESS
LOOP
0
2
4
6
8
TWO INITIATING DEVICE CIRCUITS (L & H),
EACH POWER LIMITED TO 230 A @ 12VDC MAX.
ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED
Figure 3. Typical 2-wire initiating circuit conguration, NFPA Style B:
A78-2280-39
N500-75-00                                               2                                               I56-1463-02 
                                                                                                     ©2001 Notier 