
9
8
7
6
5
4
3
2
1
0
ADDRESS
0
TENS
ONES
7
8
6
5
4
3
2
1
9
10
11
12
13
14
15
0
2
4
6
8
INSTALLATION AND MAINTENANCE INSTRUCTIONS
9
8
7
6
5
4
3
2
1
0
TENS
ONES
ADDRESS
LOOP
0
7
8
6
5
4
3
2
1
9
10
11
12
13
14
15
0
2
4
6
8
0
1
2
3
4
9
8
7
6
5
0
T
E
N
S
O
N
E
S
AD
D
R
E
S
S
LO
O
P
8
6
4
2
0
9
8
7
6
5
4
3
2
1
10
11
12
13
14
15
FDM-1 Dual Monitor Module
Specications
Normal Operating Voltage: 15 to 32 VDC
Maximum Current Draw: 5.7 mA (LED on)
Average Operating Current: 750µA (LED ashing)
EOL Resistance: 47K Ohms
Maximum IDC wiring resistance: 1,500 Ohms
Temperature Range: 32˚F to 120˚F (0˚C to 49˚C)
Humidity: 10% to 93% Noncondensing
Dimensions: 4
Accessories: SMB500 Electrical Box
Before Installing
This information is included as a quick reference installation
guide. Refer to the control panel installation manual for detailed
system information. If the modules will be installed in an existing
operational system, inform the operator and local authority that
the system will be temporarily out of service. Disconnect power to
the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this
equipment.
General Description
The Dual Monitor Module is intended for use in intelligent, two
wire systems. It provides two independent 2-wire initiating device
circuits (IDC), at two separate, consecutive addresses. It is capable
of monitoring normally open contact re alarm and supervisory
devices, or either normally open or normally closed security devices. The module has a single panel controlled red LED.
Compatibility Requirements
To ensure proper operation, this module shall be connected to a
compatible Notier system control panel (list available from Noti-
er).
Mounting
Mounts directly to 4” square electrical boxes (see Figure 2A). The
box must have a minimum depth of 2
trical boxes (SMB500) are available from Notier.
Wiring
NOTE: All wiring must conform to applicable local codes, or-
dinances, and regulations. This module is intended for
power limited wiring only.
1. Install module wiring in accordance with the job drawings and
appropriate wiring diagrams.
2. Set the address on the module per job drawings.
Note: Some panels support extended addressing. In order
to set the module above address 99 on compatible systems,
carefully remove the stop on the upper rotary switch with
thumb in the direction shown in Figure 1.
Note: Monitor module L (using terminals 6 and 7) re-
sponds at the address set on the code switches. Monitor
module H (using terminals 8 and 9) will automatically respond at the next higher address. For example, if the code
switches are set to 76, module L will respond at address 76
and module H will respond at address 77. Use caution to
N500-75-00 1 I56-1463-02
Technical Manuals Online! - http://www.tech-man.com
1
/2″ H x 4″ W x 11/4″ D (Mounts to a 4″ square by 21/8″ deep box.)
1
/8”. Surface mounted elec-
12 Clintonville Rd
Northford, CT 06472-1653
(203) 484-7161
avoid duplicate addressing of modules on the system.
3. Secure module to electrical box (supplied by installer), as
shown in Figure 2A.
Figure 1. Removing
Rotary Switch Stop:
A78-2318-13
Figure 2A. Module mounting:
Figure 2B:
A78-2611-19
A78-2610-14

0
7
8
6
5
4
3
2
1
9
10
11
12
13
14
15
FROM PANEL OR
(+)
(—)
TO NEXT
(+)
(—)
DEVICE
(+)
(—)
MONITOR
CONNECT MODULES TO LISTED COMPATIBLE
32 VDC MAX.
SHIELDED-TWISTED PAIR
IS RECOMMENDED
NOTIFIER CONTROL PANELS ONLY
PREVIOUS DEVICE
COMMUNICATION LINE
MONITOR A (TERMINALS 6 & 7) RESPONDS AT ADDRESS
SET ON CODE SWITCHES. MONITOR B (TERMINALS 8 & 9)
RESPONDS AT NEXT HIGHER ADDRESS.
ANY NUMBER OF UL LISTED CONTACT CLOSURE
DEVICES MAY BE USED. DO NOT MIX FIRE
ALARM INITIATING, SUPERVISORY, OR SECURITY
DEVICES ON THE SAME INITIATING DEVICE CIRCUIT.
INSTALL CONTACT CLOSURE DEVICES PER
MANUFACTURER’S INSTALLATION INSTRUCTIONS.
47 K EOL
RESISTOR
ELR-47K
MODULE
47 K EOL
RESISTOR
ELR-47K
H
L
9
8
7
6
5
4
3
2
1
0
TENS
ONES
ADDRESS
LOOP
0
2
4
6
8
TWO INITIATING DEVICE CIRCUITS (L & H),
EACH POWER LIMITED TO 230 A @ 12VDC MAX.
ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED
Figure 3. Typical 2-wire initiating circuit conguration, NFPA Style B:
A78-2280-39
N500-75-00 2 I56-1463-02
©2001 Notier
Technical Manuals Online! - http://www.tech-man.com