Notifier FCPS-24S8 User Manual

FCPS-24S6(C/E) & FCPS­24S8(C/E)
6- & 8-Amp 24-Volt Remote Power Supplies
General
NOTE: Unless otherwise specified, the terms FCPS-24S6 and FCPS-24S8 used in this document refers to the standard FCPS­24S6 and FCPS-24S8, FCPS-24S6C and FCPS-24S8C, the FCPS-24S6E and FCPS-24S8E
Features
• UL-Listed NAC synchronization using System Sensor, Wheelock, or Gentex “Commander
• Operates as a “sync-follower” or as a “sync-generator” (default). See note on page 2.
• Contains two fully-isolated input/control circuits - triggered from FACP NAC (NAC expander mode) or jumped perma­nently “ON” (stand-alone mode).
• Four Class B (Style Y) or four Class A (Style Z, with ZNAC-4 module) NACs.
• 6-amp (FCPS-24S6) or 8-amp (FCPS-24S8) full load out­put, with 3 amps maximum/circuit, in NAC expander mode (UL 864).
• 4-amp (FCPS-24S6) or 6-amp (FCPS-24S8) continuous output in stand-alone mode (UL 1481).
• Compatible with coded inputs; signals passed through.
• Optional power-supervision relay (EOLR-1).
• In stand-alone mode, output power circuits may be config­ured as: resettable, (reset line from FACP required), non-resettable, or a mix of two and two.
• Fully regulated and filtered power output - optimal for pow­ering four-wire smoke detectors, annunciators, and other system peripherals requiring regulated/filtered power.
• Power-limiting technology meets UL power-limiting require­ments.
• Form-C normally-closed trouble relay.
• Fully supervised power supply, battery, and NACs.
• Selectable earth fault detection.
• AC trouble report selectable for immediate 2-hour delay.
• Works with virtually any UL 864 fire alarm control which uti­lizes an industry-standard reverse-polarity notification cir­cuit (including unfiltered and unregulated bell power).
• Requires input trigger voltage of 9 - 32 VDC.
• Self-contained in compact, locking cabinet - 15”H x 14.5”W x 2.75”D (cm: 38.1H x 36.83W x 6.985D).
2
” appliances.
dn-6927:a
Power Supplies
6927pho1.jpg
• Includes integral battery charger capable of charging up to 18 AH batteries. Cabinet capable of housing 7.0 AH batter­ies.
• Battery charger may be disabled via DIP switch for applica­tions requiring larger batteries.
• Fixed, clamp-type terminal blocks accommodate up to 12 AWG (3 .1m m
2
) wire.
Specifications
Primary (AC) Power:
• FCPS-24S6C/-24S8C: 120 VAC, 60 Hz, 3.2A maximum.
• FCPS-24S6E/-24S8E: 240 VAC, 50 Hz, 1.6A maximum.
• Wire Size: minimum #14 AWG (2.0mm tion.
Control Input Circuit:
Trigger Input Voltage: 9 to 32 VDC.
Trigger Current: 2.0 mA (16 - 32 V); Per Input: 1.0 mA (9
- 16 V).
Trouble Contact Rating: 5 A at 24 VDC.
Auxiliary Power Output: Specific application power 500 mA
maximum.
Output Circuits:
• +24 VDC filtered, regulated.
• 3.0 A maximum for any one circuit.
• Total continuous current for all outputs (stand-alone mode):
FCPS-24S6: 4.0 A maximum.FCPS-24S8: 6.0 A maximum.
• Total short-term current for all outputs (NAC expander mode):
FCPS-24S6: 6.0 A maximum.FCPS-24S8: 8.0 A maximum.
Secondary Power (Battery) Charging Circuit:
• Supports lead-acid batteries only.
• Float-charge voltage: 27.6 VDC.
2
) with 600 V insula-
dn-6927:a • 04/30/09 — Page 1 of 2
• Maximum current charge: 1.5 A.
• Maximum battery capacity: 18 AH.
Applications
Example 1: Expand notification appliance power an additional
6.0 A (FCPS-24S6) or 8.0 A (FCPS-24S8). Use up to four Class B (Style Y) outputs or four Class A (Style Z) outputs (using ZNAC-4). For example, the FACP notification appliance circuits will activate the FCPS when reverse-polarity activation occurs. Trouble conditions on the FCPS are sensed by the FACP through the notification appliance circuit.
Example 2: Use the FCPS to expand auxiliary regulated 24­volt system power up to 4.0 A (FCPS-24S6) or up to 6.0 A (FCPS-24S8). Both resettable and non-resettable power options are available. Resettable outputs are created by con­necting the resettable output from the FACP to one or both of the FCPS inputs.
Example 3: Use addressable control modules to activate the FCPS instead of activating it through the FACP notification appliance circuits. This typically allows for mounting the FCPS at greater distances* away from the FACP while expanding system architecture in various applications.
For example, an addressable control module is used to acti­vate the FCPS, and an addressable monitor module is used to sense FCPS trouble conditions. Local auxiliary power output from the FCPS provides power to the addressable control module.
*NOTE: Addressable FACPs are capable of locating control and monitor modules at distances of up to 12,500 feet (3,810 meters).
Sync Follower/Generator Note
In some installations, it is necessary to synchronize the flash timing of all strobes in the system for ADA compliance. Strobes accomplish this by monitoring very short timing pulses on the NAC power which are created by the FACP. When installed at the end of a NAC wire run, the FCPS-24S6/-24S8 can track (i.e. “follow”) the strobe synchronization timing pulses on the existing NAC wire run. This maintains the overall system flash timing of the additional strobes attaches to the FCPS.
When the FCPS-24S6/-24S8 is configured (via DIP switch set­tings) as a “sync follower,” the FCPS’s NAC outputs track the strobe synchronization pulses present at the FCPS’s sync input terminal. The pulses originate from an upstream FACP or other power supply.
When the FCPS-24S6/-24S8 are configured (via DIP switch settings) as a “sync generator,” the FCPS’s sync input termi­nals are not used. Rather, the FCPS is the originator of the strobe synchronization pulses on the FCPS’s NAC outputs. In “sync generator” mode, the sync type (System Sensor, Whee­lock, or Gentex) is selectable via DIP switch settings.
Standards and Codes
The FCPS-24S6 and FCPS-24S8 comply with the following standards:
NFPA 72 National Fire Alarm Code.
UL 864 Standard for Control Units for Fire Alarm Systems (NAC expander mode).
UL 1481 Power Supplies for Fire Alarm Systems.
Agency Listings and Approvals
These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status.
UL Listed: S635, S674
ULC Listed: S635 (FCPS-24S6C & FCPS-24S8C)
CSFM Approved: 7315-0028:225
MEA: 299-02-E
• FM Approved
Ordering Information
FCPS-24S6: 6.0 A, 120 VAC remote charger power supply. Includes main printed circuit board, transformers, enclosure (15”H x 14.5”W x 2.75”D [cm: 38.1H x 36.83W x 6.985D]), and installation instructions.
FCPS-24S6C: Same as above, ULC-listed.
FCPS-24S6R: Same as FCPS-24S6 with red enclosure.
FCPS-24S6E: 6.0 A, 240 VAC remote charger power supply.
Includes main printed circuit board, transformers, enclosure (15”H x 14.5”W x 2.75”D [cm: 38.1H x 36.83W x 6.985D]), and installation instructions.
FCPS-24S8: 8.0 A, 120 VAC remote charger power supply. Includes main printed circuit board, transformers, enclosure (15”H x 14.5”W x 2.75”D [cm: 38.1H x 36.83W x 6.985D]), and installation instructions.
FCPS-24S8C Same as above, ULC-listed.
FCPS-24S8R: Same as FCPS-24S8 with red enclosure.
FCPS-24S8E: 8.0 A, 240 VAC remote charger power supply.
Includes main printed circuit board, transformers, enclosure (15”H x 14.5”W x 2.75”D [cm: 38.1H x 36.83W x 6.985D]), and installation instructions.
ZNAC-4: Class A (Style Y) NAC option module.
EOLR-1: 12/24 VDC end-of-line relay for monitoring four-wire
smoke detector power.
BAT-1270: Battery, 12-volt, 7.0 AH (two required, see BAT Series data sheet DN-6933).
PS-1270: Battery, 12-volt, 7.0 AH (two required, see PS Series data sheet DN-1109)
Page 2 of 2 — dn-6927:a • 04/30/09
System Sensor® and NOTIFIER® are registered trademarks of Honeywell International Inc. ©2009 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
This document is not intended to be used for installation purposes.