Notifier FCO-851 User Manual

FCO-851(A) IntelliQuad™ PLUS
60689cov.JPG
FCO-851(A) in B200S(COA) Sounder Base
Advanced Multi-Criteria Fire/CO Detector
General
World-class fire and carbon monoxide (CO) detection com­bined in a single addressable device provides a practical solu­tion for today’s market.
The IntelliQuad PLUS FCO-851(A) Advanced Multi-Criteria Fire/CO Detector is a plug-in, addressable device that pro­vides both fire and carbon monoxide (CO) detection. For fire, the detector combines four separate sensing elements in one unit (smoke, CO, light/flame, and heat) to sense multiple com­ponents of a fire. This approach enables enhanced sensitivity to real fire with heightened immunity to nuisance particulate. For CO, the detector’s electrochemical sensing cell creates a separate signal for life safety CO detection.
CO is a colorless, odorless, and deadly gas that is virtually impossible to detect with the human senses. It is released whenever carbon-based fuels (from fossil fuels to firewood) burn without enough oxygen to form CO tial exists for dangerous levels of CO to accumulate in almost any building, legislation mandating the use of CO detection in commercial spaces continues to increase across the U.S. and Canada. The FCO-851(A) is listed to the UL 268 standard for smoke detectors and the UL 2075 standard for system-con­nected life safety carbon monoxide monitoring.
The FCO-851(A) should be used in conjunction with the B200S(COA) intelligent sounder base, which can generate either a Temp 3 pattern for fire or a Temp 4 pattern for CO alarm indication.
The B200S(COA) recognizes the System Sensor synchroniza­tion protocol. This enables it to be used as a component of the general evacuation signal — along with other System Sensor horns, horn strobes, and chimes — when connected to a power supply or Fire Alarm Control Panel (FACP) output capa­ble of generating the System Sensor synchronization pulses. With each sounder base carrying a unique address, the FACP can then command an indvidual sounder — or a group of sounders — to activate. The command set from the panel can be tailored to the specific event, allowing selection of volume, tone, and group.
NOTE: The FCO-851(A) is compatible with the NFS-320(C), NFS­320SYS, NFS2-640, and NFS2-3030 operating with firmware ver­sion 17.0 (or higher) in FlashScan® mode; CLIP mode not sup­ported.
Features
• Unique ability to detect all four major elements of a fire.
• Separate CO detection signal.
• Highest nuisance alarm immunity.
• Automatic drift compensation of smoke sensor and CO cell.
• Uses only one address on the SLC.
• RealTest® CO testing capability.
• Separates audible signal for fire or CO alarm when used with the B200S base (B200SCOA in Canada).
• CO cell end-of-life warning and fault.
• FlashScan operation.
. Because the poten-
2
Sensitivity Settings and Suggested Applications
Level 1: 1% / ft of smoke. Suggested for very clean envi-
Level 2: 2% / ft of smoke. Suggested for clean environ-
Level 3: 3% / ft of smoke. Suggested for moderately clean
Level 4: 3% / ft of smoke with different algorithm process-
Level 5: 4% / ft of smoke. Suggested for equipment rooms,
Level 6: Thermal alarm at 135°F (57°C). Once the CO cell has reached end-of-life, the CO sensor no
longer provides life safety protection; however, when the fire detector enters Photo, Thermal, Infrared (PTIR) mode, the fol­lowing sensitivities apply:
Level 1: 1% / ft of smoke. Suggested for very clean envi-
Level 2: 2% / ft of smoke. Suggested for clean environ-
Level 3: 3% / ft of smoke. Suggested for moderately clean
Level 6: Thermal alarm at 135°F (57°C).
Specifications
PHYSICAL SPECIFICATIONS
Size: 3.46" (8.79 cm) high x 6.875" (17.46 cm) diameter installed in B200S(COA) base.
Shipping weight: 4.6 oz. (130.41 g).
Color: Ivory.
DN-60689:B
Intelligent/Addressable Devices
ronments such as laboratories.
ments such as offices.
environments such as hotel rooms, dorm rooms.
ing and weighting of sensor elements. Suggested for hotel rooms near a shower, boiler rooms.
kitchens, paint shops.
ronments such as laboratories.
ments such as offices.
environments such as hotel rooms, dorm rooms.
DN-60689:B • 12/3/2012 — Page 1 of 2
Made in the U.S. A.
Operating humidity range: 15% – 90% relative humidity (noncondensing).
Operating temperature: 0°C to 38°C (32°F to 100°F).
Air velocity: 0 – 4000 ft./min. (0 to 20 m/sec.).
ELECTRICAL SPECIFICATIONS
Operating Voltage range: 15 – 32 volts VDC.
Standby current (max. avg.): 300 μA at 24 VDC (one com-
munication every 5 seconds with LED blink enabled).
Maximum Alarm Current (LED on): 7.2 mA at 24 VDC.
CO ALARM ACTIVATION LEVELS
Alarm activation levels as defined by UL Standard 2034:
Concentration
of CO
70 (+/- 5) PPM 240 min (not less than 60 min)
150 (+/- 5) PPM 50 min (not less than 10 min)
400 (+/- 10) PPM 15 min (not less than 4 min)
Maximum Alarm Time
Response
Ordering Information
NOTE: “A suffix indicates ULC listed model.
FCO-851: IntelliQuad PLUS Advanced Multi-Criteria Fire/CO Detector.
FCO-851A: IntelliQuad PLUS Advanced Multi-Criteria Fire/CO Detector, ULC listed.
B200S: Intelligent programmable sounder base.
B200SCOA: Intelligent programmable sounder base, ULC
listed. Includes CO detector markings in English and French.
M02-04-00: Detector Test Magnet.
M02-09-00: Telescoping Test Magnet.
Agency Listings and Approvals
The listings and approvals below apply to the primary product. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult fac­tory for latest listing status.
UL: S1115 (FCO-851).
ULC: S1115 (FCO-851A).
CSFM: 7275-0028:0264.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
Page 2 of 2 — DN-60689:B • 12/3/2012
IntelliQuad™ is a trademark and NOTIFIER®, RealTest® and FlashScan® are registered trademarks of Honeywell International Inc. ©2012 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
www.notifier.com