Notifier Dual Voltage Evacuation Speakers User Manual

SpectrAlert® Advance
6
0
3
2
7
p
h
o
1
.
j
p
g
Indoor Selectable Output Speaker Strobes and Dual Voltage Evacuation Speakers
General
The SpectrAlert Advance Series of speakers and speaker strobes is designed to reduce ground faults. The plug-in design allows the installer to pre-wire mounting plates and dress the wires before plugging in the speakers. The plastic cover pre­vents nicked wires by covering exposed speaker components.
This design also allows faster installations with instant feedback to ensure that wiring is properly connected; rotary switches to select voltage and power settings; and 11 field selectable can­dela settings for wall and ceiling speaker strobes.
The low total harmonic distortion of the SP speaker offers high fidelity sound output while the SPV speaker offers high volume sound output for use in high ambient noise applications.
SpectrAlert Advance makes installation easy
• Attach a universal mounting plate to a 4” x 4” x 2-1/8” back box. Flush mount applications are achievable without the need for an extension ring.
• Connect the notification appliance circuit or speaker wiring to the PEMS terminals on the mounting plate.
• Attach the speaker or speaker strobe to the mounting plate by inserting the product tabs into the mounting plate grooves. Rotate the device into position to lock the product pins into the mounting plate terminals. The device will temporarily hold in place with a catch until it is secured with a captured mount­ing screw.
Features
• Plug-in design
• Protective cover isolates speaker components, reduces ground faults
• Electrical compatibility with existing SpectrAlert products
• Field selectable candela settings on wall and ceiling units:
Standard: 15, 15/75, 30, 75, 95, 110, 115High: 135, 150, 177, 185
• Shorting spring on mounting plate tests continuity before installation
• Rotary switch simplifies field selection of speaker voltage and power settings
• Universal mounting plate for wall- and ceiling-mount units
• Compatible with System Sensor synchronization protocol
• SP speakers offer high fidelity sound output
• SPV speakers offer high volume sound output
• Automatic selection of 12 or 24 volt operation at 15 and 15/75 candela
• No extension ring required
• Ceiling and wall mount application
• Optional tamper resistant Torx head screw included
Specifications
PHYSICAL SPECIFICATIONS
Operating Temperature: 32°F to 120°F (0°C to 49°C) Humidity Range: 10 to 93% non-condensing Dimensions, Wall-Mount: –
SPS Speaker Strobe: 6.0”L x 5.0”W x 4.7”D (includes lens
and speaker)
DN-60327:B1
Audio/Visual Devices
– SPSV Speaker Strobe: 6.0”L x 5.0”W x 4.9”D (includes
lens and speaker)
SP Speaker: 6.0”L x 5.0”W x 2.8”DSPSV Speaker: 6.0”L x 5.0”W x 2.9”D
Dimensions, Ceiling-Mount:
SPS Speaker Strobe: 6.8”Dia x 4.7”D (includes lens and
speaker)
– SPSV Speaker Strobe: 6.8”Dia x 4.8”D (includes lens and
speaker)
SP Speaker: 6.8”Dia x 2.8”DSPSV Speaker: 6.8”Dia x 2.9”D
ELECTRICAL/OPERATING SPECIFICATIONS
Nominal Voltage (speakers): 25 Volts or 70.7 Volts Maximum Supervisory Voltage (speakers): 50VDC Strobe Flash Rate: 1 flash per second Nominal Voltage (strobes): Regulated 12VDC/FWR or regu-
lated 24DC/FWR
Operating Voltage Range (includes fire alarm panels with built-in sync): 8 to 17.5V (12V nominal) or 16 to 33V (24V
nominal) Operating Voltage with MDL Sync Module: 9 to 17.5V (12V
nominal) or 17 to 33V (24V nominal)
Frequency Range: 400 to 4000 Hz Power: ¼, ½, 1, 2 watts
(nominal)
Agency Listings and Approvals
In some cases, certain modules may not be listed by certain approval agencies, or listing may be in progress. Consult fac-
tory for latest listing status.
UL/ULC Listed: S4048
MEA: 10-08-E
CSFM: 7320-1653:201
• FM Approved
DN-60327:B1 • 11/9/11 — Page 1 of 2
Made in the U.S. A.
UL Maximum Strobe Current Draw (mA RMS)
8 to 17.5 Volts 16 to 33 Volts
DC FWR DC FWR
Standard
Candela
Range
High
Candela
Range
Candela
15 123 128 66 71
15/75 142 148 77 81
30 NA NA 94 96 75 NA NA 158 153
95 NA NA 181 176 110 NA NA 202 195 115 NA NA 210 205 135 NA NA 228 207 150 NA NA 246 220 177 NA NA 281 251 185 NA NA 286 258
Sound Output
UL Reverberant (dBA @ 10ft) 2W 1W ½W ¼W Wall Mount SP Series 86 83 80 77 Wall Mount SPV Series 90 87 84 81 Ceiling Mount SPC Series 86 83 80 77 Ceiling Mount SPCV Series 90 87 84 81 Wall Mount SPS Series 85 82 79 76 Wall Mount SPSV Series 89 86 83 80 Ceiling Mount SPSC Series 85 82 79 76 Ceiling Mount SPSCV Series 89 86 83 80
Architectural/Engineering Specifications
GENERAL
SpectrAlert Advance speaker and speaker strobes shall mount to a 4” x 4” x 2-1/8” backbox. A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance circuit and amplifier wiring shall terminate at the universal mounting plate. Also, SpectrAlert Advance speaker strobes, when used with the Sync Circuit. Module accessory, shall be powered from a non-coded notification appli­ance circuit output and shall operate on a nominal 12 or 24volts. When used with the Sync.Circuit Module, 12 volt rated notification appliance cir­cuit outputs shall operate between nine and 17.5 volts; 24 volt rated notifi­cation appliance circuit outputs shall operate between 17 and 33 volts. Indoor SpectrAlert Advance products shall operate between 32°F and 120°F from a regulated DC, or full-wave rectified, unfiltered power supply. Speaker strobes shall have field-selectable candela settings including 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, 185.
SPEAKER
The speaker shall be a System Sensor SpectrAlert Advance model _______ dual-voltage transformer speaker capable of operating at 25.0 or
70.7 nominal Vrms. It should be listed to UL/ULC 1480 and shall be approved for fire protective service. The speaker shall have a frequency range of 400 to 4000Hz and shall have an operating temperature between 32°F and 120°F. Speaker shall have power taps and voltage that are selected by rotary switches.
SPEAKER STROBE COMBINATION
The speaker strobe shall be a System Sensor SpectrAlert Advance model __________ listed to UL1480 and UL/ULC 1971 and be approved for fire protective signaling systems. Speaker shall be capable of operating at
25.0 or 70.7 nominal Vrms selected via rotary switch, and shall have a fre­quency range of 400 to 4000Hz. Speaker shall have power taps which are selected by rotary switch. The strobe shall comply with the NFPA 72 requirements for visible signaling appliances, flashing at 1Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system.
SYNCHRONIZATION MODULE
The module shall be a System Sensor Sync Circuit model MDL listed to UL/ULC 464 and shall be approved for fire protective service. The module shall synchronize SpectrAlert strobes at 1Hz. The module shall mount to a 4-11/16” x 4-11/16” x 2-1/8” backbox. The module shall also control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply.
Ordering Information
NOTE: (W) indicates white coloring; (R), red. NOTE: “A” suffix indicates ULC-Listed model.
WALL MOUNT
SP(W)(R)(A): Speaker only. SP(W)(R)V(A): Speaker only, high dB; white. SPS(W)(R)(A)*: Speaker strobe, selectable candela (15, 15/75,
30, 75, 95, 110, 115). SPS(W)(R)H(A)*: Speaker strobe, selectable candela, high cd
(135, 150, 177, 185). SPS(W)(R)V(A)*: Speaker strobe, selectable candela, high dB.
CEILING MOUNT
SPC(W)(R)(A): Speaker only. SPC(W)(R)V(A): Speaker only, high dB. SPSC(W*)(R)(A): Speaker strobe, selectable candela (15, 15/
75, 30, 50, 75, 95, 110, 115) SPSC(W*)(R)H(A): Speaker strobe, selectable candela, high
cd (135, 150, 177, 185) SPSC(W*)(R)V(A): Speaker strobe, selectable candela, high
dB (15, 15/75, 30, 50, 75, 95, 110, 115). SPSC(W*)(R)VH(A): Speaker strobe, selectable candela, high
dB, high cd (135, 150, 177, 185).
ACCESSORIES
RFP(A): Retrofit plate (5 pack), red. RFPW(A): Retrofit plate (5 pack), white. SPBBSC(A): Ceiling mount backbox skirt, red. SPBBSCW(A): Ceiling mount backbox skirt, white. SPBBS(A): Wall mount backbox skirt, red. SPBBSW(A): Wall mount backbox skirt, white. TR(A): Wall mount trim ring, red, package of 5. TRW(A): Wall mount trim ring, white, package of 5. TRC(A): Ceiling mount trim ring, red, package of 5. TRCW(A): Ceiling mount trim ring, white, package of 5. MWBB(A): Wall mount, metal weatherproof backbox MWBBW(A): Wall mount, metal weatherproof backbox, white MWBBC(A): Ceiling mount, metal weatherproof backbox MWBBCW(A): Ceiling mount, metal weatherproof backbox,
white
*NOTE: Add -P to model number for plain housing (no ‘FIRE’ marking on the cover), e.g. SPSW-P
Page 2 of 2 — DN-60327:B1 • 11/9/11
SpectrAlert® is a registered trademark of Honeywell International Inc. ©2011 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Loading...