While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system—typically made up of
smoke detectors, heat detectors, manual pull stations, audible
warning devices, and a fire alarm control panel with remote
notification capability—can provide early warning of a developing fire. Such a system, however, does not assure protection
against property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the
recommendations of the current edition of the National Fire
Protection Association Standard 72 (NFPA 72), manufacturer's
recommendations, State and local codes, and the recommendations contained in the Guides for Proper Use of System
Smoke Detectors, which are made available at no charge to all
installing dealers. These documents can be found at http://
www.systemsensor.com/html/applicat.html. A study by the
Federal Emergency Management Agency (an agency of the
United States government) indicated that smoke detectors
may not go off in as many as 35% of all fires. While fire alarm
systems are designed to provide early warning against fire,
they do not guarantee warning or protection against fire. A fire
alarm system may not provide timely or adequate warning, or
simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors. Smoke detectors
also may not sense a fire on another level or floor of a building.
A second-floor detector, for example, may not sense a firstfloor or basement fire.
Particles of combustion or “smoke” from a developing fire
may not reach the sensing chambers of smoke detectors
because:
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow.
• Smoke particles may become “cold,” stratify, and not reach
the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air
outlets.
• Smoke particles may be drawn into air returns before
reaching the detector.
The amount of “smoke” present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm at
various levels of smoke density. If such density levels are not
created by a developing fire at the location of detectors, the
detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing
limitations. Detectors that have photoelectronic sensing
chambers tend to detect smoldering fires better than flaming
fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires
better than smoldering fires. Because fires develop in different
ways and are often unpredictable in their growth, neither type
of detector is necessarily best and a given type of detector
may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and violent
explosions (caused by escaping gas, improper storage of
flammable materials, etc.).
Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise
heat detectors may be subject to reduced sensitivity over time.
For this reason, the rate-of-rise feature of each detector
should be tested at least once per year by a qualified fire protection specialist. Heat detectors are designed to protect
property, not life.
IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so
located, a developing fire may damage the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert people
if these devices are located on the other side of closed or
partly open doors or are located on another floor of a building.
Any warning device may fail to alert people with a disability or
those who have recently consumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause seizures
in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they
hear a fire alarm signal, do not respond or comprehend the
meaning of the signal. It is the property owner's responsibility to conduct fire drills and other training exercise to
make people aware of fire alarm signals and instruct them
on the proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can
cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical
power. If AC power fails, the system will operate from standby
batteries only for a specified time and only if the batteries have
been properly maintained and replaced regularly.
Equipment used in the system may not be technically compatible with the control panel. It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a
premise to a central monitoring station may be out of service
or temporarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended.
The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in
excellent working order, ongoing maintenance is required per
the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of NFPA 72 shall be
followed. Environments with large amounts of dust, dirt or
high air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled
monthly or as required by National and/or local fire codes and
should be performed by authorized professional fire alarm
installers only. Adequate written records of all inspections
should be kept.
Limit-C1-2-2007
2DAA2 & DAX — P/N 53265:A1 8/24/2011
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be
connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is
energized. Do not attempt to install, service, or operate this
unit until manuals are read and understood.
CAUTION - System Re-acceptance Test after Software
Changes: To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or
deletion of system components, or after any modification,
repair or adjustment to system hardware or wiring. All components, circuits, system operations, or software functions known
to be affected by a change must be 100% tested. In addition,
to ensure that other operations are not inadvertently affected,
at least 10% of initiating devices that are not directly affected
by the change, up to a maximum of 50 devices, must also be
tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49º
C/32-120º F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful
life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature
ranges and humidity. Therefore, it is recommended that this
system and its peripherals be installed in an environment with
a normal room temperature of 15-27º C/60-80º F.
Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a
10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to lightning induced transients. Although no system is completely
immune from lightning transients and interference, proper
grounding will reduce susceptibility. Overhead or outside aerial
wiring is not recommended, due to an increased susceptibility
to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or
inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure. When possible, make
all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, or printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Overtightening may damage threads, resulting in reduced terminal
contact pressure and difficulty with screw terminal removal.
This system contains static-sensitive components.
Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the
body. Use static suppressive packaging to protect electronic
assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to
avoid damage to the control panel and associated equipment.
FACP operation and reliability depend upon proper installation.
Precau-D1-9-2005
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual may
cause interference to radio communications. It has been
tested and found to comply with the limits for class A
computing devices pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when devices are
operated in a commercial environment. Operation of this
equipment in a residential area is likely to cause interference, in which case the user will be required to correct
the interference at his or her own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits
for radiation noise emissions from digital apparatus set
out in the Radio Interference Regulations of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits
radioelectriques depassant les limites applicables aux
appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par le
ministere des Communications du Canada.
HARSH™, NIS™, and NOTI•FIRE•NET™ are all trademarks; and Acclimate® Plus, FlashScan®, NION®, NOTIFIER®, ONYX®, ONYXWorks®, UniNet®,
VeriFir e®, and VIEW® are all registered trademarks of Honeywell International Inc.HARSH™, NIS™, and NOTI•FIRE•NET™ are all trademarks; and
Acclimate® Plus, FlashScan®, NION®, NOTIFIER®, ONYX®, ONYXWorks®, UniNet®, Veri Fire®, and VIEW® are all registered trademarks of Honeywell
International Inc. Echelon® is a registered trademark and LonWorks™ is a trademark of Echelon Corporation. ARCNET® is a registered trademark of
Datapoint Corporation. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation.
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make
frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest
features, we strongly recommend that you download the most current version of software for each product prior to
commissioning any system. Contact Technical Support with any questions about software and the appropriate version for
a specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about
our online Help or printed manuals, you can email us.
Please include the following information:
•Product name and version number (if applicable)
•Printed manual or online Help
•Topic Title (for online Help)
•Page number (for printed manual)
•Brief description of content you think should be improved or corrected
•Your suggestion for how to correct/improve documentation
Send email messages to:
FireSystems.TechPubs@honeywell.com
Please note this email address is for documentation feedback only. If you have any technical issues, please contact
Technical Services.
4DAA2 & DAX — P/N 53265:A1 8/24/2011
Table of Contents
Table of Contents
Section 1: General Information................................................................................................9
1.2: Standards and Other Documents....................................................................................................................9
1.4: Cautions and Warnings ................................................................................................................................10
Section 2: DAA2 Digital Audio Amplifiers ............................................................................13
AC Power .............................................................................................................................................25
2.4.1: Sig Sil Control ...................................................................................................................................42
2.4.2: Volume Control - Master and Auxiliary............................................................................................42
2.4.3: FFT Communication .........................................................................................................................42
AC Power..............................................................................................................................................52
3.4.3: Read/Alter Status ...............................................................................................................................66
Section 4: BDA Backup Digital Amplifiers ...........................................................................67
4.1: Features ........................................................................................................................................................67
C.1.2: Features .............................................................................................................................................90
C.5.3: Read/Alter Status ............................................................................................................................122
C.5.4: FFT Communication .......................................................................................................................122
Index ......................................................................................................................................124
8DAA2 & DAX — P/N 53265:A1 8/24/2011
1.1 Overview
DVC
DAA2
DAX
DAA
DAX
DAA2
DAL Address 1
DAL Address 5
DAL Address 3
DAL Address 2
DAL Address 32
Optional return
Connections between any two DAL devices may be either wire or fiber. A
DAL does not need to be all wire or all fiber, but can be a mix of both.
This manual describes the DAA2 and DAX digital audio amplifiers, which may be used as devices
on a digital audio loop (DAL). It also describes compatible backup amplifiers and fiber option
conversion modules. They include:
• DAA2 and DAX digital audio amplifiers, which connect directly to the DAL. These boards
• BDA backup digital amplifiers, which connect to DAA2 and DAX amplifiers for backup.
• Fiber option modules, which convert DAA2 and DAX boards from wire to fiber, as well as
All wire and fiber models of the DVC, DAA2, DAX and DAA are compatible together on a DAL.
Section 1: General Information
each occupy one of the 32 addresses on the DAL.
Alternately, when used with a DAA2 series amplifier, a BDA can be added to support a
second audio channel.
provide compatibility with fiber DVCs and DAAs.
Figure 1.1 DAL (Digital Audio Loop) Block Diagram
Digital audio amplifiers are backed up by BDAs, or by another amplifier of the same digital type:
that is, a DAA2 must be backed up by a BDA or another DAA2, a DAX must be backed up a BDA
or another DAX, etc.
DAA-PCA and -PCB boards are described in Appendix C of this manual.
1.2 Standards and Other Documents
The Digital Series products in this manual comply with the following standards:
•NFPA 72 2007 National Fire Alarm Code
•Underwriter Laboratories Standard UL 864
•Underwriter Laboratories of Canada (ULC) ULC-S527-99 Standard of Control Units for Fire
Alarm Systems
•Part 15 Class A conducted and radiated emissions as required by the FCC
The installer should be familiar with the following documents and standards:
NFPA Standards
NFPA 72 National Fire Alarm Code
Underwriter Laboratories
UL 464 Audible Signaling Appliances
UL 864 Standard for Control Unit and Accessories for Fire Alarm Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1638 Visual Signaling Appliances - Private-Mode Emergency and General Utility Signaling
DAA2 & DAX — P/N 53265:A1 8/24/2011 9
General InformationSupplemental Documentation
!
UL 1711 Amplifiers for Fire Protective Signaling Systems
UL 60950 Safety of Information Technology Equipment
UL 1971 Signaling Devices for the Hearing Impaired
Underwriters Laboratories of Canada (ULC)
ULC-S527-99 Standard of Control Units for Fire Alarm Systems
Other
FCC Part 15 Class A Conducted and Radiated Emissions
1.3 Supplemental Documentation
The table below provides a list of documents referenced in this manual, as well as documents for
other compatible devices.
VeriFire Tools CD help file and CD pamphletVERIFIRE-TCD, 51690
DVC Digital Voice Command Manual52411
Wire Guide Addendum for Digital Audio Loops52916ADD
Heat Dissipation for Cabinets with Digital Audio Products53645
NFS2-3030 Installation, Programming and Operations Manuals52544, 52545, 52546
NFS2-640 Installation, Programming and Operations Manuals52741, 52742, 52743
AMPS-24 Manual51907
ACPS-610 Addressable Power Supply Manual53018
NCA-2 Network Control Annunciator Manual52482
ONYXWorksI Workstation Manual52342
DAL Devices Product Information Sheet52410
AA Series Audio Amplifier Manual52526
ACS Annunciator Manual15842
AFAWS Automatic Fire Alarm Warden Station50705
CFFT-1 Chassis for FireFighter Telephone Product Information Document53289
FTM-1 Firephone Control Module156-1391-02
ACT-4 Audio Coupling Transformer53431
ACT-25 Audio Coupling Transformer53432
ACT-70 Audio Coupling Transformer53240
RM-1 Series Remote Microphones51138
CAB-4 Series Cabinets Installation Instructions15330
EQ-CAB Series Installation Instructions53412
RSM-1A Residential Silence ModuleI56-006-000
AIM-1A Audible Isolation ModuleI56-006-002
CIM-2A/CSM-1A Isolator and Silencing ModulesI56-2200-002
RPJ-1 Remote Paging Jack15058
FPJ Firefighter Phone Jack15510
Related Documentation Table
1.4 Cautions and Warnings
This manual contains cautions and warnings to alert the reader as follows:
CAUTION:
INFORMATION ABOUT PROCEDURES THAT COULD CAUSE PROGRAMMING ERRORS,
RUNTIME ERRORS, OR EQUIPMENT DAMAGE.
10DAA2 & DAX — P/N 53265:A1 8/24/2011
Cautions and WarningsGeneral Information
!
WARNING:
INDICATES INFORMATION ABOUT PROCEDURES THAT COULD CAUSE IRREVERSIBLE
DAMAGE TO THE CONTROL PANEL, IRREVERSIBLE LOSS OF PROGRAMMING DATA, OR
PERSONAL INJURY.
DAA2 & DAX — P/N 53265:A1 8/24/2011 11
Notes
12DAA2 & DAX — P/N 53265:A1 8/24/2011
Section 2: DAA2 Digital Audio Amplifiers
2.1 Description
The DAA2 Digital Audio Amplifiers are multi-featured amplifiers with digital audio functionality.
They are designed to work with the DVC Digital Voice Command.
NOTE: The term DAA2 is used in this manual to refer to all the model versions listed in Table 2.1.
Individual part numbers are used to distinguish features or functions that differ.
50 Watt DAA2s
DAA2-5025 (120 VAC)25
DAA2-5025E (220 - 240 VAC)25
DAA2-5070 (120 VAC)70
DAA2-5070E (220 - 240 VAC)70
75 Watt DAA2s
DAA2-7525 (120 VAC)25
DAA2-7525E (220 - 240 VAC)25
NOTE: All boards are wire. They may be converted to
fiber by using a fiber option module.
Speaker
Circuit Output
RMS
RMS
RMS
RMS
RMS
RMS
Table 2.1 Digital Audio Amplifier Models
NOTE: The term DVC is used in this manual to refer to all DVC wire and fiber model versions.
Individual part numbers are used in this manual only to distinguish features or functions that differ.
Available models are described in the DVC Digital Voice Command manual.
Refer to Figure 1.1 on page 9 for a simplified illustration of DAL devices on a digital audio loop.
NOTE:
Speaker placement must be given careful consideration when planning an audio system.
• Place speakers from different DALs (Digital Audio Loops) so they are not within the audible
areas of other DALs.
• Carefully consider the audible distance of speakers within a DAL; overlapping audio messages
can be confusing.
2.1.1 Features
The DAA2 audio amplifiers have the following features:
•50W total output power at 25V
DAA2-5070 model versions).
•75W total output power at 25V
•Two Class A connections for high-level audio output, or alternately, four Class B connections.
•Audio output activation via network control-by-event equations resident within the DVC.
•Isolated alarm bus input, to be used for backup activation of alarm messages when normal
digital communication is lost.
DAA2 & DAX — P/N 53265:A1 8/24/2011 13
(all DAA2-5025 model versions) or 70 V
RMS
(all DAA2-7525 model versions).
RMS
RMS
(all
DAA2 Digital Audio AmplifiersDescription
•Amplifies one channel of digital audio (two channels using the BDA card as a second channel)
and distributes it on up to four outputs.
•Remote microphone paging option with RM-1.
•FireFighter telephone (FFT) riser.
•Auxiliary input for 1V
, to be used for background music input, an interface with a
RMS
telephone paging source, or other compatible audio sources. Includes user audio level
adjustment feature.
•Uploads and downloads via the DVC. Programmable through VeriFire Tools.
•Up to106 seconds of Backup Digital message storage (Emergency tone, Non-Emergency tone,
and FFT busy tone) for use in the event of communication loss- either standard quality or high
quality, from the VeriFire Tools message library or created by the installer.
•Disconnect of deeply-discharged battery (low battery disconnect).
•Backup amplifier options.
•Meets UL THD Distortion requirements for 500 Hz to 4 KHz bandwidth.
Meets ULC THD Distortion requirements for 400 Hz to 4 KHz bandwidth.
2.1.2 Specifications
CPS-24 Power Supply Board
AC Power - TB1
120 VAC 60 Hz input*
220-240 VAC 50/60 Hz input (“E” versions)*
*Maximum AC draw varies by DAA2 model. These draws are given in Appendix A, “AC
Current Draw Calculations”, along with a worksheet to determine the actual AC draw.
Recommended 12-14 AWG (1.6 mm O.D.) with 600 VAC insulation.
Fuse: 8 amps, 250V, 5 x 20 mm, Fast-Acting, ceramic. Notifier p/n 12117.
Secondary Power 5V and 24V AUX Outputs - TB2
24V AUX:
Power-limited: 24V @ 0.5A
Utilizes wire sizes 12-18 AWG (3.31 mm
2
- 2.08 mm2)
5V: Future Use
Battery Connections - TB3
Supplied cable connections to batteries for CAB-4 and CHS-BH1. For battery sharing, use 12
AWG either in the same cabinet or in conduit for no more than 20 ft (6.09 m).
Battery Charger
Current-limited sealed lead acid battery charger which charges two 12 volt batteries in series,
up to 200AH. Table 2.2 gives battery-charging capabilities for the DAA2 boards. The charger
enable/disable option is available for all DAA2 models.
Charge
Batteries Less
Than 26AH
DAA2-5025
DAA2-5070
DAA2-7525YesYesNo
Yes
Yes
Charge
26AH to <
50AH
Batteries
Yes
Yes
Charge
50AH to
200AH
Batteries
Yes
Yes
Table 2.2 Battery Charging Capabilities
14DAA2 & DAX — P/N 53265:A1 8/24/2011
DescriptionDAA2 Digital Audio Amplifiers
Charge
Batteries Less
Than 26AH
DAA2-5025 w/ BDA in Group 2 of VeriFire
Tools programming*
DAA2-5070 w/ BDA in Group 2 of VeriFire
Tools programming*
* Refer to “DAA2-50 Configurations with BDA” on page 72 for further explanation.
No
No
Charge
26AH to <
50AH
Batteries
No
No
Charge
50AH to
200AH
Batteries
No
No
Table 2.2 Battery Charging Capabilities
Charger voltage: 27.6 VDC.
For battery calculation worksheet and standby operating times, refer to Appendix B.1, “DAA2
Battery Calculations”, on page 84.
Utilizes wire sizes 12-18 AWG..
NOTE: A 50 watt DAA2 with 2 groups will have its charger disabled automatically. Groups are
explained in the Audio Groups appendix of the DVC Digital Voice Command manual.
When AC power is lost, the deeply-discharged battery cutoff protection will be invoked at 17
volts. The power supply will be disconnected from the batteries. The power supply’s normal
operation will be restored when AC power returns.
DAA2-5025/70 and DAA2-7525 Boards
Wire Digital Audio Ports A and B - TB2, TB3
Refer to the Wiring Guide, p/n 52916ADD, for acceptable wire types.
EIA-485 format.
Power-limited and supervised.
Refer to Section 5, “Fiber Option Modules”, on page 75 for fiber connection information.
When a fiber option module is mounted on a DAA2, it disables the corresponding wire
terminals. TB2 (Digital Audio Port A) is disabled when a fiber option board is connected at J9.
TB3 (Digital Audio Port B) is disabled when a fiber option board is connected at J10.
Alarm Bus - TB4
Power-limited and supervised by source.
Recommended wiring: 14-18 AWG twisted-pair.
Requires 16VDC minimum @ 20mA across the terminals to activate. Nominal 24 VDC.
Max. distance between remote microphone and DAA2: 1000 ft (304.8 m).
FFT Riser - TB7
Power-limited output.
Supervised.
Class A or Class B operation.
Class B 2-wire connections require a 3.9k ohm 1/2 watt resistor (P/N R-3.9K).
Max. wiring resistance (including individual telephone zone to last handset) permitted is 50
ohms, 10,000 ft (3048 m) max. wiring distance at 14 AWG to last handset.
DAA2 & DAX — P/N 53265:A1 8/24/2011 15
DAA2 Digital Audio AmplifiersDescription
Auxiliary Input A (AUX A) - TB 9
Signal strength from low-level analog audio input (such as background music or telephone
paging): 1V
max. Optional supervision through programming.
p-p
Recommended wiring: 14-18 AWG, twisted-pair.
Supervision programmable.
Auxiliary input source must be within 20 ft. ( 6.1 m) of the DAA2, and within the same room.
Speaker Circuits - TB10, TB11, TB12 and TB13
Power-limited outputs.*
* Exception: A DAA2-5070 speaker circuit used with any Canadian Room Isolator
module is non-power-limited. Speaker circuit 1 (TB10) can not be used.
DAA2-5025/70 - Each circuit rated up to 50 watts.**
DAA2-7525 - Each circuit rated up to 75 watts.**
**Total wattage may vary. Refer to “BDA Backup Digital Amplifiers” on page 67 for
•Not supervised when inactive. Supervised by backup source when active.
•Must be in the same room or enclosure.
16DAA2 & DAX — P/N 53265:A1 8/24/2011
DescriptionDAA2 Digital Audio Amplifiers
OUT 4 +
OUT 4 SHIELD
+
SHIELD
+
SHIELD
SHIELD
+
SHIELD
SHIELD
OUT1 -
+
-
SHIELD
-
+
OUT1 +
SHIELD
OUT3 +
OUT3 -
BDA Power J6
BDA Control J5
OUT 3
TB12
See p.33
BKUP3
TB16
See p.37
OUT 4
TB13
See p.33
BKUP4
TB17
See p.37
OUT 1
TB10
See p.33
SHIELD
-
+
BKUP1
TB14
See p.37
OUT 2
TB11
See p.33
SHIELD
OUT2 -
OUT2 +
DAPA +
DAPA -
DAPA REF
TB2 - Digital
Audio Port A
Refer to page 29
DAPB +
DAPB -
DAPB REF
TB3 - Digital
Audio Port B
Refer to page 29
FFT OUT RISER (+)
FFT OUT RISER (-)
FFT OUT SHIELD
FFT RTN (+)
FFT RTN (-)
FFT RTN SHIELD
FFT Riser
- TB7
Refer to
page 30
AUXA R +
AUXA R -
AUXA L +
AUXA L -
AUXA - TB9
Refer to
page 32
RM1 AUDIO SHLD
RM1 - TB5
See page 32
RM1 AUDIO -
RM1 AUDIO +
RM1 PWR SHLD
RM1 PWR -
RM1 PWR +
ALM IN
ALM OUT
REF
REF
TB4 - Alarm
See page 28
USB Connector J2
Future Use
SHIELD
-
+
SHIELD
-
+
BKUP2
TB15
See p.37
Top of Board
Bottom of Board
Dotted line indicates position of
the DAA2’s CPS-24 Power
Supply Board
Fiber option
module mounting
holes. Refer to
Figure 5.2, “DAA2
Fiber Option
Module
Installation” on
page 77
J9
J10
See p.70
See p.70
2.1.3 DAA2 Layout
Connection Locations
A DAA2 is comprised of two boards; a larger rear board, and a smaller front power supply board.
Figures 2.1 and 2.2 below show the layout.
Figure 2.1 DAA2 Rear Board
DAA2 & DAX — P/N 53265:A1 8/24/2011 17
DAA2 Digital Audio AmplifiersDescription
BAT +
BAT -
TB3 - Battery
Connections
+24V AUX
COM
COM - Future Use
+5V AUX - Future Use
HOT
NEU
EARTH
GROUND
TB1
AC INPUT
Refer to
page 25
CPS-24 Power
Supply Board
DAA2PCA brd.wmf
CPS24-bboard.wmf
TB2
AC Fuse F4
Figure 2.2 DAA2’s CPS-24 Power Supply Board
18DAA2 & DAX — P/N 53265:A1 8/24/2011
DescriptionDAA2 Digital Audio Amplifiers
LED Indicators. Refer to Table 2.3 on page 20
DAP A TX:
LED 19
DAP A RX:
LED 20
DAP B TX:
LED 21
DAP B RX:
LED 22
AL BUS: LED 10
AMP FAIL: LED 4
AUDIO: LED 13
STATUS: LED 25
TRBL: LED 9
SIG SIL: LED 24
AUX: LED 11
FFT: LED 12
RST: LED 23
USB: LED 18
ON1: LED 8
TRBL1: LED 14
SW3:
ONES
SW2:
TENS
SW5:
SIG SIL
2 WIRE/4 WIRE:
SW1
ON2: LED7
TRBL2:
LED 15
ON3: LED 6
TRBL3:
LED 16
ON4: LED 5
TRBL4:
LED17
DA2APCA brd.wmf
CPS24-bboard.wmf
+24V AUX: LED 5
+5V AUX: LED 6
LOGIC POWER: LED 1
TROUBLE: LED 2
EARTH FAULT: LED 3
AC: LED 4
GND FAULT: SW1
BACKUP FAIL: LED 26
RM-1: LED 1
Dotted line indicates position of
the DAA2’s CPS-24 Power
Supply Board
PRIMARY AMP:
SW4
Indicator, Jumper and Switch Locations
Switches and LED indicator locations are illustrated in Figure 2.3.
DAA2 & DAX — P/N 53265:A1 8/24/2011 19
Figure 2.3 LED Indicator, Jumper and Switch Locations
DAA2 Digital Audio AmplifiersDescription
Indicators
Diagnostic colored LEDs indicate various conditions and troubles. Table 2.3 lists and describes
each.
DAA2 Board
LED Name ColorDescriptionLED #
RM-1Green Illuminates steadily while the RM-1 has a channel.1
AMP FAILYellow Illuminates steadily while audio amplifier failure detected.4
ON 4Green Illuminates steadily while analog signal is on speaker circuit 4, or while 200Hz tone is on speaker
circuit 4.
ON 3Green Illuminates steadily while analog signal is on speaker circuit 3, or while 200Hz tone is on speaker
circuit 3.
ON 2Green Illuminates steadily while analog signal is on speaker circuit 2, or while 200Hz tone is on speaker
ON 1Green Illuminates steadily while analog signal is on speaker circuit 1, or while 200Hz tone is on speaker
TRBLYellow Blinks when there is an unacknowledged trouble, illuminates steadily when a trouble is
AL BUSRedIlluminates steadily while alarm bus input is active. 10
AUXGreen Illuminates while audio detected on AUX IN A.11
FFTGreen Illuminates steadily when the FFT has been granted a digital phone channel. Flashes when an
AUDIOGreen OFF - No audio signal is present.
TRBL 1Yellow Illuminates steadily while a short is detected on speaker circuit 1. Blinks slowly (once a second)
TRBL 2Yellow Illuminates steadily while a short is detected on speaker circuit 2. Blinks slowly (once a second)
TRBL 3Yellow Illuminates steadily while a short is detected on speaker circuit 3. Blinks slowly (once a second)
TRBL 4Yellow Illuminates steadily while a short is detected on speaker circuit 4.Blinks slowly (once a second)
USBGreen Illuminated while communication is established on the USB port. Future Use.18
DAP A TXGreen Illuminates while data transmitted on Digital Audio Port A (wire only). Light will flicker, turning on
DAP A RXGreen Illuminates while data received on Digital Audio Port A (wire only). Light will flicker, turning on
DAP B TXGreen Illuminates while data transmitted on Digital Audio Port B (wire only). Light will flicker, turning on
DAP B RXGreen Illuminates while data received on Digital Audio Port B (wire only). Light will flicker, turning on
RSTYellow Illuminates when the board is not operational and maintenance is required. Call the factory.23
SIG SILYellow Illuminates when the SIG SIL button is pressed to silence local speaker outputs 1 through 4.24
STATUSGreen Blinks slowly (once a second) under normal operation, Blinks fast (4 times a second) when the
BACKUP
FAIL
Yellow Illuminates for diagnostics of the BDA amplifier.26
circuit 2.
circuit 1.
acknowledged but unresolved.
FFT on a DAA2 requests a phone channel.
Fast blink (4 times a second) - The DAA2 is receiving audio from the DVC.
Slow blink (once a second) - The DAA2 is playing audio from stored backup tones.
Steady - The DAA2 is playing audio from its AUX input.
while an open is detected. Blinks fast (4 times a second) when this speaker circuit is disabled.
while an open is detected. Blinks fast (4 times a second) when this speaker circuit is disabled.
while an open is detected. Blinks fast (4 times a second) when this speaker circuit is disabled.
while an open is detected. Blinks fast (4 times a second) when this speaker circuit is disabled.
when activity is detected and off when it is not. Does not illuminate for fiber connections. Check
the RX and TX LEDs on the fiber option module for activity indication.
when activity is detected and off when it is not. Check the RX and TX LEDs on the fiber option
module for activity indication.
when activity is detected and off when it is not. Check the RX and TX LEDs on the fiber option
module for activity indication.
when activity is detected and off when it is not. Check the RX and TX LEDs on the fiber option
module for activity indication.
DAA2 is in bootload or diagnostic mode. Does not blink when the board is not operational or
starting up. Call the factory if this LED is off for a prolonged period of time.
5
6
7
8
9
12
13
14
15
16
17
19
20
21
22
25
CPS-24 Power Supply Board
LED Name ColorDescriptionLED #
Table 2.3 DAA2 LED Indicators (1 of 2)
20DAA2 & DAX — P/N 53265:A1 8/24/2011
DAA2 InstallationDAA2 Digital Audio Amplifiers
DAA2 Board
LED Name ColorDescriptionLED #
LOGIC
POWER
TRBLYellow Software-controlled as follows:
EARTH
FAULT
ACGreen AC power is on.4
+24V AUXGreen Illuminated while +24V auxiliary power is on.5
+5V AUXGreen Future Use6
Green +5V logic power is OK.1
– OFF when the following system troubles are not present.
– 1 blink - AC FAIL. Priority 1, highest priority.
– 2 blinks - HIGH BATTERY. Priority 2.
– 3 blinks - LOW BATTERY. Priority 3.
– 4 blinks - CHARGER TROUBLE. Priority 4, lowest priority.
If multiple troubles are present, the highest priority trouble will blink until cleared, then the next
priority trouble will blink until cleared, etc.
Yellow When earth fault switch SW1 is enabled:
• Illuminates while earth fault is detected anywhere on the DAA2 except DAP A.
• If batteries are shared, illuminates when an earth fault is detected on any non-isolated circuits in
the sharing set.
2
3
Table 2.3 DAA2 LED Indicators (2 of 2)
Switches
The switches described in Table 2.4 are for configuring the DAA2.
DAA2 Board
NameSwitch # DescriptionDefault
2 WIRE/4 WIRE SW1Changes FFT Riser indication to 2- or 4-wire, depending on
whether the riser is wired Class B or Class A.
TENSSW2BCD rotary address tens selection switch. Refer to page 41.0
ONESSW3BCD rotary address ones selection switch. Refer to page 41.0
PRIMARY AMP SW4ON is the normal state. OFF will induce an AMP FAIL trouble. Refer
to page 42.
SIG SILSW5Pushbutton to silence speaker circuits during communication loss
with DVC.
2-wire
ON
N/A
GND FAULTSW 1Ground fault detection switch. When this switch is set to enable it
2.2 DAA2 Installation
2.2.1 Cabinet
The DAA2 arrives from the factory already installed on its chassis. A BDA-25/70V, NCM, or HSNCM, can be mounted on it. (Refer to Figure 2.5). A CHS-BH1 Battery Chassis may be mounted
to the left of the DAA2. The DAA2 chassis mounts in a CAB-4 Series cabinet, as well as in the
EQCAB Series backboxes.
Prior to installation,
• Review the installation precautions at the front of this manual.
• Installers should be familiar with the standards and codes specified in “Standards and Other
Documents” on page 9.
• Ensure all wiring will comply with national and local codes.
CPS-24 Power Supply Board
Enable
will enable earth fault detection for Digital Audio Port A. Refer to
page 41
Table 2.4 DAA2 Switches
DAA2 & DAX — P/N 53265:A1 8/24/2011 21
DAA2 Digital Audio AmplifiersDAA2 Installation
!
• Review the installation instructions in this section.
WARNING:
Wear a static discharge wrist strap to prevent equipment damage.
Locate the cabinet backbox on a surface that is in a clean, dry, vibration-free area. The top should
be located so that all operational buttons, switches, displays, etc. are easily accessible and/or
viewable to the operator - usually no more than 66 inches (1.7 m) above the floor. Allow sufficient
clearance around the cabinet for the door to swing freely, and for easy installation and maintenance
of equipment.
Follow the instructions below.
1.Mark and pre-drill two holes for the keyhole mounting bolts. Install bolts.
2.Select and punch open the appropriate cabinet knock-outs. (For selection guidelines, see
“UL Power-limited Wiring Requirements” on page 40.)
3.Using the keyholes, mount the backbox on the two bolts.
4.Mark the location of the two lower holes, remove backbox and drill the mounting holes.
5.Mount the backbox over the top two screws, then install the remaining fasteners. Tighten
all fasteners securely.
6.Feed wires through appropriate knockouts.
7.Install DAA2 according to the following instructions before installing the door per the
CAB-4 Series Cabinet Installation Document.
The DAA2 fills one row of any EQ or CAB-4 series cabinet.
EQ Series Cabinets and Doors
The EQ Series cabinets come in B, C, and D sizes. The row spacing allows DAA2 amplifiers to be
mounted in any row, and the doors are equipped with ventilated panels for heat dissipation. The cabinets
were designed so that all DAA2 boards can be used in any or all cabinet rows.Batteries must be
accommodated in separate cabinets or battery backboxes.
The following models are available:
• EQCAB-D4 - Four rows. Accommodates four DAA2s. Consists of P/Ns EQBB-D4 (black
backbox) and EQDR-D4 (black door with ventilated panels).
• EQCAB-C4 - Three rows. Accommodates three DAA2s. Consists of P/Ns EQBB-C4 (black
backbox) and EQDR-C4 (black door with ventilated panels).
• EQCAB-B4 - Two rows. Accommodates two DAA2s. Consists of P/Ns EQBB-B4 (black
backbox) and EQDR-B4 (black door with ventilated panels).
NOTE: Digital amplifiers can produce significant heat during their duty cycles. Different cabinets
can handle different amounts of heat. Refer to the Heat Dissipation Calculation document (53645)
to determine dissipation figures for the equipment you are installing, and match it with an
appropriate cabinet.
22DAA2 & DAX — P/N 53265:A1 8/24/2011
DAA2 InstallationDAA2 Digital Audio Amplifiers
DAA2 Mounting
Locations
CABDAA_D4.wmf
Figure 2.4 EQCAB-D4 Backbox and EQDR-D4 Door
DAA2 & DAX — P/N 53265:A1 8/24/2011 23
DAA2 Digital Audio AmplifiersDAA2 Installation
1.Place the DAA2 chassis over the chassis
standoffs at the locations indicated. Secure
with two 10/32 nuts.
DAA2mtgcab4.wmf
Using the hardware that
comes with the DP-1B
dress panel, attach it at the
points indicated.
DP-1B
DP-1B.wmf
Optional BDA-25/70V or Network Control
Module (wire or fiber NCM or HS-NCM)
Mounting:
1. Fasten four 2 3/8” steel 4-40 male/female
standoffs ( P/N 42227, included with the
DAA2) at the bottom of the chassis.
2. Position the card over the 4 fastening
points and secure with four 4-40 screws (P/N
2820-0039, included with the option card.)
Refer to page 38 for BDA harness
installation.
!
CAB-4 Series
Figure 2.5 illustrates a typical DAA2 installation. A DP-1B dress panel, ordered separately, can be
used to cover the row.
NOTE: Digital amplifiers can produce significant heat during their duty cycles. Different cabinets
can handle different amounts of heat. Refer to the Heat Dissipation Calculation document (53645)
to determine dissipation figures for the equipment you are installing, and match it with an
appropriate cabinet.
2.2.2 Batteries
WARNING: Batteries contain sulfuric acid which can cause severe burns to the skin and eyes, and
can destroy fabrics. If contact is made with sulfuric acid, immediately flush skin or eyes with water for
15 minutes and seek immediate medical attention.
The DAA2 works with two 12 volt batteries. See Appendix B.1, “DAA2 Battery Calculations”, on
page 84 for current draw calculations to determine the battery size required for this installation.
Batteries for the DAA2 may be installed in any of the following configurations:
24DAA2 & DAX — P/N 53265:A1 8/24/2011
Figure 2.5 DAA2 Cabinet Installation
• In a CHS-BH1 battery chassis (12AH batteries only), designed for use with the DAA2
chassis.
• In the bottom of a CAB-4 series cabinet that holds the DAA2.
DAA2 InstallationDAA2 Digital Audio Amplifiers
CHS-BHtoDAAchassisa.wmf
CHS-BHwbattsa.wmf
Place battery holder against DAA2 chassis, resting
on support. Align chassis standoffs with holes.
Fasten with the two washers (P/N 43123) and 8-32
KEPS hex nuts (P/N 36047) supplied.
Place batteries in the trays.
Support
Figure 2.6 Mounting the CHS-BH1
CAB4DwDAAbats.wmf
DAA2 in top row
of CAB-D4
Figure 2.7 Battery Installation
Within the Cabinet
Batteries for
DAA2
!
• In a cabinet adjacent to the cabinet that holds a DAA2, with connections in conduit.
CHS-BH1 Battery Chassis
This chassis will hold two 12AH batteries, and will mount on the left side of the DAA2 chassis, so
that the DAA2 and batteries are contained in a single cabinet row.
To mount the CHS-BH1 onto the DAA2 chassis: Place battery holder against DAA2 chassis,
resting on support as shown in Figure 2.6. Align chassis standoffs with holes. Fasten with the two
8/32” hex nuts supplied.
Place the batteries on their sides in their trays before wiring. Refer to “Batteries” on page 26 for
wiring instructions.
Within the CAB-4 Enclosure
If the batteries will not be housed in a CHS-BH1, place
the batteries in the bottom of the cabinet, as shown in
Figure 2.7. Refer to“Batteries” on page 26 for wiring
instructions.
Outside the DAA2 Enclosure
Batteries may be installed outside the DAA2 enclosure.
The battery cables must be in conduit between the
enclosures for the batteries and the DAA2. Refer to
“Batteries” on page 26 for wiring instructions.
2.2.3 Wiring
AC Power
WARNING: High Voltages Present.
Use extreme caution when working with the DAA2. High voltage and AC line-connected circuits are
present. Turn off and remove all power sources. To reduce the risk of electric shock, make sure to
properly ground the DAA2.
Close the hinged cover for TB1 after wiring but before energizing.
DAA2 & DAX — P/N 53265:A1 8/24/2011 25
The DAA2 power supply requires connection to a separate dedicated AC branch circuit. Follow
these guidelines when connecting the AC branch circuit:
DAA2 Digital Audio AmplifiersDAA2 Installation
Figure 2.8 AC Power Connection
EARTH
NEUTRAL
HOT
DAACPStb1.wmf
!
DAAPStobatts.wmf
Battery
Interconnect
Cable, P/N
71070
Leave disconnected
until after initial
system power-up.
Batteries in CHS-BH1, same
cabinet row as DAA2
Batteries in different cabinet
row than DAA2.
DAAPStobattsa.wmf
A
B
P/N 75560 (pos)
P/N 75561 (neg)
P/N 75621 (neg)
P/N 71071 (pos)
• Label the branch circuit “Fire Alarm”.
• Connect the branch circuit to the line side of the main power feed of the protected premises.
• Do not power other equipment from the fire alarm branch circuit.
• Run the AC branch circuit wire continuously, without any disconnect devices, from the
power source to the power supply.
• Overcurrent protection for the AC branch circuit must comply with Article 760 of the
National Electrical Codes, as well as local codes.
• Use 12-14 AWG (1.6mm O.D.) wire with 600 VAC insulation for the AC branch circuit.
Connect primary power as follows:
1.Turn off the circuit breaker at the main power
distribution panel.
2.Connect the earth ground terminal (TB1
EARTH) to a solid earth ground (a metallic, cold
water pipe may be suitable in some installations).
This connection is vital to maintaining the power
supply’s immunity to unwanted transients
generated by lightning and electrostatic discharge.
3.Connect the primary power neutral line to the terminal marked NEUTRAL and the primary
power AC line to the terminal marked HOT.
Batteries
WARNING: Do not connect the battery interconnect cable (See Figure 2.9) at this time. Leave the
battery interconnect cable disconnected until after initial system power-up.
The DAA2 works with two 12 volt batteries. See Appendix B.1, “DAA2 Battery Calculations”, on
page 84 for current draw calculations to determine the battery size required for this installation.
Battery cables (90”, 2.28 m) are included with the DAA2 for battery installation in any CAB-4
series cabinet that includes a DAA2 in one of the rows. Shorter battery cables (18”, 0.5 m) are
included with the CHS-BH1. For battery sharing, use 12 AWG wire either in the same cabinet, or in
conduit for no more than 20 ft. (6.09 m.).
Batteries Within the Same Enclosure as the DAA2
Refer to Figure 2.9 for battery connections.
26DAA2 & DAX — P/N 53265:A1 8/24/2011
Figure 2.9 Connecting Batteries to TB3 on the CPS-24
DAA2 InstallationDAA2 Digital Audio Amplifiers
DAAbattexternal.wmf
DAA2
Batteries
Conduit between
enclosures
Battery
Interconnect
Cable
Leave disconnected
until after initial
system power-up.
If batteries are not in the same cabinet
as the DAA2s, wiring must be in conduit
that is 20 ft. long (6.09 m) or less.
CPS-24tb3batshare.wmf
DAA2 1
TB3 on CPS-24
SW1 must be set to
“Disable” on all but
one of these DAA2s.
VeriFire Tools
programming must
indicate all but one
charger is disabled.
DAA2 2
TB3 on CPS-24
DAA2 3
TB3 on CPS-24
DAA2 4
TB3 on CPS-24
Batteries Outside the DAA2 Enclosure
When the batteries are installed outside the DAA2 cabinet, connections are the same as in
Figure 2.9. However, the battery cables between the two enclosures must be in conduit and the
enclosures must be within 20 feet (6.09 m) of each other within the same room.
Figure 2.10 Using Conduit
Battery Sharing
Up to four DAA2s may share a set of batteries. When DAA2s share batteries
• the ground fault switch on the DAA2 power supply (SW1) must be set to “Disable” on all
but one DAA2 attached to the set of batteries.
• In VeriFire Tools programming, “Disable Charger” must be checked in the “DAA2
Amplifier Programming Service - General II” screen for all but one DAA2.
The enabled ground fault switch does not have to be on the same DAA2 as the enabled charger.
Connect all DAA2s sharing a set of batteries directly to the batteries using 12 AWG. If the batteries
are located outside of the DAA2 cabinet, the wiring must be in conduit that is no greater than 20 ft
(6.09 m) long.
Figure 2.11 Four DAA2s Sharing Batteries
DAA2 & DAX — P/N 53265:A1 8/24/2011 27
DAA2 Digital Audio AmplifiersDAA2 Installation
FCM-1*
ALARM Bus to next DAA2
ELR-47K,
1/2 watt
resistor
DAA2
FZMFCMtpHa.wmf
TB4
TB4
14-18 AWG twisted-pair
recommended
Program the control module at the
FACP with an appropriate alarm
Type ID per the FACP manual.
Alarm Bus requires 16VDC
at 20mA across the
terminals to activate.
Nominal 24 VDC.
To Power
Supply
+
-
SLC
from
FACP
SLC to
next device
+
-
+
-
+
-
*If the SLC device does
not match the one in this
figure, refer to the SLC
manual appendix, which
contains wiring conversion charts for type V
and type H modules.
ALM
REF
ALM REF
OUT
IN
ALM
REF
ALM REF
OUT
IN
NAC Circuit
A -
A +
B +
B -
ALARM Bus to next DAA2
DAABRDtb4.wmf
DAA2
TB4
TB4
ELR per panel
or power
supply manual.
14-18 AWG twisted-pair
recommended
Listed compatible
panel or power
supply with onboard
NAC circuits.
Alarm Bus requires 16VDC
at 20mA across the
terminals to activate.
Nominal 24VDC.
ALM
REF
ALM REF
OUT
IN
ALM
REF
ALM REF
OUT
IN
Alarm Bus
The DAA2 general alarm connections are used to receive general alarm messages from an FACP
via an SLC device, or via the Notification Appliance Circuit of an FACP or power supply.
Figure 2.12 Alarm Bus Connections to FCM-1
Refer to the SLC manual and specific panel or power supply manual for more information.
Figure 2.13 Alarm Bus Connections to NAC
28DAA2 & DAX — P/N 53265:A1 8/24/2011
DAA2 InstallationDAA2 Digital Audio Amplifiers
DVC
Refer to the Wiring Guide, p/n 52916ADD, for acceptable wire types
and associated distances between ports.
Do not splice a cable. Splicing will degrade the signal, and the
recommended distance will no longer apply.
DAPA, TB3
DAPB, TB2
REF
DAA2 #1
Optional Style 7 return
Connections are polarity
sensitive.
Connections are port
sensitive. Always connect
Port A to Port B.
DAA2 #2
DAA2 #32
TB2
TB2
TB2
TB3
TB3
TB3
DAP A
REF
DAP A
REF
DAP A
REF
DAP B
REF
DAP B
REF
DAP B
REF
REF
Digital Audio Ports A and B, Wire Connections
Digital Audio Ports A and B (DAP A and DAP B) allow digital communication with the DVC over
the Digital Audio Loop (DAL); Amplifier programming from the DVC; control, audio, trouble,
address and firefighter telephone data; and live voice paging can be communicated through these
ports. They may also act as repeaters, in that what is received at one port is transmitted out the
other. Events generated at the DAA2 will be transmitted out both ports.
Figure 2.14 Wire the DAA2 Digital Audio Loop Connections
NOTE: Digital Audio Ports A and B must be wired in Style 4 or Style 7 configuration. Do not wire
them in bus configuration.
NOTE: Style 4 configuration must be installed in accordance with the requirements for
survivability from attack by fire in the National Fire Alarm Code, NFPA 72.
Digital Audio Ports A and B, Fiber and Wire/Fiber Connections
DAA2 boards are wire, but may be converted partially or fully to fiber boards with the use of fiber
option modules DS-FM and DS-SFM. (Refer to Section 5.3.1, “DAA2 Installation”, on page 77 for
information on installing fiber option modules.) The fiber, or wire/fiber cabling between these ports
provides a Digital Audio Loop (DAL) for programming; alarm, control, trouble, automatic audio
messages, address and firefighter telephone data; and live voice paging communications.
Figure 2.15 illustrates an example of how a DAL can be formed using mixed wire and fiber
connectors.
DAA2 & DAX — P/N 53265:A1 8/24/2011 29
DAA2 Digital Audio AmplifiersDAA2 Installation
DAAmixedDALa.wmf
Optional Style
7 return
DAA2
w/ one wire port and one
multi-mode port.
Consult manufacturer’s
guidelines for minimum
radius of bend for fiber
optic media.
DAA2
w/ two multi-mode ports.
Connections are port
sensitive. Always
connect Port A to Port B.
Wire connections are
polarity sensitive.
DAA2
w/ one multi-mode port
and one single-mode port.
DAA2
w/ one wire port and one
single-mode port.
DVC
DS-FM at
DAP A
DS-SFM
at DAP B
DS-SFM
at DAP A
DS-FM at
DAP B
DS-FM at
DAP A
DS-FM at
DAP B
A DS-RFM fiber module must be used to connect a DAA2 to a multi-mode fiber DVC or DAA.
Refer to “Fiber Option Modules” on page 75 for more information on this module.
NOTE: If a fiber option module is installed at a DAP, that DAP may not also be used for a wire
connection.
30DAA2 & DAX — P/N 53265:A1 8/24/2011
Figure 2.15 Fiber/Wire DAL Configuration
NOTE: Style 4 configuration must be installed in accordance with the requirements for
survivability from attack by fire in the National Fire Alarm Code, NFPA 72.
FFT Riser Connections
The Firefighter Telephone Riser connections (TB7) provide for the use of firefighter telephones
(FFTs) on an analog network. They are a means of connecting various FFT telephone control
modules and devices, such as FTM-1 modules, AFAWS, FPJ or RPJ-1 telephone circuits to the
DAA2.
The FFT riser may be wired in NFPA Class A or Class B configuration. For trouble supervision,
VeriFire Tools must be used to indicate whether a riser is installed or not. SW1 must be set to
indicated whether the wiring is Class A or Class B. (Refer to page 41 for switch settings.) Class B
2-Wire configurations require a 3.9K ohm 1/2 watt end-of-line resistor (P/N R-3.9K). Class A 4wire configurations have an internal ELR and do not require an external ELR
There are two ways that firefighter telephones may be installed on a DAA2 FFT riser. Both
configurations have a limit of seven active phones. (Refer to the FFT appendix in the DVC Digital
Voice Command manual for more information on limits.)
1.“Install FTM” selected - FireFighter Telephones must be wired to the output of the FTM
modules. The telephone points will be SLC addresses.
Loading...
+ 98 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.