Notifier DAX, DAA2 User Manual

DAA2 and DAX
Amplifiers
Manual
for the DVC Digital Voice
Document 53265 8/24/2011 Rev:
P/N 53265:A1 ECN 10-680
A1
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system—typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control panel with remote notification capability—can provide early warning of a develop­ing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detec­tors be located throughout a protected premise following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommen­dations contained in the Guides for Proper Use of System Smoke Detectors, which are made available at no charge to all installing dealers. These documents can be found at http:// www.systemsensor.com/html/applicat.html. A study by the Federal Emergency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a first­floor or basement fire.
Particles of combustion or “smoke” from a developing fire may not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow.
• Smoke particles may become “cold,” stratify, and not reach the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air outlets.
• Smoke particles may be drawn into air returns before reaching the detector.
The amount of “smoke” present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ion­izing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of flammable materials, etc.).
Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predeter­mined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire pro­tection specialist. Heat detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the sys­tem for the connection of alarm transmission wiring, communi­cations, signaling, and/or power. If detectors are not so located, a developing fire may damage the alarm system, crip­pling its ability to report a fire.
Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol or medica­tion. Please note that:
• Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property owner's responsi­bility to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.
Equipment used in the system may not be technically com­patible with the control panel. It is essential to use only equip­ment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against tele­phone line failure, backup radio transmission systems are rec­ommended.
The most common cause of fire alarm malfunction is inade­quate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA stan­dards. At a minimum, the requirements of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent maintenance. A main­tenance agreement should be arranged through the local man­ufacturer's representative. Maintenance should be scheduled monthly or as required by National and/or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records of all inspections should be kept.
Limit-C1-2-2007
2 DAA2 & DAX — P/N 53265:A1 8/24/2011
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associ­ated equipment may be damaged by removing and/or insert­ing cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood.
CAUTION - System Re-acceptance Test after Software Changes: To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any pro­gramming operation or change in site-specific software. Re­acceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All compo­nents, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49º C/32-120º F and at a relative humidity 93% ± 2% RH (non­condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic com­ponents may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27º C/60-80º F.
Verify that wire sizes are adequate for all initiating and indi­cating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to light­ning induced transients. Although no system is completely immune from lightning transients and interference, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Ser­vices Department if any problems are anticipated or encoun­tered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifi­cations, verify that they will not interfere with battery, trans­former, or printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over­tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
This system contains static-sensitive components. Always ground yourself with a proper wrist strap before han­dling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and pro­gramming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation.
Precau-D1-9-2005
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing devices pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when devices are operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interfer­ence, in which case the user will be required to correct the interference at his or her own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Cana­dian Department of Communications.
Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.
HARSH™, NIS™, and NOTI•FIRE•NET™ are all trademarks; and Acclimate® Plus, FlashScan®, NION®, NOTIFIER®, ONYX®, ONYXWorks®, UniNet®, VeriFir e®, and VIEW® are all registered trademarks of Honeywell International Inc.HARSH™, NIS™, and NOTI•FIRE•NET™ are all trademarks; and Acclimate® Plus, FlashScan®, NION®, NOTIFIER®, ONYX®, ONYXWorks®, UniNet®, Veri Fire®, and VIEW® are all registered trademarks of Honeywell
International Inc. Echelon® is a registered trademark and LonWorks™ is a trademark of Echelon Corporation. ARCNET® is a registered trademark of Datapoint Corporation. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation.
©2011 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
DAA2 & DAX — P/N 53265:A1 8/24/2011 3
Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly recommend that you download the most current version of software for each product prior to commissioning any system. Contact Technical Support with any questions about software and the appropriate version for a specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online Help or printed manuals, you can email us.
Please include the following information:
•Product name and version number (if applicable)
•Printed manual or online Help
•Topic Title (for online Help)
•Page number (for printed manual)
•Brief description of content you think should be improved or corrected
•Your suggestion for how to correct/improve documentation
Send email messages to:
FireSystems.TechPubs@honeywell.com
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services.
4 DAA2 & DAX — P/N 53265:A1 8/24/2011
Table of Contents
Table of Contents
Section 1: General Information................................................................................................9
1.1: Overview........................................................................................................................................................9
1.2: Standards and Other Documents....................................................................................................................9
1.3: Supplemental Documentation......................................................................................................................10
1.4: Cautions and Warnings ................................................................................................................................10
Section 2: DAA2 Digital Audio Amplifiers ............................................................................13
2.1: Description...................................................................................................................................................13
2.1.1: Features..............................................................................................................................................13
2.1.2: Specifications.....................................................................................................................................14
CPS-24 Power Supply Board ...............................................................................................................14
DAA2-5025/70 and DAA2-7525 Boards .............................................................................................15
2.1.3: DAA2 Layout ....................................................................................................................................17
Connection Locations...........................................................................................................................17
Indicators ..............................................................................................................................................20
Switches................................................................................................................................................21
2.2: DAA2 Installation........................................................................................................................................21
2.2.1: Cabinet...............................................................................................................................................21
EQ Series Cabinets and Doors .............................................................................................................22
CAB-4 Series........................................................................................................................................24
2.2.2: Batteries .............................................................................................................................................24
CHS-BH1 Battery Chassis ...................................................................................................................25
Within the CAB-4 Enclosure................................................................................................................25
Outside the DAA2 Enclosure ...............................................................................................................25
2.2.3: Wiring................................................................................................................................................25
AC Power .............................................................................................................................................25
Batteries................................................................................................................................................26
Alarm Bus.............................................................................................................................................28
Digital Audio Ports A and B, Wire Connections .................................................................................29
Digital Audio Ports A and B, Fiber and Wire/Fiber Connections........................................................29
FFT Riser Connections.........................................................................................................................30
RM-1 Remote Microphone Interface ...................................................................................................32
Auxiliary Input A .................................................................................................................................32
Speaker Circuits....................................................................................................................................33
UL Power-limited Wiring Requirements .............................................................................................40
2.3: DAA2 Configuration ...................................................................................................................................41
2.3.1: Setting the Configuration Switches ...................................................................................................41
GND Fault Switch - SW1 on CPS-24 ..................................................................................................41
2WIRE/4WIRE Switch - SW1 on DAA2 Board..................................................................................41
Address Switches - SW2, SW3 ............................................................................................................41
PRIMARY AMP Switch - SW4...........................................................................................................42
2.3.2: Programming .....................................................................................................................................42
2.4: DAA2 Operation..........................................................................................................................................42
2.4.1: Sig Sil Control ...................................................................................................................................42
2.4.2: Volume Control - Master and Auxiliary............................................................................................42
2.4.3: FFT Communication .........................................................................................................................42
2.4.4: Trouble Messages..............................................................................................................................42
2.4.5: Read/Alter Status...............................................................................................................................42
Section 3: DAX Digital Audio Amplifiers ..............................................................................43
3.1: DAX Overview............................................................................................................................................43
3.1.1: Description.........................................................................................................................................43
3.1.2: Features..............................................................................................................................................43
3.1.3: Specifications.....................................................................................................................................44
AC Power - TB7...................................................................................................................................44
DAA2 & DAX — P/N 53265:A1 8/24/2011 5
Table of Contents
Battery Connections - TB8, TB9..........................................................................................................44
Battery Charger (DAX-35 Boards Only)..............................................................................................44
Wire Digital Audio Ports A and B - TB1, TB2 ....................................................................................44
Alarm Bus - TB3 ..................................................................................................................................44
Speaker Circuits - TB4 and TB5 ..........................................................................................................45
Backup from Alternate Amplifier - TB10 and TB11 ...........................................................................45
3.1.4: DAX Board Layouts ..........................................................................................................................46
Connection Locations ...........................................................................................................................46
DAX Indicators, Switches, and Jumper................................................................................................47
Switches and Jumper ............................................................................................................................48
3.2: DAX Installation..........................................................................................................................................48
3.2.1: Cabinet...............................................................................................................................................48
EQ Series Cabinets and Doors..............................................................................................................49
CAB-4 Series........................................................................................................................................51
3.2.2: Batteries .............................................................................................................................................51
Within the CAB-4 Enclosure................................................................................................................52
Outside the DAX Enclosure .................................................................................................................52
3.2.3: Wiring ................................................................................................................................................52
AC Power..............................................................................................................................................52
Batteries ................................................................................................................................................52
Alarm Bus.............................................................................................................................................55
Digital Audio Ports A and B.................................................................................................................55
Speaker and Backup Circuits................................................................................................................57
UL Power-limited Wiring Requirements..............................................................................................64
3.3: DAX Configuration .....................................................................................................................................65
3.3.1: Setting the Configuration Switches ...................................................................................................65
EARTH FAULT (Switch 5) - DAX-35 Only.......................................................................................65
Address Switches..................................................................................................................................65
3.3.2: Programming .....................................................................................................................................65
3.4: DAX Operation............................................................................................................................................65
3.4.1: Volume ..............................................................................................................................................65
3.4.2: Trouble Messages ..............................................................................................................................65
3.4.3: Read/Alter Status ...............................................................................................................................66
Section 4: BDA Backup Digital Amplifiers ...........................................................................67
4.1: Features ........................................................................................................................................................67
4.2: Specifications...............................................................................................................................................67
4.2.1: When Used with DAA2-75 ...............................................................................................................67
4.2.2: When Used with DAA2-50 ...............................................................................................................67
4.2.3: When Used with DAX-50 .................................................................................................................68
4.2.4: When Used with DAX-35 .................................................................................................................68
4.3: Board Layout ...............................................................................................................................................68
4.4: Installation....................................................................................................................................................69
4.4.1: DAA2.................................................................................................................................................69
4.4.2: DAX...................................................................................................................................................70
4.4.3: BDA Power and Control Cables........................................................................................................70
4.5: Configuration ...............................................................................................................................................71
4.5.1: Wattage Switches, SW5 - SW7 .........................................................................................................71
4.5.2: FAIL TEST Switch, SW4..................................................................................................................71
4.5.3: DAA2-50 Configurations with BDA.................................................................................................72
DAA2-75 Configurations with BDA....................................................................................................73
4.5.4: Operation ...........................................................................................................................................74
Volume .................................................................................................................................................74
Section 5: Fiber Option Modules........................................................................................... 75
5.1: Specifications...............................................................................................................................................75
5.2: Layout ..........................................................................................................................................................76
5.3: Installation....................................................................................................................................................77
6 DAA2 & DAX — P/N 53265:A1 8/24/2011
Table of Contents
5.3.1: DAA2 Installation..............................................................................................................................77
5.3.2: DAX Installation................................................................................................................................77
5.3.3: Single- or Multi-mode DVC (DVC-PCB or less) or DAA Installation ............................................78
Single-mode..........................................................................................................................................78
Multi-mode...........................................................................................................................................78
Appendix A: AC Current Draw Calculations ........................................................................79
A.1: DAA2 Current Draw Calculations..............................................................................................................79
A.1.1: Worksheet Procedures ......................................................................................................................79
A.1.2: Worksheets .......................................................................................................................................79
A.2: DAX Current Draw Calculations................................................................................................................82
A.2.1: Worksheet Procedures ......................................................................................................................82
A.2.2: Worksheets .......................................................................................................................................82
Appendix B: Battery Calculations.........................................................................................84
B.1: DAA2 Battery Calculations ......................................................................................................................84
B.2: DAX Battery Calculations ..........................................................................................................................86
Appendix C: DAA Digital Audio Amplifiers .......................................................................... 89
C.1: Overview.....................................................................................................................................................89
C.1.1: Description........................................................................................................................................89
C.1.2: Features .............................................................................................................................................90
C.1.3: Specifications....................................................................................................................................91
DAA-PS Power Supply Board .............................................................................................................91
DAA-5025/70 and DAA-7525 Boards .................................................................................................91
C.1.4: DAA Board Layouts .........................................................................................................................94
Wire Versions.......................................................................................................................................94
Fiber Versions ......................................................................................................................................96
Indicators ..............................................................................................................................................97
Switches and Jumper ............................................................................................................................99
C.2: Installation...................................................................................................................................................99
C.2.1: Cabinet ..............................................................................................................................................99
CAB-3 Cabinets..................................................................................................................................100
CAB-4 Series......................................................................................................................................101
EQCAB Series Cabinets.....................................................................................................................101
C.2.2: Batteries ..........................................................................................................................................102
In a CHS-BH1 Battery Chassis ..........................................................................................................103
Within the CAB-4 Enclosure..............................................................................................................103
Outside the DAA Enclosure ...............................................................................................................103
C.2.3: Wiring .............................................................................................................................................103
Connecting the DAA Power Supply to AC Power.............................................................................103
Connecting the DAA Power Supply to the Batteries .........................................................................104
Connecting the Alarm and Trouble Buses..........................................................................................107
Digital Audio Ports A and B on Wire Version Boards ......................................................................109
RXA, RXB, TXA, TXB Fiber Version Board Connections ..............................................................109
FFT Riser Connections.......................................................................................................................110
Auxiliary Inputs A and B ...................................................................................................................111
Speaker and Backup Circuits..............................................................................................................112
In Riser Mode to CIM/CSM Series Canadian Room Isolator Modules.............................................116
UL Power-limited Wiring Requirements ...........................................................................................119
C.3: Configuration ............................................................................................................................................120
C.3.1: Setting the Configuration Switches ................................................................................................120
EFA and EFB (Switches 9 and 10).....................................................................................................120
4WIRE (Switch 11) ............................................................................................................................120
Address Switches................................................................................................................................121
Volume Control..................................................................................................................................121
C.4: Programming.............................................................................................................................................121
DAA2 & DAX — P/N 53265:A1 8/24/2011 7
Table of Contents
C.5: Operation...................................................................................................................................................121
C.5.1: Pushbutton Controls........................................................................................................................121
C.5.2: Volume Control...............................................................................................................................122
C.5.3: Read/Alter Status ............................................................................................................................122
C.5.4: FFT Communication .......................................................................................................................122
C.5.5: Trouble Messages ...........................................................................................................................122
C.6: Battery Calculations ..................................................................................................................................122
Index ......................................................................................................................................124
8 DAA2 & DAX — P/N 53265:A1 8/24/2011
1.1 Overview
DVC
DAA2
DAX
DAA
DAX
DAA2
DAL Address 1
DAL Address 5
DAL Address 3
DAL Address 2
DAL Address 32
Optional return
Connections between any two DAL devices may be either wire or fiber. A
DAL does not need to be all wire or all fiber, but can be a mix of both.
This manual describes the DAA2 and DAX digital audio amplifiers, which may be used as devices on a digital audio loop (DAL). It also describes compatible backup amplifiers and fiber option conversion modules. They include:
• DAA2 and DAX digital audio amplifiers, which connect directly to the DAL. These boards
• BDA backup digital amplifiers, which connect to DAA2 and DAX amplifiers for backup.
• Fiber option modules, which convert DAA2 and DAX boards from wire to fiber, as well as
All wire and fiber models of the DVC, DAA2, DAX and DAA are compatible together on a DAL.
Section 1: General Information
each occupy one of the 32 addresses on the DAL.
Alternately, when used with a DAA2 series amplifier, a BDA can be added to support a second audio channel.
provide compatibility with fiber DVCs and DAAs.
Figure 1.1 DAL (Digital Audio Loop) Block Diagram
Digital audio amplifiers are backed up by BDAs, or by another amplifier of the same digital type: that is, a DAA2 must be backed up by a BDA or another DAA2, a DAX must be backed up a BDA or another DAX, etc.
DAA-PCA and -PCB boards are described in Appendix C of this manual.
1.2 Standards and Other Documents
The Digital Series products in this manual comply with the following standards:
NFPA 72 2007 National Fire Alarm Code
Underwriter Laboratories Standard UL 864
Underwriter Laboratories of Canada (ULC) ULC-S527-99 Standard of Control Units for Fire Alarm Systems
Part 15 Class A conducted and radiated emissions as required by the FCC
The installer should be familiar with the following documents and standards:
NFPA Standards
NFPA 72 National Fire Alarm Code
Underwriter Laboratories
UL 464 Audible Signaling Appliances UL 864 Standard for Control Unit and Accessories for Fire Alarm Systems UL 1481 Power Supplies for Fire Protective Signaling Systems UL 1638 Visual Signaling Appliances - Private-Mode Emergency and General Utility Signaling
DAA2 & DAX — P/N 53265:A1 8/24/2011 9
General Information Supplemental Documentation
!
UL 1711 Amplifiers for Fire Protective Signaling Systems UL 60950 Safety of Information Technology Equipment UL 1971 Signaling Devices for the Hearing Impaired
Underwriters Laboratories of Canada (ULC)
ULC-S527-99 Standard of Control Units for Fire Alarm Systems
Other
FCC Part 15 Class A Conducted and Radiated Emissions
1.3 Supplemental Documentation
The table below provides a list of documents referenced in this manual, as well as documents for other compatible devices.
VeriFire Tools CD help file and CD pamphlet VERIFIRE-TCD, 51690
DVC Digital Voice Command Manual 52411
Wire Guide Addendum for Digital Audio Loops 52916ADD
DVC-AO Audio Option Board Installation Document 52728
Heat Dissipation for Cabinets with Digital Audio Products 53645
NFS2-3030 Installation, Programming and Operations Manuals 52544, 52545, 52546
NFS2-640 Installation, Programming and Operations Manuals 52741, 52742, 52743
AMPS-24 Manual 51907
ACPS-610 Addressable Power Supply Manual 53018
NCA-2 Network Control Annunciator Manual 52482
ONYXWorksI Workstation Manual 52342
DAL Devices Product Information Sheet 52410
AA Series Audio Amplifier Manual 52526
ACS Annunciator Manual 15842
AFAWS Automatic Fire Alarm Warden Station 50705
CFFT-1 Chassis for FireFighter Telephone Product Information Document 53289
FTM-1 Firephone Control Module 156-1391-02
ACT-4 Audio Coupling Transformer 53431
ACT-25 Audio Coupling Transformer 53432
ACT-70 Audio Coupling Transformer 53240
RM-1 Series Remote Microphones 51138
CAB-4 Series Cabinets Installation Instructions 15330
EQ-CAB Series Installation Instructions 53412
RSM-1A Residential Silence Module I56-006-000
AIM-1A Audible Isolation Module I56-006-002
CIM-2A/CSM-1A Isolator and Silencing Modules I56-2200-002
RPJ-1 Remote Paging Jack 15058
FPJ Firefighter Phone Jack 15510
Related Documentation Table
1.4 Cautions and Warnings
This manual contains cautions and warnings to alert the reader as follows:
CAUTION:
INFORMATION ABOUT PROCEDURES THAT COULD CAUSE PROGRAMMING ERRORS, RUNTIME ERRORS, OR EQUIPMENT DAMAGE.
10 DAA2 & DAX — P/N 53265:A1 8/24/2011
Cautions and Warnings General Information
!
WARNING:
INDICATES INFORMATION ABOUT PROCEDURES THAT COULD CAUSE IRREVERSIBLE DAMAGE TO THE CONTROL PANEL, IRREVERSIBLE LOSS OF PROGRAMMING DATA, OR PERSONAL INJURY.
DAA2 & DAX — P/N 53265:A1 8/24/2011 11
Notes
12 DAA2 & DAX — P/N 53265:A1 8/24/2011
Section 2: DAA2 Digital Audio Amplifiers
2.1 Description
The DAA2 Digital Audio Amplifiers are multi-featured amplifiers with digital audio functionality. They are designed to work with the DVC Digital Voice Command.
NOTE: The term DAA2 is used in this manual to refer to all the model versions listed in Table 2.1. Individual part numbers are used to distinguish features or functions that differ.
50 Watt DAA2s
DAA2-5025 (120 VAC) 25
DAA2-5025E (220 - 240 VAC) 25
DAA2-5070 (120 VAC) 70
DAA2-5070E (220 - 240 VAC) 70
75 Watt DAA2s
DAA2-7525 (120 VAC) 25
DAA2-7525E (220 - 240 VAC) 25
NOTE: All boards are wire. They may be converted to fiber by using a fiber option module.
Speaker
Circuit Output
RMS
RMS
RMS
RMS
RMS
RMS
Table 2.1 Digital Audio Amplifier Models
NOTE: The term DVC is used in this manual to refer to all DVC wire and fiber model versions.
Individual part numbers are used in this manual only to distinguish features or functions that differ. Available models are described in the DVC Digital Voice Command manual.
Refer to Figure 1.1 on page 9 for a simplified illustration of DAL devices on a digital audio loop.
NOTE:
Speaker placement must be given careful consideration when planning an audio system.
• Place speakers from different DALs (Digital Audio Loops) so they are not within the audible
areas of other DALs.
• Carefully consider the audible distance of speakers within a DAL; overlapping audio messages
can be confusing.
2.1.1 Features
The DAA2 audio amplifiers have the following features:
50W total output power at 25V DAA2-5070 model versions).
75W total output power at 25V
Two Class A connections for high-level audio output, or alternately, four Class B connections.
Audio output activation via network control-by-event equations resident within the DVC.
Isolated alarm bus input, to be used for backup activation of alarm messages when normal digital communication is lost.
DAA2 & DAX — P/N 53265:A1 8/24/2011 13
(all DAA2-5025 model versions) or 70 V
RMS
(all DAA2-7525 model versions).
RMS
RMS
(all
DAA2 Digital Audio Amplifiers Description
Amplifies one channel of digital audio (two channels using the BDA card as a second channel) and distributes it on up to four outputs.
Remote microphone paging option with RM-1.
FireFighter telephone (FFT) riser.
Auxiliary input for 1V
, to be used for background music input, an interface with a
RMS
telephone paging source, or other compatible audio sources. Includes user audio level adjustment feature.
Uploads and downloads via the DVC. Programmable through VeriFire Tools.
•Up to 106 seconds of Backup Digital message storage (Emergency tone, Non-Emergency tone, and FFT busy tone) for use in the event of communication loss- either standard quality or high quality, from the VeriFire Tools message library or created by the installer.
Disconnect of deeply-discharged battery (low battery disconnect).
Backup amplifier options.
Meets UL THD Distortion requirements for 500 Hz to 4 KHz bandwidth. Meets ULC THD Distortion requirements for 400 Hz to 4 KHz bandwidth.
2.1.2 Specifications
CPS-24 Power Supply Board
AC Power - TB1
120 VAC 60 Hz input*
220-240 VAC 50/60 Hz input (“E” versions)*
*Maximum AC draw varies by DAA2 model. These draws are given in Appendix A, “AC
Current Draw Calculations”, along with a worksheet to determine the actual AC draw.
Recommended 12-14 AWG (1.6 mm O.D.) with 600 VAC insulation.
Fuse: 8 amps, 250V, 5 x 20 mm, Fast-Acting, ceramic. Notifier p/n 12117.
Secondary Power 5V and 24V AUX Outputs - TB2
24V AUX:
Power-limited: 24V @ 0.5A
Utilizes wire sizes 12-18 AWG (3.31 mm
2
- 2.08 mm2)
5V: Future Use
Battery Connections - TB3
Supplied cable connections to batteries for CAB-4 and CHS-BH1. For battery sharing, use 12 AWG either in the same cabinet or in conduit for no more than 20 ft (6.09 m).
Battery Charger
Current-limited sealed lead acid battery charger which charges two 12 volt batteries in series, up to 200AH. Table 2.2 gives battery-charging capabilities for the DAA2 boards. The charger enable/disable option is available for all DAA2 models.
Charge Batteries Less Than 26AH
DAA2-5025 DAA2-5070
DAA2-7525 Yes Yes No
Yes Yes
Charge 26AH to < 50AH Batteries
Yes Yes
Charge 50AH to 200AH Batteries
Yes Yes
Table 2.2 Battery Charging Capabilities
14 DAA2 & DAX — P/N 53265:A1 8/24/2011
Description DAA2 Digital Audio Amplifiers
Charge Batteries Less Than 26AH
DAA2-5025 w/ BDA in Group 2 of VeriFire Tools programming* DAA2-5070 w/ BDA in Group 2 of VeriFire Tools programming*
* Refer to “DAA2-50 Configurations with BDA” on page 72 for further explanation.
No
No
Charge 26AH to < 50AH Batteries
No
No
Charge 50AH to 200AH Batteries
No
No
Table 2.2 Battery Charging Capabilities
Charger voltage: 27.6 VDC.
For battery calculation worksheet and standby operating times, refer to Appendix B.1, “DAA2 Battery Calculations”, on page 84.
Utilizes wire sizes 12-18 AWG..
NOTE: A 50 watt DAA2 with 2 groups will have its charger disabled automatically. Groups are explained in the Audio Groups appendix of the DVC Digital Voice Command manual.
When AC power is lost, the deeply-discharged battery cutoff protection will be invoked at 17 volts. The power supply will be disconnected from the batteries. The power supply’s normal operation will be restored when AC power returns.
DAA2-5025/70 and DAA2-7525 Boards
Wire Digital Audio Ports A and B - TB2, TB3
Refer to the Wiring Guide, p/n 52916ADD, for acceptable wire types.
EIA-485 format.
Power-limited and supervised.
Refer to Section 5, “Fiber Option Modules”, on page 75 for fiber connection information. When a fiber option module is mounted on a DAA2, it disables the corresponding wire terminals. TB2 (Digital Audio Port A) is disabled when a fiber option board is connected at J9. TB3 (Digital Audio Port B) is disabled when a fiber option board is connected at J10.
Alarm Bus - TB4
Power-limited and supervised by source.
Recommended wiring: 14-18 AWG twisted-pair.
Requires 16VDC minimum @ 20mA across the terminals to activate. Nominal 24 VDC.
Remote Microphone Interface - TB5
RMI Power - +24VDC, power-limited @ 100mA.
Recommended wiring: 14-18 AWG twisted-pair, Max. 14 AWG.
Nominal AC signal strength 2.5V
RMS
, 3V
RMS
Max.
Power-limited.
Supervised.
Max. distance between remote microphone and DAA2: 1000 ft (304.8 m).
FFT Riser - TB7
Power-limited output.
Supervised.
Class A or Class B operation.
Class B 2-wire connections require a 3.9k ohm 1/2 watt resistor (P/N R-3.9K).
Max. wiring resistance (including individual telephone zone to last handset) permitted is 50 ohms, 10,000 ft (3048 m) max. wiring distance at 14 AWG to last handset.
DAA2 & DAX — P/N 53265:A1 8/24/2011 15
DAA2 Digital Audio Amplifiers Description
Auxiliary Input A (AUX A) - TB 9
Signal strength from low-level analog audio input (such as background music or telephone paging): 1V
max. Optional supervision through programming.
p-p
Recommended wiring: 14-18 AWG, twisted-pair.
Supervision programmable.
Auxiliary input source must be within 20 ft. ( 6.1 m) of the DAA2, and within the same room.
Speaker Circuits - TB10, TB11, TB12 and TB13
Power-limited outputs.*
* Exception: A DAA2-5070 speaker circuit used with any Canadian Room Isolator
module is non-power-limited. Speaker circuit 1 (TB10) can not be used.
DAA2-5025/70 - Each circuit rated up to 50 watts.**
DAA2-7525 - Each circuit rated up to 75 watts.**
**Total wattage may vary. Refer to “BDA Backup Digital Amplifiers” on page 67 for
configurations.
Supervision determined by programming.
25V
- DAA2-5025/DAA2-7525 speaker circuits, 70V
RMS
- DAA2-5070 speaker circuits.
RMS
Recommended wiring: 12-18 AWG twisted-pair (shielded recommended).
Class B or Class A:
Class B requires 20k end-of-line resistors (included, P/N ELR-20K).
Class A requires 10k end-of-line resistors (included, P/N R-10K) on the return.
Backup - BKUP1 (TB14), BKUP2 (TB15), BKUP3 (TB16), BKUP4 (TB17)
High-level audio input.
• 25V
• 70V
(DAA2-5025 and DAA2-7525).
RMS
(DAA2-5070).
RMS
Recommended wiring: 14-18 AWG twisted-pair (shielded recommended).
Supervision:
•Not supervised when inactive. Supervised by backup source when active.
•Must be in the same room or enclosure.
16 DAA2 & DAX — P/N 53265:A1 8/24/2011
Description DAA2 Digital Audio Amplifiers
OUT 4 + OUT 4 ­SHIELD
+
­SHIELD
+
­SHIELD
SHIELD
+
­SHIELD
SHIELD
OUT1 -
+
-
SHIELD
-
+
OUT1 +
SHIELD
OUT3 + OUT3 -
BDA Power J6
BDA Control J5
OUT 3 TB12 See p.33
BKUP3 TB16 See p.37
OUT 4 TB13 See p.33
BKUP4 TB17 See p.37
OUT 1 TB10 See p.33
SHIELD
-
+
BKUP1
TB14
See p.37
OUT 2 TB11 See p.33
SHIELD
OUT2 -
OUT2 +
DAPA +
DAPA -
DAPA REF
TB2 - Digital Audio Port A
Refer to page 29
DAPB +
DAPB -
DAPB REF
TB3 - Digital
Audio Port B
Refer to page 29
FFT OUT RISER (+)
FFT OUT RISER (-)
FFT OUT SHIELD
FFT RTN (+)
FFT RTN (-)
FFT RTN SHIELD
FFT Riser
- TB7 Refer to page 30
AUXA R +
AUXA R -
AUXA L +
AUXA L -
AUXA - TB9
Refer to
page 32
RM1 AUDIO SHLD
RM1 - TB5
See page 32
RM1 AUDIO -
RM1 AUDIO +
RM1 PWR SHLD
RM1 PWR -
RM1 PWR +
ALM IN
ALM OUT
REF
REF
TB4 - Alarm
See page 28
USB Connector J2
Future Use
SHIELD
-
+
SHIELD
-
+
BKUP2
TB15
See p.37
Top of Board
Bottom of Board
Dotted line indicates position of the DAA2’s CPS-24 Power Supply Board
Fiber option module mounting holes. Refer to Figure 5.2, “DAA2 Fiber Option Module Installation” on page 77
J9
J10
See p.70
See p.70
2.1.3 DAA2 Layout
Connection Locations
A DAA2 is comprised of two boards; a larger rear board, and a smaller front power supply board. Figures 2.1 and 2.2 below show the layout.
Figure 2.1 DAA2 Rear Board
DAA2 & DAX — P/N 53265:A1 8/24/2011 17
DAA2 Digital Audio Amplifiers Description
BAT +
BAT -
TB3 - Battery
Connections
+24V AUX
COM
COM - Future Use
+5V AUX - Future Use
HOT NEU
EARTH
GROUND
TB1 AC INPUT Refer to page 25
CPS-24 Power Supply Board
DAA2PCA brd.wmf
CPS24-bboard.wmf
TB2
AC Fuse F4
Figure 2.2 DAA2’s CPS-24 Power Supply Board
18 DAA2 & DAX — P/N 53265:A1 8/24/2011
Description DAA2 Digital Audio Amplifiers
LED Indicators. Refer to Table 2.3 on page 20
DAP A TX:
LED 19
DAP A RX:
LED 20
DAP B TX:
LED 21
DAP B RX:
LED 22
AL BUS: LED 10
AMP FAIL: LED 4
AUDIO: LED 13
STATUS: LED 25
TRBL: LED 9 SIG SIL: LED 24 AUX: LED 11
FFT: LED 12 RST: LED 23 USB: LED 18
ON1: LED 8
TRBL1: LED 14
SW3:
ONES
SW2:
TENS
SW5:
SIG SIL
2 WIRE/4 WIRE: SW1
ON2: LED7
TRBL2: LED 15
ON3: LED 6 TRBL3: LED 16
ON4: LED 5 TRBL4:
LED17
DA2APCA brd.wmf
CPS24-bboard.wmf
+24V AUX: LED 5
+5V AUX: LED 6
LOGIC POWER: LED 1
TROUBLE: LED 2
EARTH FAULT: LED 3
AC: LED 4
GND FAULT: SW1
BACKUP FAIL: LED 26 RM-1: LED 1
Dotted line indicates position of the DAA2’s CPS-24 Power Supply Board
PRIMARY AMP: SW4
Indicator, Jumper and Switch Locations
Switches and LED indicator locations are illustrated in Figure 2.3.
DAA2 & DAX — P/N 53265:A1 8/24/2011 19
Figure 2.3 LED Indicator, Jumper and Switch Locations
DAA2 Digital Audio Amplifiers Description
Indicators
Diagnostic colored LEDs indicate various conditions and troubles. Table 2.3 lists and describes each.
DAA2 Board
LED Name Color Description LED #
RM-1 Green Illuminates steadily while the RM-1 has a channel. 1
AMP FAIL Yellow Illuminates steadily while audio amplifier failure detected. 4
ON 4 Green Illuminates steadily while analog signal is on speaker circuit 4, or while 200Hz tone is on speaker
circuit 4.
ON 3 Green Illuminates steadily while analog signal is on speaker circuit 3, or while 200Hz tone is on speaker
circuit 3.
ON 2 Green Illuminates steadily while analog signal is on speaker circuit 2, or while 200Hz tone is on speaker
ON 1 Green Illuminates steadily while analog signal is on speaker circuit 1, or while 200Hz tone is on speaker
TRBL Yellow Blinks when there is an unacknowledged trouble, illuminates steadily when a trouble is
AL BUS Red Illuminates steadily while alarm bus input is active. 10
AUX Green Illuminates while audio detected on AUX IN A. 11
FFT Green Illuminates steadily when the FFT has been granted a digital phone channel. Flashes when an
AUDIO Green OFF - No audio signal is present.
TRBL 1 Yellow Illuminates steadily while a short is detected on speaker circuit 1. Blinks slowly (once a second)
TRBL 2 Yellow Illuminates steadily while a short is detected on speaker circuit 2. Blinks slowly (once a second)
TRBL 3 Yellow Illuminates steadily while a short is detected on speaker circuit 3. Blinks slowly (once a second)
TRBL 4 Yellow Illuminates steadily while a short is detected on speaker circuit 4.Blinks slowly (once a second)
USB Green Illuminated while communication is established on the USB port. Future Use. 18
DAP A TX Green Illuminates while data transmitted on Digital Audio Port A (wire only). Light will flicker, turning on
DAP A RX Green Illuminates while data received on Digital Audio Port A (wire only). Light will flicker, turning on
DAP B TX Green Illuminates while data transmitted on Digital Audio Port B (wire only). Light will flicker, turning on
DAP B RX Green Illuminates while data received on Digital Audio Port B (wire only). Light will flicker, turning on
RST Yellow Illuminates when the board is not operational and maintenance is required. Call the factory. 23
SIG SIL Yellow Illuminates when the SIG SIL button is pressed to silence local speaker outputs 1 through 4. 24
STATUS Green Blinks slowly (once a second) under normal operation, Blinks fast (4 times a second) when the
BACKUP FAIL
Yellow Illuminates for diagnostics of the BDA amplifier. 26
circuit 2.
circuit 1.
acknowledged but unresolved.
FFT on a DAA2 requests a phone channel.
Fast blink (4 times a second) - The DAA2 is receiving audio from the DVC. Slow blink (once a second) - The DAA2 is playing audio from stored backup tones. Steady - The DAA2 is playing audio from its AUX input.
while an open is detected. Blinks fast (4 times a second) when this speaker circuit is disabled.
while an open is detected. Blinks fast (4 times a second) when this speaker circuit is disabled.
while an open is detected. Blinks fast (4 times a second) when this speaker circuit is disabled.
while an open is detected. Blinks fast (4 times a second) when this speaker circuit is disabled.
when activity is detected and off when it is not. Does not illuminate for fiber connections. Check the RX and TX LEDs on the fiber option module for activity indication.
when activity is detected and off when it is not. Check the RX and TX LEDs on the fiber option module for activity indication.
when activity is detected and off when it is not. Check the RX and TX LEDs on the fiber option module for activity indication.
when activity is detected and off when it is not. Check the RX and TX LEDs on the fiber option module for activity indication.
DAA2 is in bootload or diagnostic mode. Does not blink when the board is not operational or starting up. Call the factory if this LED is off for a prolonged period of time.
5
6
7
8
9
12
13
14
15
16
17
19
20
21
22
25
CPS-24 Power Supply Board
LED Name Color Description LED #
Table 2.3 DAA2 LED Indicators (1 of 2)
20 DAA2 & DAX — P/N 53265:A1 8/24/2011
DAA2 Installation DAA2 Digital Audio Amplifiers
DAA2 Board
LED Name Color Description LED #
LOGIC POWER
TRBL Yellow Software-controlled as follows:
EARTH FAULT
AC Green AC power is on. 4
+24V AUX Green Illuminated while +24V auxiliary power is on. 5
+5V AUX Green Future Use 6
Green +5V logic power is OK. 1
– OFF when the following system troubles are not present. – 1 blink - AC FAIL. Priority 1, highest priority. – 2 blinks - HIGH BATTERY. Priority 2. – 3 blinks - LOW BATTERY. Priority 3. – 4 blinks - CHARGER TROUBLE. Priority 4, lowest priority.
If multiple troubles are present, the highest priority trouble will blink until cleared, then the next priority trouble will blink until cleared, etc.
Yellow When earth fault switch SW1 is enabled:
• Illuminates while earth fault is detected anywhere on the DAA2 except DAP A.
• If batteries are shared, illuminates when an earth fault is detected on any non-isolated circuits in the sharing set.
2
3
Table 2.3 DAA2 LED Indicators (2 of 2)
Switches
The switches described in Table 2.4 are for configuring the DAA2.
DAA2 Board
Name Switch # Description Default
2 WIRE/4 WIRE SW1 Changes FFT Riser indication to 2- or 4-wire, depending on
whether the riser is wired Class B or Class A.
TENS SW2 BCD rotary address tens selection switch. Refer to page 41. 0
ONES SW3 BCD rotary address ones selection switch. Refer to page 41. 0
PRIMARY AMP SW4 ON is the normal state. OFF will induce an AMP FAIL trouble. Refer
to page 42.
SIG SIL SW5 Pushbutton to silence speaker circuits during communication loss
with DVC.
2-wire
ON
N/A
GND FAULT SW 1 Ground fault detection switch. When this switch is set to enable it
2.2 DAA2 Installation
2.2.1 Cabinet
The DAA2 arrives from the factory already installed on its chassis. A BDA-25/70V, NCM, or HS­NCM, can be mounted on it. (Refer to Figure 2.5). A CHS-BH1 Battery Chassis may be mounted to the left of the DAA2. The DAA2 chassis mounts in a CAB-4 Series cabinet, as well as in the EQCAB Series backboxes.
Prior to installation,
• Review the installation precautions at the front of this manual.
• Installers should be familiar with the standards and codes specified in “Standards and Other Documents” on page 9.
• Ensure all wiring will comply with national and local codes.
CPS-24 Power Supply Board
Enable will enable earth fault detection for Digital Audio Port A. Refer to page 41
Table 2.4 DAA2 Switches
DAA2 & DAX — P/N 53265:A1 8/24/2011 21
DAA2 Digital Audio Amplifiers DAA2 Installation
!
• Review the installation instructions in this section.
WARNING:
Wear a static discharge wrist strap to prevent equipment damage.
Locate the cabinet backbox on a surface that is in a clean, dry, vibration-free area. The top should be located so that all operational buttons, switches, displays, etc. are easily accessible and/or viewable to the operator - usually no more than 66 inches (1.7 m) above the floor. Allow sufficient clearance around the cabinet for the door to swing freely, and for easy installation and maintenance of equipment.
Follow the instructions below.
1. Mark and pre-drill two holes for the keyhole mounting bolts. Install bolts.
2. Select and punch open the appropriate cabinet knock-outs. (For selection guidelines, see “UL Power-limited Wiring Requirements” on page 40.)
3. Using the keyholes, mount the backbox on the two bolts.
4. Mark the location of the two lower holes, remove backbox and drill the mounting holes.
5. Mount the backbox over the top two screws, then install the remaining fasteners. Tighten all fasteners securely.
6. Feed wires through appropriate knockouts.
7. Install DAA2 according to the following instructions before installing the door per the CAB-4 Series Cabinet Installation Document.
The DAA2 fills one row of any EQ or CAB-4 series cabinet.
EQ Series Cabinets and Doors
The EQ Series cabinets come in B, C, and D sizes. The row spacing allows DAA2 amplifiers to be mounted in any row, and the doors are equipped with ventilated panels for heat dissipation. The cabinets were designed so that all DAA2 boards can be used in any or all cabinet rows. Batteries must be accommodated in separate cabinets or battery backboxes.
The following models are available:
• EQCAB-D4 - Four rows. Accommodates four DAA2s. Consists of P/Ns EQBB-D4 (black
backbox) and EQDR-D4 (black door with ventilated panels).
• EQCAB-C4 - Three rows. Accommodates three DAA2s. Consists of P/Ns EQBB-C4 (black
backbox) and EQDR-C4 (black door with ventilated panels).
• EQCAB-B4 - Two rows. Accommodates two DAA2s. Consists of P/Ns EQBB-B4 (black
backbox) and EQDR-B4 (black door with ventilated panels).
NOTE: Digital amplifiers can produce significant heat during their duty cycles. Different cabinets can handle different amounts of heat. Refer to the Heat Dissipation Calculation document (53645) to determine dissipation figures for the equipment you are installing, and match it with an appropriate cabinet.
22 DAA2 & DAX — P/N 53265:A1 8/24/2011
DAA2 Installation DAA2 Digital Audio Amplifiers
DAA2 Mounting Locations
CABDAA_D4.wmf
Figure 2.4 EQCAB-D4 Backbox and EQDR-D4 Door
DAA2 & DAX — P/N 53265:A1 8/24/2011 23
DAA2 Digital Audio Amplifiers DAA2 Installation
1. Place the DAA2 chassis over the chassis standoffs at the locations indicated. Secure with two 10/32 nuts.
DAA2mtgcab4.wmf
Using the hardware that comes with the DP-1B dress panel, attach it at the points indicated.
DP-1B
DP-1B.wmf
Optional BDA-25/70V or Network Control Module (wire or fiber NCM or HS-NCM) Mounting:
1. Fasten four 2 3/8” steel 4-40 male/female standoffs ( P/N 42227, included with the DAA2) at the bottom of the chassis.
2. Position the card over the 4 fastening points and secure with four 4-40 screws (P/N 2820-0039, included with the option card.) Refer to page 38 for BDA harness installation.
!
CAB-4 Series
Figure 2.5 illustrates a typical DAA2 installation. A DP-1B dress panel, ordered separately, can be used to cover the row.
NOTE: Digital amplifiers can produce significant heat during their duty cycles. Different cabinets can handle different amounts of heat. Refer to the Heat Dissipation Calculation document (53645) to determine dissipation figures for the equipment you are installing, and match it with an appropriate cabinet.
2.2.2 Batteries
WARNING: Batteries contain sulfuric acid which can cause severe burns to the skin and eyes, and
can destroy fabrics. If contact is made with sulfuric acid, immediately flush skin or eyes with water for 15 minutes and seek immediate medical attention.
The DAA2 works with two 12 volt batteries. See Appendix B.1, “DAA2 Battery Calculations”, on page 84 for current draw calculations to determine the battery size required for this installation.
Batteries for the DAA2 may be installed in any of the following configurations:
24 DAA2 & DAX — P/N 53265:A1 8/24/2011
Figure 2.5 DAA2 Cabinet Installation
• In a CHS-BH1 battery chassis (12AH batteries only), designed for use with the DAA2 chassis.
• In the bottom of a CAB-4 series cabinet that holds the DAA2.
DAA2 Installation DAA2 Digital Audio Amplifiers
CHS-BHtoDAAchassisa.wmf
CHS-BHwbattsa.wmf
Place battery holder against DAA2 chassis, resting on support. Align chassis standoffs with holes. Fasten with the two washers (P/N 43123) and 8-32 KEPS hex nuts (P/N 36047) supplied.
Place batteries in the trays.
Support
Figure 2.6 Mounting the CHS-BH1
CAB4DwDAAbats.wmf
DAA2 in top row of CAB-D4
Figure 2.7 Battery Installation
Within the Cabinet
Batteries for DAA2
!
• In a cabinet adjacent to the cabinet that holds a DAA2, with connections in conduit.
CHS-BH1 Battery Chassis
This chassis will hold two 12AH batteries, and will mount on the left side of the DAA2 chassis, so that the DAA2 and batteries are contained in a single cabinet row.
To mount the CHS-BH1 onto the DAA2 chassis: Place battery holder against DAA2 chassis, resting on support as shown in Figure 2.6. Align chassis standoffs with holes. Fasten with the two 8/32” hex nuts supplied.
Place the batteries on their sides in their trays before wiring. Refer to “Batteries” on page 26 for wiring instructions.
Within the CAB-4 Enclosure
If the batteries will not be housed in a CHS-BH1, place the batteries in the bottom of the cabinet, as shown in Figure 2.7. Refer to “Batteries” on page 26 for wiring instructions.
Outside the DAA2 Enclosure
Batteries may be installed outside the DAA2 enclosure. The battery cables must be in conduit between the enclosures for the batteries and the DAA2. Refer to “Batteries” on page 26 for wiring instructions.
2.2.3 Wiring
AC Power
WARNING: High Voltages Present.
Use extreme caution when working with the DAA2. High voltage and AC line-connected circuits are present. Turn off and remove all power sources. To reduce the risk of electric shock, make sure to properly ground the DAA2.
Close the hinged cover for TB1 after wiring but before energizing.
DAA2 & DAX — P/N 53265:A1 8/24/2011 25
The DAA2 power supply requires connection to a separate dedicated AC branch circuit. Follow these guidelines when connecting the AC branch circuit:
DAA2 Digital Audio Amplifiers DAA2 Installation
Figure 2.8 AC Power Connection
EARTH
NEUTRAL
HOT
DAACPStb1.wmf
!
DAAPStobatts.wmf
Battery
Interconnect
Cable, P/N
71070
Leave disconnected
until after initial
system power-up.
Batteries in CHS-BH1, same cabinet row as DAA2
Batteries in different cabinet row than DAA2.
DAAPStobattsa.wmf
A
B
P/N 75560 (pos)
P/N 75561 (neg)
P/N 75621 (neg)
P/N 71071 (pos)
• Label the branch circuit “Fire Alarm”.
• Connect the branch circuit to the line side of the main power feed of the protected premises.
• Do not power other equipment from the fire alarm branch circuit.
• Run the AC branch circuit wire continuously, without any disconnect devices, from the power source to the power supply.
• Overcurrent protection for the AC branch circuit must comply with Article 760 of the National Electrical Codes, as well as local codes.
• Use 12-14 AWG (1.6mm O.D.) wire with 600 VAC insulation for the AC branch circuit.
Connect primary power as follows:
1.Turn off the circuit breaker at the main power distribution panel.
2.Connect the earth ground terminal (TB1 EARTH) to a solid earth ground (a metallic, cold water pipe may be suitable in some installations). This connection is vital to maintaining the power supply’s immunity to unwanted transients generated by lightning and electrostatic discharge.
3. Connect the primary power neutral line to the terminal marked NEUTRAL and the primary power AC line to the terminal marked HOT.
Batteries
WARNING: Do not connect the battery interconnect cable (See Figure 2.9) at this time. Leave the
battery interconnect cable disconnected until after initial system power-up.
The DAA2 works with two 12 volt batteries. See Appendix B.1, “DAA2 Battery Calculations”, on page 84 for current draw calculations to determine the battery size required for this installation.
Battery cables (90”, 2.28 m) are included with the DAA2 for battery installation in any CAB-4 series cabinet that includes a DAA2 in one of the rows. Shorter battery cables (18”, 0.5 m) are included with the CHS-BH1. For battery sharing, use 12 AWG wire either in the same cabinet, or in conduit for no more than 20 ft. (6.09 m.).
Batteries Within the Same Enclosure as the DAA2
Refer to Figure 2.9 for battery connections.
26 DAA2 & DAX — P/N 53265:A1 8/24/2011
Figure 2.9 Connecting Batteries to TB3 on the CPS-24
DAA2 Installation DAA2 Digital Audio Amplifiers
DAAbattexternal.wmf
DAA2
Batteries
Conduit between enclosures
Battery
Interconnect
Cable
Leave disconnected until after initial system power-up.
If batteries are not in the same cabinet as the DAA2s, wiring must be in conduit that is 20 ft. long (6.09 m) or less.
CPS-24tb3batshare.wmf
DAA2 1 TB3 on CPS-24
SW1 must be set to “Disable” on all but one of these DAA2s. VeriFire Tools programming must indicate all but one charger is disabled.
DAA2 2 TB3 on CPS-24
DAA2 3 TB3 on CPS-24
DAA2 4 TB3 on CPS-24
Batteries Outside the DAA2 Enclosure
When the batteries are installed outside the DAA2 cabinet, connections are the same as in Figure 2.9. However, the battery cables between the two enclosures must be in conduit and the enclosures must be within 20 feet (6.09 m) of each other within the same room.
Figure 2.10 Using Conduit
Battery Sharing
Up to four DAA2s may share a set of batteries. When DAA2s share batteries
• the ground fault switch on the DAA2 power supply (SW1) must be set to “Disable” on all
but one DAA2 attached to the set of batteries.
• In VeriFire Tools programming, “Disable Charger” must be checked in the “DAA2
Amplifier Programming Service - General II” screen for all but one DAA2.
The enabled ground fault switch does not have to be on the same DAA2 as the enabled charger.
Connect all DAA2s sharing a set of batteries directly to the batteries using 12 AWG. If the batteries are located outside of the DAA2 cabinet, the wiring must be in conduit that is no greater than 20 ft (6.09 m) long.
Figure 2.11 Four DAA2s Sharing Batteries
DAA2 & DAX — P/N 53265:A1 8/24/2011 27
DAA2 Digital Audio Amplifiers DAA2 Installation
FCM-1*
ALARM Bus to next DAA2
ELR-47K, 1/2 watt resistor
DAA2
FZMFCMtpHa.wmf
TB4
TB4
14-18 AWG twisted-pair recommended
Program the control module at the FACP with an appropriate alarm Type ID per the FACP manual.
Alarm Bus requires 16VDC at 20mA across the terminals to activate. Nominal 24 VDC.
To Power
Supply
+
-
SLC from FACP
SLC to
next device
+
-
+
-
+
-
*If the SLC device does not match the one in this
figure, refer to the SLC manual appendix, which contains wiring conver­sion charts for type V and type H modules.
ALM
REF
ALM REF
OUT
IN
ALM
REF
ALM REF
OUT
IN
NAC Circuit
A -
A +
B +
B -
ALARM Bus to next DAA2
DAABRDtb4.wmf
DAA2
TB4
TB4
ELR per panel or power supply manual.
14-18 AWG twisted-pair
recommended
Listed compatible panel or power supply with onboard NAC circuits.
Alarm Bus requires 16VDC
at 20mA across the
terminals to activate.
Nominal 24VDC.
ALM
REF
ALM REF
OUT
IN
ALM
REF
ALM REF
OUT
IN
Alarm Bus
The DAA2 general alarm connections are used to receive general alarm messages from an FACP via an SLC device, or via the Notification Appliance Circuit of an FACP or power supply.
Figure 2.12 Alarm Bus Connections to FCM-1
Refer to the SLC manual and specific panel or power supply manual for more information.
Figure 2.13 Alarm Bus Connections to NAC
28 DAA2 & DAX — P/N 53265:A1 8/24/2011
DAA2 Installation DAA2 Digital Audio Amplifiers
DVC
Refer to the Wiring Guide, p/n 52916ADD, for acceptable wire types and associated distances between ports. Do not splice a cable. Splicing will degrade the signal, and the recommended distance will no longer apply.
DAPA, TB3
DAPB, TB2
REF
DAA2 #1
Optional Style 7 return
Connections are polarity sensitive. Connections are port sensitive. Always connect Port A to Port B.
DAA2 #2
DAA2 #32
TB2
TB2
TB2
TB3
TB3
TB3
DAP A
REF
DAP A
REF
DAP A
REF
DAP B
REF
DAP B
REF
DAP B
REF
REF
Digital Audio Ports A and B, Wire Connections
Digital Audio Ports A and B (DAP A and DAP B) allow digital communication with the DVC over the Digital Audio Loop (DAL); Amplifier programming from the DVC; control, audio, trouble, address and firefighter telephone data; and live voice paging can be communicated through these ports. They may also act as repeaters, in that what is received at one port is transmitted out the other. Events generated at the DAA2 will be transmitted out both ports.
Figure 2.14 Wire the DAA2 Digital Audio Loop Connections
NOTE: Digital Audio Ports A and B must be wired in Style 4 or Style 7 configuration. Do not wire
them in bus configuration.
NOTE: Style 4 configuration must be installed in accordance with the requirements for survivability from attack by fire in the National Fire Alarm Code, NFPA 72.
Digital Audio Ports A and B, Fiber and Wire/Fiber Connections
DAA2 boards are wire, but may be converted partially or fully to fiber boards with the use of fiber option modules DS-FM and DS-SFM. (Refer to Section 5.3.1, “DAA2 Installation”, on page 77 for information on installing fiber option modules.) The fiber, or wire/fiber cabling between these ports provides a Digital Audio Loop (DAL) for programming; alarm, control, trouble, automatic audio messages, address and firefighter telephone data; and live voice paging communications.
Figure 2.15 illustrates an example of how a DAL can be formed using mixed wire and fiber connectors.
DAA2 & DAX — P/N 53265:A1 8/24/2011 29
DAA2 Digital Audio Amplifiers DAA2 Installation
DAAmixedDALa.wmf
Optional Style
7 return
DAA2
w/ one wire port and one multi-mode port.
Consult manufacturer’s guidelines for minimum radius of bend for fiber optic media.
DAA2
w/ two multi-mode ports.
Connections are port sensitive. Always connect Port A to Port B.
Wire connections are polarity sensitive.
DAA2
w/ one multi-mode port and one single-mode port.
DAA2
w/ one wire port and one single-mode port.
DVC
DS-FM at DAP A
DS-SFM at DAP B
DS-SFM at DAP A
DS-FM at DAP B
DS-FM at DAP A
DS-FM at DAP B
A DS-RFM fiber module must be used to connect a DAA2 to a multi-mode fiber DVC or DAA. Refer to “Fiber Option Modules” on page 75 for more information on this module.
NOTE: If a fiber option module is installed at a DAP, that DAP may not also be used for a wire connection.
30 DAA2 & DAX — P/N 53265:A1 8/24/2011
Figure 2.15 Fiber/Wire DAL Configuration
NOTE: Style 4 configuration must be installed in accordance with the requirements for survivability from attack by fire in the National Fire Alarm Code, NFPA 72.
FFT Riser Connections
The Firefighter Telephone Riser connections (TB7) provide for the use of firefighter telephones (FFTs) on an analog network. They are a means of connecting various FFT telephone control modules and devices, such as FTM-1 modules, AFAWS, FPJ or RPJ-1 telephone circuits to the DAA2.
The FFT riser may be wired in NFPA Class A or Class B configuration. For trouble supervision, VeriFire Tools must be used to indicate whether a riser is installed or not. SW1 must be set to indicated whether the wiring is Class A or Class B. (Refer to page 41 for switch settings.) Class B 2-Wire configurations require a 3.9K ohm 1/2 watt end-of-line resistor (P/N R-3.9K). Class A 4­wire configurations have an internal ELR and do not require an external ELR
There are two ways that firefighter telephones may be installed on a DAA2 FFT riser. Both configurations have a limit of seven active phones. (Refer to the FFT appendix in the DVC Digital Voice Command manual for more information on limits.)
1. “Install FTM” selected - FireFighter Telephones must be wired to the output of the FTM
modules. The telephone points will be SLC addresses.
Loading...
+ 98 hidden pages