Notifier Chime Strobes User Manual

SpectrAlert® Advance
Selectable Output CHRA, CHWA Chimes and CHSRA, CHSWA Chime/Strobes
dn-7089:a3 • J-75
Audio/Visual Devices
System Sensor SpectrAlert® Advance selectable-output chimes and chime/strobes are private-mode notification appli­ances used to alert trained personnel to investigate possible emergency situations and to take appropriate action. Security guard and nurse workstations are ideal locations for chime products.
SpectrAlert Advance chimes and chime/strobes are rich with features guaranteed to cut installation times and maximize profits. The SpectrAlert Advance series of notification appli­ances is designed to simplify your installations, with features such as: plug-in designs, instant feedback messages to ensure correct installation of individual devices, and seven field-selectable candela settings for chime/strobes.
More specifically, when installing Advance products, first attach a universal mounting plate to a four-inch (10.16 cm) square, four-inch octagonal, single-gang, or double-gang junc­tion box.
Then, connect the notification appliance circuit wiring to the SEMS terminals on the mounting plate.
Finally, attach the chime or chime/strobe to the mounting plate by inserting the product’s tabs in the mounting plate’s grooves. The device will rotate into position, locking the product’s pins into the mounting plate’s terminals. The device will temporarily hold in place with a catch until it is secured with a captive mounting screw.
SpectrAlert Advance products allow you to choose:
• 12 or 24 volts.
• At 24 volts, 15, 15/75, 30, 75, 95, 110, or 115 candela by way of rear-mounted slide-switch and front-view window.
• Chime tones and volume by way of rotary switch.
Features
• Plug-in design.
• Shorting spring on mounting plate for pre-installation conti­nuity check.
• Captive mounting screw.
• Torx screw for tamper resistance.
• Field-selectable candela settings: 15, 15/75, 30, 75, 95, 110, 115.
• Automatic selection of 12- or 24-volt operation at 15 and 15/ 75 candela.
• Minimal intrusion into the backbox.
• Rotary switch for tone selection.
• Two volume settings.
• Electrically compatible with existing SpectrAlert products.
Engineering Specifications
SpectrAlert Advance chimes and chime/strobes shall mount to a standard 4.0" x 4.0" x 1.5" backbox, 4.0" octagonal backbox, single-gang 2.0" x 4.0" x 1.875" backbox, or double-gang backbox. A universal mounting plate shall be used for mounting products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, SpectrAlert Advance products, when used with the
7089pho1.tif
P2F-P-rgb.bmp
Chime (CHW) Chime/Strobe (CHSR)
Sync•Circuit™ Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt rated notification appliance circuit outputs shall operate between 9 and 17.5 volts; 24-volt rated notification appliance circuit outputs shall operate between 17 and 33 volts. Indoor SpectrAlert Advance products shall operate between 32°F and 120°F from a regulated DC, or full­wave-rectified, unfiltered power supply. Chime/strobes shall have field-selectable candela settings of 15, 15/75, 30, 75, 95, 110, and 115.
CHIME/STROBE COMBINATION
The chime/strobe shall be a System Sensor SpectrAlert Advance Model _______ listed to UL/ULC 1638 and UL/ULC
464. The chime/strobe shall comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The chime shall have two audibility options and an option to switch between a temporal three-pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch.
SYNCHRONIZATION MODULE
The module shall be a System Sensor Sync•Circuit _______ listed to UL/ULC 464 and shall be approved for fire protective service. The module shall synchronize SpectrAlert strobes at 1 Hz and chimes at Temporal 3. Also, while operating the strobes, the module shall silence the chimes on chime/strobe models over a single pair of wires. The module shall mount to a 4.688" x 4.688" x 2.125" backbox. The module shall also control two Style Y (Class B) circuits or one Style Z (Class A) circuit. The module shall synchronize multiple zones. Daisy­chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply.
Operating Specifications
Standard operating temperature: 32°F to 120°F.
Humidity range: 10% to 93% non-condensing (indoor
products).
Strobe flash rate: 1 flash per second.
dn-7089:a3 • 4/20/10 — Page 1 of 4
Nominal voltage: regulated 12 VDC/FWR or regulated 24 VDC/FWR.
Operating voltage range: 8 V to 17.5 V (12 V nominal); or 16 V to 33 V (24 V nominal). NOTE: CHS products will
operate at 12 V nominal only for 15 cd and 15/75 cd.
Input terminal wire gauge: 12 to 18 AWG.
Chime/strobe dimensions (including lens): 5.6" H x 4.7" W x 2.5" D.
Chime dimensions: 5.6" H x 4.7" W x 1.3" D.
Agency Listings and Approvals
The listings and approvals below apply to SpectrAlert Advance Selectable Output Chimes and Chime/Strobes. In some cases, certain modules may not be listed by certain approval agen­cies, or listing may be in process. Consult factory for latest list­ing status.
UL/ULC Listed: file S4011.
FM approved.
MEA approved: file 452-05-E.
CSFM approved: file 7125-1653:188 (CHSR, CHSW); file
7135-1653:189 (CHR, CHW).
Ordering Information
CHR: Chime, red.
CHRA: Same as above with ULC listing.
CHW: Chime, white.
CHWA: Same as above with ULC listing.
CHSR: Chime/strobe, red.
CHSRA: Same as above with ULC listing.
CHSW: Chime/strobe, white.
CHSWA: Same as above with ULC listing.
BBS-2: Backbox skirt, wall, red.
BBS-2A: Same as above with ULC listing.
BBSW-2: Backbox skirt, wall white.
BBSW-2A: Same as above with ULC listing.
Current Draw, UL Maximum (mA RMS)
8 – 17.5 Volts 16 – 33 Volts
Input, Pattern, dB Out
DC, 1-Second Chime, HIGH 131 142 65 76 94 160 185 207 213
DC, 1-Second Chime, LOW 131 142 64 75 92 157 183 203 212
DC, 1/4-Second Chime, HIGH 129 142 66 75 95 159 184 205 212
DC, 1/4-Second Chime, LOW 129 142 64 74 91 155 181 204 211
DC, Temporal Chime, HIGH 125 142 64 74 91 156 181 205 211
DC, Temporal Chime, LOW 129 141 65 75 92 155 180 200 209
DC, 5-Second Whoop, HIGH 133 145 70 81 99 165 189 210 217
DC, 5-Second Whoop, LOW 130 143 66 77 95 160 186 206 214
DC, One-Time Chime 127 141 64 76 93 156 182 203 210
FWR, 1-Second Chime, HIGH 128 150 72 82 98 158 183 202 210
FWR, 1-Second Chime, LOW 127 150 71 81 97 157 182 202 210
FWR, 1/4-Second Chime, HIGH 129 149 72 82 99 160 183 203 211
FWR, 1/4-Second Chime, LOW 128 149 71 81 97 154 179 196 205
FWR, Temporal Chime, HIGH 128 148 71 81 97 157 179 199 206
FWR, Temporal Chime, LOW 125 147 71 81 97 156 180 200 206
FWR, 5-Second Whoop, HIGH 136 152 84 93 110 170 193 212 220
FWR, 5-Second Whoop, LOW 132 150 77 86 102 161 184 203 214
FWR, One-Time Chime 127 147 72 82 97 157 181 200 210
15 cd 15/75 cd 15 cd 15/75 cd 30 cd 75 cd
95 cd 110 cd 115 cd
Page 2 of 4 — dn-7089:a3 • 4/20/10
Tone Selection
Chime tone selection is accomplished by using the rotary switch on the back of the product. The current draw and sound measurements for various chime tones are listed below.
Chime Current Draw, UL Maximum (mA RMS)
8 – 17.5 Volts 16 – 33 Volts
Sound Pattern dB
1-Second Chime HIGH 34 mA 50 mA 58 mA 51 mA
1-Second Chime LOW 30 mA 51 mA 51 mA 54 mA
1/4-Second Chime HIGH 34 mA 51 mA 50 mA 50 mA
1/4-Second Chime LOW 31 mA 51 mA 50 mA 52 mA
Temporal Chime HIGH 30 mA 50 mA 48 mA 54 mA
Temporal Chime LOW 30 mA 47 mA 50 mA 51 mA
5-Second Whoop HIGH 32 mA 52 mA 34 mA 54 mA
5-Second Whoop LOW 30 mA 40 mA 34 mA 52 mA
One Test Chime HIGH 48 mA 49 mA 50 mA 50 mA
DCFWRDCFWR
Sound Output (dBA), Chime and Chime/Strobe
8 – 17.5 Volts 16 – 33 Volts
Switch
Setting Sound Pattern dB
1 1-Second Chime HIGH 58 dBA 59 dBA 61 dBA 61 dBA
2 1-Second Chime LOW 53 dBA 54 dBA 55 dBA 55 dBA
3 1/4-Second Chime HIGH 63 dBA 64 dBA 66 dBA 66 dBA
4 1/4-Second Chime LOW 58 dBA 59 dBA 60 dBA 60 dBA
5 Temporal Chime HIGH 62 dBA 64 dBA 68 dBA 69 dBA
6 Temporal Chime LOW 55 dBA 57 dBA 60 dBA 60 dBA
7 5-Second Whoop HIGH 68 dBA 71 dBA 75 dBA 77 dBA
8 5-Second Whoop LOW 62 dBA 64 dBA 67 dBA 68 dBA
9 One Test Chime HIGH 57 dBA 55 dBA 61 dBA 57 dBA
DCFWRDCFWR
Chime Patterns
Setting Repetition Rate dB Out
1 1-Second Chime HIGH
2 1-Second Chime LOW
3 1/4-Second Chime HIGH
4 1/4-Second Chime LOW
5 Temporal Chime HIGH
6 Temporal Chime LOW
7 5-Second Whoop HIGH
8 5-Second Whoop LOW
9 One Test Chime HIGH
SpectrAlert Advance Chime/Strobe Dimensions
7089dim1.tif
dn-7089:a3 • 4/20/10 — Page 3 of 4
Page 4 of 4 — dn-7089:a3 • 4/20/10
Sync•Circuit™ is a trademark and Notifier®, SpectrAlert® and System Sensor® are registered trademarks of Honeywell International Inc.
©2010 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Made in the U.S. A.
Loading...