Selectable Output CHRA, CHWA Chimes
and CHSRA, CHSWA Chime/Strobes
dn-7089:a3 • J-75
Audio/Visual Devices
General
System Sensor SpectrAlert® Advance selectable-output
chimes and chime/strobes are private-mode notification appliances used to alert trained personnel to investigate possible
emergency situations and to take appropriate action. Security
guard and nurse workstations are ideal locations for chime
products.
SpectrAlert Advance chimes and chime/strobes are rich with
features guaranteed to cut installation times and maximize
profits. The SpectrAlert Advance series of notification appliances is designed to simplify your installations, with features
such as: plug-in designs, instant feedback messages to
ensure correct installation of individual devices, and seven
field-selectable candela settings for chime/strobes.
More specifically, when installing Advance products, first
attach a universal mounting plate to a four-inch (10.16 cm)
square, four-inch octagonal, single-gang, or double-gang junction box.
Then, connect the notification appliance circuit wiring to the
SEMS terminals on the mounting plate.
Finally, attach the chime or chime/strobe to the mounting plate
by inserting the product’s tabs in the mounting plate’s grooves.
The device will rotate into position, locking the product’s pins
into the mounting plate’s terminals. The device will temporarily
hold in place with a catch until it is secured with a captive
mounting screw.
SpectrAlert Advance products allow you to choose:
• 12 or 24 volts.
• At 24 volts, 15, 15/75, 30, 75, 95, 110, or 115 candela by
way of rear-mounted slide-switch and front-view window.
• Chime tones and volume by way of rotary switch.
Features
• Plug-in design.
• Shorting spring on mounting plate for pre-installation continuity check.
• Automatic selection of 12- or 24-volt operation at 15 and 15/
75 candela.
• Minimal intrusion into the backbox.
• Rotary switch for tone selection.
• Two volume settings.
• Electrically compatible with existing SpectrAlert products.
Engineering Specifications
SpectrAlert Advance chimes and chime/strobes shall mount to
a standard 4.0" x 4.0" x 1.5" backbox, 4.0" octagonal backbox,
single-gang 2.0" x 4.0" x 1.875" backbox, or double-gang
backbox. A universal mounting plate shall be used for
mounting products. The notification appliance circuit wiring
shall terminate at the universal mounting plate. Also,
SpectrAlert Advance products, when used with the
7089pho1.tif
P2F-P-rgb.bmp
Chime (CHW)Chime/Strobe (CHSR)
Sync•Circuit™ Module accessory, shall be powered from a
non-coded notification appliance circuit output and shall
operate on a nominal 12 or 24 volts. When used with the
Sync•Circuit Module, 12-volt rated notification appliance circuit
outputs shall operate between 9 and 17.5 volts; 24-volt rated
notification appliance circuit outputs shall operate between 17
and 33 volts. Indoor SpectrAlert Advance products shall
operate between 32°F and 120°F from a regulated DC, or fullwave-rectified, unfiltered power supply. Chime/strobes shall
have field-selectable candela settings of 15, 15/75, 30, 75, 95,
110, and 115.
CHIME/STROBE COMBINATION
The chime/strobe shall be a System Sensor SpectrAlert
Advance Model _______ listed to UL/ULC 1638 and UL/ULC
464. The chime/strobe shall comply with the Americans with
Disabilities Act requirements for visible signaling appliances,
flashing at 1 Hz over the strobe’s entire operating voltage
range. The strobe light shall consist of a xenon flash tube and
associated lens/reflector system. The chime shall have two
audibility options and an option to switch between a temporal
three-pattern and a non-temporal (continuous) pattern. These
options are set by a multiple position switch.
SYNCHRONIZATION MODULE
The module shall be a System Sensor Sync•Circuit _______
listed to UL/ULC 464 and shall be approved for fire protective
service. The module shall synchronize SpectrAlert strobes at 1
Hz and chimes at Temporal 3. Also, while operating the
strobes, the module shall silence the chimes on chime/strobe
models over a single pair of wires. The module shall mount to
a 4.688" x 4.688" x 2.125" backbox. The module shall also
control two Style Y (Class B) circuits or one Style Z (Class A)
circuit. The module shall synchronize multiple zones. Daisychaining two or more synchronization modules together will
synchronize all the zones they control. The module shall not
operate on a coded power supply.
Operating Specifications
• Standard operating temperature: 32°F to 120°F.
• Humidity range: 10% to 93% non-condensing (indoor
products).
• Strobe flash rate: 1 flash per second.
dn-7089:a3 • 4/20/10 — Page 1 of 4
• Nominal voltage: regulated 12 VDC/FWR or regulated 24
VDC/FWR.
• Operating voltage range: 8 V to 17.5 V (12 V nominal); or
16 V to 33 V (24 V nominal). NOTE: CHS products will
operate at 12 V nominal only for 15 cd and 15/75 cd.
• Input terminal wire gauge: 12 to 18 AWG.
• Chime/strobe dimensions (including lens): 5.6" H x 4.7"
W x 2.5" D.
• Chime dimensions: 5.6" H x 4.7" W x 1.3" D.
Agency Listings and Approvals
The listings and approvals below apply to SpectrAlert Advance
Selectable Output Chimes and Chime/Strobes. In some cases,
certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status.
Chime tone selection is accomplished by using the rotary switch on the back
of the product. The current draw and sound measurements for various
chime tones are listed below.
Chime Current Draw,
UL Maximum (mA RMS)
8 – 17.5 Volts16 – 33 Volts
Sound PatterndB
1-Second ChimeHIGH34 mA50 mA58 mA51 mA
1-Second ChimeLOW30 mA51 mA51 mA54 mA
1/4-Second ChimeHIGH34 mA51 mA50 mA50 mA
1/4-Second ChimeLOW31 mA51 mA50 mA52 mA
Temporal ChimeHIGH30 mA50 mA48 mA54 mA
Temporal ChimeLOW30 mA47 mA50 mA51 mA
5-Second WhoopHIGH32 mA52 mA34 mA54 mA
5-Second WhoopLOW30 mA40 mA34 mA52 mA
One Test ChimeHIGH48 mA49 mA50 mA50 mA
DCFWRDCFWR
Sound Output (dBA), Chime and Chime/Strobe
8 – 17.5 Volts16 – 33 Volts
Switch
SettingSound PatterndB
11-Second ChimeHIGH58 dBA 59 dBA 61 dBA 61 dBA
21-Second ChimeLOW53 dBA 54 dBA 55 dBA 55 dBA
31/4-Second ChimeHIGH63 dBA 64 dBA 66 dBA 66 dBA
41/4-Second ChimeLOW58 dBA 59 dBA 60 dBA 60 dBA
5Temporal ChimeHIGH62 dBA 64 dBA 68 dBA 69 dBA
6Temporal ChimeLOW55 dBA 57 dBA 60 dBA 60 dBA
75-Second WhoopHIGH68 dBA 71 dBA 75 dBA 77 dBA
85-Second WhoopLOW62 dBA 64 dBA 67 dBA 68 dBA
9One Test ChimeHIGH57 dBA 55 dBA 61 dBA 57 dBA
DCFWRDCFWR
Chime Patterns
SettingRepetition RatedB Out
11-Second ChimeHIGH
21-Second ChimeLOW
31/4-Second ChimeHIGH
41/4-Second ChimeLOW
5Temporal ChimeHIGH
6Temporal ChimeLOW
75-Second WhoopHIGH
85-Second WhoopLOW
9One Test ChimeHIGH
SpectrAlert Advance Chime/Strobe Dimensions
7089dim1.tif
dn-7089:a3 • 4/20/10 — Page 3 of 4
Page 4 of 4 — dn-7089:a3 • 4/20/10
Sync•Circuit™ is a trademark and Notifier®, SpectrAlert® and System
Sensor® are registered trademarks of Honeywell International Inc.