Notifier CFP-600-E Installation And Operating Manual

Page 1
Installation and Operating Manual
Document:
M-131.1-CFP600-ENG
Issue :
07/1999
Rev.:
B.1
12-Zone Conventional
Control Panel
NOTIFIER ITALIA
a Pittway Company
Complies with EN54.2
Page 2
INSTALLATION PRECAUTIONS
ADHERENCE TO THE FOLLOWING WILL AID IN PROBLEM-FREE INSTALLATION WITH LONG-TERM RELIABILITY
WARNING
Several different sources of power can be connected to this fire alarm control panel. Disconnect all sources of power bef- ore servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood.
CAUTION
The System
and all its components have to be installed in an environment with the following features:
Temperature: 0-35° C
Humidity: 80% RH (non-condensing) @ 30°C.
However,theusefullife of the system's standby batteries and the electronic components may be adversely affected by ex- treme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a nominal room temperature of 15-27° C.
Verify
that wire sizes are adequate for all initiating and indicating device loop. Most devices cannot tolerate more
than a 10% I.R. drop from the specified device voltage.
Like all solid state electronic devices
, this system may operate erratically or can be damaged when subjected to lightning induced transients. Although no system is completely immune from lightning transients and interferences, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increa- sed susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encountered.
Disconnect AC power
and batteries prior to removing or inserting circuits boards. Failure to do so can damage cir-
cuits.
Remove all electronic assemblies
prior to any drilling, filing, reaming, or punching of the enclosure. When possib- le, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, and printed circuit board location.
Do not tighten screw terminals
more than 9 in-lbs. Overtightening may damage threads, resulting in reduced ter-
minal contact pressure and difficulty with screw terminal removal.
This system
contains static-sensitive components. Always ground yourself with a proper wrist strap before han- dling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions
in the installation, operating and programming manuals. These instructions must be fol- lowed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation.
Smoke detectors
may not sense fire where smoke cannot reach the detectors such as in chimneys, in walls, or roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor buil- ding. Furthermore, all types of smoke detectors have sensing limitations.
A fire alarm system
will not operate without any electrical power. If AC power fails, the system will operate from
standby batteries only for a specified time.
Equipment used in the system
may not be technically compatible with the control. It is essential to use only
equipment listed for service with your control panel.
The most common cause
of fire alarm malfunctions, however, is inadequate maintenance. All devices and system wiring should be tested and maintained by professional fire alarm installers following written procedures supplied with each device. System inspection and testing should be scheduled monthly or as required by National and/or lo- cal fire codes. Adequate written records of all inspections should be kept.
INDEX.VP Installation and Operating Manual Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA
Page 3
INDEX
Keypad & LED Indicators 1
Alarm and Trouble Display 1
Control Silence - Silenced Control Reset - Evacuation 2
Buzzer Silence 2
Lamp test 2
Alarm or Trouble Reset 2
Entering Passwords 3
USER MENU - LEVEL 1 - 3
Enable Release Channels 3
Display Zone Status 4
Change Zones - Enable/Disable Status 5
Change Day/Night Mode 5
Display Historical Log 5
Change Prealarm Recognition Time (Level 3 Password required) 6
Alarm Counter 6
Change Date/Time (Level 3 Password required) 6
Change LEVEL 1 Password 7
TEST MENU - LEVEL - 2 7
Display Line Status 7
Change Controls - Enable/Disable Status 8
Select Zone for Walk-Test Mode 8
Display Firmware revision 8
Change LEVEL 2 Password 9
CONFIGURATION MENU - LEVEL 4 9
Change Zones - Include/Exclude Status 10
Programming the CBE Equation 10
Change Service Enabling Status 11
Change Zone parameters 12
Change Verification Times 12
Programming the Relay mapping (on optional 16- relay board) 13
Enabling the Relay Signal Silence (on optional 16-relay board) 13
INDEX.VP Installation and Operating Manual Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA
Page 4
Change Zone description 14
Change System Time Delay 14
Change Alarm Time parameter 15
Programmming the alarm control modulation 15
Programming the release zone mapping 16
Change release time 16
Select event type for Historical Log 16
Programming the System Name 17
Clearing the control panel memory 17
Change Language Display 17
Change all level passwords 18
APPENDIX A 19
Control Panel Operation in Day/Night Mode 19
Automatic Release Channel Management 20
APPENDIX B 21
Menu Item list 21
INSTALLATION 22
Control Panel Internal view 22
Cabinet dimensions and wall-mounting instructions 22
Control Panel Wiring 23
Optional Boards 24
16-relay optional board 24
2-release channel optional board 25
Electrical Features 26
GLOSSARY 27
Installation and Operating Manual INDEX.VP
NOTIFIER ITALIA Rev. B.1 Doc. M-131.1-CFP600-ENG
Page 5
KEYPAD
The Control Panel keypad is made up of 7 keys:
LED INDICATORS
ALARM AND TROUBLE DISPLAY
ALARM ACKNOWLEDGEMENT
The
UPWARDS CURSOR
Key allows to display, on the second and third line, all zones in alarm status, as follows:
CFP-600-Prog-1.VP Installation and Operating Manual Page 1 Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA
CHANNEL 2
KEY TO ENABLE KEYPAD
Buzzer Silence
Reset
ESC
ENTER
Cursor Keys
- ON= During Alarm
- ON= During Pre-alarm
- ON= General Trouble
- ON= Line Trouble
- ON= Mains Failure
- ON= Battery Trouble
- Blink.= Disab.Zone / ON=Excl. Zone
- Blink.= During Walk Test
- ON= During Signal Silence
- ON= During Day
- OFF= CPU Mains Trouble
- Control Panel Power ON Signal
- ON= CPU or WD Trouble
Evacuation in progress Release occured Release Control Trouble Release Inhibited
Evacuation in progress Release occured Release Control Trouble Release Inhibited
CHANNEL 1
First zone in alarm status Last zone in alarm status Last zone in trouble status First zone in trouble status
Total of Zones in alarm status Total of Zones in Trouble status Total of disabled Zones
A1:Z11 ALARM | A04 A1:Z11 ALARM | G03 FIRST FLOOR | D00 T1:Z01 LINE SHORT C. | E00
The second line shows the number of the zone in alarm status. The third line shows a max. 16-character programmable label, mapped to the zone.
Event progressive number on alarm file Number of the zone in alarm status
Event progressive number on trouble file
Number of the zone in trouble status
Signal Silence
A1:Z11 ALARM | A04
A4:Z08 ALARM | G03
T3:Z04 LINE SHORT C. | D00
T1:Z01 LINE SHORT C. | E00
Acknowledgement is carried out when all the events on alarm file have been displayed by using the
UPWARDS CUR-
SOR
Key. The events are displayed from the first to the last event, in chronological order.
Press
ESC
Key to leave alarm display.
N.B. :A)Reset, Control Silence and Buzzer Silence, are not allowed during alarm acknowledgement.
B)
Reset is allowed only after carring out all event acknowledgement.
Page 6
TROUBLE ACKNOWLEDGEMENT
The
DOWNWARDS CURSOR
Key allows to display, on the second and third line, all zones in trouble status, as
follows:
Acknowledgement is carried out when all the events, on trouble file, have been displayed by using the
DOWNWARDS
CURSOR
key. The events are displayed from the first to the last event, in chronological order.
Press
ESC
key to leave trouble display.
NOTE:A
) Reset, Control Silence and Buzzer Silence, are not allowed during trouble acknowledgement.
B
) Reset is allowed only after carring out all event acknowledgement.
CONTROL SILENCE - SILENCED CONTROL RESET - EVACUATION
CONTROL SILENCE: in Alarm or Trouble conditions, the first pression of this key silences all indicating applian- ces wired to control modules that have been programmed as silenceable. To execute the signal silence, the operator has to know Level 1 Password. SILENCED CONTROL RESET: in Alarm or Trouble conditions, the second pression of this key, clears all alarms or troubles in the system, and all general controls that have been programmed as silenceable.
EVACUATION: during normal condition, the first pression of this key, after a confirmation request, activates all general outputs and all programmable controls.
EVACUATION STOP: during normal condition, the second pression of this key, after a confirmation request, deactivates all general outputs and all programmable controls .
BUZZER SILENCE
This key allows the buzzer silence.
LAMP TEST
Lamp Test can be executed only in normal condition, by pressing ESC key.
ALARM OR TROUBLE RESET
This key clears all Alarms or Troubles in the system.
»
N.B.:reset is allowed only after all event (Alarms or Troubles) acknowledgement. In order to reset the events, the operator has to know LEVEL 1 PASSWORD.
Page 2 Installation and Operating Manual CFP-600-Prog-1.VP NOTIFIER ITALIA Rev. B.1 Doc. M-131.1-CFP600-ENG
A1:Z11 ALARM | A04 T1:Z01 LINE SHORT C. | G03 FILE | D00 T1:Z01 LINE SHORT C. | E00
The second line shows the number of the zone in trouble status The third line shows a max.16-character programmable label mapped to the zone.
Page 7
ENTERING PASSWORDS
To perform the functions available on the control panel, it needs to enter a specific Password, made up of 1 to 4 figures, depending on the programmings carried out. Factory default passwords are:
Level 1 = 1
Level 2 = 2
Level 3 = 3
Level 4 = 4
Use
CURSOR
keys to enter passwords. By pressing them, the display will show a
figure which can be increased or decreased always by pressing
CURSOR
keys.
After choosing each figure, press
ENTER.
If the password is accomplished,press
ENTER
key again, otherwise choose next figure, always by using
CURSOR
keys,
followed by
ENTER
.
Level 1 Password can be modified from any other higher level (2 to 4).
USER MENU - LEVEL-1-
To have access to User Functions, press
ENTER
, and the display will show:
Press
UPWARDS CURSOR
Key.
Level Password will be required. Enter the relevant programmed password.
The display will show the first available function in USER mode:
Use
CURSOR KEYS
to display the desired function, choosing among:
Enable Release Channels
Display ZONE status
Change Zones - Enable/Disable Status
Change Day-Night mode
Display Historical Log
Change Prealarm Recognition Time (Level 3 Password required)
Alarm counter
Change Date/Time (Level 3 Password required)
Change Level 1 Password
Press
ENTER
to confirm the selection.
ENABLE RELEASE CHANNELS
This function allows to enable or disable the two release channels. If one channel is disabled and the release board is programmed as installed (See Configuration Menu), the release inhibi- tion yellow LED of the relevant channel will blink.
Press
ENTER
key
Use
CURSOR
keys to select the release channel
Press
ENTER
to change the release channel programming.
CFP-600-Prog-1.VP Installation and Operating Manual Page 3 Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA
:User Mode | A08 :Test Mode | G08 :Configuration | D00 :Exit | E00
USER MODE |A08 ZONES STATUS |G02
|D00 |E00
LEV.1 PASSW. | A08
__ | G02
| D00 | E00
LEV.1 PASSW. | A08
__ | G02
| D00 | E00
LEV.1 PASSW. | A08
* * __ | G02
| D00 | E00
ENA.REL.CHAN.|A00
N 1 |G00 N 0 |D00
|E00
USER MODE |A00
ENA.REL.CHAN.|G00
|D00 |E00
ENA.REL.CHAN.|A00
N 1 |G00 N 0 |D00
Modify Exit|E00
NOTE
: If at Level 4 of Configuration Menu, the release board enabling (Enabling Function Menu), has not been programmed, it is not possible to modify the release channel enabling. At the power ON of the control panel the release channels are disabled.
Page 8
q LED STATUS OF RELEASE BOARD
DISPLAY ZONE STATUS
The display will show the first zone status, with the following messages:
NORMAL = Included and Enabled Zone, without Alarms or Troubles
ALARM = Included and Enabled Zone, in Alarm status
LINE SHORT. C. = Included and Enabled Zone, in Short Circuit status
LINE CUT = Included and Enabled Zone with wire cut
DISABLED = Included Zone but Disabled, without Troubles
EXCLUDED = Excluded Zone
To select another zone use
CURSOR KEYS
Press
ESC
to leave this function.
Page 4 Installation and Operating Manual CFP-600-Prog-1.VP NOTIFIER ITALIA Rev. B.1 Doc. M-131.1-CFP600-ENG
RELEASE BOARD
PROGRAMMED
RELEASE BOARD
INSTALLATION
INHIBITION RELEASE TROUBLE
LED
RELEASE INHIBITION
LED
Included
\
Excluded
Installed
\
Not installed
YES
NO
Turned ON
Blinking
\
Turned OFF
Turned ON
Blinking
\
Turned OFF
Included
\
Excluded
Installed
Not installed
YES
\
NO
Turned ON
Blinking
\
Turned OFF
\
Turned ON
Blinking
Turned OFF
\
Included
Excluded
Installed
Not installed
YES
NO
Turned ON
\
Blinking
Turned OFF
\
Turned ON
Blinking
Turned OFF
\
Included
Excluded
Installed
Not installed
YES
NO
Turned ON
Blinking
\
Turned OFF
Turned ON
Blinking
\
Turned OFF
\
Included
Excluded
\
Installed
Not installed
\
YES
NO
Turned ON
Blinking
\
Turned OFF
Turned ON
\
Blinking
Turned OFF
ZONE STATUS |A08
|G02
Z01 ALARM |D00
|E00
Page 9
CHANGE ZONES - ENABLE/DISABLE STATUS
By using
CURSOR KEYS
, enter the desired zone number.
By pressing ENTER key, the current status of the selected zone will be displayed.
Press
ENTER
to Disable or Enable.
If you do not want to change the zone status, press
ESC
.
»
NOTE: A)
CHANGE DAY-NIGHT MODE
By pressing
ENTER
, the display will show the control panel status
To change it, press
ENTER
.
NIGHT= Day/Night LED= Turned OFF
DAY= Day/Night LED = Turned ON
If you do not want to change the control panel status, press
ESC
.
DISPLAY HISTORICAL LOG
Press
ENTER
to display the Historical Log Function.
Use
CURSOR KEYS
to display the events
Press
ESC
to leave the Historicl Log Function
»
NOTE: Historical Log may store maximum 50 events. To display the Historical Log, enter the Level 2 PASSWORD.
CFP-600-Prog-1.VP Installation and Operating Manual Page 5 Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA
USER MODE |A08 ENA./DIS.ZONE |G08
|D00 |E00
ENA./DIS.ZONE |A08 Z. |G08
|D00 |E00
ENA./DIS.ZONE |A08 Z. 01 NORMAL |G08
|D00
Modify Exit |E00
Zone Status Detector Alarms Detector Troubles Enabled YES YES Disabled NO YES Excluded NO NO
B) if a zone is DISABLED, it detects only troubles. (See config. Menu - Lev.4 about “Exclusion function”)
USER MODE |A08 DAY-NIGHT |G08
|D00 |E00
|A08
>NIGHT< |G08
|D00
Modify Exit |E00
USER MODE |A08 HISTORICAL LOG |G08
|D00 |E00
HISTORICAL LOG |A08 01: 14-04 17:31|G08 Z.01 ALARM |D00 HIST. LOG |E00
Date Event nr. Zone nr.
HOURS-MINUTES
Event
Programmable Label mapped to the zone
Page 10
CHANGE PREALARM RECOGNITION TIME (Level 3 Password required)
Press
ENTER
to display as follows.
Press
ENTER
to change the Recognition Time.
Use
CURSOR
keys to program the new Recognition Time.
Then, press
ENTER
to confirm.
»
NOTE : by pressing the control signal silence key, the operator, in case of prealarm, may start the Recogni- tion Time. This time allows the operator to carry out a system recognition to verify the real presence of fire. If the Recognition time expires before performing a reset the control panel will activate alarm signals. For further details see Appendix A: Day/Night Operation. Values admitted are: 1 minute to 19, 59
NOTE: enter the Level 3 PASSWORD to display the Recognition Time.
ALARM COUNTER
By pressing
ENTER
key the display will show a screen as follows, in-
dicating the number of alarm events.
NOTE
: the alarm event max number is equals to 9999
By pressing
ENTER
key the operator may clear the counter only if he
knows the Level 4 password
CHANGE DATE/TIME (Level 3 Password required)
Use
ENTER key
and
CURSOR KEYS
to program date and time.
»
NOTE: enter the Level 3 PASSWORD to program date and time.
Page 6 Installation and Operating Manual CFP-600-Prog-2.VP NOTIFIER ITALIA Rev. B.1 Doc. M-131.1-CFP600-ENG
USER MODE | A08 RECOGN. TIME | G08
| D00 | E00
LEV.3 PASSW. |
| | |
USER MODE | A08 RECOGN. TIME | G08 10'00''05'00''| D00
| E00
TimeDate
USER MODE | A00 DATE/TIME | G00
| D00
01-01-97 00:48| E00
USER MODE | A00 ALARM COUNTER | G00
| D00 | E00
ALARM COUNTER | A00
10 | G00
| D00
Modify Exit | E00
Page 11
CHANGE LEVEL 1 PASSWORD
Pressing
ENTER
, it will be possible to select a new level 1 Password.
Use
CURSOR
keys, to select the level number and press ENTER
to confirm.
The programmable Password may be made up of 1 to 14 figures (numbers)
To enter a figure:
Select the desired number, using the CURSOR keys
Press ENTER
To escape the programming, press ENTER a second time.
If you do not want to change the programming, press ESC.
TEST MENU - LEVEL 2 -
Press ENTER o have access to the test functions, and the display will show:
Press the
DOWNWARDS CURSOR
Key.
Level 2 Password will be required. Enter it.
The display will show the first availabe function in TEST mode: Use cursor keys to display the desired function, choosing among:
Display Line Status
Change Controls - Enable/Disable status
Select Zone for Walk Test Mode
Display Firmware Revision
Change Level 2 Password
Press
ESC
to go back to the main screen.
DISPLAY LINE STATUS
On the display will appear the line status in the following form:
Display will follow line status in real time. This function may be usedas generic check after installing the control panel or just before performing the Walk Test. Press
ESC
to leave this function.
Anyway,thecontrolpanelwillescape this function after a maximum programmable time-out (see SYSTEM TIME DELAY)
CFP-600-Prog-2.VP Installation and Operating Manual Page 7 Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA
USER MODE | A08 CHANGE PASSW. | G08
| D00 | E00
CHANGE PASSW. | A08 LEV. PASSW. | G08
| D00 | E00
CHANGE PASSW. | A08 LEV. PASSW. | G08 1 0001 | D00
| E00
:User Mode | A08 :Test Mode | G08 :Configuration | D00 :Exit | E00
LEV. 2 PASSW. | A08
| G08 | D00 | E00
TEST MODE | A08 LINE STATUS | G08
| D00 | E00
N= not Alarm
A= Alarm
SH.C= Short circuit
W.CUT= Wire cut
E= Enabled
D= Disabled
E= Excluded
T=Test
NE NE NE NE NE NE NE NE NE NE NE NE
Line nr. 1 Line nr. 5 Line nr. 9
Line nr. 4 Line nr. 8 Line nr. 12
Page 12
CHANGE CONTROLS - ENABLE/DISABLE STATUS
This function allows to disable the following controls:
General Relays (Trouble, Pre-Alarm, Alarm, Sounders)
External Relays (All controls of 16-relay Board)
Release (Both the Release Board channels)
Use
CURSOR
Keys to select one of the following controls:
General relays
External relays
Release
Then press
ENTER
to modify the programming status of the control se- lected. The control panel will display the screen as in the example. Press
ENTER
to Enable or Disable.
Press
ESC
to go back to the main screen.
By programming the panel with disabled controls, the Zone Test LED will switch ON.
»
NOTE: by disabling a control, it will never activate.
SELECT ZONE FOR WALK-TEST MODE
This function let you manually test detector alarms. Press ENTER to have access to Walk-Test function.
During the test, the screen will show:
If during the Walk-Test a sensor alarm is detected the control panel, after a programmable time-out (see Configuration Menu) will carry out zone reset. The operator who has simulated a detector alarm, will see the sensor LED to turn-off, and he will be able to test the next detector. During the Walk-Test the Zone Test LED will flash. In order to accomplish manually the Walk-Test,the operator has to go into WALK TEST menu and clear the number of the zone under test.
DISPLAY FIRMWARE REVISION
By pressing
ENTER
, it is possible to display the Software Revision Number installed on the control panel.
Will you please always quote this number for your assistance requests.
Press
ESC
to go back to the main screen.
Page 8 Installation and Operating Manual CFP-600-Prog-2.VP NOTIFIER ITALIA Rev. B.1 Doc. M-131.1-CFP600-ENG
DIS. CONTROLS | A08 GENER. RELAYS | G08
NO | D00
| E00
DIS. CONTROLS | A08 GENER. RELAYS | G08
NO | D00
Modify Exit | E00
WALK TEST | A08
ZONE | G08
0 | D00
| E00
Press ENTER
WALK TEST | A08
ZONE | G08
0 01 | D00
| E00
Use CURSOR keys to Select the zone to be tested
TEST MODE | A08 WALK ZONE | G08 Z.01 A:000 | D00
| E00
Zone nr. in Walk Test
Total alarms detected during the Test
WALK TEST | A08
ZONE | G08
1 | D00
| E00
Press ENTER
Use CURSOR keys to select 00
TEST MODE | A08 FIRMWARE REVIS.| G08
| D00 | E00
FIRMWARE REVIS.| A08
| G08
CFP-600/170397 | D00
| E00
WALK TEST | A08
ZONE | G08
1 00 | D00
| E00
Page 13
CHANGE LEVEL 2 PASSWORD
By pressing
ENTER
, it is possible to select the level whose password has to be changed.
Use
CURSOR
keys, to select the level number, then press
ENTER
to confirm.
The programmable password may be made up of 1 to 4 figures (num- bers).
To Enter a figure:
Select the desired number with cursor keys
Press ENTER
To accomplish the programming press
ENTER
a second time. If you do not want to modify the programming, press
ESC
CONFIGURATION MENU - LEVEL 4
Press ENTER to go into Configuration Functions and the display will show:
Press
RESET
key. Level 4 Password will be required. Enter the Password by using
CURSOR
keys.
On the display will appear the first available function in the CONFIGURATION mode. Use cursor keys to display the desired function, choosing among:
CHANGE ZONES - INCLUDE/EXCLUDE STATUS
PROGRAMMING THE CBE EQUATION
CHANGE SERVICE ENABLING STATUS
CHANGE ZONE PARAMETERS
CHANGE VERIFICATION TIMES
PROGRAMMING THE RELAY MAPPING
ENABLING THE RELAY SIGNAL SILENCE
CHANGE ZONE DESCRIPTION
CHANGE SYSTEM TIME DELAY
CHANGE ALARM TIME PARAMETERS
PROGRAMMING THE ALARM CONTROL MODULATION
PROGRAMMING THE RELEASE ZONE MAPPING
CHANGE RELEASE TIME
SELECT EVENT TYPE FOR HISTORICAL LOG
PROGRAMMING THE SYSTEM NAME
CLEARING THE CONTROL PANEL MEMORY
CHANGE LANGUAGE DISPLAY
CHANGE ALL LEVEL PASSWORDS
Press
ESC
to go back to the main screen.
CFP-600-Prog-2.VP Installation and Operating Manual Page 9 Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA
TEST MODE | A08 MODIFY PASSW. | G08
| D00 | E00
MODIFY PASSW. | A08 LEV. PASSW._|G08
| D00 | E00
MODIFY PASSW. | A08 LEV.2 PASSW._ | G08 2 0002 | D00
| E00
:User Mode | A08 :Test Mode | G08 :Configuration | D00 :Exit | E00
LEV.4 PASSW. | A08
| G00 | D00 | E00
CONFIGURAT. | A08 INC./EXC.ZONES| G00
| D00 | E00
Page 14
CHANGE ZONES - INCLUDE/EXCLUDE STATUS
An EXCLUDED Zone does not signal neither Alarms nor Troubles.
Use
CURSOR KEYS
to enter the zone number on which operate.
By pressing
ENTER
key, on the display appears the status of the zone
selected.
Press
ENTER
to modify the zone status.
If you do not want to change the zone status, press
ESC
.
»
NOTE: A)
PROGRAMMING THE CBE EQUATIONS
This function allows to map a set of events to each LOGIC ZONE (from the 13th one to the 20th), to activate it. The admitted events are:
Alarm or Prealarm for initiating circuits (from 1 to 12);
Activated, for logic zones (from 13 to 20)
Maximum 4 events mapped to a logic zone can be programmed.
Each event is connected to the other by two types of conditions:
OR= it means either...or
AND= it means both...and
Example:
Follow this procedure to performe the programming:
Phase A)
Enter the zone number for which you wish to program the equation (13 to 20)
Now, enter 2 data: a zone number + its status (Alarm or Prealarm).
It is possible entering an operator of AND or OR with other zones and to continue the equation.
Page 10 Installation and Operating Manual CFP-600-Prog-3.VP NOTIFIER ITALIA Rev. B.1 Doc. M-131.1-CFP600-ENG
INC./EXC.ZONES |A08 Z. __ |G08
|D00 |E00
INC./EXC. ZONES|A08 Z. 01 NORMAL |G08
|D00
Modify Exit |E00
Zone Status Detector Alarms Detector Troubles
Enabled YES YES
Disabled NO YES
Excluded NO NO
B) if a zone is EXCLUDED, any operation on it, is inhibited (See config. Menu - Lev. 4 about Exclusion function)
DESCRIPTION CHARACTERS TO BE PROGRAMMED
Result Zone nr. 20 active if... Z. 20
Event nr. 1 Zone nr. 1 in Alarm status 01 A
Condition or +
Event nr. 2 Zone nr. 2 in Pre-Alarm status 02 P
EQUATION
CONFIGURATION
EQUATION for Z. _ EQUATION for Z.2_ EQUATION for Z. 20
Page 15
During these steps, it needs to follow some rules:
Use
CURSOR
keys to select the field to program.
Use
ENTER
key to go into the field and modify it.
If the cursor on the display is a blinking square, it means you are selecting a field. If the cursor on the display is a blinking line, it means you are programming a field value.
While programming or modifying a field:
Use
CURSOR
keys to set a value for the character, in the cursor position.
Press
ENTER
to confirm the value.
As far as the zone number is concerned, after the second figure programming, it needs to press
ENTER
again to confirm the complete zone number.
Example:(after phase A):
Phase B) - program the Zone number:
Phase C) - Select the Zone status:
CHANGE SERVICE ENABLING STATUS
This section includes several enabling functions and services, supplied by the control panel.
Select the desired function by using
CURSOR
keys, then press
ENTER
.
In this example is showed only how to modify the first function, as for the other ones, the procedure is exactly the same. Press
ENTER
to ENABLE and DISABLE the function.
If you DO NOT WANT to modify, press
ESC
.
CFP-600-Prog-3.VP Installation and Operating Manual Page 11 Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA
EQUATION for Z. 20
EQUATION for Z.20
1
EQUATION for Z. 20
12
EQUATION for Z. 20
12A
EQUATION for Z.20
12P
Now:
- press ESC to accomplish the equation
- press UPWARDS CURSOR Key to go on.
EQUATION for Z. 20
12P+
Select an operator (+ means OR, * means AND) by using CURSOR keys. After confirming with ENTER, repeat the procedure starting from phase B.
Initiating circuit for Remote Reset
Initiating circuit for Remote Signal Silence
Mains Trouble Signal
Battery trouble Signal
Power Supply Trouble Enabling
Sounder Trouble Enabling
16-relay board Installation
Release board Installation
Enabling operation of Manual release 1
Enabling operation of Manual release 2
REMOTE RESET |A08 ENABLING |G08
YES |D00
|E00
REMOTE RESET |A08 ENABLING |G08
YES |D00
Modify Exit |E00
REMOTE RESET |A08 ENABLING |G08
NO |D00
Modify Exit |E00
Page 16
CHANGE ZONE PARAMETERS
This section allows to program the following functions, for each zone.
2 THRESHOLDS for each ZONE (this programming allows to detect an alarm coming from 2 different detectors of the same zone, and use only 1 zone for exstinguishing purposes)
ZONE ALWAYS IN NIGHT MODE (for fire alarm push buttons)
RESET RELAY (this programming enables the resettable voltage output to be activated or not when the zone is in Walk Test Mode or the zone verification time is enabled).
Press
ENTER
to start the programming
Use
CURSOR
keys and
ENTER
key to select the zone
Press
ENTER
to have access to the Modify menu
Press
ENTER
to modify
CHANGE VERIFICATION TIMES
This section allows to program the alarm verification time for the single zones.
Press
ENTER
Use
CURSOR
Keys to select the zone number on which you wish
to modify the verification time, then press
ENTER
to confirm the
zone number.
Press twice
ENTER
key.
Use
CURSOR
Keys and
ENTER
to set the verification time.
It is possible to program a 999-second maximum time.
Page 12 Installation and Operating Manual CFP-600-Prog-3.VP NOTIFIER ITALIA Rev. B.1 Doc. M-131.1-CFP600-ENG
ZONE PARAMETER |A08 CONFIGURATION |G08
|D00 |E00
Z. __ |A08
|G08 |D00 |E00
Z. 01 |A08 2 AL. THRESH. |G08
|D00 |E00
Z. 01 |A08 2 AL. THRESH. |G08
NO |D00
Modify Exit |E00
VERIF. TIME |A08 CONFIGURATION |G08
|D00 |E00
VERIF. TIMES |A08 Z. __ |G08
|D00 |E00
VERIF. TIMES | Z. 01 |
| |
VERIF. TIMES | Z. 01 |
0 __ |
|
Page 17
PROGRAMMING THE RELAY MAPPING (on optional 16-relay board)
This function allows to map each zone (1-20, 12 lines + 8 logic zones) to a control of those available on the optional 16-re- lay board.
Press
ENTER
to have access to the function.
By using
CURSOR
key, enter the ZONE number.
Press
ENTER
to confirm.
By using
CURSOR
key, enter the RELAY number.
Press
ENTER
to confirm.
»
NOTE: by entering the relay number equals to 0, it means that no relay will be mapped. In addition, it is possible to map the same control relay to more zones, obtaining the OR function of the zone.
ENABLING THE RELAY SIGNAL SILENCE (on optional 16-relay board)
This function allows to enable the signal silence of each control relay.
Press
ENTER
Use
CURSOR
keys to select the relay number to be changed.
Press
ENTER
to confirm
.
Press
ENTER
to enable and disable the signal silence.
CFP-600-Prog-3.VP Installation and Operating Manual Page 13 Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA
RELAY MAPPING | A00 CONFIGURATION | G00
| D00 | E00
RELAY MAPPING | A00 Z. 01 | G00
0 02 | D00
| E00
RELAY MAPPING | A00 Z.01 | G00
| D00 | E00
IMPORTANT NOTE: CONTROL PANEL ZONES
During the programming 20 ZONES are available.
And exactly:
The first 12 zones are the line initiating circuits (DETECTOR ZONES)
Zones 13 to 20 are LOGIC ZONES which can be used to program the actions to carry out in case of Alarm or Prealarm condition.
RELAY PROGR. | A00 CONFIGURATION | G00
| D00 | E00
R. __ | A00
| G00 | D00 | E00
R. 02 |A08 SILENCEABLE |G08
YES |D00
Modify Exit |E00
Page 18
CHANGE ZONE DESCRIPTION
This function allows to program a label (16 characters max), for each zone.
Press
ENTER
to have access to the function.
Use
CURSOR
keys to enter the zone number, then press
ENTER
to confirm.
Use
CURSOR
keys to enter the letters, then press
ENTER
after pressing each character.
CHANGE SYSTEM TIME DELAY
This section shows the programmings of several time delays, supplied by the control panel.
Select the function from the menu by using
CURSOR
keys, and press
ENTER
.
The programming is carried out as the previous one, except that it is possible to enetr different figures according to the time you are programming.
To enter the figures use
CURSOR
keys and press
ENTER
key to confirm.
Maximum Time in Day Mode
By pressing
ENTER
key the following display appears
Enter the hours by using the
CURSOR
keys
To accomplish the programming press
ENTER
key
»
NOTE: The programming time cannot exceed 18 hours.
Page 14 Installation and Operating Manual CFP-600-Prog-3.VP NOTIFIER ITALIA Rev. B.1 Doc. M-131.1-CFP600-ENG
ZONE DESCRIPT. | A00 CONFIGURATION | G00
| D00 | E00
ZONE DESCRIPT. | A00 Z. __ | G00
| D00 | E00
ZONE DESCRIPT. | A00 Z. 02 | G00
| D00
FIRST LOOR | E00
DEFAULT MIN MAX
5 seconds 5 seconds 60 seconds
10 seconds 10 seconds 60 seconds
2 minutes 0 minutes 60 minutes 30 seconds 001 second 120 seconds 30 seconds 001 second 120 seconds 30 seconds 001 second 120 seconds 60 minutes 10 minutes 60 minutes
Reset time
Waiting Time after an alarm in Walk Test
Maximum Time in Day Mode
Minimum Time for Mains Trouble signal
Prealarm control Stand-by Time
Alarm control Stand-by Time
Sounder control Stand-by Time
Memory Verification Time
MAX SYSTEM TIME | A00 IN DAY MODE | G00
1h |D00
| E00
MAX SYSTEM TIME | A00 IN DAY MODE | G00
1 h __ | D00
| E00
Page 19
CHANGE ALARM TIME PARAMETER
This section shows the programmings of several times, supplied by the control panel.
Select the function from the menu by using
CURSOR
keys, and press
ENTER
The programming is carried out as the previous one, except that it is possible to enetr different figures according to the time you are programming. To enter the figures use
CURSOR
keys and press
ENTER
key to confirm.
* Note 1 - ALARM CONTROL: to program a duration time equal to INFINITE, that is to say til the RESET, enter: 00-00
»
NOTE: the above list shows the control panel factory-default times. The same times are programmed in case of PROGRAMMING CLEARING
PROGRAMMING THE ALARM CONTROL MODULATION
This function allows to modify the relay operating frequency of: ALARM, PREALARM and SOUNDERS, when activated. It is possible to achieve pause and activation times multiple of 1 second which may be programmed in cycles of 8 seconds repetitive.
SOUND EXAMPLES:
Example Nr. 1= two 1-second beeps + one 3-second sound (repeated) Example Nr. 2= 2-second beep (repeated) Example Nr. 3= 3-second beep (repeated)
If the sequence programming is carried out entering a value equal to 1, a steady sound will be obtained (this is the factory- default value).
The following controls may be programmed:
PREALARM
ALARM
SOUNDER
Use
CURSOR
keys to select the control, then press
ENTER
to modify it.
Use
CURSOR
keys to program 0/1 values, then press
ENTER
to confirm the programming.
The same as for the other functions, press
ESC
key to leave the function without changing the existing programming.
CFP-600-Prog-4.VP Installation and Operating Manual Page 15 Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA
DEFAULT MIN MAX
30 seconds 1 second 09-59
2 minutes 0 seconds 19-59 30 seconds 0 seconds 19-59 20 minutes 20 minutes 99-59
Prealarm Time (Day mode)
Alarm Time (* Note 1)
Sounder Control Activation Time
Walk-Test and Line test max Time
0 1 0 1 0 111
01100 11 0
111 0 111 0
ALARM MODULAT. |A08 CONFIGURATION |G08
|D00 |E00
ALARM MODULAT. |A08 PREAL. SEQUENCE|G08
11111111 |D00
|E00
Page 20
PROGRAMMING THE RELEASE ZONE MAPPING
This function allows to map TWO detecting zones or a single 2-threshold zone, to one of the two release channels, provi- ded that the optional release board has been installed.
Use
CURSOR
keys to program each figure, then press
ENTER
to confirm. Press
ESC
to save.
CHANGE RELEASE TIME
This function allows to program timings concerning the release channel management. Programming is valid for both the channels.
For further details see diagram on Appendix A (Release Time).
SELECT EVENT TYPE FOR HISTORICAL LOG
This function allows to select which of the following events store in the historical Log:
TROUBLES (Line and System Troubles)
RESET (control Panel Reset)
CONFIGURATION (Configuration Menu Access)
TEST MODE (Control Panel in Test Mode)
Press
ENTER
to have access into the Historical Log Functions.
The display shows the first function available.
Press
CURSOR
keys to select the desired function.
Press
ENTER
to change the programming.
Page 16 Installation and Operating Manual CFP-600-Prog-4.VP NOTIFIER ITALIA Rev. B.1 Doc. M-131.1-CFP600-ENG
RELEASE ZONE |A08 CONFIGURATION |G08
|D00 |E00
RELEASE ZONE |A08 CHANNEL Nr. __ |G08
|D00 |E00
RELEASE ZONE |A08 CHANNEL Nr. 2 |G08
|D00 |E00
RELEASE ZONE |A08 CHANNEL Nr.2 |G08 Z. __ Z. __ |D00
|E00
DEFAULT MIN MAX
30-00 1 minute 59-59 00-30 5 seconds 4-59 00-05 00-00 19-59 00-30 10 4-59
2nd ALARM Waiting Time
EVACUATION Time
Release Actuation Time (0000 INFINITE)
Release Repetition (Waiting Time before repeating the release, in case of negative result).
HISTORICAL LOG |A08 CONFIGURATION |G08
|D00 |E00
TROUBLE |A08
HISTORICAL LOG |G08
|D00 |E00
TROUBLE |A08
HISTORICAL LOG |G08
YES |D00
Modify Exit |E00
Page 21
PROGRAMMING THE SYSTEM NAME
This programming is referred to the max 16-character programmable label which appears on the display when no Alarms or Troubles exist.
Press
ENTER
Use
CURSOR
keys to enter the letters, then press
ENTER
after entering each character
Press
ESC
key if you DO NOT WANT to change the programming.
CLEARING THE CONTROL PANEL MEMORY
This function allows to clear the programmings and to reset the factory-default values. Select the desired operation on the menu and press ENTER. After confirming the operation a control panel restart will be carried out, giving the factory-default values.
CHANGE LANGUAGE DISPLAY
Seven languages are availble on the EPROM installed on the control panel. The user may choose in which language read the messages that appear on the liquid crystal display.
Use
CURSOR
keys to select the number corresponding to the desired language.
Press
ENTER
key
The abbreviation used refer to the following languages:
»
On request, it is also available a Software Version in ENGLISH and RUSSIAN CYRILLIC characters.
CFP-600-Prog-4.VP Installation and Operating Manual Page 17 Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA
SYSTEM NAME |A08 CONFIGURATION |G08
|D00 |E00
SYSTEM NAME |A08 CONFIGURATION |G08
|D00
NOTIFIER |E00
MEMORY CLEARING|A08 CONFIGURATION |G08
|D00 |E00
MEMORY CLEARING|
| |
: YES Exit |
Press
ENTER
to confirm.
LANGUAGE SEL. |A08 CONFIGURATION |G08
|D00 |E00
LANGUAGE SEL. |A08 1:I 2:E 3:F 4:DU |G08 5:ES 6:D 7:SV __ |D00
|E00
EPROM/STD
1:I = ITALIAN
2:E = ENGLISH
3:F = FRENCH
4:DU= DUTCH
5:ES= SPANISH
6:D = GERMAN
7:SV= SWEDISH
EPROM/EST
1:EN = ENGLISH
2:M = MACEDONIAN
3:Y = SERBIAN
4:U = HUNGARIAN
5:SLO= SLOVENIAN
6:RO = ROMANIAN
7:C = CROATIAN
EPROM/RUSSIAN
1:EN= ENGLISH
2:R = RUSSIAN
3:I = ITALIAN
Page 22
CHANGE ALL LEVEL PASSWORDS
Press
ENTER
to select the level whose password has to be modified.
Use
CURSOR
keys to select the level number and press
ENTER
to
confirm
The programmable Password may be made up of 1 to 4 figures (numbers 0000 to 9999). Password lenght is programmable.
To enter a figure it needs to select the desired number by using
CURSOR
keys and press
ENTER
to confirm it.
Press
ENTER
again to accomplish the programming.
Press
ESC
if you DO NOT WANT to modify the programming.
Page 18 Installation and Operating Manual CFP-600-Prog-4.VP NOTIFIER ITALIA Rev. B.1 Doc. M-131.1-CFP600-ENG
PASSWORD CHANGE|A08 CONFIGURATION |G08
|D00 |E00
PASSWORD CHANGE|A08 LEV.3 PASSW.__ |G08
1 0003 |D00
|E00
PASSWORD CHANGE|A08 LEV. PASSW. __ |G08
|D00 |E00
Page 23
APPENDIX-A-
Control Panel Operation in DAY Mode (Day/Night LED= ON)
Control Panel Operation in NIGHT Mode (Day/Night Led = OFF)
CFP-600-Prog-5.VP Installation and Operating Manual Page 19 Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA
ZONE ALARM
PREALARM LED= FLASHING
DISPLAY= 01 : ZXX PREAL
PREALARM RELAY= ON
BUZZER= STEADY SOUND
PREALARM LED= OFF
PREALARM RELAY= OFF
ALARM LED= FLASHING
ALARM RELAY= ON
SOUNDER RELAY= ON
SIGNAL SILENCE LED= OFF
BUZZER= STEADY SOUND
DISPLAY= 01: ZXX AL
SIGNAL SILENCE
EXPIRED PREALARM TIME
SIGNAL SILENCE
ALARM LED= ON
SIGNAL SILENCE LED= ON
ALARM RELAY= OFF
SOUNDER RELAY= OFF
BUZZER= SILENT
DISPLAY= 01: ZXX AL
RECOGNITION TIME EXPIRED
RESET
YES
ZONE ALARM
ALARM LED= FLASHING
ALARM RELAY= ON
SOUNDER RELAY= ON
BUZZER= STEADY SOUND
DISPLAY= 01: ZXX AL
CONTROL TIMINGS EXPIRED
SIGNAL SILENCE
PREALARM LED= ON
PREALARM RELAY= OFF
SIGNAL SILENCE LED= ON
BUZZER= INTERMITTENT SOUND
DISPLAY= 01 : ZXX PREAL
YES
ALARM LED= ON
ALARM RELAY= OFF
SOUNDER RELAY= OFF
BUZZER= SILENT
DISPLAY= 01: ZXX AL
SIGNAL SILENCE LED
=ON
YES
NO
Manual Evacuation?
YES
NO
NOTE:ZONE ALARM
Single threshold Zone: First Alarm= Zone in Alarm status
Double threshold Zone: First Alarm= Zone in Prealarm status Second Alarm= Zone in Alarm status
NO
ALL SIGNALS
=
OFF
YES
NOTE:ZONE ALARM
Single threshold Zone: First Alarm= Zone in Alarm status
Double threshold Zone: First Alarm= Zone in Prealarm status Second Alarm= Zone in Alarm status
Page 24
Automatic Release Channel Management
Page 20 Installation and Operating Manual CFP-600-Prog-5.VP NOTIFIER ITALIA Rev. B.1 Doc. M-131.1-CFP600-ENG
YES NO
NO
NO
FIRST ALARM
PREALARM LED= FLASHING PREALARM RELAY= ON BUZZER= STEADY SOUND
INHIBITION?
RELEASE INHIBITION LED= FLASHING
SIGNAL SILENCE?
PREALARM LED= ON PREALARM RELAY= OFF BUZZER= intermittent sound Release Inhibition LED=Flashing Silenced control LED= ON
SECOND ALARM
ALARM LED= Flashing ALARM RELAY= ON SOUNDER RELAY= ON EVACUATION RELAY= ON EVACUATION LED= ON BUZZER= Steady sound Release Inhibition LED=Flashing
RELEASE INHIBITED
WAITING FOR RESET
SIGNAL SILENCE?
PREALARM LED= ON PREALARM RELAY= OFF BUZZER= Intermittent sound SILENCED CONTROL LED= ON
Second alarm
Wait Time
= Expired?
SECOND ALARM
ALARM LED= FLASHING ALARM RELAY= ON SOUNDER RELAY= ON EVACUATION RELAY= ON EVACUATION LED= ON BUZZER= STEADY SOUNDER
Detector Line Automatic RESET
Prealarm LED= OFF Prealarm RELAY= OFF Silenced Control LED= OFF BUZZER= OFF
WAITING FOR RESET
SIGNAL SILENCE?
ALARM RELAY= OFF SOUNDER RELAY= OFF SILENCED CONTROL LED= ON BUZZER= INTERMITTENT SOUNDER
EVACUATION TIME
= EXPIRED?
Release Actuation
Release LED= ON
PRESSURE-METER ACTIVATED?
RELEASE ACTUATION
RELEASE ACTUATION= 3?
TROUBLE LED= FLASHING TROUBLE RELAY= ON BUZZER= INTERMITTENT SOUND
WAITING FOR RESET
EVACUATION 1 LED= ON RELEASE 1 LED= ON RELEASE 1 TROUBLE LED= FLASHING TROUBLE RELAY= ON TROUBLE LED= ON BUZZER= INTERMITTENT SOUND
YES
NO
NO
YES
YES
YES
NO
NOTE:ZONE ALARM
Single threshold Zone: First Alarm= Zone in Alarm status
Double threshold Zone: First Alarm= Zone in Prealarm status Second Alarm= Zone in Alarm status
»
NOTE: In “battery trouble” condition the release never occurs.
Page 25
APPENDIX B - MENU ITEM LIST
CFP-600-Prog-5.VP Installation and Operating Manual Page 21 Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA
USER MENU
ENABLE RELEASE CHANNELS DISPLAY ZONE STATUS CHANGE ZONE STATUS / ENABLE-DISABLE CHANGE DAY-NIGHT MODE DISPLAY HISTORICAL LOG CHANGE PREALARM RECOGNITION TIME ALARM COUNTER CHANGE DATE/TIME CHANGE LEVEL 1 PASSWORD
TEST MENU
DISPLAY LINE STATUS CHANGE CONTROLS - ENABLE/DISABLE STATUS SELECT ZONE FOR WALK TEST MODE DISPLAY FIRMWARE REVISION CHANGE LEVEL 2 PASSWORD
CONFIGURATION MENU
CHANGE ZONES - INCLUDE/EXCLUDE STATUS PROGRAMMING THE CBE EQUATION CHANGE SERVICE ENABLING STATUS CHANGE ZONE PARAMETERS CHANGE VERIFICATION TIMES PROGRAMMING THE REALY MAPPING ENABLING THE RELAY SIGNAL SILENCE CHANGE ZONE DESCRIPTION CHANGE SYSTEM TIME DELAY CHANGE ALARM TIME PARAMETERS PROGRAMMING THE ALARM CONTROL MODULTION PROGRAMMING THE RELEASE ZONE MAPPING CHANGE RELEASE TIME SELECT EVENT TYPE FOR HISTORICAL LOG PROGRAMMING THE SYSTEM NAME CLEARING THE CONTROL PANEL MEMORY CHANGE LANGUAGE DISPLAY CHANGE ALL LEVEL PASSWORDS
Reset Time Waiting time after an alarm in Walk test Maximum Time in Day Mode Minimum Time for Mains Trouble signal Prealarm control Stand-by Time Alarm control Stand-by Time Sounder control Stand-by Time Memory Verification Time
Initiating Circuit for Remote Reset Initiating Circuit for Remote Signal Silence Mains Trouble Signal Battery Trouble Signal Power Supply Trouble Enabling Sounder Trouble Enabling 16-relay Board Installation Release Board Installation Enabling operation of Manual Release 1 Enabling operation of Manual Release 2
Prealarm Time Alarm Time Sounder Control Activation Time Walk-Test and Line test max Time
2nd Alarm Waiting Time Evacuation Time Release Actuation Time Release Repetition
Troubles Reset Configuration Test Mode
Page 26
INSTALLATION
Control Panel Internal view
Page 22 Installation and Operating Manual CFP-600-Instal-1.VP NOTIFIER ITALIA Rev. B.1 Doc. M-131.1-CFP600-ENG
CENTRALE ATTIVA
08-08-93 16 : 09
CENTRALE ATTIVA
08-08-93 16 : 09
INIBIZ.SPEGN.2
GUASTOSPEGN.2
SCARICA2
EVACUAZIONE2
INSERVIZIO
GIORNO/ NOTTE
USCITETACITATE
ZONEDISINSER.
GUASTOBATT.
GUASTORETE
GUASTOGEN.
PREALLARME
ALLARMEGEN.
INIBIZ.SPEGN.1
GUASTOSPEGN.1
SCARICA1
EVACUAZIONE1
220 VAC Input
Flat cable for optional boards
2-Release Channel Optional board
16-relay
Optional board
Initiating Circuits
2x6 Ah batteries
HOW OPENING THE PANEL
A) unscrew the two screws placed on the bottom part
of the cabinet B) lower the cover C) remove the cover horizontally
Invert the procedure to close the panel
DIMENSIONS
A: 388 mm. B: 305 mm. C: 125 mm.
4 fixing back holes: diam. 7.9 mm.
(wheel-base 243x319 mm.)
Page 27
CFP-600-E Control Panel Wiring
1
15
EXTERNAL N.O. SILENCE PUSH BUTTON
220 VAC MAINS
MAINS FILTER
MAINS
FUSE
5x201A
CNA
EXTERNAL N.O. RESET PUSH BUTTON
+Z.12
GND
+Z11
+Z10
GND
+Z.9
+Z.8
GND
+Z.7
+Z.6
GND
+Z.5
+Z.4
GND
+Z.3
+Z.2
GND
+Z.1
2 X BATTERIES ( 12V , 6Ah Max.)
24V Ancillary device Fuse (1AT)
Battery Fuse (3,15AF)
External Sirens
1AT FUSE
FLAT CABLE to :
16-Relay Board
2-Release channel Board
4
3
F3
2
1
F1
F2
TRANSFORMER
External Power Supply Input
24 VDC Nominals
1
3
NO*
C
NC
C
NO
NC
C
NO
NC
-
+
1
10
Watch-Dog Enabling DO NOT TAMPER
W-1
PROG
OFF
W-3
OFF
ON
CPU Reset
TROUBLE
PREALARM
ALARM
SIRENS
W1=PROG - Programming Enabling W1=OFF - Disabled Programming
SIREN
BELL
W-2
SIREN CONNECTION TYPE W2=SIREN - EOL Res.2K7- Check SHORT C. and OPEN C. W2=BELL - Diode - Check OPEN CIRCUITt
CPU Reset = Panel uP Reset WD Reset = WD Trouble Reset (it turns off the WD-CPU TRB Led)
5
1
-
+
2.7K 1/4W
Polarized
Electronic SIREN
SUPERVISED
WD
Reset
Keyboard key
24V RESETTABLE OUTPUT for ancillary devices
24V NOT RESETTABLE OUTPUT for ancillary devices
18
2.7K
1/4W
1K
1/2W
N.O.
Conventional Detector with relay output or Push Button N.O.
Conventional Detector 2451 - 5451 - 1451
2.7K 1/4W
+
2
3
4
1
-
2
3
4
1
LED Indicator
LED Indicator
2 Threshold Zone detector wiring:
Connect a 560 Ohm 1/2 W EOL resistor each detector
2.7K 1/4W
560 Ohm
1/2 W
560 Ohm
1/2 W
+
2
3
4
1
-
2
3
4
1
BELL
DIODE
5
876
1
432
M4
Receiver 6424
N.O.
Alarm Contact
Transmitter 6424
1K
1/2 W
2.7K 1/4W
Doc.M-131.1-CFP600-ENG Installation and Operating Manual NOTIFIER ITALIA CFP-600-Cablrv21-E.cdr Rev. B.1 Page 23
+
-
+
-
+
-
+
-
+
-
+
-
+
-
* When powered
Page 28
OPTIONAL BOARDS
16-RELAY OPTIONAL BOARD
CFP-600-Instal-1.VP Installation and Operating Manual Page 24 Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA
1 5 9 132 6
10
14
3 7 11 15
4 8 12 16 17 21 25 2918 22
26
30
19 23 27 31
20 24 28 32
CENTRALE ATTIVA
08-08-93 16 : 09
CENTRALE ATTIVA
08-08-93 16 : 09
CONNECTOR TO RELEASE OPT. BOARD
N.O.
N.C.
CFP-600-E Control Panel Main card
Cabinet slide to fix the boards
Spacer to fix the board
Release board
16-RELAY board
Spacers to fix the board
Flat cable for optional boards
Spacer to fix the board
Main board connection Release board connection
JUMPER FOR RELAY CONTACT SELECTION
OPEN or CLOSED
CONTROL CONNECTOR
CONNECTOR TO MAIN BOARD
RELAY CONTACTS: 30 VDC - 3A
NOTE: place the jumpers according to the desired type of contact.
TERM. RELAY Nr. CONTACT
1 1 Common 2 NO/NC 3 2 Common 4 NO/NC 5 3 Common 6 NO/NC 7 4 Common 8 NO/NC 9 5 Common
10 NO/NC
11 6 Common 12 NO/NC 13 7 Common 14 NO/NC 15 8 Common 16 NO/NC
TERM. RELAY Nr. CONTACT
17 9 Common 18 NO/NC 19 10 Common 20 NO/NC 21 11 Common 22 NO/NC 23 12 Common 24 NO/NC 25 13 Common 26 NO/NC 27 14 Common 28 NO/NC 29 15 Common 30 NO/NC 31 16 Common 32 NO/NC
Page 29
The CFP-600 Control Panel can manage 2-automatic release channels via the SK-2SP optional board. The release lines are supervised against wire cut therefore cartridges or electro-valves used have to support 1 mA super- vising current. Follow the manufacturer's instructions as for the exploding cartridges or electro-valves connection. As far as wiring is concerned use shielded cable by connecting the shield to the panel ground. Each control can support an electro-valve powered with 24 VDC with a maximum power equal to 15 W.
Page 25 Installation and Operating Manual CFP-600-Instal-1.VP NOTIFIER ITALIA Rev. B.1 Doc. M-131.1-CFP600-ENG
M-2 TERMINAL BLOCK
TERM. SIGNAL FUNCTION
1 + 24 VDC PSU 2 - GND
-
+
-
-
+
+
NOTE
: the linesnotused must be closed with a 2K7 ¼ W end-of-line-resistor
-
+
-
+
-
+
-
+
TYPICAL CONNECTIONS
PRESSURE-METER 1
RELEASE 1 INHIBITION
RELEASE 1 OUTPUT
}
NOTE
: connect with a faston to the panel cabinet and connect the latter to the ground
2K7 ¼ W
10-Ohm- 1 W
End of Line resistor
10-Ohm- 1 W
End of Line resistor
PRESSURE-METER 2
RELEASE 2 INHIBITION
MANUAL RELEASE 1 PUSH BUTTON (N.O)
MANUAL RELEASE 2 PUSH BUTTON (N.O)
EVACUATION 1 OUTPUT N.O. CONTACT RELAY
EVACUATION 2 OUTPUT N.O. CONTACT RELAY
RELEASE 1 OUTPUT
RELEASE 2 OUTPUT
TO M4-1 TERMINAL BLOCK
TO M4-2 TERMINAL BLOCK
24 VDC Power supply
FLAT CABLE TO MAIN BOARD OR RELAY BOARD
2-RELEASE CHANNEL OPTIONAL BOARD
M-1 TERMINAL BLOCK
TERM. SIGNAL FUNCTION
1 NC Pressure-meter 1 2 - GND 3 NC Pressure-meter 2 4 NC Release 1 Inhibition 5 - GND 6 NC Release 2 Inhibition 7 Balanced Manual Release 1 Push button 8 - GND 9 Balanced Manual Release 2 Push button
10 C Channel 1 evacuation relay
11 NO 12 C Channel 2 evacuation relay 13 NO 14 + Channel 1 Release output 15 - 16 + Channel 2 Release output 17 -
RELEASE 2 OUTPUT
RELEASE 1 OUTPUT
RELEASE 2 OUTPUT
SHIELDED CABLE
SHIELDED CABLE
SHIELDED CABLE
SHIELDED CABLE
ELECTRO-VALVE
ELECTRO-VALVE
CARTRIDGE
CARTRIDGE
Page 30
ELECTRICAL FEATURES
q POWER SUPPLY
The CFP-600 Control Panel is normally powered by 220 VAC mains. In case of mains trouble back-up batteries allow operation for a limited time. Power Supply input= Voltage: 220 VAC monophase +10%, -15% max., Frequency: 50 Hz +/- 0,5 Hz.
Power Supply unit consists of two parts: a) Control panel power supply, optional boards and external devices (detectors and controls); b) Back-up battery-charger.This part includes an input to power the whole system via a 24 V. external power supply unit.
This may be useful to use a single set of batteries in addition to the external PSU, in case of internal power low.
q CONTROLS
a) Control Panel power supply, optional boards and external devices:
Voltage: 27,6 VDC
Max. current: 1,3 A (for: panel, detectors, controls and user controls)
b) Back-up battery-charger:
Voltage: 27,6 VDC
Max current: 400 mA
Nr. of batteries that may be connected:2x12V/max6Ah
Battery Trouble Threshold: 22,4 V
Re-charge Time (batteries run down): about 10 hours.
c) Detector Line power supply:
Voltage: 27,5 V
Current: max 1 A
d) User Output:
Resettable 24 VDC output
Non-resettable 24 VDC output
q INPUTS
Via external power supply:
Input Voltage: 24 VDC minimum - 27,6 VDC max
Input Ripple : 200 mV max
Back-up battery consumption, in case of mains trouble:
Control Panel main board: 230 mA
16-relay board: 100 uA (no relay activated)
Release board: 20 mA
q DETECTOR CONNECTION LINES
End-of-line resistor
: it must be lower than 40 Ohm,
type of cable:
it must be a two-wire shielded cable.
Table of minimum sections according to the line length:
Up to 500 mt.: 2 x 0.5 mm2cable
Up to 1000 mt.:2x1mm2cable
Up to 1500 mt.: 2 x 1,5 mm2cable
Up to 2000 mt.:2x2mm2cable
Up to 2500 mt.: 2 x 2,5 mm2cable
Follow the below listed instructions for wiring: a) cables have to be installed far from voltage lines or from possible sources of interferences (electric engines, radio link). b) the shield have to be continuous and grounded in the panel cabinet.
q NR. OF DETECTORS PER LINE
(as for the detectors not listed please, refer to the relevant data sheets for consumption data)
q OUTPUT RELAY FEATURES
Alarm= 1 SPDT switch - 24 VDC-1Aresistive. Prealarm= 1 SPDT switch - 24 VDC-1Aresistive. Trouble= 1 SPDT switch - 24 VDC-1Aresistive. Sounders= 1 supervised contact 24 VDC-1Aresistive.
CFP-600-Instal-1.VP Installation and Operating Manual Page 26 Doc. M-131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA
TYPE OF DETECTOR STAND-BY CURRENT MAX. NUMBER PER LINE
CP-651 E IONIZ.-LOW PROFILE 30 uA 25
SD-651 E PHOTOEL. 100 uA 25
2451 THE-PHOTOEL./THERMAL 120 uA 25
4451 E - THERMAL 100 uA 25
5451 - RATE-OF-RISE 100 uA 25
Page 31
GLOSSARY
q WATCH-DOG: bright signal and circuit which surveys the microprocessor correct operating.
q ZONE ENABLED: zone which detects alarms and troubles.
q ZONE DISABLED: zone which detects only troubles (line cut and short circuit).
q ZONE EXCLUDED: zone which does not detect either alarms or troubles.
q CONTROL PANEL IN “DAY MODE”: operating mode which allows the operator to inspect the event on
field, before signal silence or reset. See flow chart in Appendix A.
q CONTROL PANEL IN “NIGHT MODE”: automatic operating mode. See flow chart in Appendix A.
q CONTROL PANEL POWER ON: signal which latches the control panel power ON.
q RECOGNITION TIME: time which allows the operator to carry out a system recognition in alarm condition
(only with the control panel in “Day Mode”), before alarm and siren output activation.
q WALK TEST: zone manual test which allows to performe a manual detector test.
q VERIFICATION TIME: this function allows to prevent false alarms from a zone. When detecting a zone
alarm with programmed verification time the system performes an automatic zone reset; if detecting an alarm coming from the same zone, before the verification time end, the panel activates the alarm sequence.
q PREALARM OUTPUT ACTIVATION TIME: it is the time during which the prealarm relay remains active in
zone prealarm condition.
q ALARM OUTPUT ACTIVATION TIME: it is the time during which the alarm relay remains active in zone
alarm condiiton.
q SIREN OUTPUT ACTIVATION TIME: it is the time during which the siren relay remains active in zone
alarm condition.
q PREALARM OUTPUT STAND-BY TIME: it is the time during which the prealarm relay remains in OFF po-
sition even in presence of a new zone prealarm. This timing starts when the prealarm output activation time ends.
q ALARM OUTPUT STAND-BY TIME: it is the time during which the alarm relay remains in OFF position
even in presence of a new zone alarm. This timing starts when the alarm output activation time ends.
q SIREN OUTPUT STAND-BY TIME: it is the time during which the siren relay remains in OFF position even
in presence of a new zone alarm. This timing starts when the siren output activation time ends.
q MEMORY VERIFICATION: integrity test of the EEPROM memory (all the user programmings are stored in
the EEPROM memory).
q SIGNAL SILENCE: manual operation which allows in case of zone alarm to silence the buzzer and the si-
lenceable alarm outputs, leaving the event on the LCD display. By pressing again this front panel key the previous cleared outputs reactivate.
q RESET: manual operation which allows in case of zone alarm to silence the buzzer and the not silenceable
alarm outputs as well as allows to clear the alarms on the display.
Page 27 Installation and Operating Manual CFP-600-Gloss-E.VP NOTIFIER ITALIA Rev. B.1 Doc. M.131.1-CFP600-ENG
Page 32
q GENERAL RELAIS: Trouble Relais, Alarm Relais and Siren Relais.
q EXTERNAL RELAIS: 16-Relay optional board.
q DOUBLE THRESHOLD ZONE: by means of this programming the following signals will be displayed in
case of detector alarm: only one detector in alarm= zone in prealarm condition; two or more detectors in alarm= zone in alarm condition.
q ENABLING THE INHIBITION OF THE MANUAL RELEASE INPUT: the operator can avoid that the control
panel consider the status of the inhibiton input of the single release channels. In this case the manual relea­se input activation is always allowed and it will activate the release channel.
LOGICAL DIAGRAM
»
NOTE: In “Battery trouble condition” the release NEVER occurs.
CFP-600-Gloss-E.VP Installation and Operating Manual Page 28 Doc. M.131.1-CFP600-ENG Rev. B.1 NOTIFIER ITALIA
MANUAL RELEASE
INPUT
AUTOMATIC RELEASE FOR TWO
ZONES IN ALARM CONDITION
PROGRAMMING THE
INHIBITION INPUT ENABLING
INHIBITION
INPUT
RELEASE
ACTIVATED DO NOT CARE DISABLED DO NOT CARE YES
DO NOT CARE DO NOT CARE
ACTIVATED ACTIVATED
DISABLED DISABLED
= NOT INHIBITED
= INHIBITED
YES
NO
ACTIVATED ACTIVATED
DO NOT CARE DO NOT CARE
ENABLED ENABLED
= NOT INHIBITED
= INHIBITED
YES
NO
DO NOT CARE DO NOT CARE
ACTIVATED ACTIVATED
DO NOT CARE DO NOT CARE
= NOT INHIBITED
= INHIBITED
YES
NO
MANUAL RELEASE
AUTOMATIC RELEASE
INHIBITION INPUT DISABLED
INHIBITION INPUT
INHIBITION INPUT ENABLED
RELEASE
Page 33
All rights reserved.
All specifications are subject to change without notice.
Delivery times depend on product availability.
Document:
M-131.1-CFP600-ENG
Issue :
07/1999
Rev.:
B.1
NOTIFIER ITALIA S.r.l.
Via Grandi, 22 - 20097 San Donato Milanese (MI)
Tel.: 02/51897.1 (ISDN)
Fax: 02/5189730
http://www.notifier.it
Loading...