While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system—typically made up of smoke detec-
tors, heat detectors, manual pull stations, audible warning devices,
and a fire alarm control panel with remote notification capability—can
provide early warning of a developing fire. Such a system, however,
does not assure protection against property damage or loss of life
resulting from a fire.
The Manufacturer recommends that smoke and/or heat detectors be
located throughout a protected premise following the recommendations of the current edition of the National Fire Protection Association
Standard 72 (NFPA 72), manufacturer's recommendations, State and
local codes, and the recommendations contained in the Guide for
Proper Use of System Smoke Detectors, which is made available at
no charge to all installing dealers. These documents can be found at
http://www.systemsensor.com/html/applicat.html.
A study by the Federal Emergency Management Agency (an agency
of the United States government) indicated that smoke detectors may
not go off in as many as 35% of all fires. While fire alarm systems are
designed to provide early warning against fire, they do not guarantee
warning or protection against fire. A fire alarm system may not provide
timely or adequate warning, or simply may not function, for a variety
of reasons:
Smoke detectors may not sense fire where smoke cannot reach the
detectors such as in chimneys, in or behind walls, on roofs, or on the
other side of closed doors. Smoke detectors also may not sense a fire
on another level or floor of a building. A second-floor detector, for
example, may not sense a first-floor or basement fire.
Particles of combustion or “smoke” from a developing fire may not
reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, or chimneys
may inhibit particle or smoke flow.
• Smoke particles may become “cold,” stratify, and not reach the ceiling
or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air outlets.
• Smoke particles may be drawn into air returns before reaching the
detector.
The amount of “smoke” present may be insufficient to alarm smoke
detectors. Smoke detectors are designed to alarm at various levels of
smoke density. If such density levels are not created by a developing
fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photo-electronic sensing chambers tend to
detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend
to detect fast-flaming fires better than smoldering fires. Because fires
develop in different ways and are often unpredictable in their growth,
neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning of
fires caused by arson, children playing with matches (especially in
bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of flammable materials, etc.).
Heat detectors do not sense particles of combustion and alarm only
when heat on their sensors increases at a predetermined rate or
reaches a predetermined level. Rate-of-rise heat detectors may be
subject to reduced sensitivity over time. For this reason, the rate-ofrise feature of each detector should be tested at least once per year
by a qualified fire protection specialist. Heat detectors are designed to
protect property, not life.
IMPORTANT! Smoke detectors must be installed in the same room
as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or
power. If detectors are not so located, a developing fire may damage
the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert people if these
devices are located on the other side of closed or partly open doors or
are located on another floor of a building. Any warning device may fail
to alert people with a disability or those who have recently consumed
drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause seizures in people
with conditions such as epilepsy.
• Studies have shown that certain people, even when they hear a fire
alarm signal, do not respond or comprehend the meaning of the signal.
It is the property owner's responsibility to conduct fire drills and other
training exercise to make people aware of fire alarm signals and
instruct them on the proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
A fire alarm system
will not operate without any electrical power. If
AC power fails, the system will operate from standby batteries only for
a specified time and only if the batteries have been properly maintained and replaced regularly.
Equipment used in the system may not be technically compatible
with the control panel. It is essential to use only equipment listed for
service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a
central monitoring station may be out of service or temporarily disabled. For added protection against telephone line failure, backup
radio transmission systems are recommended.
The most common cause of fire alarm malfunction is inadequate
maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer's
recommendations, and UL and NFPA standards. At a minimum, the
requirements of NFPA 72 shall be followed. Environments with large
amounts of dust, dirt or high air velocity require more frequent maintenance. A maintenance agreement should be arranged through the
local manufacturer's representative. Maintenance should be scheduled monthly or as required by National and/or local fire codes and
should be performed by authorized professional fire alarm installers
2BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Page 3
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to
the fire alarm control panel.
servicing. The control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting
cables while the unit is energized. Do not attempt to install, service,
or operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software Changes. To
ensure proper system operation, this product must be tested in accordance with NFPA 72 after any programming operation or change in
site-specific software. Reacceptance testing is required after any
change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions
known to be affected by a change must be 100% tested. In addition,
to ensure that other operations are not inadvertently affected, at least
10% of initiating devices that are not directly affected by the change,
up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at 0°C to 49°C
(32°F to 120°F) and at a relative humidity 93% ± 2% RH (non-condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the
system's standby batteries and the electronic components may be
adversely affected by extreme temperature ranges and humidity.
Therefore, it is recommended that this system and all peripherals be
installed in an environment with a nominal room temperature of 1527° C/60-80° F.
Verify that wire sizes are adequate for all initiating and indicating
device loops. Most devices cannot tolerate more than a 10% I.R.
drop from the specified device voltage.
Disconnect all sources of power before
Like all solid state electronic devices this system may operate errati-
cally or can be damaged when subjected to lightning-induced transients. Although no system is completely immune from lightning
transients and interferences, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an
increased susceptibility to nearby lightning strikes. Consult with the
Technical Services if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting cir-
cuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming,
or punching of the enclosure. When possible, make all cable entries
from the sides or rear. Before making modifications, verify that they
will not interfere with battery, transformer, and printed circuit board
location.
Do not tighten screw terminals more than 9 in-lbs. Over-tightening
may damage threads, resulting in reduced terminal contact pressure
and difficulty with screw terminal removal.
Though designed to last many years, system components can fail at
any time. This system contains static-sensitive components. Always
ground yourself with a proper wrist strap before handling any circuits
so that static charges are removed from the body. Use static-suppressive packaging to protect electronic assemblies removed from
the unit.
Follow the instructions in the installation, operating, and program-
ming manuals. These instructions must be followed to avoid damage
to the control panel and associated equipment. FACP operation and
reliability depend upon proper installation by authorized personnel.
FCC Warning
WAR NING: This equipment generates, uses, and can radi-
ate radio frequency energy and if not installed and used in
accordance with the instruction manual, may cause interference to radio communications. It has been tested and
found to comply with the limits for class A computing
device pursuant to Subpart B of Part 15 of FCC Rules,
which is designed to provide reasonable protection against
such interference when operated in a commercial environment. Operation of this equipment in a residential area is
likely to cause interference, in which case the user will be
required to correct the interference at his own expense.
Acclimate Plus™
ONYX®, FlashScan®, UniNet®, VIEW®, NOTIFIER® are registered trademarks of Honeywell. Simplex® is registered trademark of Tyco
International Ltd. Echelon®
, HARSH™, NOTI•FIRE•NET™, VeriFire™, NION™, NOTIFER Intergrated Systems™ and ONYXWorks™ are trademarks, and
is a registered trademark and LonWorks™ is a trademark of Echelon Corporation. ARCNET® is a registered trademark of Datapoint
Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. LEXAN® is a registered trademark of GE Plastics, a subsidiary of
Canadian Requirements: This digital apparatus does not
exceed the Class A limits for radiation noise emissions
from digital apparatus set out in the Radio Interference
Regulations of the Canadian Department of Communications. This Class A digital apparatus complies with Canadian ICES-003.
Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils
numeriques de la classe A prescrites dans le Reglement
sur le brouillage radioelectrique edicte par le ministere des
Communications du Canada. Cet appareil numerique de la
classe A est conforme a la norme NMB-003 du Canada.
3BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Page 4
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments, you can email
us.
Please include the following information:
•Product name and version number (if applicable)
•Manual page number
•Your comment
Send email messages to:
FireSystems.TechPubs@honeywell.com
Please note this email address is for documentation feedback only. If you have any technical issues, please contact
Technical Services.
4BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Page 5
Table of Contents
Section 1 NOTIFIER® BACnet Gateway-3 Features .............................................................. 7
1.2: Related Documentation .................................................................................................................................8
Table 1.1 Related Documentation ..........................................................................................................8
1.6: Upgrade Information ...................................................................................................................................10
1.7: System Requirements ..................................................................................................................................10
1.8: System Architecture.....................................................................................................................................11
1.8.1: Single Panel Architecture ..................................................................................................................11
Figure 1.1 BACnet GW-3 Single Panel Diagram ................................................................................11
2.3: Installing a CAB3/CAB4 Cabinet ...............................................................................................................18
Figure 2.3 CAB-3/CAB-4 Series Installation Document, 15330 .........................................................18
2.4: Installing a CHS-4L Chassis........................................................................................................................19
Figure 2.4 Installing a Chassis..............................................................................................................19
2.5: Installing the BACnet GW-3 Board.............................................................................................................20
3.1.3: Connect the Configuration Computer to the BACnet GW-3 ............................................................26
3.1.4: Prepare the Configuration Computer to Communicate with BACnet GW-3....................................26
3.1.5: Log into the BACnet GW-3 for Configuration .................................................................................27
3.1.6: Configure the BACnet GW-3............................................................................................................28
3.1.7: Viewing BACnet GW-3 Activity with the BACNet Gateway Configuration Tool ..........................33
3.2: Connect the BACnet GW-3 to the NFN Network or FACP ........................................................................33
5BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Page 6
Table of Contents
Table 3.1 BACnet GW-3 to Fire System Connection Options.............................................................34
3.2.1: Connecting BACnet GW-3 to a High Speed NFN Network Control Module ..................................35
Figure 3.1 USB Connection..................................................................................................................35
Figure 3.2 NUP to NUP Connection ....................................................................................................36
3.2.2: Connecting BACnet GW-3 to an NFN Network Control Module ....................................................37
Figure 3.3 NUP to NUP Connection ....................................................................................................37
3.2.3: Connecting BACnet GW-3 Directly to a Fire Alarm Control Panel .................................................38
Figure 3.4 NUP to NUP Connection ....................................................................................................38
3.3: Back Up BACnet GW-3...............................................................................................................................38
Index ........................................................................................................................................53
6BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Page 7
Section 1 NOTIFIER® BACnet Gateway-3 Features
1.1 Product Description
The NOTIFIER® BACnet Gateway-3 (BACnet GW-3) provides a communication link between
networks that use the BACnet communication protocol and Fire Alarm Control Panels (FACP)
resident on an NFN network or high speed NFN network. The BACnet GW-3 acts like any other
node on an NFN network or high speed NFN network. The NFN network communicates with the
gateway through an HS-NCM-W/SF/MF or NCM-W/F network control module that is on that NFN
network or through a direct connection to a single NOTIFIER® panel. The BACnet
communication protocol is an American National Standard (ANSI/ASHRAE 135-1995).
The BACnet GW-3 application represents physical fire devices as BACnet objects and manages the
object database. As events occur, the object properties are updated in real-time, and messages are
sent to the appropriate BACnet report destination (BACnet computer clients are computers with the
graphical user interface workstation front end). BACnet clients may make requests to read
properties of the BACnet objects. Those properties are the values of the device status and
programming. The user subscribes to Event Notification objects per FACP, and the BACnet device
receives events from objects on the FACP as a result of this subscription.
The BACnet client workstation front end must conform to BACnet Standard Annex J for IP and
support Device Objects, Binary Output Objects, and Multi-state Input or Life Safety Points/Zones.
It is also required to write to Notification Objects and receive confirmed/unconfirmed event
notification messages. For details, refer to Appendix A, “PIC Statement”, on page 41.
The BACnet GW-3 Configuration Tool, an offline programming utility that is included with the
BACnet GW-3 assembly when ordered, is used to configure the BACnet GW-3. It is installed onto
a computer that will be used to configure the gateway. Refer to “BACnet GW-3 Configuration” on
page 27.
1.1.1 BACnet GW-3 Features
Below are some of the features of the BACnet GW-3.
•Multiple Gateways can be used for large networks (greater than 15 panels/15,000 objects).
•Use of ethernet port for BACnet GW-3 configuration with the BACnet GW-3 Configuration
Tool.
NOTE: This manual is written with the understanding that its user is trained in BACnet operations
and services. The information provided here is solely for the configuration of the Gateway to
communicate event information to an existing BACnet network.
7BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Panels and AnnunciatorsNFS-320 Installation/Operation/Programming Manual
NFS-640 Installation/Operation/Programming Manual
NFS2-640 Installation/Operation/Programming Manual
NFS-3030 Installation/Operation/Programming Manual
NFS2-3030 Installation/Operation/Programming Manual
Network Control Annunciator (NCA) Manual
Network Control Annunciator-2 (NCA-2) Manual
Network Control Station (NCS) Manual
AM2020/AFP1010 Installation, Operation, and Programming Manual
DVC Series Digital Voice Command Manual
1.3 Agency Listings
NOTE:
UL 864, 9th Edition—Notifier systems work with products that have been UL 864, 9th Edition
listed as well as products that have not received UL 864, 9th Edition certification. Operation of
systems that are comprised of equipment that is UL 864, 9th Edition listed together with products
that are not UL 864, 9th Edition listed requires the approval of the local Authority Having
Jurisdiction (AHJ).
CAN/ULC-S559-04, 1st Edition—Notifier systems work with products that have been CAN/ULC-
S559-04, 1st Edition listed as well as products that have not received CAN/ULC-S559-04, 1st
Edition certification. Operation of systems that are comprised of equipment that is CAN/ULCS559-04, 1st Edition listed together with products that are not CAN/ULC-S559-04, 1st Edition
listed requires the approval of the local Authority Having Jurisdiction (AHJ).
This product has been investigated to, and found to be in compliance with the following standards.
National Fire Protection Association
•NFPA 72—National Fire Alarm Code
Underwriters Laboratories
•UL-864—Control Units for Fire Alarm Systems, Ninth Edition
•UL-2017—General-Purpose Signaling Devices and Systems, First Edition
Underwriters Laboratories Canada
•CAN/ULC-S527-99—Standard for Control Units for Fire Alarm Systems, Second Edition
8BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Page 9
Environmental RequirementsNOTIFIER® BACnet Gateway-3 Features
•CAN/ULC-S559-04—Equipment for Fire Signal Receiving Centres and Systems, First
Edition
1.3.2 Installation
This product is intended to be installed in accordance with the following regulatory agencies.
Local
•AHJ—Authority Having Jurisdiction
National Fire Protection Association
•NFPA 70—National Electrical Code
•NFPA 72—National Fire Alarm Code
•NFPA 101—Life Safety Code
Underwriters Laboratories
•UL-1076—In certified applications, the unit shall be installed in accordance with Proprietary
Burglar Alarm Units and Systems, Fifth Edition
Underwriters Laboratories Canada
•C22.1–98—Canadian Electrical Code, Part I (Twentieth Edition), Safety Standard for
Electrical Installation
•CAN/ULC-S524-06—Standard for the installation of Fire Alarm Systems, Fifth Edition
•CAN/ULC-S561-03—Installation and Services for Fire Signal Receiving Centres and
Systems, First Edition
WARNING: Installation
!
Improper installation, maintenance, and lack of routine testing could result in system malfunction.
About Ethernet Network Installations
“Listed for the purpose” has been formally interpreted by NFPA (Formal Interpretation 72-99-1)
for equipment on packet switched networks as being listed to the requirements applicable to
general purpose communications network equipment.
For ULC applications, the Internet cannot be used for either primary or ancillary functionality.
“Listed for the purpose” has been formally interpreted by NFPA (Formal Interpretation 72-99-1)
for equipment on packet switched networks as being listed to the requirements applicable to
general purpose communications network equipment.
For ULC applications, the Internet cannot be used for either primary or ancillary functionality.
1.4 Environmental Requirements
This product must be installed in the following environmental conditions:
•Temperature range of 0°C to 49°C (32°F - 120°F).
•93% humidity non-condensing at 30°C (86°F).
The contents of this manual are important and must be kept in close proximity of the hardware. If
building ownership is changed, this manual and all other testing and maintenance information must
also be passed to the current owner of the facility. A copy of this manual was shipped with the
equipment and is also available from the manufacturer.
NOTE: Refer to Appendix A, “PIC Statement”, on page 41 for the BACnet PIC statement.
9BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Page 10
NOTIFIER® BACnet Gateway-3 FeaturesCompatibility
1.5 Compatibility
NOTE: The BACnet GW-3 requires that at least one node on the NFN network be an ONYX
series panel. BACnet GW-3 does not run on an NFN network with no ONYX series panels.
Refer to Appendix B, “BACnet GW-3 Compatible Node Types”, on page 47 for supported panels
and annunciators.
1.6 Upgrade Information
Firmware for systems running BACnet GW-3 versions prior to 3.11 should not be upgraded unless
there is an ONYX series panel on the system. BACnet GW-3 does not run on an NFN network with
no ONYX series panels.
1.7 System Requirements
The BACnet GW-3 can monitor up to fifteen panels, but the combined object count across the
monitored panels cannot exceed 15,000 objects. This includes all detectors, monitor modules,
control modules, bell circuits, etc. Refer to the NFN network manual for details about wiring
limitations.
The computer on which the BACnet GW-3Configuration Tool is installed should be Windows 2000
or Window XP. The computer must communicate with the BACnet GW-3 over IP or through a
crossover cable from the BACnet GW-3 ethernet port.
10BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Page 11
System ArchitectureNOTIFIER® BACnet Gateway-3 Features
1.8 System Architecture
NOTE: The BACnet GW-3 client workstation is not intended as a primary annunciator and is ancillary
in nature.
These are connections options for the BACnet GW-3 architecture.
An Internet or Intranet IP network connection is used with both architectures.
1.8.1 Single Panel Architecture
Direct panel connection; a connection is made directly to a supported NOTIFIER® panel or
annunciator (Figure 1.1 on page 11). Refer to Appendix B, “BACnet GW-3 Compatible Node
Types”, on page 47 for supported panels and annunciators.
BACnet/IP Client with Workstation Front End
IP connection over
Ethernet
Figure 1.1 BACnet GW-3 Single Panel Diagram
1.8.2 NFN Network Architecture
NFN network connection; a NUP connection is made to an NCM or HS-NCM board on the NFN
network as the BACnet GW-3 (Figure 1.2 on page 12)
BACnet GW-3
NUP connection
FACP
11BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
14BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Page 15
Section 2 BACnet GW-3 Embedded Installation
NOTE: The BACnet GW-3 is for ancillary use only and does not increase the burglary grade of service
for the system.
2.1 Required Equipment
The BACnet GW-3 requires the following:
BACnet GW-3 Assembly
The following are shipped with the BACnet GW-3:
•BACnet GW-3 board
•PNET-1 surge suppressor (P/N PNET-1)
•NUP to NUP Cable (P/N 75556)—used to connect the BACnet GW-3 board to an HS-NCMW/SF/MF boardl or NCM-W/F board and supported panel
•USB Cable (P/N 75665)—used to connect the BACnet GW-3 board to an HS-NCM-W/SF/MF
boardl
•Wire Leads to NUP Network Communications Module power cable (P/N 75583)
Network Components
•RJ45 to RJ45 standard Ethernet network cable—customer’s internet or intranet connection to
BACnet GW-3
•Workstation v3.11 or above (sold separately)
•NFN network—version 5.0 or above (sold separately)
•High Speed Network Communications Module: HS-NCM-W/SF/MF board—used to facilitate
network communication between the BACnet GW-3 and a High Speed NFN network (sold
separately) OR
•Network Communications Module: NCM-W/F board—used to facilitate network
communication between the BACnet GW-3 and an NFN network (sold separately).
NOTE: No HS-NCM-W/SF/MF board or NCM-W/F board is required when the BACnet GW-3
connects directly to a supported NOTIFIER® panel or annunciator when it is a standalone panel
or annunciator. Refer to “Panel Communication Connection Table” on page 47 for a list of
supported panels.
Cabinet and Hardware (sold separately)
•CAB-3/CAB-4 series cabinet
•CHS-4L chassis
Customer Supplied Equipment
•A computer to run the BACNet Gateway Configuration Tool and configure the BACnet GW-3.
Contact Technical Support for software version compatibility.
15BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Mounting Hole with
Surrounding
Grounding Area (5
locations)
NUP A Serial Data
Connector (J6)
not used (J7)
TB6:NO
Not Used
ComNC
TB1:
-24 V Out
+24 V Out
-24 V In
+24 V In
Figure 2.2 BACnet GW-3 Board
17BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Page 18
BACnet GW-3 Embedded InstallationInstalling a CAB3/CAB4 Cabinet
2.3 Installing a CAB3/CAB4 Cabinet
Install a new CAB-3/CAB-4 series cabinet according to the requirements of the local authority
having jurisdiction or prepare an existing CAB-3/CAB-4 series cabinet that houses a supported
NOTIFIER® panel or annunciator. Refer to Appendix B, “BACnet GW-3 Compatible Node
Types”, on page 47 for list of supported panels and annunciators.
NOTE: The CAB3/CAB4 cabinet is ordered separately. For installation details, refer to the CAB-3/
CAB-4 Series Installation Document, 15330 and or the panel’s or annunciator’s documentation.
NOTE: Knockouts are provided on the unit so that the field wiring may be run in conduit if
required by the local authority having jurisdiction. All field wiring connections are intended to be
made at the installation wiring terminals provided as part of the unit.
CAB-3/CAB-4 Series Cabinets
Product Installation Document
1 General
All cabinets are fabricated from 16 gauge steel. The cabinet consists of two basic components: a backbox and a locking
door.
The key-locked door is provided with a pin-type hinge, two keys, and the necessary hardware to mount the door to the
backbox. The backbox has been engineered to provide ease-of-entry for the installer. Knockouts are positioned at
numerous points to let the installer bring conduit into the enclosure easily. Doors can be mounted on the left or right-hand
side. The same hinge works in both configurations, so that this choice can be made in the field. The door opens 180°.
Cabinets are available in five sizes: A through D, and AA. The outside dimensions are noted on each enclosure diagram.
“A” size accommodates one chassis, a power supply, and two 26 AH batteries; “D” size accommodates four chassis, a
power supply, and two 26 AH batteries; “AA” size holds one chassis with no compartment for batteries. A trim ring
option is available for semi-flush mounting. The CAB-3/CAB-4 Series is compatible with multiple chassis including the
CHS-M2, CHS2-M2, CHS-M3, CHS-4, CHS-4L, CHS-4N, CHS-BH, CHS-PS, CA-1, and CA-2. Note: CAB-4 series
backboxes and doors are sold separately.
2 Before You Begin
CAB door LH.wmf
opened when the door is at less than a 120° angle to the cabinet. If you are using the left-hand mounting option, be sure
that the door can open at least 120°. This is especially important if the cabinet is to be mounted in a closed area, such as a
closet or utility room.
3 Door Assembly Instructions
Hinges can be either left or right hand mounted. The illustrations and text depict a left hand mounted example. For a right
hand mounting, simply substitute right for left in the instructions.
1. Insert door hinges (A) into the top and bottom slots of the side to be hinged (in this case the LEFT side). Secure the
hinges to the studs in the backbox with the #8 hex nuts provided. Note that the small hole on the outer tab faces
outward.
2. Thread stud (B) into the BOTTOM hinge first. Thread from the bottom up. Place the grounding “star” washer on the
stud. Place the door's lower corner onto this stud. Placing the door on the lower stud first provides a place for the door
to rest while you complete the assembly.
3. Align the door on the backbox, so that the door sits directly under the top hinge. Thread remaining stud (B) into the
TOP hinge and through the hole in the top of the door. Your door should now swing freely.
PN 15330:I 10/23/07 07-695
The option of mounting doors in either a left/right hand configuration
will aid in installation and service when two control panels are
mounted in a confined area or side by side (as shown). In this manner
the doors can be opened “barn door” style, permitting an open work
space. Note that in this type of installation it is necessary to leave
enough space between cabinets to insert a key into the locks on the
CAB door RH.wmf
door frames.
IMPORTANT: Attach the two hinges and two alignment tabs to the
backbox before any equipment is installed. With chassis installed,
space is very limited.
Display Interface Assembly Note: When the door is left-hand
mounted, the Display Interface Assembly (DIA) dress panel cannot be
Figure 2.3 CAB-3/CAB-4 Series Installation Document, 15330
18BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Page 19
Installing a CHS-4L ChassisBACnet GW-3 Embedded Installation
2.4 Installing a CHS-4L Chassis
Figure 2.4 Installing a Chassis
19BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Page 20
BACnet GW-3 Embedded InstallationInstalling the BACnet GW-3 Board
2.5 Installing the BACnet GW-3 Board
Install BACnet GW-3 board onto the mounting studs on the CHS-4L chassis, making sure to use
only the mounting holes bordered by grounding area.
Grounding area
Figure 2.5 Install BACnet GW-3 Board onto Chassis
NOTE: There must be enough clearance on the right side of the printed circuit board to allow an
Ethernet cable to be connected to the Ethernet port.
2.5.1 BACnet GW-3Power Supply Connection
The BACnet GW-3 requires +24VDC @450mA nominal and supervised battery backup in
accordance with local code requirements. Outside Canada, the BACnet GW-3 can be powered by
any regulated, UL 1481 listed, power limited, battery backed, +24 VDC power supply. For
Canadian installation, The BACnet GW-3 must be powered by a ULC listed Fire Alarm Control
Unit or a ULC listed power supply for fire application. Conform to UL or ULC standards as
applicable in your area.
Table 2.1 Power Supply Specifications
NOMINAL
Input Voltage+24VDC
Input Current @ +24VDC450 mA without NCM or HS-NCM
20BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Page 21
Installing the BACnet GW-3 BoardBACnet GW-3 Embedded Installation
TB1
24 V IN
Figure 2.6 BACnet GW-3 Power Connection
NOTE: All wiring from the power supply is power limited, and a separation of at least ¼” (6.35
mm) must be maintained between power limited and non-power limited wiring.
CAUTION: Power Sources
!
Different sources of power are used in conjunction with the BACnet GW-3 product. Disconnect all
sources of power before servicing. This device and associated equipment may be damaged by
removing and/or inserting cards, modules or interconnecting cables while this unit is powered. This
damage may adversely affect the operation of this unit, but its effect may not be readily apparent.
For specific information about power configurations involving fire alarm control panels and
network communications modules, refer to Embedded Gateway Power Connections, PN 53600.
2.5.2 Wiring Restrictions
NOTE: All wiring connections are supervised and power limited.
NOTE: USB and NUP wiring connections to the HS-NCM must be located within 20 feet and
encased in conduit within the same room.
NOTE: In Canada, if the gateway is installed in a separate cabinet, the cabinet must be
connected to the Fire Alarm Control Panel (FACP) with a close nipple fitting.
RS232 (NUP)
•Line Impedance 5k ohm
•Max Distance 50 feet
Ethernet
•Line Impedance 100 ohm
•Max Distance 100 meters
21BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Page 22
BACnet GW-3 Embedded InstallationInstalling the BACnet GW-3 Board
This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire
Alarm Systems, UL 864 9th Edition.
The following products have not received UL 864 9th Edition certification and may only be used in retrofit applications.
Operation of the NCM-W, NCM-F with products not tested for UL 864 9th Edition has not been evaluated and may not
comply with NFPA 72 and/or the latest edition of UL 864. These applications will require the approval of the local
Authority Having Jurisdiction (AHJ).
• AM2020/AFP1010
•MIB
• NAM-232
2 Product Overview
The Network Communications Module (NCM) provides a means for connecting specific Notifier fire alarm control
products to
NOTI•FIRE•NET™. There are two types of NCMs available: NCM-W for connecting nodes with twisted-
pair wire, and NCM-F for connecting nodes with fiber-optic cable.
In most applications, one NCM is required per
NOTI•FIRE•NET™ node (including fire alarm control panels and
network annunciators) . Even though the NCM has two NUP ports, only one may be connected to a
NOTI•FIRE•NET™.
node. Except in some DVC applications, do not connect two NCMs via NUP ports (aka “NUP to NUP”).
For instructions on the additional capabilities available with the DVC, refer to the DVC Manual.
• Input power requirements: 24 VDC , 0.11 amps, regulated, power-limited compatible power supply UL/ULC listed
for fire protective signalling use.
• Communications circuit requirements: Refer to the
NOTI•FIRE•NET™ Manual (Network Version 4.0 and Higher)
for wiring length and threshold information.
USB
•Line Impedance 90 ohm ±15%
•Max Distance 40 meters
2.5.3 Installing the Network Communication Module
Install the type of network communication module you will use (whether high speed or not, wire or
fibre) onto the chassis in the new CAB3/CAB4 cabinet or an existing panel’s or annunciator’s
cabinet.
Table 2.2 Network Communication Module Details
HIGH SPEED NFN NETWORKS—USE HS-NCM ONLYNFN NETWORKS—USE NCM ONLY
Use the High Speed Network Control Module circuit board
configuration that fits your installation needs.
• HS-NCM-W with twisted pair wire
• HS-NCM-SF with single mode fiber-optic cable
Use the Control Module circuit board configuration that fits
your installation needs.
High Speed Network Communications Module Product Installation Document
1 Product Overview
The High-Speed Network Communications Module (HS-NCM) provides a means for connecting specific Notifier fire
alarm control products to High-Speed NOTI•FIRE•NET™. There are six types of HS-NCMs available: HS-NCM-W for
connecting nodes with twisted-pair wire; HS-NCM-MF and HS-NCM-SF are used for connecting nodes with fiber-optic
cable; HS-NCM-WMF and HS-NCM-WSF are used for connecting nodes with fiber-optic cables to nodes with twistedpair wire; HS-NCM-MFSF for connecting nodes with multi-mode fiber cable to nodes with single-mode fiber cable. The
following UL 9th Edition equipment may be used with the HS-NCM:
• NFS2-30 30
• NFS2-64 0
• NFS-320
•NCA-2
• DVC
One HS-NCM can provide network communication for up to two nodes (including fire alarm control panels and network
annunciators).
The HS-NCM can also be configured as a repeater. In this configuration, the HS-NCM can boost data signals between
network nodes to extend communication distances or to pass data transmissions between two differently configured
network segments when wire and fiber co-exist on a network. For limitations and network wiring information for the HSNCM in repeater mode, refer to the High-Speed Noti•Fire•Net Manual. When using the HS-NCM as a repeater, the node
address for the HS-NCM must be set to zero (default). The node address can be changed through a fire alarm control
panel’s network programming or
For instructions on the additional capabilities available with the DVC, refer to the DVC Manual.
• Input power requirements: 24 VDC, 0.375 amps, regulated, power-limited compatible power supply UL/ULC listed
for fire protective signalling use.
• Communications circuit requirements: Refer to the High-Sp eed Noti•Fire•Net Manual for segment length limitations.
2 The Network Communications Module for Wire (HS-NCM-W)
• Supports twisted-pair wire medium.
• NFPA Style 4 (Class B) operation or NFPA Style 7
(Class A) operation.
• Transformer coupling provides electrical isolation
between nodes.
• Pluggable terminal wiring with strain relief.
• Pluggable service connector (feeds signal directly
through) in the event that power must be removed from
a node (HS-NBB).
• Data is regenerated at each node.
• Two network ports to allow simultaneous connection to
fire alarm control panel and to programming computer.
• Enables software and database upload/download over
High-Speed Noti•Fire•Net.
Figure 2.7 HS-NCM Installation Document
PN 54014
PN 54014:A 01/23/08 07-XXX
through VeriFire Tools. Refer to the VeriFire™ Tools CD on-line help file.
Channel A
Connection
Ground Fault
Detection
Switches
S1=CH. A
S2=CH. B
Figure 1 HS-NCM-W
Channel B
Connection
US
Connection
EtherNet
Connection
NUP
Ports
HS-NCMwire.wmf
Figure 2.8 NCM Installation Document
PN 51533
BE SURE TO INSTALL THE CORRECT SPEED NETWORK CONTROL MODULE, BASED ON WHETHER YOU
HAVE AN NFN NETWORK OR A HIGH SPEED NFN NETWORK.
22BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Page 23
Connecting BACnet GW-3 to an IP NetworkBACnet GW-3 Embedded Installation
2.6 Connecting BACnet GW-3 to an IP Network
This allows the BACnet GW-3 to communicate through your IP network (Internet or Intranet)
Step 1. Plug the PNET-1 surge suppressor into the BACnet GW-3 board Ethernet connector.
Step 2. Plug the RJ45 cable into the PNET-1.
Step 3. Plug the RJ45 cable into your IP network.
PNET-1
Ethernet
Connector (J8)
Figure 2.9 IP Cable Connection
NOTE: The Ethernet wire must be connected through the PNET-1 surge suppressor.
NOTE: The Ethernet port is power limited.
Customer Supplied Cable
To Internet or Intranet
2.7 Connecting BACnet GW-3 to an NFN Network or High
Speed NFN Network
The BACnet GW-3 should not be connected to the NFN network until after it has been properly
configured. For more information, please refer to Section 3, “BACnet GW-3 Configuration and
Operation”, on page 25.
Once the BACnet GW-3 has been configured, refer to Section 3.2, “Connect the BACnet GW-3 to
the NFN Network or FACP” on page 33 for more information.
23BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Page 24
BACnet GW-3 Embedded InstallationConnecting BACnet GW-3 to an NFN Network or High Speed NFN Network
24BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Page 25
Section 3 BACnet GW-3 Configuration and Operation
3.1 BACnet GW-3 Configuration
CAUTION:
!
Different sources of power are used in conjunction with this product
before servicing
cards, modules or interconnecting cables while this unit is powered
the operation of this unit, but its effect may not be readily apparent.
. This device and associated equipment may be damaged by removing and/or inserting
3.1.1 BACnet GW-3 Configuration Overview
Perform the gateway configuration in this order:
•“BACNet Gateway Configuration Tool Installation” on page 25
•“Connect the Configuration Computer to the BACnet GW-3” on page 26
•“Prepare the Configuration Computer to Communicate with BACnet GW-3” on page 26
•“Log into the BACnet GW-3 for Configuration” on page 27
•“Configure the BACnet GW-3” on page 28
•“Connect the BACnet GW-3 to the NFN Network or FACP” on page 33
The BACNet Gateway Configuration Tool CD-ROM is provided when the gateway is ordered.
Use these steps as guideline to install the application onto the computer that has Windows 2000 or
XP installed.
Step 1. Insert the CD-ROM into the CD-ROM drive on the computer that will be connected to the
gateway so the gateway can be configured.
Step 2. From Windows Explorer or the Run command, select and start the setup.exe file that is
located in the CD-ROM’s root directory. The installation program starts.
Step 3. Follow the displayed instructions to install the BACNet Gateway Configuration Tool.
25BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Page 26
BACnet GW-3 Configuration and OperationBACnet GW-3 Configuration
3.1.3 Connect the Configuration Computer to the BACnet GW-3
If your configuration computer is on the same IP network you connected the BACnet GW-3 to in
the section, Section 2.6, “Connecting BACnet GW-3 to an IP Network” on page 23, then your
configuration computer is already connected to the BACnet GW-3. Proceed to Section 3.1.4,
“Prepare the Configuration Computer to Communicate with BACnet GW-3” on page 26.
Otherwise, refer to Appendix C, “BACnet GW-3 Local Configuration”, on page 49.
3.1.4 Prepare the Configuration Computer to Communicate with
BACnet GW-3
Configure your configuration computer to communicate with the default BACnet GW-3 IP address
of 192.168.1.2.:
Step 1. From the Windows taskbar, click Start Ö Connect To Ö Show All Connections.
Step 2. Right-click your LAN connection, and then click Properties in the menu that appears.
Step 3. Select Internet Protocol (TCP/IP), and then click Properties.
26BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Page 27
BACnet GW-3 ConfigurationBACnet GW-3 Configuration and Operation
Step 4. Record your current Internet Protocol (TCP/IP) property settings so you can restore them
later.
Step 5. Click Use the following IP address, and then type 192.168.1.X into the IP address field.
NOTE: X can be any number between 0 and 255 except for 2 (since the BACnet GW-3 default IP
address is 192.168.1.2).
Step 6. Click OK, and then close all remaining open windows.
3.1.5 Log into the BACnet GW-3 for Configuration
NOTE: The BACNet Gateway Configuration Tool must run at a resolution of 1024 X 768 or
greater.
Step 1. Launch the BACNet Gateway Configuration Tool by clicking Start Ö All Programs Ö
BACnet Gateway Config Tool from the Windows taskbar.
Step 2. Click the Address field, and then click the default gateway IP address 192.168.1.2 in the
menu that drops down.
Step 3. Click File Ö Login....
27BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Page 28
BACnet GW-3 Configuration and OperationBACnet GW-3 Configuration
Step 4. Type the default password, 00000000, and then click OK.
3.1.6 Configure the BACnet GW-3
Set Up the SNTP Server
Synchronizing with an SNTP server allows the BACnet GW-3 to keep accurate time.
NOTE: By default, the BACnet GW-3 synchronizes its internal clock with the NFN network time,
or with the Fire Alarm Control Panel in the case of a direct connection. Configuring the SNTP
server is only necessary if you want the gateway to synchronize with another server, such as an
ONYXWorks® Workstation or an SNTP time server.
Step 1. In the left pane of the BACNet Gateway Configuration Tool under the Gateway heading,
click SNTP Configuration.
Step 2. Click the SNTP Server Address field under the Value heading, and then type the address
of the SNTP server.
Configure Time Zone Settings
Step 1. In the left pane of the BACNet Gateway Configuration Tool under the Gateway heading,
click Time Zone Configuration.
Step 2. Use the fields under the Value heading to enter your local Greenwich Mean Time offset
value as well as the appropriate information about the observance of Daylight Savings
Time.
28BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Page 29
BACnet GW-3 ConfigurationBACnet GW-3 Configuration and Operation
Configure IP Settings
Step 1. In the left pane of the BACNet Gateway Configuration Tool under the Gateway heading,
click IP Configuration.
Step 2. Click the fields under the Value heading, and type the IP, Subnet Mask, and Gateway
(router) addresses this BACnet GW-3 will use on your network.
Step 3. Click Apply to activate these settings.
The BACnet GW-3 reboots automatically.
Restore Your Standard Internet Protocol (TCP/IP) Settings
Step 1. From the Windows taskbar, click Start Ö Connect To Ö Show All Connections.
Step 2. Right-click your LAN connection, and then click Properties in the menu that appears.
29BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Page 30
BACnet GW-3 Configuration and OperationBACnet GW-3 Configuration
Step 3. Select Internet Protocol (TCP/IP), and then click Properties.
Step 4. Enter the settings you recorded earlier into the Internet Protocol (TCP/IP) Properties
dialogue, and then click OK to return your configuration computer to your IP network.
Finalize the BACnet GW-3 Configuration
Log into the BACnet GW-3
Step 1. Click View Ö Refresh Gateway List to refresh the gateway address list.
Step 2. Click the Address field, and then, from the menu that drops down, click the IP address
you assigned this BACnet GW-3.
Step 3. Click File Ö Login....
Step 4. Type the default password, 00000000, and then click OK.
30BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Page 31
BACnet GW-3 ConfigurationBACnet GW-3 Configuration and Operation
The BACNet Gateway Configuration Tool now displays the remaining configurable
settings for the BACnet GW-3. Click the fields under the Value heading to enter
appropriate values, following the guidelines in the following steps.
Gateway Properties
•We recommend you select the Life Safety Notification Type if your system supports it.
Otherwise, virtually all clients support Multi State notification.
•Set the NCM address to a nonzero number.
•If you are adding the BACnet GW-3 to a network that already includes another gateway or
gateways, assign the Network Number based on the highest Network Number used by any
gateway already on the network. The Network Number for the new BACnet GW-3 must be
greater than the highest Network Number by one thousand. For example, if the network
already includes a gateway with a Network Number of 1001, then the lowest Network Number
which can be assigned to the new BACnet GW-3 is 2001.
BBMD Configuration
•If the BACnet GW-3 and the Building Management System (BMS) are connected to the IP
network across different subnets, they must be connected through a BACnet Broadcast
Management Device (BBMD). When using a BBMD, set the Foreign Device value to True
and enter values for IP Address, Port and Register Time.
31BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Page 32
BACnet GW-3 Configuration and OperationBACnet GW-3 Configuration
Multiple Gateways
•NFN networks with more than 15 nodes must be monitored using the Multiple Gateway
option.
•When using this Multiple Gateway option, set the Multiple Gateway value to True, and enter a
value for each network node to be monitored by this BACnet GW-3.
•You may enter up to 14 nodes for FACPs to be monitored, since the BACnet GW-3 can support
15 nodes including itself.
Apply Settings
Step 5. Once all BACnet GW-3 settings have been properly configured, click Apply at the bottom
of the Value pane to apply the settings and reboot the gateway.
NOTE: If you are changing settings on a BACnet GW-3 previously configured with monitored
nodes, this screen button will be labeled Apply And Delete Objects.
32BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Page 33
Connect the BACnet GW-3 to the NFN Network or FACPBACnet GW-3 Configuration and Operation
3.1.7 Viewing BACnet GW-3 Activity with the BACNet Gateway
Configuration Tool
The Gateway Activity window displays information about panels, network objects and NUP events
processed by the BACnet GW-3. This utility tracks up to the 4,000 most recent records. Store this
information permanently by clicking Save.
NOTE: The NFN network must be stable with very few events in order for the discovery process
to discover all objects upon initial configuration. After initial configuration, the BACnet GW-3
updates the network daily at its specified Network Update Time (the default time is 2:00:00).
It is helpful to launch the Gateway Activity window before connecting the BACnet GW-3 to an
NFN network or directly to a Fire Alarm Control Panel, so you can monitor the messages the
BACnet GW-3 generates in its initial Auto Discovery and Property Search routines. To open the
Gateway Activity window:
Step 1. Log into the BACnet GW-3 (refer to “Log into the BACnet GW-3” on page 30).
Step 2. Click View Ö Gateway Activity.
The Gateway Activity window opens. Network traffic will affect the time required to populate the
Gateway Activity window.
3.2 Connect the BACnet GW-3 to the NFN Network or FACP
The BACnet client workstation front end must conform to BACnet Standard Annex J for
IP and support Device Objects, Binary Output Objects, and Multi-state Input or Life
Safety Points/Zones. It is also required to write to Notification Objects and receive
confirmed/unconfirmed event notification messages. For details, refer to Appendix A,
“PIC Statement”, on page 41.
33BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Page 34
BACnet GW-3 Configuration and OperationConnect the BACnet GW-3 to the NFN Network or FACP
Find Your Fire System Connection Option
Once the BACnet GW-3 is connected to the IP network, connect it to either a fire alarm control
panel or an appropriate network control module. Refer to Table 3.1, "BACnet GW-3 to Fire System
Connection Options" for details.
NOTE: Make only one of these connections.
Table 3.1 BACnet GW-3 to Fire System Connection Options
When Connecting...Refer to
...to a high speed NFN network consisting exclusively of
High Speed compatible panels
...to an NFN networkSection 3.2.2, “Connecting BACnet GW-3 to an NFN
directly to a fire alarm control panel to be accessed
through the BACnet GW-3
Section 3.2.1, “Connecting BACnet GW-3 to a High
Speed NFN Network Control Module” on page 35
Network Control Module” on page 37
Section 3.2.3, “Connecting BACnet GW-3 Directly to a
Fire Alarm Control Panel” on page 38
34BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Page 35
Connect the BACnet GW-3 to the NFN Network or FACPBACnet GW-3 Configuration and Operation
3.2.1 Connecting BACnet GW-3 to a High Speed NFN Network
Control Module
•Use a HS-NCM-W for a twisted pair wire connection.
•Use a HS-NCM-SF for a single mode fiber-optic cable connection.
•Use a HS-NCM-MF for a multimode fiber-optic cable connection.
Connecting the BACnet GW-3 to an HS-NCM-W/SF/MF allows the gateway to communicate with
devices on a high speed NFN network. Connect an BACnet Gateway-3 to a High Speed Network
Control Moduleusing either of these methods:
USB to USB Cable Connection
Connecting the BACnet GW-3 to an HS-NCM-W, HS-NCM-SF or HS-NCM-MF allows the
gateway to communicate with devices on a high speed NFN network. Connect the cable between
the USB “A” port on a BACnet GW-3 board and the USB “B” port on an HS-NCM-W, HS-NCMSF or HS-NCM-MF. Or, connect the cable between the USB “B” port on a BACnet GW-3 board
and the USB “A” port on an HS-NCM-W, HS-NCM-SF or HS-NCM-MF.
USB cable
BACnet GW-3
HS-NCM-W/MF/SF
Figure 3.1 USB Connection
35BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Page 36
BACnet GW-3 Configuration and OperationConnect the BACnet GW-3 to the NFN Network or FACP
NUP to NUP Cable Connection
A NUP to NUP cable is used to connect between the gateway and the NFN network. Connect the
cable between to the BACnet GW-3 circuit board NUP “A” connector and an HS-NCM-W/SF/MF
board NUP “A” connector.
NUP to NUP cable
NUP A (J6)
USE NUP A ONLY
Connect to an HS-NCM-W/SF/MF
using NUP “A” only
Figure 3.2 NUP to NUP Connection
36BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Page 37
Connect the BACnet GW-3 to the NFN Network or FACPBACnet GW-3 Configuration and Operation
3.2.2 Connecting BACnet GW-3 to an NFN Network Control
Module
•Use an NCM-W for a twisted pair wire connection.
•Use an NCM-F for a fiber-optic cable connection.
Connecting the BACnet GW-3 to an NCM-W or NCM-F allows the gateway to communicate with
devices on an NFN network.
NUP to NUP Cable Connection
Connect the cable between to the BACnet GW-3 NUP “A” connector and an NCM-W or NCM-F
NUP connector.
NUP A (J6)
Use NUP “A” only.
NUP to NUP cable
Figure 3.3 NUP to NUP Connection
Connect to an NCM-W/F,
37BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Page 38
BACnet GW-3 Configuration and OperationBack Up BACnet GW-3
3.2.3 Connecting BACnet GW-3 Directly to a Fire Alarm Control
Panel
The BACnet GW-3 connects to Fire Alarm Control panels over NUP. Refer to Appendix B.1,
“Direct Connect Node Type Compatibility”, on page 47 for a list of supported panels.
NUP A (J6)
Use NUP “A” only.
NUP to NUP cable
Connect to FACP
Figure 3.4 NUP to NUP Connection
3.3 Back Up BACnet GW-3
Backing up the BACnet GW-3 is important once the gateway is working properly. In some cases, if
the gateway loses power while saving files, the gateway object database may be deleted. Without a
backup file, the gateway will need to rediscover the network and the recipient list may also need to
be set up again.
CAUTION: Auto Discovery and Property Search
!
To ensure the full object database is preserved, give the BACnet GW-3 time to complete its initial
Auto Discovery and Property Search procedures before backing it up. For more information, please
refer to “Viewing BACnet GW-3 Activity with the BACNet Gateway Configuration Tool” on page 33.
Step 1. Log into the BACnet GW-3 (refer to “Log into the BACnet GW-3” on page 30).
Step 2. Click Tools Ö Backup Gateway.
38BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Page 39
Restore BACnet GW-3BACnet GW-3 Configuration and Operation
Step 3. Navigate to where you want to store the backup file, type a name for the file, and then
click Save.
3.4 Restore BACnet GW-3
Follow these steps to restore a previously backed up BACnet GW-3.
Step 1. Log into the BACnet GW-3 (refer to “Log into the BACnet GW-3” on page 30).
Step 2. Click Tools Ö Restore Gateway.
Step 3. Navigate to where the backup file (.bnk) was saved, click on the file name, and then click
Open.
The gateway is restored, and reboots automatically.
39BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Page 40
BACnet GW-3 Configuration and OperationBACnet GW-3 Operation
3.5 BACnet GW-3 Operation
3.5.1 About BACnet GW-3 Start Up
On start up, the gateway auto discovers devices (panels and annunciators.) and objects (detectors,
modules, panels circuits, zones, loops, battery, AC Power, Ground, etc....) on NFN network it is
connected to and creates BACnet objects according to your configuration.
Devices and objects are given names Below are some format examples:
An AFP1010 as node 142: .Name = 142AFP1010 (BACnet Device Object)
An NFS640 as node 234: .Name = 234_NFS640 (BACnet Device Object)
(Detector) Loop 5, Detector 83: L005D083 (BACnet Life Safety Point or Multi-state Input Object)
(Zone) Zone 134: ZONE0134 (BACnet Life Safety Zone or Multi-state Input Object)
Any Node, Loop 5, Control Module 12: L005C012 (BACnet Binary Output Object)
An AM2020 as node 120:.Name = 120_AM2020 (_ denotes spaces) (BACnet Device Object)
An NCM as node 11 connected to BACnet GW:.Name = 011_ _ _ BACGW (BACnet Device Object)
(Module) Loop 9, Module 120: L009M120 (BACnet Life Safety Point or Multi-state Input Object)
(Zone) Zone 1003: ZONE1003 (BACnet Life Safety Zone or Multi-state Input Object)
(Panel Internal Devices)--LOOP 8, LOOP10, BATTERY, ANNUN021, ACPOWER, PANEL (BACnet Life Safety Point or
Multi-state Input Object)
40BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Page 41
Appendix A: PIC Statement
A.1 BACnet Protocol Implementation Conformance
Statement (Normative)
(This appendix is part of this Standard and is required for its use.)
•Applications Software Version: 3.11
•Firmware Revision: 3.11
•BACnet Protocol Revision: 1.2
Product Description:
This product presents NOTIFIER® Fire Panel and Annunciator nodes (operating as part of a NFN
network or stand-alone) and their associated objects as BACnet objects. Event notification for
Alarms, Troubles and other states are sent to registered BACnet client workstations.
BACnet Standardized Device Profile (Annex L)
BACnet Inter-operability Building Blocks Supported (Annex K)
46BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Page 47
Appendix B: BACnet GW-3 Compatible Node Types
NOTE: The BACnet GW-3 requires that at least one node on the NFN network be an ONYX
series panel. BACnet GW-3 does not operate on an NFN network with no ONYX series panels.
B.1 Direct Connect Node Type Compatibility
Refer to Section 3.2.3, “Connecting BACnet GW-3 Directly to a Fire Alarm Control Panel” on
page 38.
Table B.1 Panel Communication Connection Table
Supported Panel Types
NFS-320
NFS2-640
NFS2-3030
NCM
NFS-640
NFS-3030
47BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Page 48
BACnet GW-3 Compatible Node TypesDirect Connect Node Type Compatibility
48BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Page 49
Appendix C: BACnet GW-3 Local Configuration
NOTE: This procedure is only necessary if you are configuring an BACnet GW-3 using a
Configuration computer that is not already on the same IP network as the BACnet GW-3. Refer to
“Connecting BACnet GW-3 to an IP Network” on page 23.
NOTE: A direct connection requires that a cross over Ethernet cable to be made or purchased
by the customer.
C.1 Direct Connection to the Gateway Board
Step 1. Connect the cross over cable between the configuration computer network card’s Ethernet
connector and the BACnet GW-3 board’s Ethernet connector (refer to "Cross Over Cable
Specifications").
PNET-1
Ethernet
Connector (J8)
To Configuration Computer
Customer Supplied Cable
Figure C.1 Configuration Computer Direct Connection
Step 2. You have completed the connections, proceed to “Add the IP Subnet of the BACnet GW-3
into the Configuration PC” on page 28.
Cross Over Cable Specifications
This cross over cable will be directly connected between the configuration computer network card
Ethernet connector and the BACnet GW-3 board Ethernet connector.
49BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Page 50
BACnet GW-3 Local ConfigurationDirect Connection to the Gateway Board
The cross over cable can be purchased or you can make one. Please use the following information
for the correct pinout requirements for each end of the cable. EIA/TIA wire color-code standard
568B is applicable.
Table C.1 Cross Over Cable (568B)
RJ45 Pin #
(END 1)
1White/Orange1White/Green
2Orange2Green
3White/Green3White/Orange
4Blue4Blue
5White/Blue5White/Blue
6Green6Orange
7White/Brown7White/Brown
8Brown8Brown
Wire ColorDiagram End #1
RJ45 Pin #
(END 2)
Wire ColorDiagram End #2
50BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Page 51
Appendix D: Glossary
B
NOTIFIER® BACnet Gateway-3 An interface that
allows the NFN network to communicate with a
BACnet network.
F
FTP File Transfer Protocol, used to back up the
NOTIFIER® BACnet Gateway-3 database and
download firmware for field upgrades.
H
HS-NCM-W/SF/MF High Speed Network Control
Module, a network interface enabling the NOTIFIER®
BACnet Gateway-3 to communicate with other NFN
devices.
I
IP Address Logical address designating a node on an
IP network with the format NNN.NNN.NNN.NNN,
where NNN groups can be between 0 and 255.
NFN The network of Fire Alarm Control
Panels.Ethernet - Local area network protocol.
T
Telnet An Internet protocol that allows you to
communicate directly with another computer on the
Internet by specifying the host name, port and terminal
type.
51BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Page 52
Glossary
52BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Page 53
Index
A
ANSI/ASHRAE 135-1995 7
architecture
system
11
ARCNET
45
B
BACnet Configuration Tool
installation procedure
BACnet Gateway
Features
BACnet Gateway part number
BACnet Inter-operability Building Blocks
BACnet Standard Annex J for IP
Bacnet Standardized Device Profile
Binary Output Objects
7
25
15
7
41
7
C
Cabinet Installation 18
Character Sets Supported
Configuration computer
connections
configuration computer
direct connection
26
45
49
41
configuration
features
Hardware Installation
IP cable connection
Required Equipment
gateway
configuration overview
Gateway board
layout
Gateway Installation
Overview
49
7
17
16
H
HS-NCM board 22
I
Installation
Environmental Conditions
IP Address
51
L
Life Safety Points 7
Life Safety Zones
Line Impedance
53BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Page 54
P
PIC STATEMENT 41
PNET-1
Power Connections
15
20
R
Related Documentation 8
RS232
Line Impedance
Max Distance
21
21
S
Segmentation Capability 41
Serial Configuration Tool
operating system
Standard Object Types Supported
Supported - Binary Output
System Requirements
10
44
10
T
twisted pair wire 22
Index
41
U
USB
Line Impedance
Max Distance
W
Wiring
Power
22
22
20
54BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Page 55
Limited Warranty
Honeywell International Inc. warrants products manufactured by
it to be free from defects in materials and workmanship for
eighteen (18) months from the date of manufacture, under normal
use and service. Products are date stamped at time of
manufacture. The sole and exclusive obligation of Honeywell
International Inc. is to repair or replace, at its option, free of charge
for parts and labor, any part that is defective in materials or
workmanship under normal use and service. All returns for credit
are subject to inspection and testing at the factory before actual
determination is made to allow credit. Honeywell InternationalInc. does not warrant products not manufactured by it, but assigns
to the purchaser any warranty extended by the manufacturer of
such products. This warranty is void if the product is altered or
repaired by anyone other than Honeywell International Inc. or as
expressly authorized by Honeywell International Inc. in writing, or
is serviced by anyone other than Honeywell International Inc. or
its authorized distributors. This warranty is also void if there is a
failure to maintain the products and systems in which they operate
in a proper and workable manner. In case of defect, secure a
Return Material Authorization form from our Return Authorization
Department.
This writing constitutes the only warranty made by Honeywell
International Inc., with respect to its products. Honeywell
International Inc., does not represent that its products will prevent
any loss by fire or otherwise, or that its products will in all cases
provide the protection for which they are installed or intended.
Buyer acknowledges that Honeywell International Inc., is not an
insurer and assumes no risk for loss or damages or the cost of any
inconvenience, transportation damage, misuse, abuse, accident or
similar incident.
HONEYWELL INTERNATIONAL INC. GIVES NO WARRANTY,
EXPRESS OR IMPLIED, OF MERCHANTABILITY, FITNESS FOR
ANY PARTICULAR PURPOSE, OR OTHERWISE WHICH
EXTENDS BEYOND THE DESCRIPTION ON THE FACE
HEREOF. UNDER NO CIRCUMSTANCES SHALL HONEYWELL
INTERNATIONAL INC. BE LIABLE FOR ANY LOSS OF OR
DAMAGE TO PROPERTY, DIRECT, INCIDENTAL OR
CONSEQUENTIAL, ARISING OUT OF THE USE OF, OR
INABILITY TO USE HONEYWELL INTERNATIONAL INC.’S
PRODUCTS. FURTHERMORE, HONEYWELL INTERNATIONALINC. SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR
DEATH WHICH MAY ARISE IN THE COURSE OF, OR AS A
RESULT OF, PERSONAL, COMMERCIAL OR INDUSTRIAL USE
OF ITS PRODUCTS.
55NOTIFIER® BACnet Gateway-3 - Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Page 56
World Headquarters
12 Clintonville Road
Northford, CT 06472-1610 USA
203-484-7161
fax 203-484-7118
www.notifier.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.