While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system—typically made up of smoke detec-
tors, heat detectors, manual pull stations, audible warning devices,
and a fire alarm control panel with remote notification capability—can
provide early warning of a developing fire. Such a system, however,
does not assure protection against property damage or loss of life
resulting from a fire.
The Manufacturer recommends that smoke and/or heat detectors be
located throughout a protected premise following the recommendations of the current edition of the National Fire Protection Association
Standard 72 (NFPA 72), manufacturer's recommendations, State and
local codes, and the recommendations contained in the Guide for
Proper Use of System Smoke Detectors, which is made available at
no charge to all installing dealers. These documents can be found at
http://www.systemsensor.com/html/applicat.html.
A study by the Federal Emergency Management Agency (an agency
of the United States government) indicated that smoke detectors may
not go off in as many as 35% of all fires. While fire alarm systems are
designed to provide early warning against fire, they do not guarantee
warning or protection against fire. A fire alarm system may not provide
timely or adequate warning, or simply may not function, for a variety
of reasons:
Smoke detectors may not sense fire where smoke cannot reach the
detectors such as in chimneys, in or behind walls, on roofs, or on the
other side of closed doors. Smoke detectors also may not sense a fire
on another level or floor of a building. A second-floor detector, for
example, may not sense a first-floor or basement fire.
Particles of combustion or “smoke” from a developing fire may not
reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, or chimneys
may inhibit particle or smoke flow.
• Smoke particles may become “cold,” stratify, and not reach the ceiling
or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air outlets.
• Smoke particles may be drawn into air returns before reaching the
detector.
The amount of “smoke” present may be insufficient to alarm smoke
detectors. Smoke detectors are designed to alarm at various levels of
smoke density. If such density levels are not created by a developing
fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photo-electronic sensing chambers tend to
detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend
to detect fast-flaming fires better than smoldering fires. Because fires
develop in different ways and are often unpredictable in their growth,
neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning of
fires caused by arson, children playing with matches (especially in
bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of flammable materials, etc.).
Heat detectors do not sense particles of combustion and alarm only
when heat on their sensors increases at a predetermined rate or
reaches a predetermined level. Rate-of-rise heat detectors may be
subject to reduced sensitivity over time. For this reason, the rate-ofrise feature of each detector should be tested at least once per year
by a qualified fire protection specialist. Heat detectors are designed to
protect property, not life.
IMPORTANT! Smoke detectors must be installed in the same room
as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or
power. If detectors are not so located, a developing fire may damage
the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert people if these
devices are located on the other side of closed or partly open doors or
are located on another floor of a building. Any warning device may fail
to alert people with a disability or those who have recently consumed
drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause seizures in people
with conditions such as epilepsy.
• Studies have shown that certain people, even when they hear a fire
alarm signal, do not respond or comprehend the meaning of the signal.
It is the property owner's responsibility to conduct fire drills and other
training exercise to make people aware of fire alarm signals and
instruct them on the proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
A fire alarm system
will not operate without any electrical power. If
AC power fails, the system will operate from standby batteries only for
a specified time and only if the batteries have been properly maintained and replaced regularly.
Equipment used in the system may not be technically compatible
with the control panel. It is essential to use only equipment listed for
service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a
central monitoring station may be out of service or temporarily disabled. For added protection against telephone line failure, backup
radio transmission systems are recommended.
The most common cause of fire alarm malfunction is inadequate
maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer's
recommendations, and UL and NFPA standards. At a minimum, the
requirements of NFPA 72 shall be followed. Environments with large
amounts of dust, dirt or high air velocity require more frequent maintenance. A maintenance agreement should be arranged through the
local manufacturer's representative. Maintenance should be scheduled monthly or as required by National and/or local fire codes and
should be performed by authorized professional fire alarm installers
2BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to
the fire alarm control panel.
servicing. The control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting
cables while the unit is energized. Do not attempt to install, service,
or operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software Changes. To
ensure proper system operation, this product must be tested in accordance with NFPA 72 after any programming operation or change in
site-specific software. Reacceptance testing is required after any
change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions
known to be affected by a change must be 100% tested. In addition,
to ensure that other operations are not inadvertently affected, at least
10% of initiating devices that are not directly affected by the change,
up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at 0°C to 49°C
(32°F to 120°F) and at a relative humidity 93% ± 2% RH (non-condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the
system's standby batteries and the electronic components may be
adversely affected by extreme temperature ranges and humidity.
Therefore, it is recommended that this system and all peripherals be
installed in an environment with a nominal room temperature of 1527° C/60-80° F.
Verify that wire sizes are adequate for all initiating and indicating
device loops. Most devices cannot tolerate more than a 10% I.R.
drop from the specified device voltage.
Disconnect all sources of power before
Like all solid state electronic devices this system may operate errati-
cally or can be damaged when subjected to lightning-induced transients. Although no system is completely immune from lightning
transients and interferences, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an
increased susceptibility to nearby lightning strikes. Consult with the
Technical Services if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting cir-
cuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming,
or punching of the enclosure. When possible, make all cable entries
from the sides or rear. Before making modifications, verify that they
will not interfere with battery, transformer, and printed circuit board
location.
Do not tighten screw terminals more than 9 in-lbs. Over-tightening
may damage threads, resulting in reduced terminal contact pressure
and difficulty with screw terminal removal.
Though designed to last many years, system components can fail at
any time. This system contains static-sensitive components. Always
ground yourself with a proper wrist strap before handling any circuits
so that static charges are removed from the body. Use static-suppressive packaging to protect electronic assemblies removed from
the unit.
Follow the instructions in the installation, operating, and program-
ming manuals. These instructions must be followed to avoid damage
to the control panel and associated equipment. FACP operation and
reliability depend upon proper installation by authorized personnel.
FCC Warning
WAR NING: This equipment generates, uses, and can radi-
ate radio frequency energy and if not installed and used in
accordance with the instruction manual, may cause interference to radio communications. It has been tested and
found to comply with the limits for class A computing
device pursuant to Subpart B of Part 15 of FCC Rules,
which is designed to provide reasonable protection against
such interference when operated in a commercial environment. Operation of this equipment in a residential area is
likely to cause interference, in which case the user will be
required to correct the interference at his own expense.
Acclimate Plus™
ONYX®, FlashScan®, UniNet®, VIEW®, NOTIFIER® are registered trademarks of Honeywell. Simplex® is registered trademark of Tyco
International Ltd. Echelon®
, HARSH™, NOTI•FIRE•NET™, VeriFire™, NION™, NOTIFER Intergrated Systems™ and ONYXWorks™ are trademarks, and
is a registered trademark and LonWorks™ is a trademark of Echelon Corporation. ARCNET® is a registered trademark of Datapoint
Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. LEXAN® is a registered trademark of GE Plastics, a subsidiary of
Canadian Requirements: This digital apparatus does not
exceed the Class A limits for radiation noise emissions
from digital apparatus set out in the Radio Interference
Regulations of the Canadian Department of Communications. This Class A digital apparatus complies with Canadian ICES-003.
Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils
numeriques de la classe A prescrites dans le Reglement
sur le brouillage radioelectrique edicte par le ministere des
Communications du Canada. Cet appareil numerique de la
classe A est conforme a la norme NMB-003 du Canada.
3BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments, you can email
us.
Please include the following information:
•Product name and version number (if applicable)
•Manual page number
•Your comment
Send email messages to:
FireSystems.TechPubs@honeywell.com
Please note this email address is for documentation feedback only. If you have any technical issues, please contact
Technical Services.
4BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Table of Contents
Section 1 NOTIFIER® BACnet Gateway-3 Features .............................................................. 7
1.2: Related Documentation .................................................................................................................................8
Table 1.1 Related Documentation ..........................................................................................................8
1.6: Upgrade Information ...................................................................................................................................10
1.7: System Requirements ..................................................................................................................................10
1.8: System Architecture.....................................................................................................................................11
1.8.1: Single Panel Architecture ..................................................................................................................11
Figure 1.1 BACnet GW-3 Single Panel Diagram ................................................................................11
2.3: Installing a CAB3/CAB4 Cabinet ...............................................................................................................18
Figure 2.3 CAB-3/CAB-4 Series Installation Document, 15330 .........................................................18
2.4: Installing a CHS-4L Chassis........................................................................................................................19
Figure 2.4 Installing a Chassis..............................................................................................................19
2.5: Installing the BACnet GW-3 Board.............................................................................................................20
3.1.3: Connect the Configuration Computer to the BACnet GW-3 ............................................................26
3.1.4: Prepare the Configuration Computer to Communicate with BACnet GW-3....................................26
3.1.5: Log into the BACnet GW-3 for Configuration .................................................................................27
3.1.6: Configure the BACnet GW-3............................................................................................................28
3.1.7: Viewing BACnet GW-3 Activity with the BACNet Gateway Configuration Tool ..........................33
3.2: Connect the BACnet GW-3 to the NFN Network or FACP ........................................................................33
5BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Table of Contents
Table 3.1 BACnet GW-3 to Fire System Connection Options.............................................................34
3.2.1: Connecting BACnet GW-3 to a High Speed NFN Network Control Module ..................................35
Figure 3.1 USB Connection..................................................................................................................35
Figure 3.2 NUP to NUP Connection ....................................................................................................36
3.2.2: Connecting BACnet GW-3 to an NFN Network Control Module ....................................................37
Figure 3.3 NUP to NUP Connection ....................................................................................................37
3.2.3: Connecting BACnet GW-3 Directly to a Fire Alarm Control Panel .................................................38
Figure 3.4 NUP to NUP Connection ....................................................................................................38
3.3: Back Up BACnet GW-3...............................................................................................................................38
Index ........................................................................................................................................53
6BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Section 1 NOTIFIER® BACnet Gateway-3 Features
1.1 Product Description
The NOTIFIER® BACnet Gateway-3 (BACnet GW-3) provides a communication link between
networks that use the BACnet communication protocol and Fire Alarm Control Panels (FACP)
resident on an NFN network or high speed NFN network. The BACnet GW-3 acts like any other
node on an NFN network or high speed NFN network. The NFN network communicates with the
gateway through an HS-NCM-W/SF/MF or NCM-W/F network control module that is on that NFN
network or through a direct connection to a single NOTIFIER® panel. The BACnet
communication protocol is an American National Standard (ANSI/ASHRAE 135-1995).
The BACnet GW-3 application represents physical fire devices as BACnet objects and manages the
object database. As events occur, the object properties are updated in real-time, and messages are
sent to the appropriate BACnet report destination (BACnet computer clients are computers with the
graphical user interface workstation front end). BACnet clients may make requests to read
properties of the BACnet objects. Those properties are the values of the device status and
programming. The user subscribes to Event Notification objects per FACP, and the BACnet device
receives events from objects on the FACP as a result of this subscription.
The BACnet client workstation front end must conform to BACnet Standard Annex J for IP and
support Device Objects, Binary Output Objects, and Multi-state Input or Life Safety Points/Zones.
It is also required to write to Notification Objects and receive confirmed/unconfirmed event
notification messages. For details, refer to Appendix A, “PIC Statement”, on page 41.
The BACnet GW-3 Configuration Tool, an offline programming utility that is included with the
BACnet GW-3 assembly when ordered, is used to configure the BACnet GW-3. It is installed onto
a computer that will be used to configure the gateway. Refer to “BACnet GW-3 Configuration” on
page 27.
1.1.1 BACnet GW-3 Features
Below are some of the features of the BACnet GW-3.
•Multiple Gateways can be used for large networks (greater than 15 panels/15,000 objects).
•Use of ethernet port for BACnet GW-3 configuration with the BACnet GW-3 Configuration
Tool.
NOTE: This manual is written with the understanding that its user is trained in BACnet operations
and services. The information provided here is solely for the configuration of the Gateway to
communicate event information to an existing BACnet network.
7BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Panels and AnnunciatorsNFS-320 Installation/Operation/Programming Manual
NFS-640 Installation/Operation/Programming Manual
NFS2-640 Installation/Operation/Programming Manual
NFS-3030 Installation/Operation/Programming Manual
NFS2-3030 Installation/Operation/Programming Manual
Network Control Annunciator (NCA) Manual
Network Control Annunciator-2 (NCA-2) Manual
Network Control Station (NCS) Manual
AM2020/AFP1010 Installation, Operation, and Programming Manual
DVC Series Digital Voice Command Manual
1.3 Agency Listings
NOTE:
UL 864, 9th Edition—Notifier systems work with products that have been UL 864, 9th Edition
listed as well as products that have not received UL 864, 9th Edition certification. Operation of
systems that are comprised of equipment that is UL 864, 9th Edition listed together with products
that are not UL 864, 9th Edition listed requires the approval of the local Authority Having
Jurisdiction (AHJ).
CAN/ULC-S559-04, 1st Edition—Notifier systems work with products that have been CAN/ULC-
S559-04, 1st Edition listed as well as products that have not received CAN/ULC-S559-04, 1st
Edition certification. Operation of systems that are comprised of equipment that is CAN/ULCS559-04, 1st Edition listed together with products that are not CAN/ULC-S559-04, 1st Edition
listed requires the approval of the local Authority Having Jurisdiction (AHJ).
This product has been investigated to, and found to be in compliance with the following standards.
National Fire Protection Association
•NFPA 72—National Fire Alarm Code
Underwriters Laboratories
•UL-864—Control Units for Fire Alarm Systems, Ninth Edition
•UL-2017—General-Purpose Signaling Devices and Systems, First Edition
Underwriters Laboratories Canada
•CAN/ULC-S527-99—Standard for Control Units for Fire Alarm Systems, Second Edition
8BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Environmental RequirementsNOTIFIER® BACnet Gateway-3 Features
•CAN/ULC-S559-04—Equipment for Fire Signal Receiving Centres and Systems, First
Edition
1.3.2 Installation
This product is intended to be installed in accordance with the following regulatory agencies.
Local
•AHJ—Authority Having Jurisdiction
National Fire Protection Association
•NFPA 70—National Electrical Code
•NFPA 72—National Fire Alarm Code
•NFPA 101—Life Safety Code
Underwriters Laboratories
•UL-1076—In certified applications, the unit shall be installed in accordance with Proprietary
Burglar Alarm Units and Systems, Fifth Edition
Underwriters Laboratories Canada
•C22.1–98—Canadian Electrical Code, Part I (Twentieth Edition), Safety Standard for
Electrical Installation
•CAN/ULC-S524-06—Standard for the installation of Fire Alarm Systems, Fifth Edition
•CAN/ULC-S561-03—Installation and Services for Fire Signal Receiving Centres and
Systems, First Edition
WARNING: Installation
!
Improper installation, maintenance, and lack of routine testing could result in system malfunction.
About Ethernet Network Installations
“Listed for the purpose” has been formally interpreted by NFPA (Formal Interpretation 72-99-1)
for equipment on packet switched networks as being listed to the requirements applicable to
general purpose communications network equipment.
For ULC applications, the Internet cannot be used for either primary or ancillary functionality.
“Listed for the purpose” has been formally interpreted by NFPA (Formal Interpretation 72-99-1)
for equipment on packet switched networks as being listed to the requirements applicable to
general purpose communications network equipment.
For ULC applications, the Internet cannot be used for either primary or ancillary functionality.
1.4 Environmental Requirements
This product must be installed in the following environmental conditions:
•Temperature range of 0°C to 49°C (32°F - 120°F).
•93% humidity non-condensing at 30°C (86°F).
The contents of this manual are important and must be kept in close proximity of the hardware. If
building ownership is changed, this manual and all other testing and maintenance information must
also be passed to the current owner of the facility. A copy of this manual was shipped with the
equipment and is also available from the manufacturer.
NOTE: Refer to Appendix A, “PIC Statement”, on page 41 for the BACnet PIC statement.
9BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
NOTIFIER® BACnet Gateway-3 FeaturesCompatibility
1.5 Compatibility
NOTE: The BACnet GW-3 requires that at least one node on the NFN network be an ONYX
series panel. BACnet GW-3 does not run on an NFN network with no ONYX series panels.
Refer to Appendix B, “BACnet GW-3 Compatible Node Types”, on page 47 for supported panels
and annunciators.
1.6 Upgrade Information
Firmware for systems running BACnet GW-3 versions prior to 3.11 should not be upgraded unless
there is an ONYX series panel on the system. BACnet GW-3 does not run on an NFN network with
no ONYX series panels.
1.7 System Requirements
The BACnet GW-3 can monitor up to fifteen panels, but the combined object count across the
monitored panels cannot exceed 15,000 objects. This includes all detectors, monitor modules,
control modules, bell circuits, etc. Refer to the NFN network manual for details about wiring
limitations.
The computer on which the BACnet GW-3Configuration Tool is installed should be Windows 2000
or Window XP. The computer must communicate with the BACnet GW-3 over IP or through a
crossover cable from the BACnet GW-3 ethernet port.
10BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
System ArchitectureNOTIFIER® BACnet Gateway-3 Features
1.8 System Architecture
NOTE: The BACnet GW-3 client workstation is not intended as a primary annunciator and is ancillary
in nature.
These are connections options for the BACnet GW-3 architecture.
An Internet or Intranet IP network connection is used with both architectures.
1.8.1 Single Panel Architecture
Direct panel connection; a connection is made directly to a supported NOTIFIER® panel or
annunciator (Figure 1.1 on page 11). Refer to Appendix B, “BACnet GW-3 Compatible Node
Types”, on page 47 for supported panels and annunciators.
BACnet/IP Client with Workstation Front End
IP connection over
Ethernet
Figure 1.1 BACnet GW-3 Single Panel Diagram
1.8.2 NFN Network Architecture
NFN network connection; a NUP connection is made to an NCM or HS-NCM board on the NFN
network as the BACnet GW-3 (Figure 1.2 on page 12)
BACnet GW-3
NUP connection
FACP
11BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
14BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Section 2 BACnet GW-3 Embedded Installation
NOTE: The BACnet GW-3 is for ancillary use only and does not increase the burglary grade of service
for the system.
2.1 Required Equipment
The BACnet GW-3 requires the following:
BACnet GW-3 Assembly
The following are shipped with the BACnet GW-3:
•BACnet GW-3 board
•PNET-1 surge suppressor (P/N PNET-1)
•NUP to NUP Cable (P/N 75556)—used to connect the BACnet GW-3 board to an HS-NCMW/SF/MF boardl or NCM-W/F board and supported panel
•USB Cable (P/N 75665)—used to connect the BACnet GW-3 board to an HS-NCM-W/SF/MF
boardl
•Wire Leads to NUP Network Communications Module power cable (P/N 75583)
Network Components
•RJ45 to RJ45 standard Ethernet network cable—customer’s internet or intranet connection to
BACnet GW-3
•Workstation v3.11 or above (sold separately)
•NFN network—version 5.0 or above (sold separately)
•High Speed Network Communications Module: HS-NCM-W/SF/MF board—used to facilitate
network communication between the BACnet GW-3 and a High Speed NFN network (sold
separately) OR
•Network Communications Module: NCM-W/F board—used to facilitate network
communication between the BACnet GW-3 and an NFN network (sold separately).
NOTE: No HS-NCM-W/SF/MF board or NCM-W/F board is required when the BACnet GW-3
connects directly to a supported NOTIFIER® panel or annunciator when it is a standalone panel
or annunciator. Refer to “Panel Communication Connection Table” on page 47 for a list of
supported panels.
Cabinet and Hardware (sold separately)
•CAB-3/CAB-4 series cabinet
•CHS-4L chassis
Customer Supplied Equipment
•A computer to run the BACNet Gateway Configuration Tool and configure the BACnet GW-3.
Contact Technical Support for software version compatibility.
15BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09