Notifier BACnet GW-3, BACnet Gateway-3 Installation And Operation Manual

BACnet Gateway-3
Installation and Operation Manual
Document 53372 5/6/09 Rev:
P/N: 53372:A ECN: 08-717
A

Fire Alarm System Limitations

An automatic fire alarm system—typically made up of smoke detec-
tors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control panel with remote notification capability—can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the recommenda­tions of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guide for Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. These documents can be found at http://www.systemsensor.com/html/applicat.html.
A study by the Federal Emergency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the
detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a first-floor or basement fire.
Particles of combustion or “smoke” from a developing fire may not
reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow.
• Smoke particles may become “cold,” stratify, and not reach the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air outlets.
• Smoke particles may be drawn into air returns before reaching the detector.
The amount of “smoke” present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limita­tions. Detectors that have photo-electronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visi­ble smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detec­tor may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in
bedrooms), smoking in bed, and violent explosions (caused by escap­ing gas, improper storage of flammable materials, etc.).
Heat detectors do not sense particles of combustion and alarm only
when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of­rise feature of each detector should be tested at least once per year by a qualified fire protection specialist. Heat detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the same room
as the control panel and in rooms used by the system for the connec­tion of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so located, a developing fire may damage the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert people if these
devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property owner's responsibility to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can cause tempo­rary or permanent hearing loss.
A fire alarm system
will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly main­tained and replaced regularly.
Equipment used in the system may not be technically compatible
with the control panel. It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a
central monitoring station may be out of service or temporarily dis­abled. For added protection against telephone line failure, backup radio transmission systems are recommended.
The most common cause of fire alarm malfunction is inadequate
maintenance. To keep the entire fire alarm system in excellent work­ing order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent mainte­nance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be sched­uled monthly or as required by National and/or local fire codes and should be performed by authorized professional fire alarm installers
2 BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09

Installation Precautions

Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel.
servicing. The control unit and associated equipment may be dam­aged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software Changes. To
ensure proper system operation, this product must be tested in accor­dance with NFPA 72 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any mod­ification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper sys­tem operation verified.
This system meets NFPA requirements for operation at 0°C to 49°C
(32°F to 120°F) and at a relative humidity 93% ± 2% RH (non-con­densing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and all peripherals be installed in an environment with a nominal room temperature of 15­27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and indicating
device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.
Disconnect all sources of power before
Like all solid state electronic devices this system may operate errati-
cally or can be damaged when subjected to lightning-induced tran­sients. Although no system is completely immune from lightning transients and interferences, proper grounding will reduce susceptibil­ity. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting cir-
cuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming,
or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over-tightening
may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
Though designed to last many years, system components can fail at
any time. This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static-sup­pressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and program-
ming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation by authorized personnel.

FCC Warning

WAR NING: This equipment generates, uses, and can radi-
ate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause inter­ference to radio communications. It has been tested and found to comply with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when operated in a commercial environ­ment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at his own expense.
Acclimate Plus™ ONYX®, FlashScan®, UniNet®, VIEW®, NOTIFIER® are registered trademarks of Honeywell. Simplex® is registered trademark of Tyco International Ltd. Echelon®
Corporation. General Electric Company.
© 2009 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
, HARSH™, NOTI•FIRE•NET™, VeriFire™, NION™, NOTIFER Intergrated Systems™ and ONYXWorks™ are trademarks, and
is a registered trademark and LonWorks™ is a trademark of Echelon Corporation. ARCNET® is a registered trademark of Datapoint
Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. LEXAN® is a registered trademark of GE Plastics, a subsidiary of
Canadian Requirements: This digital apparatus does not
exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communica­tions. This Class A digital apparatus complies with Cana­dian ICES-003.
Le present appareil numerique n'emet pas de bruits radio­electriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada. Cet appareil numerique de la classe A est conforme a la norme NMB-003 du Canada.
3BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments, you can email us.
Please include the following information:
Product name and version number (if applicable)
Manual page number
Your comment
Send email messages to:
FireSystems.TechPubs@honeywell.com
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services.
4 BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09

Table of Contents

Section 1 NOTIFIER® BACnet Gateway-3 Features .............................................................. 7
1.1: Product Description .......................................................................................................................................7
1.1.1: BACnet GW-3 Features.......................................................................................................................7
1.2: Related Documentation .................................................................................................................................8
Table 1.1 Related Documentation ..........................................................................................................8
1.3: Agency Listings .............................................................................................................................................8
1.3.1: Compliance..........................................................................................................................................8
1.3.2: Installation ...........................................................................................................................................9
1.4: Environmental Requirements ........................................................................................................................9
1.5: Compatibility ..............................................................................................................................................10
1.6: Upgrade Information ...................................................................................................................................10
1.7: System Requirements ..................................................................................................................................10
1.8: System Architecture.....................................................................................................................................11
1.8.1: Single Panel Architecture ..................................................................................................................11
Figure 1.1 BACnet GW-3 Single Panel Diagram ................................................................................11
1.8.2: NFN Network Architecture ...............................................................................................................11
Figure 1.2 Notifier System Example 1- A Single NFN Network.........................................................12
Figure 1.3 Notifier System Example 2 - Multiple NFN Networks ......................................................13
Section 2 BACnet GW-3 Embedded Installation.................................................................. 15
2.1: Required Equipment ....................................................................................................................................15
2.2: BACnet GW-3 Installation Overview..........................................................................................................16
2.2.1: Gateway Installation Process Overview Flow Diagram....................................................................16
Figure 2.1 Gateway Installation Process Flow Diagram ......................................................................16
2.2.2: BACnet GW-3 Board Layout............................................................................................................17
Figure 2.2 BACnet GW-3 Board..........................................................................................................17
2.3: Installing a CAB3/CAB4 Cabinet ...............................................................................................................18
Figure 2.3 CAB-3/CAB-4 Series Installation Document, 15330 .........................................................18
2.4: Installing a CHS-4L Chassis........................................................................................................................19
Figure 2.4 Installing a Chassis..............................................................................................................19
2.5: Installing the BACnet GW-3 Board.............................................................................................................20
Figure 2.5 Install BACnet GW-3 Board onto Chassis .........................................................................20
2.5.1: BACnet GW-3 Power Supply Connection .......................................................................................20
Table 2.1 Power Supply Specifications................................................................................................20
Figure 2.6 BACnet GW-3 Power Connection......................................................................................21
2.5.2: Wiring Restrictions............................................................................................................................21
2.5.3: Installing the Network Communication Module ...............................................................................22
Table 2.2 Network Communication Module Details ...........................................................................22
Figure 2.7 HS-NCM Installation Document PN 54014 .......................................................................22
Figure 2.8 NCM Installation Document
PN 51533..............................................................................................................................................22
2.6: Connecting BACnet GW-3 to an IP Network..............................................................................................23
Figure 2.9 IP Cable Connection .........................................................................................................23
2.7: Connecting BACnet GW-3 to an NFN Network or High Speed NFN Network .........................................23
Section 3 BACnet GW-3 Configuration and Operation ....................................................... 25
3.1: BACnet GW-3 Configuration......................................................................................................................25
3.1.1: BACnet GW-3 Configuration Overview...........................................................................................25
3.1.2: BACNet Gateway Configuration Tool Installation ...........................................................................25
3.1.3: Connect the Configuration Computer to the BACnet GW-3 ............................................................26
3.1.4: Prepare the Configuration Computer to Communicate with BACnet GW-3....................................26
3.1.5: Log into the BACnet GW-3 for Configuration .................................................................................27
3.1.6: Configure the BACnet GW-3............................................................................................................28
3.1.7: Viewing BACnet GW-3 Activity with the BACNet Gateway Configuration Tool ..........................33
3.2: Connect the BACnet GW-3 to the NFN Network or FACP ........................................................................33
5BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Table of Contents
Table 3.1 BACnet GW-3 to Fire System Connection Options.............................................................34
3.2.1: Connecting BACnet GW-3 to a High Speed NFN Network Control Module ..................................35
Figure 3.1 USB Connection..................................................................................................................35
Figure 3.2 NUP to NUP Connection ....................................................................................................36
3.2.2: Connecting BACnet GW-3 to an NFN Network Control Module ....................................................37
Figure 3.3 NUP to NUP Connection ....................................................................................................37
3.2.3: Connecting BACnet GW-3 Directly to a Fire Alarm Control Panel .................................................38
Figure 3.4 NUP to NUP Connection ....................................................................................................38
3.3: Back Up BACnet GW-3...............................................................................................................................38
3.4: Restore BACnet GW-3 ................................................................................................................................39
3.5: BACnet GW-3 Operation.............................................................................................................................40
3.5.1: About BACnet GW-3 Start Up..........................................................................................................40
Appendix A: PIC Statement ................................................................................................... 41
A.1: BACnet Protocol Implementation Conformance Statement (Normative) ..................................................41
Appendix B: BACnet GW-3 Compatible Node Types .......................................................... 47
B.1: Direct Connect Node Type Compatibility...................................................................................................47
Table B.1 Panel Communication Connection Table ............................................................................47
Appendix C: BACnet GW-3 Local Configuration ................................................................. 49
C.1: Direct Connection to the Gateway Board ...................................................................................................49
Figure C.1 Configuration Computer Direct Connection ......................................................................49
Table C.1 Cross Over Cable (568B).....................................................................................................50
Appendix D: Glossary ............................................................................................................51
Index ........................................................................................................................................53
6 BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09

Section 1 NOTIFIER® BACnet Gateway-3 Features

1.1 Product Description

The NOTIFIER® BACnet Gateway-3 (BACnet GW-3) provides a communication link between networks that use the BACnet communication protocol and Fire Alarm Control Panels (FACP) resident on an NFN network or high speed NFN network. The BACnet GW-3 acts like any other node on an NFN network or high speed NFN network. The NFN network communicates with the gateway through an HS-NCM-W/SF/MF or NCM-W/F network control module that is on that NFN network or through a direct connection to a single NOTIFIER® panel. The BACnet communication protocol is an American National Standard (ANSI/ASHRAE 135-1995).
The BACnet GW-3 application represents physical fire devices as BACnet objects and manages the object database. As events occur, the object properties are updated in real-time, and messages are sent to the appropriate BACnet report destination (BACnet computer clients are computers with the graphical user interface workstation front end). BACnet clients may make requests to read properties of the BACnet objects. Those properties are the values of the device status and programming. The user subscribes to Event Notification objects per FACP, and the BACnet device receives events from objects on the FACP as a result of this subscription.
The BACnet client workstation front end must conform to BACnet Standard Annex J for IP and support Device Objects, Binary Output Objects, and Multi-state Input or Life Safety Points/Zones. It is also required to write to Notification Objects and receive confirmed/unconfirmed event notification messages. For details, refer to Appendix A, “PIC Statement”, on page 41.
The BACnet GW-3 Configuration Tool, an offline programming utility that is included with the BACnet GW-3 assembly when ordered, is used to configure the BACnet GW-3. It is installed onto a computer that will be used to configure the gateway. Refer to “BACnet GW-3 Configuration” on
page 27.

1.1.1 BACnet GW-3 Features

Below are some of the features of the BACnet GW-3.
Multiple Gateways can be used for large networks (greater than 15 panels/15,000 objects).
Use of ethernet port for BACnet GW-3 configuration with the BACnet GW-3 Configuration Tool.
NOTE: This manual is written with the understanding that its user is trained in BACnet operations and services. The information provided here is solely for the configuration of the Gateway to communicate event information to an existing BACnet network.
7BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
NOTIFIER® BACnet Gateway-3 Features Related Documentation

1.2 Related Documentation

Below is a list of documentation that relates to the use of the BACnet GW-3.

Table 1.1 Related Documentation

For information on Refer to Part No.
Compatible Devices Device Compatibility Document 15378
Cabinets & Chassis CAB-3/CAB-4 Series Installation Document 15330
Offline Programming Utility Veri•Fire™ Tools on-line help file
Veri•Fire™ Medium Systems on-line help file
VeriFire-TCDNetworking NFN Manual
NCM-W/F Installation Document HS-NCM-W/SF/MF Installation Document MIB Media Interface Board Manual
Panels and Annunciators NFS-320 Installation/Operation/Programming Manual
NFS-640 Installation/Operation/Programming Manual NFS2-640 Installation/Operation/Programming Manual NFS-3030 Installation/Operation/Programming Manual NFS2-3030 Installation/Operation/Programming Manual Network Control Annunciator (NCA) Manual Network Control Annunciator-2 (NCA-2) Manual Network Control Station (NCS) Manual AM2020/AFP1010 Installation, Operation, and Programming Manual DVC Series Digital Voice Command Manual

1.3 Agency Listings

NOTE: UL 864, 9th Edition—Notifier systems work with products that have been UL 864, 9th Edition
listed as well as products that have not received UL 864, 9th Edition certification. Operation of systems that are comprised of equipment that is UL 864, 9th Edition listed together with products that are not UL 864, 9th Edition listed requires the approval of the local Authority Having Jurisdiction (AHJ). CAN/ULC-S559-04, 1st Edition—Notifier systems work with products that have been CAN/ULC- S559-04, 1st Edition listed as well as products that have not received CAN/ULC-S559-04, 1st Edition certification. Operation of systems that are comprised of equipment that is CAN/ULC­S559-04, 1st Edition listed together with products that are not CAN/ULC-S559-04, 1st Edition listed requires the approval of the local Authority Having Jurisdiction (AHJ).
VeriFire-TCD VeriFire-CD
51584 51533 54014 50255
52745/52746/52747 52544/52545/52546 52741/52742/52743 51330/51344/51345 52544/52546/52545 51482 52482 51095 15088 52411

1.3.1 Compliance

This product has been investigated to, and found to be in compliance with the following standards.
National Fire Protection Association
NFPA 72—National Fire Alarm Code
Underwriters Laboratories
UL-864—Control Units for Fire Alarm Systems, Ninth Edition
UL-2017—General-Purpose Signaling Devices and Systems, First Edition
Underwriters Laboratories Canada
CAN/ULC-S527-99—Standard for Control Units for Fire Alarm Systems, Second Edition
8 BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Environmental Requirements NOTIFIER® BACnet Gateway-3 Features
CAN/ULC-S559-04—Equipment for Fire Signal Receiving Centres and Systems, First Edition

1.3.2 Installation

This product is intended to be installed in accordance with the following regulatory agencies.
Local
AHJ—Authority Having Jurisdiction
National Fire Protection Association
NFPA 70—National Electrical Code
NFPA 72—National Fire Alarm Code
NFPA 101—Life Safety Code
Underwriters Laboratories
UL-1076—In certified applications, the unit shall be installed in accordance with Proprietary Burglar Alarm Units and Systems, Fifth Edition
Underwriters Laboratories Canada
C22.1–98—Canadian Electrical Code, Part I (Twentieth Edition), Safety Standard for Electrical Installation
CAN/ULC-S524-06—Standard for the installation of Fire Alarm Systems, Fifth Edition
CAN/ULC-S561-03—Installation and Services for Fire Signal Receiving Centres and Systems, First Edition
WARNING: Installation
!
Improper installation, maintenance, and lack of routine testing could result in system malfunction.
About Ethernet Network Installations
“Listed for the purpose” has been formally interpreted by NFPA (Formal Interpretation 72-99-1) for equipment on packet switched networks as being listed to the requirements applicable to general purpose communications network equipment.
For ULC applications, the Internet cannot be used for either primary or ancillary functionality.
“Listed for the purpose” has been formally interpreted by NFPA (Formal Interpretation 72-99-1) for equipment on packet switched networks as being listed to the requirements applicable to general purpose communications network equipment.
For ULC applications, the Internet cannot be used for either primary or ancillary functionality.

1.4 Environmental Requirements

This product must be installed in the following environmental conditions:
Temperature range of 0°C to 49°C (32°F - 120°F).
93% humidity non-condensing at 30°C (86°F).
The contents of this manual are important and must be kept in close proximity of the hardware. If building ownership is changed, this manual and all other testing and maintenance information must also be passed to the current owner of the facility. A copy of this manual was shipped with the equipment and is also available from the manufacturer.
NOTE: Refer to Appendix A, “PIC Statement”, on page 41 for the BACnet PIC statement.
9BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
NOTIFIER® BACnet Gateway-3 Features Compatibility

1.5 Compatibility

NOTE: The BACnet GW-3 requires that at least one node on the NFN network be an ONYX
series panel. BACnet GW-3 does not run on an NFN network with no ONYX series panels.
Refer to Appendix B, “BACnet GW-3 Compatible Node Types”, on page 47 for supported panels and annunciators.

1.6 Upgrade Information

Firmware for systems running BACnet GW-3 versions prior to 3.11 should not be upgraded unless there is an ONYX series panel on the system. BACnet GW-3 does not run on an NFN network with no ONYX series panels.

1.7 System Requirements

The BACnet GW-3 can monitor up to fifteen panels, but the combined object count across the monitored panels cannot exceed 15,000 objects. This includes all detectors, monitor modules, control modules, bell circuits, etc. Refer to the NFN network manual for details about wiring limitations.
The computer on which the BACnet GW-3Configuration Tool is installed should be Windows 2000 or Window XP. The computer must communicate with the BACnet GW-3 over IP or through a crossover cable from the BACnet GW-3 ethernet port.
10 BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
System Architecture NOTIFIER® BACnet Gateway-3 Features

1.8 System Architecture

NOTE: The BACnet GW-3 client workstation is not intended as a primary annunciator and is ancillary
in nature.
These are connections options for the BACnet GW-3 architecture.
An Internet or Intranet IP network connection is used with both architectures.

1.8.1 Single Panel Architecture

Direct panel connection; a connection is made directly to a supported NOTIFIER® panel or annunciator (Figure 1.1 on page 11). Refer to Appendix B, “BACnet GW-3 Compatible Node
Types”, on page 47 for supported panels and annunciators.
BACnet/IP Client with Workstation Front End
IP connection over Ethernet
Figure 1.1 BACnet GW-3 Single Panel Diagram

1.8.2 NFN Network Architecture

NFN network connection; a NUP connection is made to an NCM or HS-NCM board on the NFN network as the BACnet GW-3 (Figure 1.2 on page 12)
BACnet GW-3
NUP connection
FACP
11BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
NOTIFIER® BACnet Gateway-3 Features System Architecture
IP Network
BACnet/IP Client with Workstation Front End
FACP FACP
BACnet/IP Client with Workstation Front End
HS-NCM W/SF/MF
or
NCM W/F
BACnet GW-3
NFN Network
FACP
Figure 1.2 Notifier System Example 1- A Single NFN Network
12 BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
System Architecture NOTIFIER® BACnet Gateway-3 Features
IP Network
Workstation/
BACnet/IP Client with Workstation Front End
PC Gateway
HS-NCM W/SF/MF
or
NCM W/F
BACnet GW-3
FACP
NFN Network
FACP
FACP
Style 4 or 6
Echelon
Network Wire
or Fiber
Workstation/Echelon Gateway
NION
NION
NION
FACP FACP
NFN Network
FACP
Figure 1.3 Notifier System Example 2 - Multiple NFN Networks
13BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
NOTIFIER® BACnet Gateway-3 Features System Architecture
14 BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09

Section 2 BACnet GW-3 Embedded Installation

NOTE: The BACnet GW-3 is for ancillary use only and does not increase the burglary grade of service
for the system.

2.1 Required Equipment

The BACnet GW-3 requires the following:
BACnet GW-3 Assembly
The following are shipped with the BACnet GW-3:
BACnet GW-3 board
PNET-1 surge suppressor (P/N PNET-1)
NUP to NUP Cable (P/N 75556)—used to connect the BACnet GW-3 board to an HS-NCM­W/SF/MF boardl or NCM-W/F board and supported panel
USB Cable (P/N 75665)—used to connect the BACnet GW-3 board to an HS-NCM-W/SF/MF boardl
Wire Leads to NUP Network Communications Module power cable (P/N 75583)
Network Components
RJ45 to RJ45 standard Ethernet network cable—customer’s internet or intranet connection to BACnet GW-3
Workstation v3.11 or above (sold separately)
NFN network—version 5.0 or above (sold separately)
High Speed Network Communications Module: HS-NCM-W/SF/MF board—used to facilitate network communication between the BACnet GW-3 and a High Speed NFN network (sold separately) OR
Network Communications Module: NCM-W/F board—used to facilitate network communication between the BACnet GW-3 and an NFN network (sold separately).
NOTE: No HS-NCM-W/SF/MF board or NCM-W/F board is required when the BACnet GW-3 connects directly to a supported NOTIFIER® panel or annunciator when it is a standalone panel or annunciator. Refer to “Panel Communication Connection Table” on page 47 for a list of supported panels.
Cabinet and Hardware (sold separately)
CAB-3/CAB-4 series cabinet
CHS-4L chassis
Customer Supplied Equipment
A computer to run the BACNet Gateway Configuration Tool and configure the BACnet GW-3. Contact Technical Support for software version compatibility.
15BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
BACnet GW-3 Embedded Installation BACnet GW-3 Installation Overview

2.2 BACnet GW-3 Installation Overview

CAUTION: Multiple BACnet GW-3 Installations
!
BACnet GW-3s must be installed and configured one at a time because all BACnet GW-3s use the same predefined IP address and node number.

2.2.1 Gateway Installation Process Overview Flow Diagram

Start
“Installing a CAB3/CAB4
Cabinet” on page 18
“Installing the BACnet
GW-3 Board” on page 20
“Installing the Network
Communication Module”
on page 22
“Connecting BACnet GW-3 to an IP
Network” on page 23
To Section 3, “BACnet
GW-3 Configuration”, on
page 27
Figure 2.1 Gateway Installation Process Flow Diagram
16 BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
BACnet GW-3 Installation Overview BACnet GW-3 Embedded Installation

2.2.2 BACnet GW-3 Board Layout

USB “B” Device (J14)USB “A” Host (J13)
Ethernet Connector (J8)
Mounting Hole with Surrounding Grounding Area (5 locations)
NUP A Serial Data Connector (J6)
not used (J7)
TB6: NO
Not Used
Com NC TB1:
-24 V Out +24 V Out
-24 V In +24 V In
Figure 2.2 BACnet GW-3 Board
17BACnet Gateway-3 Installation and Operation Manual - P/N: 53372:Rev: A 5/6/09
Loading...
+ 39 hidden pages