Notifier AIM-200 User Manual

Page 1
12 Clintonville Road Northford, CT 06472 Phone: 203-484-7161 Fax: 203-484-7118
AIM-200
The Addressable Intelligent Module
Floor 1
Floor 2
Floor 3
Floor 4
FORWARD
REVERSE
STEP
Floor 5
Floor 6
Floor 7
Floor 8
DETECTOR
ADDRESS
MODULE
Technical Manuals Online! - http://www.tech-man.com
Document# 15949 10/29/97 Revision:
P/N 15949:E1 ECN 97-407
EE
E
EE
Page 2
2
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
Page 3
T ab le of Contents
Section One: The AIM-200 ........................................................... 4
1.1: General Information ......................................... 4
Section Tw o: Inventory................................................................. 5
2.1: Optional Peripherals ........................................ 6
2.2: Addressable Modules ...................................... 7
Section Three: Installation.............................................................. 9
3.1: Installing the AIM-200...................................... 9
3.2: Wiring the Communications Circuit ................. 11
3.3: The Isolator Module ......................................... 20
3.4: The MMX-1 ...................................................... 21
3.5: The MMX-2 ...................................................... 22
3.6: The MMX-101 .................................................. 23
3.7: The CMX-2....................................................... 28
3.8: The Addressable Manual Pull Station ............. 32
3.9: The Intelligent Detector.................................... 33
3.10: Inserting the AIM-200 Cards .......................... 34
Section Four: Programming ......................................................... 35
4.1: Default Zone Map ............................................ 35
4.2: Display Status.................................................. 38
4.3: Program Edit .................................................... 40
4.4: Alarm Bus ........................................................ 41
4.5: General Alarm Service .................................... 42
4.6: Backup Alarm Bus ........................................... 43
4.7: Signal Silence Function ................................... 44
Section Five: Operation................................................................ 46
5.1: Zone Display.................................................... 46
Appendix A: Operating the Control Modules ............................ 50
Appendix B: AIM-200 Power Requirements .............................. 54
Appendix C: AIM-200 Point Annunciation ................................. 55
Document 15949 Rev. E 4/12/95 P/N 15949:E
3
Technical Manuals Online! - http://www.tech-man.com
Page 4
Section One: The AIM-200
1.1 General Description
Note: AIM-200 features discussed in this document are available with AIM-200 software
part number 73264 or greater.
The Addressable Intelligent Module (AIM-200) functions as an interface between the Sys­tem 5000 Fire Alarm Control Panel and intelligent/addressable devices. To the System 5000, the AIM-200 looks like an IZM-8 Initiating Zone Module. On its single communications loop, the AIM-200 will communicate with up to 99 addressable modules and 99 intelligent detectors. The AIM-200 will communicate with the following:
SDX-551 Intelligent Photoelectric Smoke Detector SDX-751 Low Profile Intelligent Photoelectric Smoke Detector CPX-551 Intelligent Ionization Smoke Detector CPX-751 Low Profile Intelligent Ionization Smoke Detector FDX-551 Intelligent Thermal Sensor
MMX-1 Addressable Monitor Module MMX-2 Addressable Monitor Module
MMX-101 Miniature Monitor Module
CMX-2 Addressable Control Module
BGX-101L Addressable Manual Pull Station
DHX-501/DHX-502 Intelligent Duct Detector Housing (for use with SDX-551 only)
The 198 devices are mapped into eight software zones b y the AIM-200. The status of these zones is reported to the CPU-5000. The AIM-200 includes a digital display for identifying the exact device address within a zone . The display is also used to displa y de vice types and analog detector sensitivity values.
Although the AIM-200 is intended primarily as an initiating input module, it can support CMX-2 Control Modules on the loop. The CMX-2 modules may be mapped to AIM-200 zones much like outputs are mapped to inputs during standard System 5000 programming.
The AIM-200 may be mixed in a system with any of these system modules:
IZM-8 Initiating Zone Module IZE-A Initiating Zone Expander ICM-4 Indicating Circuit Module ICE-4 Initiating Circuit Expander
CRM-4 Control Relay Module
CRE-4 Control Relay Expander
VCM-4 Voice Control Module
VCE-4 Voice Control Expander DCM-4 Dual Channel Module TCM-2 Time Control Module (Single hazard release) TCM-4 Time Control Module (Multiple hazard release)
In addition, ACM remote annunciators, AMG-1 and FFT-7 voice/telephone modules, and several power supplies can be employed with an AIM-200.
Up to ten AIM-200s may be installed in one System 5000 for a capacity of 1,980 points (subject to limitations of system power supply, refer to Appendix B).
4
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
Page 5
Section Two: Inventory
d
aim200m
The AIM-200 Addressable Intelligent Module
The AIM-200 communicates with up to 99 intelligent detectors and up to 99 addres­sable modules. The AIM-200 reports de­vice alarm or trouble activity back to the CPU as one of eight mapped zones.
This modu l e mod ito rs 8 zone s of fire deted tion de vices. Ea ch zone may consist of many individual detectors or other devices. The address of the device in alarm or trouble (fault) is indicated by the 2-digit display. If multiple addresses are displayed, press th e STEP switches to control the display. Additional information about each device is provided behind this card. This module can measure the condition and status of its detectors (intelligent). Information and controls are provided behind all cards (authorized individuals only).
AIM-200
Addressable Intel l i g en t Mod u le
FOWARD
STEP
REVER SE
DISPLAY STATUS
ENTER
DETECTOR
ADDRESS
MODULE
ON-LINE SKIP
STYLE 6
LOOP FAULT
RESET
AIMLABEL
Label Inserts
The slide-in labels are printed with identification for system-defined LEDs and switches. Space is pro­vided to type in custom informa­tion for the eight user-defined zones.
1
1
1
1
1
1
aimcard
Card File
A special card file is attached to the bottom front of the AIM-200. Several standard 4 in. by 2-1/4 in. cards are provided and may be marked with device information by the installer . A reference card, which defines all display codes, is included.
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
5
Page 6
2.1 Optional Peripherals: Intelligent Detectors
BX-501 Base
These intelligent, addressable detectors provide analog information to the AIM-200. The AIM-200 processes this analog information and con­tinually makes decisions on the alarm, maintenance, or normal status of each device. Each detector head mounts to a BX-501 base for ease of
BX-501 Base
installation or replacement. The sensitivity of each detector can be set by the programmer at the AIM-200 for one of three le vels (low , medium, and high). Each detector responds to an address that is set in the head via built-in rotary decimal switches.
BX-501BH Sounder built into base B501 Flangeless base
SDX-551
An intelligent photoelectric smoke detector that provides analog mea­surements of the optical smoke level in its chamber to the AIM-200 panel.
SDX-751
A low profile intelligent photoelectric smoke detector.
CPX-551
An intelligent ionization smoke detector that measures the level of com­bustion products in its chamber using the ionization principle and reports this measurement to the AIM-200.
CPX-751
A low profile intelligent ionization smoke detector.
FDX-551
An intelligent thermal sensor (135-degree F fixed temperature).
RA400Z
A remote single LED annunciator that can be wired directly off of an ad­dressable detector for annunciation of that detector’s alar m status.
6
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
Page 7
2.2 Optional Peripherals: Addressab le Modules
Control and Monitor Modules
The CMX-2 control module and the MMX-1 monitor module provide the interface between the System 5000 and conv entional initiating and
CAUTION
notification devices. Both types of modules respond to an address that is set by the installer with built-in rotary decimal switches. A flash­ing LED indicates power is applied. A thermoplastic cover (illustrated at left) is provided with each module for mounting to a 4-inch square mounting box.
MMX-1
An addressable monitor module that can be used to monitor conven­tional normally open contact alarm initiating devices, such as manual pull stations, 4-wire smoke detectors, heat detectors, waterflow, and supervisory devices. Supervised circuit can be wired NFPA Style B or Style D.
MMX-2
An addressable monitor module that monitors conventional 2-wire smoke detectors. Supervised circuits can be wired NFPA Style B or Style D. MMX-2 supervises initiating device circuit wiring, communi­cation loop, and input power.
CMX-2
An addressable control module that can be used as a notification appliance circuit for powering and supervising compatible, UL Listed notification appliances. Supervised circuits can be wired NFPA Style Y or Style Z. By breaking two built-in tabs, the CMX-2 can be em­ployed as a Form-C control relay.
ISO-X
The loop isolator module is an automatic switch that opens the circuit voltage to a predetermined communications loop branch(es) when­ever a fault is detected on that circuit. The remainder of the commu­nications loop leading up to the ISO-X will continue to operate, unaf­fected by the fault.
9
0
8
1
7
6
ADDRESS
2
3
4
5
LOOP
9
0
8
1
7
6
3
4
5
MMX-101
2
An addressable module that is functionally identical to an MMX-1 monitor module (Style B circuits only),
mmx10
but offered in a smaller package for mounting di­rectly in the electrical box of the device being moni-
tored.
Document 15949 Rev. E 4/12/95 P/N 15949:E
7
Technical Manuals Online! - http://www.tech-man.com
Page 8
BGX-101L
FIRE
PUSH IN
THEN
PULL DOWN
The addressable manual pull station features a key-lock reset. The pull station responds to an address set by the installer with built-in rotary decimal switches. Includes key.
System Sensor (SSD) A2143-00
The 47K end-of-line resistor assembly is used in the supervision of MMX-1 Monitor and CMX-2 Control Module circuits. It is included with each MMX-1 or CMX-2 module.
N-ELR
The N-ELR resistor assortment is required for use in Canada. It provides a variety of resistor values to mount to a single ELR plate (included). Resistors can be used for the supervision of an MMX-1 monitor module or CMX-2 control module circuit.
Resistors included: 120 ohms, 470 ohms, 1.8K, 2.2K, 4.7K, 6.8K, 10K, 27K, and 47K.
8
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
Page 9
Section Three: Installation
This section outlines the installation procedure for the AIM-200. For information on install­ing other System 5000 equipment and power limited wiring, refer to the Installation Manual, Document 15583.
3.1 Installing the AIM-200
Complete the following steps to install the AIM-200 onto the CHS-4 Chassis.
1) Mount the AIM-200 to a CHS-4 Chassis.
2) Insert the tab on the bottom of the AIM-200 into the slot on the bottom of the CHS-4.
3) Fasten the AIM-200 to the top of the CHS-4 using the two captive screws in the top corners of the module. Refer to Figure 3-1.
4) Connect the ribbon cable. See Figure 3-2.
Note: If point annunciation (192 intelligent AIM-200 points and 56 standard system circuits)
of a single AIM-200 is desired, the AIM-200 must be mounted in the second slot of the first chassis (directly to the right of the CPU). This annunciation option must also be selected in system programming.
Connecting the Alarm Bus Cable
Connect the alarm bus cable following the steps below. Use the alarm bus cable (Part No.
71033) included with the AIM-200.
1) Remove the 2-pin connector on one end of the cable.
2) Separate and strip the wires, leaving about half an inch of bare wire exposed.
3) Connect wires to Terminals 14 and 15 on the CPU.
4) Connect the other end of the trouble cable to the left-most 2-pin terminal on the bottom left-hand corner of the AIM-200. If additional AIM-200s are employed, see Figure 3-3.
AIM-200 CHS-4
Figure 3-1: Mounting the AIM-200
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
AIM-200 CHS -4
9
Page 10
FC-2000 1st Row or
CPU-5000 1st Row or
Expander Ribbon Cable
Expander Ribbon Cable
From
From
CPU-5000
CPU-2000
AIM-200
aim200-3
Figure 3-2: Connecting the Ribbon Cable
CAUTION: Do not connect any other device or circuit to the alarm relay contacts on the CPU-5000 while the alarm bus cable (Part No.
!
71033) is installed in the system.
To First AIM-200
2 13 14 15 16 17 18 19 20
To Next Module
Alarm Bus
Cable
P art No. 71 03 3
AIM-200
CPU-5000
FC-2000
Figure 3-3: Connecting the Alarm Bus Cable
Note: Refer to the System 5000 manual for power limited wiring requirements, document
number 15583.
10
Document 15949 Rev. E 4/12/95 P/N 15949:E
AIM-200
From
From
CPU-5000
CPU-2000
To Next AIM-200
aimalrm
Technical Manuals Online! - http://www.tech-man.com
Page 11
3.2 Wiring the Comm unications Loop Cir cuit
The AIM-200 communicates with intelligent and addressable initiating, monitor and control devices through a communications loop. The System 5000 can support up to ten communi­cations loops, each controlled by an AIM-200 module. The communications loops can be wired as non-redundant (Figure 3-6), redundant (Figure 3-7), or isolated redundant (Figure 3-8).
Isolator Modules
Isolator modules (ISO-X) permit a zone of detectors and modules to be electrically isolated from the remainder of the communications loop, allowing critical loop components to func­tion in the event of a circuit fault (see Figures 3-8 and 3-12).
Monitor Modules
Addressable monitor modules (MMX-1, MMX-2, and MMX-101) allow the AIM-200 to moni­tor entire circuits of conventional normally open contacts, alarm initiating devices, manual pull stations, 4-wire smoke detectors, heat detectors, and waterflow and supervisory de­vices (Figures 3-13A and 3-14A). A type of monitor module, the addressable BGX-101L, provides point annunciation of manual pull stations (Figure 3-18).
Control Modules
Through addressable control modules (CMX-2), the System 5000 can selectively activate notification appliance circuits or Form-C output relays (see Figures 3-15 through 3-17).
Intelligent Detectors
Through the communications loop, the AIM-200 communicates with intelligent ionization, photoelectric, and thermal detectors (Figure 3-19).
Loop Capacity
The capacity of each AIM-200 includes up to 99 intelligent detectors and an additional combination of up to 99 addressable pull stations, control modules, and monitor modules. One to ten AIM-200s can be employed, depending on system requirements.
Notes:
1) Communications loop is supervised and power limited.
2) Maximum loop length is 10,000 feet (total twisted pair length).
3) Maximum loop voltage: 27.6 VDC.
4) Maximum loop current: 200 mA (short circuit) 100 mA (normal operation)
5) Maximum loop resistance: 40 ohms.
6) Refer to the proper installation drawing supplied with each communications loop ap­pliance.
Document 15949 Rev. E 4/12/95 P/N 15949:E
11
Technical Manuals Online! - http://www.tech-man.com
Page 12
T ab le 3-1: Communications Loop Performance
Fault Condition
Single Open on Loop
Trouble (Note 1)
Trouble with Alarm Capability
Trouble with Alarm Capability
Single Ground on Loop
Trouble with Alarm Capability (Note 2)
Trouble with Alarm Capability
Isolated Redundant (4-Wire) Loop Operation (Note 3)
Trouble with Alarm Capability
Loop has Been Shorted
Non-Redundant (2-Wire) Loop Operation
Trouble Trouble Trouble Trouble Trouble
Redundant (4-Wire) Loop Operation
Trouble Trouble Trouble Trouble
Trouble with Alarm Capability
Loop Shorted and Opened
Trouble Trouble
Loop Shorted and Grounded
with Alarm Capability
Loop Opened and Grounded
with Alarm Capability
Trouble with Alarm Capability
Commun Loss with Control Panel
Trouble
Trouble
Notes:
1. Trouble indicates that a trouble signal will be generated at the control
panel under the abnormal condition.
2. Alarm capability indicates whether or not an alarm signal can be trans-
mitted to the control panel during the abnormal condition.
3. Isolated redundant loop operation is a method of protecting, or isolat-
ing, entire physical zones of de vices on the comm unications loop from faults that occur within other areas of the loop.
12
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
Page 13
Figure 3-4: AIM-200 Wiring Requirements Non-Redundant Circuit
Branch B Branch E
Branch D
Loop
Out
Branch A
Branch C
For Each Loop:
Add the lengths of all the branches on one loop. This sum cannot exceed 10,000 feet per loop.
(Branch A) + (Branch B) + (Branch C) + (Branch D) + (Branch E) = 10,000 feet or less
+ - + -
AIM-200
aimwire1
Branch Resistance
Short the ter mination point of one branch at a time and measure DC resistance from the beginning of the loop to the end of that particular branch. The total DC resistance from panel to branch end cannot exceed 40 ohms. Repeat this procedure for all remaining branches.
Communications Loop Out
Branch
Document 15949 Rev. E 4/12/95 P/N 15949:E
13
Technical Manuals Online! - http://www.tech-man.com
Page 14
No T-tapping is allowed on a redundant circuit.
Loop
Out
+ - + -
AIM-200
Loop
Return
aimwire2
Figure 3-5: Redundant Circuit
Total length of the communications loop pair cannot exceed 10,000 feet (measured from the control panel out, and back to the control panel).
The DC resistance of the communications loop pair cannot exceed 40 ohms. This measure­ment may be obtained by disconnecting loop out and return at the control panel, shorting the two leads of communications loop return together and metering loop out.
Loop Out
Loop Return
14
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
resistn3
Page 15
Figure 3-6: Non-Redundant Communications Loop
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
15
Page 16
Figure 3-7: Redundant Communications Loop
16
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
Page 17
Isolated-Redundant Circuit
By flanking each communications loop device with a pair of ISO-X fault isolator modules, each device is protected from short circuit faults that may occur on other devices. For example, a f ault on Zone 2 will not effect Zones 1 and 3. The isolator modules on either side of Zone 2 will open the loop. Zone 1 will still oper ate from pow er on loop out and Zone 3 will operate from loop return. Since the system will no longer be able to communicate with Zone 2, a trouble signal(s) will be generated for that device. This circuit is a variation of the redundant circuit, therefore, no T-tapping or branching is allowed. The ratings and characteristics are the same as for the redundant circuit.
ISO-X
M500XJ
Isolator Module
Protected Premises Area "2"
Protected Premises
Area "1"
ISO-X
M500XJ
Isolator Module
Protected Premises
Area "3"
ISO-X
M500XJ
Isolator Module
ISO-X
M500XJ
Isolator Module
Loop
Out
+ - + -
AIM-200
Figure 3-8: Isolated-Redundant Communications Loop
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
Loop
Return
commloop3
17
Page 18
Shield Termination in No Conduit
Do not allow the shield drain wire to enter the control panel cabinet. Connect the dr ain wire to the outside of the cabinet via a BX-type connector.
Shield
FC-2000
System 5000
Cabinet
Cabinet
( + )
( - )
Shield
Figure 3-9: Shield Termination in No Conduit
Shield Termination in Full Conduit
The shield drain wire must be connected to the negative (-) side of the loop. Do not allow the shield drain wire or the shield foil to touch the control panel cabinet.
Note: For redundant or isolated redundant field wiring of the communications loop, connect
each end of the shield to the negative side of the respective channel.
The shield must not be connected to earth ground at any point.
( + )
Shield
( - )
FC-2000
System 5000
Cabinet
Cabinet
Shield
Figure 3-10: Shield Termination in Full Conduit
Shield Termination in P artial Conduit
Do not allow the shield drain wire to enter the control panel cabinet or the conduit. Connect the drain wire to the termination point of the conduit run (such as a single-gang box as illustrated in Figure 3-11). The conduit cannot be longer than 20 feet.
18
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
Page 19
2
Shield
Must employ metal conduit and a metal box.
To AIM-200
FC-2000 Controller Enclosure
System 5000
Figure 3-11: Shield Termination in P artial Conduit
Do not allow the shield drain wire to enter the control panel cabinet or the conduit. Connect the drain wire to the termination point of the conduit run (such as a single-gang box as illustrated above).
The conduit cannot be longer than 20 feet.
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
Shield
Cabinet
19
Page 20
3.3 The Isolator Module
The loop isolator module (ISO-X) is used to protect critical elements of the communications loop from faults on other branches or sections of the loop . The ISO-X contin uously monitors the circuit connected to Terminals 3 (-) and 4 (+). Upon power up , an integral rela y is latched on. The ISO-X periodically pulses the coil of this relay. A short circuit on the loop resets the relay. The ISO-X sees this short and disconnects the faulted branch by opening the positive side of the loop (T erminal 4). This eff ectively isolates the f aulted branch from the remainder of the loop. Once the fault is removed, the ISO-X automatically reapplies power to the communications loop branch. Figure 3-12 illustrates the use of an ISO-X on a non-redundant communications loop. For employ­ing ISO-Xs on a redundant or isolated-redundant communications loop, see Figure 3-8.
Note: During a fault condition, the System 5000
will register a trouble condition for each zone mapped to the isolated loop branch.
Continuation of the Communications Loop
Loop In (-)
Loop In (+)
Loop Out (-)
Loop Out (+)
ISO-X
comloop4
Communications
Loop
1
2
3
4
M500XJ
ISO-X
T-Tapped Branch off the Communications Loop
commloop5
Figure 3-12: Isolating Non-Redundant Communications Loops
Shorts on this branch of an isolated non-redundant communications loop will be isolated from all devices installed both upstream of the ISO-X and on the continuation of the loop (shown as dotted line).
20
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
Page 21
3.4 The MMX-1 Monitor Module
The MMX-1 monitor module is an addressable module that monitors normally open con­tacts, shorting type alarm initiating devices. The supervised MMX-1 circuit can be wired as an NFPA Style B or Style D initiating device circuit. There is no limit to the n umber of contact type devices installed on a monitor module circuit. Refer to Figures 3-13A and 3-14A for MMX-1 wiring diagrams.
Communications Loop Connections
Connect the communications loop to MMX-1 Terminals 1(-) and 2 (+). The MMX-1 occupies one module address on the loop. Set the rotary switches on the MMX-1 to the particular loop address required.
NFPA Style B Initiating Device Circuit
Connect the normally open contacts of the alarm initiating devices to a single two-wire circuit. This circuit cannot be T-tapped or branched in any fashion, and must be terminated across the last device by a listed 47K, 1/2 watt ELR (Part No. A2143-00, supplied with mod­ule). Connect the circuit to MMX-1 Terminals 6 (-) and 7 (+).
NFPA Style D Initiating Device Circuit
Connect the normally open contacts of the alarm initiating devices to a single four-wire circuit. This circuit cannot be T-Tapped or branched in any fashion. No external ELR is required for Style D wiring. Connect the four-wire circuit to MMX-1 Terminals 6 (-) and 9 (-), then 7 (+) and 8 (+). The maximum initiating device circuit resistance is 20 ohms.
Document 15949 Rev. E 4/12/95 P/N 15949:E
21
Technical Manuals Online! - http://www.tech-man.com
Page 22
3.5 The MMX-2 Monitor Module
The MMX-2 monitor module is an addressable module that monitors conventional two-wire smoke detectors. The supervised MMX-2 circuit can be wired as an NFPA Style B or Style D initiating device circuit. Refer to the Device Compatibility Document for the type and number of detectors the MMX-2 will support. Refer to Figures 3-13B and 3-14B for MMX-2 wiring diagrams.
Communications Loop Connections
Connect the communications loop to MMX-2 Terminals 1(-) and 2 (+). The MMX-2 occupies one module address on the loop. Set the rotary switches on the MMX-2 to the particular loop address required.
NFPA Style B Initiating Device Circuit
Connect the alarm initiating devices to a single two-wire circuit. This circuit cannot be T-tapped or branched in any fashion, and must be terminated across the last device by a listed 3.9K ELR. Connect the circuit to MMX-2 Terminals 6 (-) and 7 (+). The maxim um initiating device circuit resistance is 25 ohms.
NFPA Style D Initiating Device Circuit
Connect the alarm initiating devices to a single four-wire circuit. This circuit cannot be T-tapped or branched in any fashion. No external ELR is required for Style D wiring. Con­nect the four-wire circuit to MMX-2 Terminals 6 (-) and 9 (-), then 7 (+) and 8 (+). The maximum initiating device circuit resistance is 25 ohms.
Power
The MMX-2 requires connection of 24 VDC filtered, power limited, regulated and resettable power on terminals 3 (-) and 4(+). Maximum stand-by current for two-wire detectors is
2.4mA. Maximum alarm current is 90mA.
22
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
Page 23
3.6 The MMX-101 Monitor Module
Set the module address
with these switches.
IDC (-) (White)
9
0
8
1
7
6
5
2
3
4
IDC (+) (Violet)
ADDRESS
LOOP
8
7
6
SLC (+)
(Red)
9
0
1
2
3
4
5
mmx101
SLC (-)
(Black)
The MMX-101 monitor module is an addressable module that is functionally and electrically identical to an MMX-1 monitor module (Style B circuits only), but offered in a smaller pack­age for mounting directly in the electrical box of the contact-type device being monitored.
NFPA Style B Initiating Device Circuit
Ter minate with an A2143-00 ELR (N-ELR in Canada).
MMX-1 and MMX-101 Monitor Module T e chnical Notes
1. Initiating device circuit is supervised and current-limited to 210 microamps @ 24 VDC (nominal).
2. Initiating device circuit provides the following services (do not mix):
a) Fire alarm service b) Automatic/manual waterflow alarm service with normally open contact devices c) Sprinkler super vision with nor mally open contact devices
3. Maximum loop resistance due to wiring is 65 ohms.
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
23
Page 24
Figure 3-13A: NFPA Style B Initiating Device Circuit
24
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
Page 25
Refer to the MMX-2 Installation Instructions, Document M500-03-00, for more details.
To next device
on loop
+ -
Listed End-of-Line
Resistor
3.9K
24 VDC Tw o-Wire
Smoke Detectors
+ -
AIM-200
9
-
-
24 VDC filtered, regulated,
1 2 3 4
MMX-2
+
­+
8
+
7
+
6
­5
ressettable power
MPS-24A, TB3 Terminals 2 (-) and 1 (+)
MPS-24B, TB2 Terminals 2 (-) and 1 (+)
UL-listed 24VDC power limited,
resettable, power supply for Fire
or
or
Protective Signaling
Figure 3-13B: NFPA Style B Initiating Device Circuit
Document 15949 Rev. E 4/12/95 P/N 15949:E
25
Technical Manuals Online! - http://www.tech-man.com
Page 26
Figure 3-14A: NFPA Style D Initiating Device Circuit
26
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
Page 27
Refer to the MMX-2 Installation Instructions, Document M500-03-00, for more details.
To next device
on loop
+ -
24 VDC
Tw o-Wire
Smoke
Detectors
+ -
AIM-200
Listed
3.9K ELR
24 VDC filtered, regulated,
1 2 3 4
-
MMX-2
+
­+
9
­8
+
7
+
6
­5
resettable power
MPS-24A, TB3 Terminals 2 (-) and 1 (+)
MPS-24B, TB2 Terminals 2 (-) and 1 (+)
UL-listed 24VDC power limited,
resettable, power supply for Fire
or
or
Protective Signaling
Figure 3-14B: NFPA Style D Initiating Device Circuit
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
27
Page 28
3.7 The Control Module
The CMX-2 control module is an addressable module that supervises and switches power to a notification appliance circuit. The CMX-2 circuit can be wired as an NFPA Style Y or Style Z notification appliance circuit. Alternately, the CMX-2 can be employed as a Form-C control relay.
(Alarm polarity shown)
CMX-2
Communications Loop Connections
Connect the communications loop to CMX-2 Terminals 1(-) and 2 (+). The CMX-2 occupies one module address on the loop. Set the rotary switches on the CMX-2 to the particular loop address required.
NFPA Style Y Notification Appliance Circuit
Connect polarized alarm notification appliances to a single 2-wire circuit. This circuit cannot be T-tapped or branched in any fashion and must be terminated across the last device by a 47K, 1/2-watt ELR (Part No. A2143-00). Connect the circuit to CMX-2 Terminals 6 (+) and 7 (-). See Figure 3-16.
NFPA Style Z Notification Appliance Circuit
Connect polarized alarm notification appliances to a single two-wire circuit. This circuit cannot be T-tapped or branched in any fashion. No external ELR is required for Style Z wiring. Connect the 4-wire circuit to CMX-2 Ter minals 6 (+) and 9 (+), then 7 (-) and 8 (-). See Figure 3-17.
Notification Appliance Power
Connect notification appliance power to CMX-2 Terminal 3 (common) and Terminal 4 (+ 24 VDC). This power must be provided b y a UL listed pow er-limited supply and must be super­vised by a UL listed power supervision relay, wired as illustrated in Figures 3-16 or 3-17.
28
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
Page 29
Figure 3-15: CMX-2 Control Module (Form-C Rela y)
Break T abs
T o configure a CMX-2 as a F orm-C relay, the two tabs must be broken off of the module. Use a pair of needle-nose pliers to break off each tab.
Communications Loop Connections
Connect the communications loop to CMX-2 Terminals 1(-) and 2 (+). The CMX-2 occupies one module address on the loop. Set the rotary switches on the CMX-2 to the particular loop address required.
Contact Connections
Wire the common and the normally-open or normally-closed contacts to the CMX-2 as needed.
Contact Ratings
Resistive: 2 amps @ 30 VDC Inductive: 1 amp @ 30 VDC (0.6 pf)
0.3 amps @ 120 VDC (0.35 pf)
Contacts are not rated for pilot duty or motor loads.
Note: Do not apply external voltage when Form-C relay configuration is used until after tabs are broken. This will prevent damage to the system from induced voltage.
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
29
Page 30
Alarm polarity shown
Figure 3-16: NFPA Style Y Notification Appliance Cir cuit
30
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
Page 31
Alarm polarity shown
Figure 3-17: NFPA Style Z Notification Appliance Circuit
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
31
Page 32
3.8 The Addressable Manual Pull Station
BGX-101L Installation
The BGX-101L is an addressable manual pull station with a key-lock reset feature.
1. Connect the communications loop to BGX-101L red wire (+) and black wire (-). If additional devices are to be connected to the SLC loop after the BGX-101L, wire-nut the continuance of the loop to the red and black wires.
2. The BGX-101L is factory preset with address “00. ” Set the address f or the pull station by using a screwdriver to turn the rotary address switches on the back of the unit to the appropriate settings.
7
6
8
5
9
4
0
3
1
2
ADDRESS
LOOP
5
7
6
8
4
3
1
2
9 0
Se t the Rotary
Decimal Sw itches.
32
bgx101-b
Figure 3-18: Wiring Addressable Manual Pull Stations
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
Page 33
3.9 The Intelligent Detector
The BX-501and B501 bases provide the connection between the AIM-200 communications loop and SDX-551 (751), CPX-551 (751), and FDX-551 intelligent detectors.
Installation
1. Connect the communications loop to Terminal 1(-) and Terminal 2(+) on the BX-501.
2. If employing an RA400Z remote LED annunciator, connect the RA400Z positive ter­minal to BX-501 Terminal 3 and the negative Terminal to BX-501 terminal 1.
3. Before installing the appropriate intelligent detector head, set the detector’s address on the head with a small slotted screwdriver. Mark this address on the base and on the head.
Channel (+)
Channel (-)
RA-400Z
+
-
SLC
2(+)
3
Loop Address Type
BX-501
B501BJ
1(-)
ION PHOTO THERM
To Next SLC Device
Figure 3-19: Wiring the BX-501 (B501) Detector Base
Channel (+)
Channel (-)
FIG2-20
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
33
Page 34
3.10 Inserting the AIM-200 Cards
Seven AIM-200 cards are provided in a plastic pouch. Remove and discard the cover card. After the appropriate point informa­tion has been entered onto the cards, they may be inserted into the module as shown below.
T
h
i
s
m
o
d
u
l
e
z
m
o
o
n
d
e
i
t
o
m
r
s
a
y
8
c
o
z
o
n
T
h
e
a
d
d
r
e
s
t
h
e
2
-d
i
g
i
t di
S
T
E
P
s
w
i
t
c
h
e
a
c
h
d
e
v
i
c
e
m
i
e
a
s
u
r
e
t
h
e
I
c
n
f
o
r
m
a
t
i
o
n
a
i
n
n
d
i
vi
d
u
a
l
s
o
nl
y
AI
Ad
In t e
)
M
-
2
0
0
d
re
s
s
ab
l
e
l
l
ge
i
n
t
M
o
d
u
l
e
d
A
M
I
-
2
o
0
0
m
e
l
u
d
si
A
r
d
d
o
n
s
e
a
b
s
e
l
o
m
c
s
i
y
h
a
T
o
n
t
I
g
e
i
l
l
e
n
m
o
M
t
d
e
l
u
e
ss
n
e
o
r
z
d
d
s
i
a
0
0
d
-2
d
t
e
M
I
o
h
A
gi
i
T
d
m
-
2
e
l
b
ch
e
a
t
l
s
s
i
e
s
e
r
d
w
h
u
d
t
A
n
s
d
o
o
P
o
c
M
c
E
t
i
n
m
e
v
g
T
i
l
l
y
e
t
e
S
n
I
s
a
d
i
s
h
h
m
s
c
e
T
a
0
e
e
r
0
r
e
n
d
2
u
-
s
o
d
M
I
z
t
a
i
ea
A
g
m
e
i
a
a
s
d
h
s
m
e
-
r
r
T
d
o
2
d
f
A
w
n
I
e
s
n
d
e
h
i
i
g
t
l
l
P
v
i
e
t
d
n
E
I
n
i
T
d
S
h
c
a
e
M
I
a
A
e
m
d
d
A
n
I
n
I
n
si
e
s
s
t
o
o
f
f
m
fi
r
e
a
n
s
of
t
h
e
d
s
pl
a
y
.
I
f
e
s
t
o
c
on
t
s
pr
o
v
i
d
e
d
on
d
it
io
n
a
d
c
o
n
t
r
o
l
s
.
e
n
zo
8
s
r
y
o
t
i
n
a
m
f
o
t
c
i
s
v
e
d
e
e
n
h
t
o
m
f
z
f
I
8
.
y
y
a
t
n
rs
n
pl
a
o
t
i
co
m
o
t
f
c
i
s
v
d
o
e
i
t
v
e
s
o
i
d
r
p
e
s
m
i
l
e
t
u
i
th
d
f
e
d
I
f
n
o
.
co
y
e
a
l
o
h
co
t
c
p
d
s
n
i
o
a
t
d
n
s
.
o
)
i
e
l
e
o
t
b
y
l
r
h
n
p
c
l
e
o
t
u
i
d
s
s
l
o
i
M
a
t
u
e
o
c
i
c
v
e
e
h
t
0
0
e
r
a
2
-
n
u
e
l
s
o
b
i
t
a
s
a
o
s
o
e
m
s
r
l
M
r
t
a
o
n
f
u
e
d
g
i
i
l
v
el
i
t
d
n
i
20
-
M
I
s
A
e
r
d
d
i
l
A
l
e
t
n
I
d
y
e
t
i
n
ed
d
i
vi
t
i
o
d
n
u
e
v
c
i
e
i
n
a
l
m
u
l
t
i
p
e
l
a
d
r
o
l
t
he
d
i
s
be
h
i
n
d
t
hi
n
d
s
t
a
t
u
s
a
r
e
p
r
o
v
i
d
e
d
e
r
i
f
f
o
d
l
s
a
u
d
i
v
i
e
o
d
t
n
i
e
m
r
d
a
l
e
a
r
i
n
e
r
i
d
f
e
f
d
d
l
1
o
a
a
e
l
s
u
p
i
d
p
t
i
l
s
o
i
u
v
i
d
d
e
n
rm
h
i
t
a
l
l
o
2
d
a
r
r
n
i
d
h
n
i
d
e
b
a
e
d
a
t
e
e
l
s
s
p
i
d
i
t
n
d
l
a
u
e
n
e
h
o
r
i
t
a
d
l
s
n
l
i
o
ro
h
r
t
t
e
n
n
b
d
e
d
d
n
i
a
v
n
a
o
ti
s
i
l
o
d
r
n
t
n
o
c
d
n
.
)
y
l
e
l
n
u
d
0
e
l
e
l
u
b
d
a
o
s
M
t
n
e
g
a
d
l
e
de
v
i
c
t
e
e
s
cto
.
a
rm
or
tro
d
re
s
s
e
s
are
p
l
a
y
.
A
ddi
s
c
ar
d
.
T
o
f
e
i
t
s
d
d
e
n
t
e
o
i
t
e
d
d
e
o
b
t
e
h
s
i
n
r
d
c
i
o
t
v
c
e
e
t
(
d
e
e
l
n
o
b
o
u
i
r
o
t
r
o
t
d
r
s
e
r
r
a
o
a
t
s
f
c
(
e
e
t
ss
t
i
e
l
d
e
b
d
A
u
d
o
.
r
y
e
t
a
r
l
.
r
a
d
r
a
s
c
t
i
e
s
s
i
d
d
h
s
t
d
s
t
i
e
A
f
o
.
.
s
y
b
u
t
d
a
l
r
d
e
p
a
d
i
c
v
o
s
i
r
s
3
t
p
h
i
t
f
o
s
d
u
t
e
a
d
i
t
v
s
o
4
r
p
e
r
rs
E
a
c
o
h
r
o
t
h
e
u
r
b
d
l
e
e
(
v
i
f
c
a
e
u
s
l
.
t)
i
s
i
n
d
di
i
c
s
a
p
t
e
l
a
d
y
e
by
d
h
,
c
t
p
on
i
re
a
a
s
s
E
l
t
i
n
h
f
s.
e
o
r
ma
s.
ce
e
i
t
h
v
c
r
e
a
f
t
d
u
o
i
s
i
T
o
i
e
T
e
d
y
c
i
on
v
i
i
s
b
e
h
m
a
d
o
b
d
c
d
o
r
e
u
u
.
a
e
h
E
t
t
o
o
r
s
.
(
s
s
e
i
)
d
t
l
l
l
u
r
c
a
a
e
r
h
y
n
i
a
l
p
s
i
s
i
)
t
l
n
i
d
l
e
a
n
y
a
l
p
m
f
s
i
n
h
i
l
a
o
n
ct
e
t
m
s
i
h
nd
i
o
h
t
c
e
t
e
d
n
i
h
e
b
t
t
l
e
s
a
c
a
c
e
y
i
n
e
d
c
b
h
i
t
n
i
i
n
v
d
s
t
e
l
s
l
ge
i
e
e
t
ut
r
nt
o
e
)
a
p
.
b
c
,
i
a
th
d
d
s
t
d
n
e
(
s
au
u
o
i
t
s
t
o
h
o
a
e
ri
b
z
r
e
m
d
a
p
or
f
n
,
n
o
ca
i
.
t
e
)
l
t
a
u
d
n
d
e
e
m
o
n
z
g
r
i
i
l
l
r
a
.
o
)
d
o
e
c
t
t
h
e
t
n
i
n
e
z
(
u
i
l
e
a
r
s
(
u
r
g
o
i
l
s
d
l
h
d
o
t
r
e
t
u
ca
n
l
i
a
l
(
a
(
s
rs
rd
a
c
l
l
a
5
6
Rolodex Cards for AIM-200
aimcard2
aimcard2
Figure 3-20: Organizing AIM-200 Car ds for Placement
Organize the cards in sequence, with number “1” on top and number “6” on the bottom. Carefully press-fit the cards over the holding clips on the module and close the front door.
This module moditors 8 zones of fire detetion devices. Each zone may consist of many individual detectors or other devices. The address of the device in alarm or trouble (fault) is indicated by the 2-digit display. If multiple addresses are displayed, press the STEP switches to control the display. Additional information about each device is provided behind this card. This module can measure the condition and status of its detectors (intelligent). Information and controls are provided behind all cards (authorized individuals only).
AIM-200
34
Addressable Intelligent Module
Carefully press-fit the cards over
the holding clips on the
AIM-200 and close the front door.
Document 15949 Rev. E 4/12/95 P/N 15949:E
1
aimcard2
Technical Manuals Online! - http://www.tech-man.com
Page 35
Section Four: Programming the AIM-200
Programming the AIM-200 involves two modes of operation: Auto-Program, (password 231-1332) and Program Edit (password 231-3112). A third function, Display Status, allows the programmer to review the entire AIM-200 prog ram. Program Clear (passw ord 231-5678), allows the clearing of an existing program from non-volatile memory.
4.1 The Programming Display
Device Type
Green LEDs indicate whether the device is a detector or a module.
Green LEDs
FORWARD
STEP
REVERSE
DETECTOR
ADDRESS
MODULE
code3
Device
The device’s type and address are alternately displayed on the 2-digit 7-segment display.
Address
Address (01-99)
(01-99)
code4
Left Digit Right Digit
P = Photo Detector Blank = Normal Sensitivity (for
I = Ion Detector L = Low Sensitivity (detectors only) H = Heat Detector H = High Sensitivity (detectors only) G = Monitor Module or Pull Station d = Disabled C = Control Module O = Form-C Selected (CMXs)
detectors), or Indicating Circuit Selected (for CMXs)
E = No response from a device (the AIM-200 is programmed for a device which is in trouble or not physically installed on the loop).
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
35
Page 36
Mapped Zones
A zone that the device has been mapped to is indicated by the red zone alarm LED . Devices ma y be mapped to any one or all of the eight AIM-200 zones. The AIM-200 will require that each MMX Monitor Module or intelli­gent detector be mapped to at least one zone (one zone must be selected at any point in time). CMX-2 Control Modules may or may not be mapped to a zone, de­pending on the particular application (see the
ing CMX-2 Control Modules
section of this document).
Operat-
Selecting Mapped Zones
Mapped zones may be selected or deselected by press­ing the switch on each respective zone (switch toggles selection of the zone).
Detector Sensitivity
To change the sensitivity of an intelligent detector, press the STEP-FORWARD or STEP-REVERSE switch. The right-hand display digit will read “L” for low, “H” for high, and blank for normal sensitivity. Either of these switches can also be used to disable the detec­tor (right-hand digit displays “d”).
FORWARD
STEP
REVERSE
When a detector is displayed
DETECTOR
ADDRESS
MODULE
When a control module is displayed
code6
_ +
Control Module (NAC)
To program a CMX-2 control module to function as a notification appliance circuit, press the STEP-FORWARD switch until the right-hand display digit is blank.
Note: The function tabs on the CMX-2 must not be broken for this type of operation.
Control Module (Form-C)
To program a CMX-2 control module as a Form-C relay , press the STEP-FOR WARD switch until the right-hand display digit reads “0.” The STEP-REVERSE switch can be used to disable the control module (right-hand digit displays a “d”).
36
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
Page 37
Programming Switches
Accepting or Rejecting Devices The ENTER and SKIP LEDs will flash while the AIM-200 is in Auto-Program or Program Edit mode.
Auto-Program
To accept a new device, press the ENTER switch. To reject a device, press the SKIP s witch. In either case, the AIM-200 will advance to the next address.
Program Edit
To store newly edited information on the device displayed, press the ENTER switch. To leave de vice unchanged, press the SKIP switch. In either case, the AIM-200 will advance to the next address.
Note: Holding in the SKIP switch will cause the AIM-200 to advance through successive
addresses quickly (10 per second).
Style 6 Loop Operation
This LED indicates that the AIM-200 has been programmed for redundant communications loop operation. Select or deselect for the entire loop by pressing the control switch.
Note 1: To function as a redundant communications loop, the AIM-200 loop must be wired in
accordance with Figure 3-7.
Note 2: An isolated-redundant circuit is a variation of a redundant circuit (see Figure 3-8). If
wired as an isolated-redundant communications loop, the AIM-200 should be pro­grammed for redundant circuit operation.
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
37
Page 38
4.2 Auto-Program Mode
Auto-Program is used when a system is first installed, or when de vice additions or deletions are necessary. It determines the number , address and type of devices to be progr ammed by polling the addressable loop. The AIM-200 determines which devices have been physically installed on the loop and compares this information against the program stored in memory. If a particular device responds differently , the AIM-200 displa ys the new address and type . If accepted by the programmer, the information is stored in the non-volatile memory. Certain other parameters are pre-selected by the AIM-200, such as zone assignment and detector sensitivity, with the installer given an opportunity to change those parameters as desired.
Entering Auto-Program Mode
Once in Auto-Program mode, the AIM-200 turns off all LEDs, places a flashing “AP” on the digital display, and begins polling all 198 possible addresses. It stores the address and type of each device as found. It then compares each new address/type with the old information stored in its memory. If the old and new address/type match, the AIM-200 proceeds to the next address, and repeats. This process could take several seconds to complete all de­vices. Only removal of the PK-1 key can abort the process.
If a mismatch is found between the actual devices installed on the loop and the information in memory, information about the actual device is displayed. The operator may accept the new device by pressing ENTER, or reject the device and retain the information that was in memory by pressing SKIP. Mismatches include an installed de vice that is not in memory, a non-existing device that is in memory, or a different Type code.
After any mismatches are accepted or rejected, the AIM-200 displays a count of the number of programmed detectors, alternating with a count of programmed modules. The operator may exit to: Progr am Edit mode by pressing ENTER; Auto-Progr am mode (repeat) by press­ing SKIP; or normal operation by removing the PK-1 key.
38
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
Page 39
T a ble 4-1: Auto-Programming the AIM-200
Programmer System 5000
1. Insert the PK-1 Programming Key.
2. Acknowledge the System Trouble (if desired).
3. Enter the Auto-Program password: 231-1332.
Push ENTER. All LEDs will be turned off
4. The device information can be changed by the AIM-200 programmer.
5. You may accept the new device by pressing ENTER, or reject the device and retain the information that was in memory by pressing SKIP.
6. You may advance to Program Edit mode by pressing ENTER; return to Auto-Program mode by pressing SKIP, or resume normal operation by removing the PK-1 key.
CPU-5000 will register a System Trouble condition.
Red alarm LEDs on Zones 1, 2, and 3 and the DISPLAY STATUS and ENTER LEDs will flash at the faster rate.
will be displayed for “Enter
EP
Password.”
The CPU-5000 piezo sounder will silence.
The LEDs illuminated on the AIM-200 will flash at the slower rate.
will be flashing for
AP
“Auto-Program.”
The AIM-200 polls all 198 possible device addresses. It stores the address and type of each device found installed on the loop (this process could take several seconds). It then compares each device against the old information stored in its memory.
If a mismatch is found between the devices installed on the loop and the information in memory, information about the new device is displayed.
See 4.1 The Programming Display.
The AIM-200 proceeds to the next mismatch, and repeats the process.
After all mismatches are accepted or rejected, the AIM-200 displays a count of the number of programmed detectors, alternating with a count of programmed modules.
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
39
Page 40
4.3 Program Edit
The Program Edit function allows the programmer to change an existing program in the AIM-200 memory. If Program Edit mode is entered directly from Auto-Program mode, the programmer will enter the Program Edit mode at Step 5 of the following instructions.
T a ble 4-2: Editing the AIM-200 Memory
Programmer System 5000
1. Insert the PK-1 Programming Key.
2. Acknowledge the System Trouble (if desired).
3. Enter the Auto-Program password: 231-3112.
4. Push ENTER. The AIM-200 will alternately display the
5 The STEP- FOR WA RD an d
STEP-REVERSE switches allow the programmer to change detector status (high, normal, low, or disab led) and module status (Form-C, notification circuit, or disabl ed).
To store newly edited information, press the ENTER switch. To leave a device unchanged, press the SKIP switch. The AIM-200 will advance to the next address
CPU-5000 will register a System Trouble condit io n.
Red alarm LEDs on Zones 1, 2, and 3 and the DISPLAY STATUS and ENTER LEDs will fl ash at the faster rate.
will be displayed for “Enter
EP
Password.”
The CPU-5000 piezo sounder will silence.
The LEDs illuminated on the AIM-200 will flas h at the slower rate.
address and device of the lowest-addressed detector.
The AIM-200 will continue to alternately display the addr ess an d devi ce type during editing.
The AIM-200 steps through all detectors and then all modules installed on the loop. After the last module is ed ited, the AIM-200 wil l begin again at t he first detector on the loop.
Note: Holding the SKIP ke y switch will cause the AIM-200 to advance through successive addresses quickly (10 per second).
6. After all des i red changes have been made, remove the programming key.
40
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
The AIM-200 will return to normal operation.
Page 41
4.4 Program LED Latch
Early version Notifier analog detectors and modules have the capability to turn on up to six LEDs on a single signaling line circuit.
Notifier "R4" devices (Release 4-1-91) have the capability to turn on up to 99 detector LEDs plus five module LEDs.
Programmer System 5000
1. Insert the PK-1 Programming Key.
2. Acknowledge the System Trouble (if desired).
3. Enter the Auto-Program password: 231-1234.
4. Push ENTER. . .
CPU-5000 will register a System Trouble condition.
Red alarm LEDs on Zones 1, 2, and 3 and the DISPLAY STATUS and ENTER LEDs will flash at the faster rate.
will be displayed for “Enter
EP
Password.”
The CPU-5000 piezo sounder will silence.
The LEDs illuminated on the AIM-200 will flash at the slower rate.
To enable the max LED mode.
Push SKIP. . .
5 After all desired changes have
been made, remove the Programming Key.
To disable the max LED mode. The AIM-200 will return to normal
operation.
Notes:
1) To employ this feature, the AIM-200 loop must contain only "R4" type addressable devices.
2) When using sounder bases or DHX-501s with auxiliary relay , you must enable max LED latching to ensure all sounders and relays will activate during alarm.
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
41
Page 42
4.5 Program Clear
The Program Clear function allows the programmer to clear an e xisting program from AIM-200 memory. After clear ing memory, the AIM-200 must be completely reprogrammed, begin­ning with Auto-Program.
T ab le 4-3: Clearing AIM-200 Memory
Programmer System 5000
1. Insert the PK-1 Programming Key.
2. Acknowledge the System Trouble (if desired).
3. Enter the Program Clear password: 231-5678.
Push ENTER.
4. You can now clear AIM-200 memory by pressing ENTER. Pressing SKIP or removing the programming key aborts Program Clear.
CPU-5000 will register a System Trouble condition.
Red alarm LEDs on Zones 1, 2, and 3 and the DISPLAY STATUS and ENTER LEDs will flash at the faster rate.
EP
The CPU-5000 piezo-sounder will silence.
The LEDs illuminated on the AIM-200 will flash at the slower rate.
PC
After the AIM-200 erases stored information,
EP
will be displayed for “Enter Password”
will be displayed for “Program Clear.”
will be displayed for “Enter Password”.
At this point, you must execute Auto-Program so that the AIM-200 can determine which devices are installed on the loop.
At least one device must be installed on the AIM-200 loop. If the programming key is re­moved after Program Clear and before Auto-Program is executed, the AIM-200 will register a trouble condition by illuminating the yello w trouble LEDs on Zones 1, 3, 5, and 7. Ref er to Table 4-1.
42
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
Page 43
4.6 Default Zone Map
Upon initial power up, and after clearing AIM-200 memory (Program Clear), intelligent de­tectors and addressable modules installed on an AIM-200 loop are automatically mapped to default zones. Any changes to this map must be made through Program Edit. This default map is illustrated in Figure 4-1.
Figure 4-1: Default Zone Map
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
43
Page 44
4.7 Display Status
When the operator wishes to view the status and program for a device, the Display Status/ Sensitivity function is used. This function is entered directly by inserting the PK-1 Program­ming Key and pressing the DISPLAY STATUS switch. No password is required.
Note: The AIM-200 will cease monitoring its devices while in this mode and the CPU-5000
will report System Trouble.
Alternately, this mode may be entered without key or pass w ord by pressing and holding the DISPLA Y STATUS switch in for two seconds. Continue to hold the DISPLAY ST ATUS switch in with one hand while performing the Step function with the other hand.
Displaying the Status of Intelligent Detectors
When the Display Status mode is entered, the digital display will repeatedly flash the ad­dress, type and sensitivity of the detector assigned to the lowest address. The user can scroll through all detectors using the STEP-FORW ARD and STEP-REVERSE switches. The SKIP switch advances addresses rapidly.
Detector Device Type/Status
The Device Type/Status field displays two characters for intelligent detectors, outlined be­low.
Left Digit Right Digit
P =Photo Detector Blank = Normal sensitivity I = Ion Detector L = Low Sensitivity H = Heat Detector H = High Sensitivity
A = Alarm F = Fault (maintenance Alert) d = Disabled E = Error--No response from a device (the AIM-200 is
programmed for a device that is in trouble or not physically installed on the loop).
U = Unsatisfactory (Failed automatic detector test)
Alarm Threshold Per centage
The percent of alarm threshold for detectors is displayed with a decimal point as illustrated below.
1.2
44
.43
43% of Alarm Threshold
Document 15949 Rev. E 4/12/95 P/N 15949:E
120% of Alarm Threshold
Technical Manuals Online! - http://www.tech-man.com
Page 45
Displaying the Status of Addressable Modules
After the AIM-200 has stepped through all detectors, it will begin displaying all modules. The digital display will repeatedly flash between the address and type/status of the module assigned to the lowest address. The user can scroll through all modules using the STEP-FORWARD and STEP-REVERSE switches. The SKIP switch advances through ad­dresses rapidly.
Module Device Type/Status
The Device Type/Status field displays two characters for modules, outlined below.
T able 4-4: Device Type/Status Field Characters
Left Digit Right Digit
C = Monitor Module or Pull Station Blank = Indicating circuit selected C = Control Module A = Alarm
F = Fault--Trouble (open monitor module
zone; open or short CMX-1)
d = Disabled O = Open (Form-C) C = Closed (Form-C) E = Error--No response from a device
(the AIM-200 is programmed for a device that is in trouble or not physically installed on the loop).
Advancing to an Address Range
By pressing any one of Zone Switches 1 through 8, the operator can advance directly to a desired range of addresses. The AIM-200 will jump to the lowest address of a programmed device within that range. The STEP-FORWARD and STEP-REVERSE switches can be used to move to devices within each range.
Address Range
01-19
01-19
20-29
20-29
30-39
30-39
40-49
40-49
Display Status Tips:
1. To view module status directly upon entering Display Status mode, press the switch on Zone 8 and advance through devices 80-99 (if present). The AIM-200 will begin display­ing modules directly after the last detector.
2. The STEP-REVERSE switch can be used to back into a lower address range. For ex­ample, to view the status of a device with Address “39,” press the switch for Zone 4, then press the STEP-REVERSE switch once.
0
1
2
3
4
Document 15949 Rev. E 4/12/95 P/N 15949:E
5
6
7
8
9
code5
50-59
50-59
60-69
60-69
70-79
70-79
80-99
80-99
45
Technical Manuals Online! - http://www.tech-man.com
Page 46
Section Five: Operating the AIM-200
5.1 Zone Display
For each of the eight zone displays, a red LED, yellow LED and a switch are provided. The 198-point capacity of the AIM-200 is assigned to these zones using a “mapping” technique. Each of the 198 devices may be mapped to one or more zones. If an initiating device mapped to more than one zone is alarmed, all mapped zones will be placed into alarm. This type of zoning could be used to provide a matrix, where one zone indicates the area and another the type of device. F or e xample, four zones could be used to indicate floor of alarm, and three zones could be used to indicate smoke alarm, manual station, and waterflow alarm. The eighth zone could be used for supervisory devices (the supervisory devices would not be mapped into a floor zone).
Display Program Switch
0
1
2
3
4
CMX-2 Control Modules are activated by the AIM-200 when the zone that the y are mapped to enters an alarm condition. If a CMX-2 is mapped to more than one zone, it will be acti­vated when any of the zones are in alarm.
The zone LEDs and switches emulate the functions of an IZM-8 module except when in Program/Display mode. Pressing the switch in Program/Display mode displays all output circuits in the system that are mapped to that zone.
Alarm LED (red) Trouble LED (yellow)
5
6
7
8
9
code5
The AIM-200 zone assumes the status of any device mapped to that zone that enters an alarm or trouble condition. If any of the initiating devices are in alarm, the zone is reported in alarm. If one or more devices (including CMX-2 modules) are in trouble, and no alarms exist, trouble is reported for the zone.
One trouble condition, called “Maintenance Alert,” will be reported for analog detectors that give readings in the 0-19% or 80-99% range. This trouble condition will result only if the detector remains at this value continuously for 24 hours (smoldering fires could linger here before passing 100%). After the detector remains at this level for about 24 hours, trouble is reported for that detector.
46
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
Page 47
Digital Display - The digital display provides two numeric digits. It displays the device numeric address (01-99). To the right of the digital display are two green LED’s: “Detector” and “Module.” When there are no devices in alarm or trouble, and the system is not in a programming mode, the digital display is blank.
DETECTOR
ADDRESS
MODULE
code3
Alarm Condition - When an alarm condition occurs, the address of the alarmed device will appear in the 2-digit, 7-segment display. If multiple alarms occur, the display will automati­cally advance through all alarms. The STEP s witches may be used to manually adv ance the display one alarm at a time. If it is necessary to display trouble addresses when an alarm exists, the program key must be inserted and the Display Status functions followed. If an alarm(s) has been silenced, and an initiating device mapped to the same software zone goes into alarm, the AIM-200 will resound the alarm signals and flash appropriate LEDs.
Trouble Condition
-
During a trouble condition (with no alarm present) the digital display will show the address of the trouble. The detector and module LEDs will be used to indicate the category of device in trouble.
Note: If a Style 6 loop fault exists , the display indicates “LF” (Loop Fault). If communication
is lost with the CPU-5000, “SF” (System Failure) is displayed.
If multiple trouble conditions exist, the digital displa y steps through all troub les automatically at a rate of one trouble per second. The STEP switches may be used to manually control the digital display. Once a STEP switch is pressed, the display advance is under control of these switches. If a troub le(s) has been silenced and a device mapped to the same software zone goes into trouble, the AIM-200 will resound the trouble signal and flash appropriate LEDs.
Step Switches - Two switches, STEP FORWARD and STEP REVERSE, are provided for advancing the display. If multiple alarms or troubles exist in the AIM-200, and the display is automatically advancing through them, pressing either of these two switches will stop the automatic advance and allow the operator to control the advancement through the display. If these two switches are not pressed again during a period of about one minute, the display will automatically resume stepping through existing events.
Each time a STEP switch is pressed, the digital display advances to the next higher/lower address that is also in alarm or trouble. After all addresses in alarm or trouble have been displayed, it returns to the first address and continues.
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
47
Page 48
Loop Fault LED and RESET
NFPA Style 6 field wiring may be used to ensure full operation in the e v ent of a single break in the loop wiring. When set f or Style 6, the AIM-200 latches a wire f ailure and then must be manually reset to re-test and clear the fault. When the loop fault is latched on, the AIM-200 turns on the yellow LOOP F A ULT LED and reports trouble for all zones that are not in alarm. If there is no alarm, “LF” is placed on the digital display. The RESET switch or the System RESET clears the latch. If a loop f ault still exists, the trouble will then resound and re-latch.
T-tap wiring is not allowed in the Style 6 configuration. Field wiring must be returned to the AIM-200 terminal block as illustrated in Figure 3-7.
ON-LINE LED and SKIP Switch
The green ON-LINE LED will flicker when communications occur on the interface to the CPU. The SKIP switch is used in programming the AIM-200. (See the
AIM-200
section of this document.)
Programming the
ENTER LED and Switch
This LED and switch are used in programming the AIM-200 (see the
AIM-200
section of this document).
Programming the
Display Status LED and Switch
This LED and switch are used in programming the AIM-200 (see the
AIM-200
section of this document).
Programming the
Automatic Detector Test
The AIM-200 automatically test all detectors on its SLC loop. This test is similar to activ ating a detector with a test magnet. The module periodically commands each detector, one at a time, to respond with an appro­priate alarm-like signal (pulse on the SLC loop). If the proper response is not returned, the AIM-200 will register a trouble condition for that detector . The troub le LED of the zone which that detector is mapped to will illuminate and the piezo will sound.
To determine which detector has failed the test, use the Displa y Status function. The status of the faulty detector will be indicated by a “U” (Unsatisfactory test) in the right digit of the
display
The RESET switch on the CPU must be pushed to clear the trouble status from the device. Unless the detector has been repaired or replaced, the AIM-200 will again register a trouble condition with the next device test. Each detector will be tested at least every 24 hours.
The automatic test is not conducted for modules.
(PU, IU, or HU).
48
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
Page 49
T a ble 5-1: AIM-200 Event Codes
Device Type Status
P
Photo Detector Normal, med. sensitivity
PL
Photo Detector Normal, low sensitivity
PH
Photo Detector Normal, high sensitivity
PA
Photo Detector Alarm
PF
Photo Detector Trouble
PE
Photo Detector No answer
Pd
Photo Detector Disabled
PU
Photo Detector Unsatisfactory (failed automatic self-test)
I
Ion Detector Normal, med. sensitivity
IL
Ion Detector Normal, low sensitivity
IH
Ion Detector Normal, high sensitivity
IA
Ion Detector Alarm
IF
Ion Detector Trouble
IE
Ion Detector No answer
Id
Ion Detector Disabled
IU
Ion Detector Unsatisfactory (failed automatic self-test)
H
Heat Detector Normal
HA
Heat Detector Alarm
HF
Heat Detector Trouble
HE
Heat Detector No answer
Hd
Heat Detector Disabled
HU
Heat Detector Unsatisfactory (failed automatic self-test)
G
Monitor Module Normal
GA
Monitor Module Alarm
GF
Monitor Module Trouble
GE
Monitor Module No answer
Gd
Monitor Module Disabled
C
Control Module (NAC) Normal
CA
Control Module (NAC) Alarm output
CF
Control Module (NAC) Trouble
CE
Control Module (NAC) No answer
Cd
Control Module (NAC) Disabled
CO
Control Module (Relay) Open (OFF)
CC
Control Module (Relay) Closed (ON)
CF
Control Module (Relay) Trouble
Cd
Control Module (Relay) Disabled
LF
SF
EP
AP
Line Fault (Style 6) CPU loss of communication Enter Password Auto Program
Note: Invalid device type = E (left digit) Maintenance Alert = F (left digit)
Document 15949 Rev. E 4/12/95 P/N 15949:E
49
Technical Manuals Online! - http://www.tech-man.com
Page 50
Appendix A: Operating Contr ol Modules
Optional CMX-2 control modules can be installed on the AIM-200 addressable loop. When using one or more CMX-2s, four types of control options are available: General Alarm, Control-by-Zone, Control-by-Module, and Control-by-Detector. The CMX-2 zone mapping and address assignments required for each control option are described below.
General Alarm - To set up General Alarm, set CMX-2 module address in the range of 01-59 and ensure that it has not been mapped to any zones. If an alarm occurs on the alarm bus (see Figure 3-3 for wiring information), the CMX-2 will be activated. This type of control can also be executed using the manual s witch on the CPU board alarm relay (manual e vacu­ation).
Alarm From CMX Address CMXMapped to
Zone(s)?
Alarm Bus 01-59 No CMX will be activated if not
mapped to any zone.
Results
Control-by-Zone - Control-by-Zone is suited for control-by-floor and floor above/floor be­low applications. No special treatment is required to ex ecute Control-by-Zone. If the AIM-200 detects an alarm from an intelligent detector or addressable monitor module, it activates which ever zone(s) are mapped to this de vice . All CMX-2 modules assigned to the alarmed zone(s) will be activated.
Alarm From Detector or Monitor
Detector or Monitor Module
Module Address
01-99 01-99 CMX-2 will be activated if mapped to
CMX-1
Address
Results
the same zone as the alarmed device.
Control-by-Module - Control-by-Module is a useful function for Air Handling Units (AHUs) controlled by 4-wire duct detectors. To set up Control-by-Module, set the monitor module address in the range 60-69. Ensure that a CMX-2 module e xists in the address range 70-79 with the same least significant address digit as the MMX-1, MMX-101, MMX-2(s) and that the CMX-2 module has not been mapped to any zones.
Alarm From MMX Address CMX Address CMXMapped to
MMX Module 60-69 70-79 No CMX will be activated if it
Zone(s)?
shares the same least significant digit with the alarmed device and is not mapped to any zones.
Results
50
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
Page 51
Control-by-Detector
-
Control-by-Detector is a useful function for activating sounders in the same room or location as the alarmed intelligent detector. To set up Control-by-Detector, set detector address in the range 80-99. Ensure that a CMX-2 module e xists with the same address as the detector, and that the CMX-2 has not been mapped to any zones.
Alarm
From
Detector 80-99 Same as
General CMX-2 Trouble
Detector Address
CMX-2
Address
detector
-
CMX-2 Mapped
to Zone(s)?
No CMX will be activated if it shares the
address of the alarmed device and is not
Results
mapped to any zone.
CMX-2 modules programmed for General Alarm, Control-by-Module, or Control-by-Detector do not have a zone assignment. If a trouble occurs on one of these devices, it is reported as trouble on Zone 1.
Non-Silenceable Notification Appliance Circuit
-
An CMX-2 configured as a Notification Appliance Circuit (tabs intact) can be programmed in AIM-200 memory as a Form-C mod­ule. The module will still function as a supervised notification appliance circuit, but will be non-silenceable. This feature is suitable in applications that require strobe lights to continue flashing after the signals have been silenced during an alarm.
-
Non-Silenceable Form-C Relays
A CMX-2 configured as a Form-C Relay (type CO)
cannot be silenced by the SIGNAL SILENCE switch on the CPU. These modules, regard­less of their mapping assignments, can only be silenced by the RESET switch on the CPU.
Supervisory Zones
-
This supervisory monitor ing function (tamper valves, etc.) is trans-
parent to the AIM-200. This programming selection is performed at the CPU. Alarm Verification - The AIM-200 performs alarm verification if this feature is programmed
at the CPU. Verification delays are performed for alarms from detectors only. Waterflow Zones - This System 5000 function (non-silenceable alarm) is transparent to
the AIM-200. If used, the installer should assign only flow switches to the zone. Walk T est - The AIM module will perform a single-person test of all devices as follows:
1)Disable all eight AIM-200 zones using the DISABLE/ENABLE control on the CPU.
2) Disable all CMX-2 modules on the AIM-200 by entering Program Edit mode and selecting the Cd code for each module. Remove the programming key.
3)Reset the system. (The remainder of the system, including other AIM-200s, contin­ues to provide fire protection.)
4)Activate (alarm) each initiating device on the AIM-200.
5)Return to the panel and verify that the AIM-200 2 digit display is stepping through all devices that were alarmed.
6)Reset the system and enable all eight AIM-200 zones.
7)Enable all CMX-2 modules on the AIM-200. Be sure to select the proper type.
8)Reset the system.
Document 15949 Rev. E 4/12/95 P/N 15949:E
51
Technical Manuals Online! - http://www.tech-man.com
Page 52
Alarm Bus - The alarm bus is implemented with a two wire daisy chain that connects to each AIM-200. It is used to provide a manual evacuation control of CMX-2 modules and to manually silence these modules; f or general alarm control functions, and to provide a backup connection between multiple AIM-200s so that the panel may still function in general alarm even if the CPU fails.
General Alarm Service - CMX-2 modules will be activated under a general alarm condi­tion provided that the module address is set to “59” or belo w and the module is not mapped to any zone. In addition, the alarm bus cable must be connected between the CPU and the AIM-200 (see Figure 3-3). This connection puts the normally open contacts of the CPU Alarm Relay across the pin connector on the AIM-200. When an alarm occurs, the alarm relay changes state, closing the connection to the AIM-200 and signaling a general alarm condition.
Note: The CPU alarm relay is dedicated to this function and should not be connected to
other circuits.
To ensure that general alar m functions proper ly, adhere to the following:
1.The CPU default program automatically maps the Form-C alarm relay to all initiating zones in the system. While this is a default map, the AIM- programmer should ensure that this relay is indeed mapped to all initiating circuits, including the eight zones on each AIM. This guarantees that any alarm in the system will activate the alarm relay, which will in turn signal a general alarm throughout all AIMs on the alar m bus connec­tion.
2.The alarm relay m ust be prog r ammed as a non-coded point. If it is not, the alarm relay contacts will pulse general alarm bus connection, causing the AIM-200(s) to oscillate in and out of alarm.
3.The CPU alar m relay must be programmed as silenceable, permitting the silencing of general alarm modules with software type
C (see Figure A-1).
52
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
Page 53
Backup Alarm Bus
provides backup general alarm capability in the event of communications failure with the CPU. Under this condition, the following events will take place.
When an alarm occurs on an AIM-200, output modules mapped to the alarmed zone will be activated. The AIM-200, unable to communicate with the CPU, will assume general alarm responsibility and will close its own alarm bus cable connection. This has the same eff ect as a signal from the alarm relay--all AIM-200s receive an alarm bus cable closure and enter a general alarm condition.
-
The interconnection of alarm bus cables between each AIM-200
Figure A-1: Alarm Bus Activity
Signal Silence Function - Signal Silence will only function for those CMX-2s that have
been programmed as notification appliance modules (software type C) and have been pro­grammed for general alarm service (see the ment).
The Signal Silence function is exercised by first closing, then opening, the alarm bus cable connection. The closure occurs after initiation of an alarm—when the alarm relay changes state. The opening occurs when the SIGNAL SILENCE switch is pressed—the Alarm Relay is silenced, opening the alarm bus connection. This signals the AIM-200(s) to silence all general alarm CMX-2 modules.
Signal Silence has no effect on CMX-2 Control Modules that are Form-C dress 60 or higher, or that are mapped to any AIM-200 zone. These modules can only be
silenced by the RESET switch on the CPU.
Document 15949 Rev. E 4/12/95 P/N 15949:E
General Alarm Service
section of this docu-
(Type CO), ad-
53
Technical Manuals Online! - http://www.tech-man.com
Page 54
Appendix B: AIM-200 Power Requirements
Regulated Po wer Required in Standb y
Use Table B-1 to determine the amount of current drawn by the AIM-200(s) during non-alarm conditions. Place the total standb y current obtained in the
nical Bulletin
in this document when calculating secondary power standby requirements for
the control panel.
T able B-1: Standby Regulated Power Requirements
Installing the System 5000 Tech-
Device Type Device
AIM-200* [ ]
Detectors and Modules [ ]
CPX-551, SDX-551, FDX-551, MMX-1, MMX-101, CPX-751, SDX-751, BGX-101L
MMX-2 [ ]
CMX-2 [ ]
ISO-X [ ]
End-of-Line Relays [ ]
Number
Total Standby Current = amps
X
X
X
X
X
X
Current
(amps)
0.050 =
0.000210 =
0.007 =
0.0003 =
0.000420 =
[ ] =
Total Current
Regulated Power Required in Alarm
Use Table B-2 to determine the amount of current drawn by the AIM-200(s) in the System 5000 during an alarm. Place the Total Alarm Current obtained in the
5000 T echnical Bulletin
in this manual when calculating regulated requirements in the alarm
state for the control panel.
T ab le B-2: Alarm State Regulated Power Requirements
Installing the System
Device Type Device
AIM-200* [ ]
Total AIM-200 Current (from Table B-1) =
Number
Total Standby Current = amps
* Maximum number of AIM-200s is determined by power supply loading limits in the
Installing the System 5000 Technical Bulletin
the following limits: 10 with the MPS-24A; 2 with the MPS-24B.
54
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
Current
(amps)
X
0.075 =
Total Current
in this manual but may never exceed
Page 55
Appendix C: AIM-200 Point Annunciation
Note: For the follo wing feature to be enabled, the AIM-200 requires softw are Part No. 73264
or higher.
The CPU can be programmed for an alternate method of annunciating the AIM-200. Up to 192 intelligent devices can be annunciated on a single AIM-200 with ACM or LDM series annunciators, or the LCD-80 Liquid Crystal Display on the RS-485 interface. The System 5000 annunciates the AIM-200 installed directly to the right of the CPU. Note that an annun­ciator cannot be used to execute manual ON/OFF control of intelligent AIM-200 points, only standard System 5000 zones. The option provides annunciation of up to 256 points for the System 5000, broken down as follows:
AIM-200
8 CPU Points 8 Unusable
AIM-200 Points
48 Points Mapped to the
Next Six Modules Installed.
aim-200
Annunciator Address 1:
8 CPU points (CPU point shift not an option). 8 unusable points. 48 points mapped to the next six modules installed in the System 5000 (which can also be AIM-200s for annunciation of their eight software zones).
Annunciator Address 2:
AIM Intelligent detectors, addressed 1-64.
Annunciator Address 3
AIM Addressable Modules, addressed 1-64.
Annunciator Address 4
AIM Intelligent detectors, addressed 65-96, followed by AIM-200 Addressable Modules, addressed 65-96.
The System 5000 Programming Manual provides programming instructions for this option. Refer to program choice "AIM(256)."
Note: AIM-200 detector and module Addresses 97, 98, and 99 may be used, but cannot be
point-annunciated.
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
55
Page 56
T a ble C-1: Comparison Report - AIM-200 vs. LCD-80
Annunciator Address AIM-200 Points LCD-80 Points
"01" 1-64 system points 1-64
"02" 1-64 AIM detectors 65-128
"03" 1-64 AIM modules 129-192
"04" 65-96 AIM detectors
65-96 AIM modules
193-224 225-256
56
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
Page 57
NOTES
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
57
Page 58
NOTES
58
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
Page 59
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
59
Page 60
BACK COVER
60
Document 15949 Rev. E 4/12/95 P/N 15949:E
Technical Manuals Online! - http://www.tech-man.com
Loading...