Notifier AFP-3030 Installation Manual

Fire Alarm Control Panel
AFP-3030
Installation Manual
New Zealand Edition
Document DOC-01-037 25/08/2016 Rev:
P/N DOC-01-037:B
B
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online Help or printed manuals, you can email us.
Please include the following information:
•Product name and version number (if applicable)
•Printed manual or online Help
•Topic Title (for online Help)
•Page number (for printed manual)
Send email messages to:
TechPubs@notifier.com.au
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services.
•Brief description of content you think should be improved or corrected
•Your suggestion for how to correct/improve docu­mentation
Installation Precautions
EMC Warning:
This is a Class A product. In a domestic environment, this product may cause radio interference in which case the user may be required to take adequate measures.
Electromagnetic Interference (EMI) tests are performed in accordance with Class A requirements of AS/NZS CISPR 22:2009
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood.
Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% voltage drop from the specified device voltage.
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning induced transients. Although no system is completely immune from lightning transients and interference, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Support Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits. Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make
all cable entries from the sides or rear . Befo re making modifica tions, verify that t hey will not interfe re with battery, transformer, or printed circuit board location.
Do not tighten screw terminals. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control p anel a nd asso ciat ed equip ment . FACP operation and reliability depend upon proper ins t al l ati on.
The equipment must be correctly programmed and installed to suit the specific application. Please ensure correct operational parameters are set prior t o co mmiss ioning . If furth er de t ai l s on programmi ng opt ions a r e required , p le ase consu lt the programming manual or contact our helpful technical support personnel.
AFP-3030 Installation Manual — P/N DOC-01-037:B 25/08/2016 ii

Table of Contents

Section 1: About This Manual .................................................................................................1
1.1: Agency Approvals.........................................................................................................................................1
1.2: Related Documents ....................................................................................................................................... 1
1.3: Cautions and Warnings ................................................................................................................................. 2
Section 2: System Overview....................................................................................................3
2.1: System Description .......................................................................................................................................3
2.1.1: Standard Features................................................................................................................................ 3
2.1.2: Options................................................................................................................................................ 3
2.1.3: System Limitations ............................................................................................................................. 3
2.2: Specifications................................................................................................................................................ 4
2.2.1: Supply Rating...................................................................................................................................... 4
2.2.2: Environmental Specifications............................................................................................................. 4
2.3: System Components...................................................................................................................................... 4
2.3.1: Replacement Kits................................................................................................................................ 5
2.4: Product Diagram ........................................................................................................................................... 6
2.4.1: Main Power Supply.............................................................................................................................8
2.5: System Cabinets............................................................................................................................................8
2.6: Compatible Equipment ................................................................................................................................. 8
Section 3: Installation ............................................................................................................10
3.1: Preparing for Installation ............................................................................................................................ 10
3.2: Installation Checklist................................................................................................................................... 10
3.2.1: Memory-Backup Battery ..................................................................................................................11
3.3: Attaching Option Boards ............................................................................................................................ 12
3.4: Connecting the Network Communications Module.................................................................................... 14
3.5: Connecting the Loop Control and Expander Modules................................................................................ 14
3.5.1: Mounting Instructions....................................................................................................................... 1 4
3.5.2: Setting SLC Loop Number ...............................................................................................................15
3.5.3: Installing a Multi-layer Module into the Chassis.............................................................................. 15
3.6: Form-C Relays on the CPU ........................................................................................................................18
3.7: Installing the SGD Interface Board............................................................................................................. 18
3.8: Installing a Replacement Zone Mimic (ACM-ZM).................................................................................... 19
3.8.1: Installing a Zone Mimic Expansion Card (AEM-ZM) ..................................................................... 20
3.9: Installing Replacement Bulgin Switches .................................................................................................... 21
3.10: Connecting Power Sources and Outputs................................................................................................... 22
3.10.1: Overview......................................................................................................................................... 2 2
3.10.2: Connecting Local and Remotely Powered Devices........................................................................23
3.10.3: Checking AC Power .................................... .................................................................. ................. 24
3.10.4: Auxiliary Power Supply Connections............................................................................................. 25
3.11: Installing Printers...................................................................................................................................... 25
3.11.1: Printer Installation Sequence .......................................................................................................... 25
3.11.2: Configuring the Printer................................................................................................................... 27
3.12: Wiring a Signalling Line Circuit (SLC).................................................................................................... 27
3.12.1: SLC Overview ................................................................................................................................ 27
3.12.2: SLC Capacity.................................................................................................................................. 27
3.12.3: SLC Installation.............................................................................................................................. 28
3.13: Connecting a FAAST Intelligent Aspiration Detector.............................................................................. 29
3.14: Connecting a PC for Programming...........................................................................................................29
Section 4: Testing the System .............................................................................................. 30
4.1: Operational Checks..................................................................................................................................... 30
4.2: Battery Checks and Maintenance................................................................................................................ 31
4.2.1: PSI Status..........................................................................................................................................32
Appendix A: Electrical Specifications..................................................................................33
A.1: Operating Power......................................................................................................................................... 33
A.2: SLC Loops ................................................................................................................................................. 33
A.3: Notification Appliance Circuits .................................................................................................................33
Table of Contents
A.4: Networks .................................................................................................................................................. 33
A.5: Wire Requirements..................................................................................................................................... 33
A.6: Power Supply Calculations ........................................................................................................................34
A.6.1: Calculating the System Current Draws............................................................................................ 34
A.6.2: How to Use the Calculating Tables..................................................................................................35
A.6.3: Calculation for Main Supply Current...............................................................................................36
A.6.4: Calculating the Maximum Secondary Power Quiescent Current Draw .......................................... 37
A.6.5: Calculating the Maximum Secondary Power Fire Alarm Current Draw......................................... 37
A.7: Calculating the Battery Requirements ....................................................................................................... 38
A.7.1: Battery Power Equations ................................................................................................................ 3 8
A.7.2: Recommended Standby Battery Sizes .............................................................................................38
Appendix B: Cabinet and Mounting Information................................................................. 39
B.1: CAB650 Mounting Details .................................................................................................................. 39
B.2: CAB900 Mounting Details .................................................................................................................... 40
B.3: CAB 18U Cabinet Mounting Dimensions ............................................................................................41
B.4: CAB 28U Cabinet Mounting Dimensions..................................................................................................42
B.5: CAB 40U Cabinet Mounting Dimensions..................................................................................................43
B.6: Laying Out Equipment in Cabinet and Chassis..........................................................................................44
B.7: Installing Replacement Equipment ........................................................................................................... 45
B.7.1: Installing a replacement keypad....................................................................................................... 45
Appendix C: Schematics ....................................................................................................... 46
Index ........................................................................................................................................ 49
AFP-3030 Installation Manual — P/N DOC-01-037:B 25/08/2016 iv

Section 1: About This Manual

1.1 Agency Approvals

NZS 4512:2010
Fire Detection and Alarm Systems in Buildings

1.2 Related Documents

The table below provides a list of documents referenced in this manual, as well as documents for selected other compatible devices.
Off-line Programming Utility Document Number
Available for download:
VeriFire Tools Programming Utilities
Fire Alarm Control Panel (FACP) and Main Power Supply Installation Document Number
AFP-3030 Installation, Programming, and Operations Manuals (NZ) DOC-01-037
NPS (Notifier Power Supply) Installation Sheet DOC-03-057 Battery Connection Installation Kit DOC-03-046
Networking Document Number
NotiFireNet Version 5.0 & Higher Manual 51584 High-Speed Notifier Network Manual 54013 HS-NCM Installation Document 54014
System Components Document Number
ARE Interface Board Installation Sheet DOC-03-062 Zone Mimic Manual DOC-01-028 ACM-8RA Installation Sheet DOC-03-052 Intrinsically Safe Barrier Manual DOC-01-029 Annunciator Name Plate Installation Sheet DOC-03-060 Extinguishing Agent release Module Manual DOC-01-005 DA Series BOWS Manual DOC-01-004 DVC Digital Voice Command Manual 52411 DVC-RPU Manual 50107425-001 DAA2 and DAX Amplifiers Manual 53265 DAL Devices Reference Document 52410 Mass Notification Systems Configuration, Programming and Operations Manual LS10063-000NF-E Annunciator Control System Manual 15842 LCD2-80 Manual 53242 LDM Series Lamp Driver Annunciator Manual 15885 SCS Smoke Control Manual (Smoke and HVAC Control Station) Manual 15712 First Command Manual LS1001-001NF-E XP10-M Ten Input Monitor Module Installation Document I56-1803 XP6-C Supervised Control Module Installation Document I56-1805 XP6-MA Six Zone Interface Module Installation Document I56-1806 XP6-R Six Relay Control Module Installation Document I56-1804 FSA-8000 FAAST Intelligent Aspiration Sensing Technology Document I56-3903 SLC-IM Manual LS10026-000NF-E
www.notifier.com.au
DOC-01-038 DOC-01-038
Table 1.1 Related Documents
Cautions and Warnings About This Manual
!
!
NOTE: Where used in this manual, the term CPU refers to the main circuit board for the fire
alarm control panel’s central processing unit (see Section 2.3 “System Components” for a more detailed list of part numbers.)

1.3 Cautions and Warnings

This manual contains cautions and warnings to alert the reader as follows:
CAUTION: SUMMARY IN BOLD
INFORMATION ABOUT PROCEDURES THAT COULD CAUSE PROGRAMMING ERRORS, RUNTIME ERRORS, OR EQUIPMENT DAMAGE.
WARNING: SUMMARY IN BOLD
INDICATES INFORMATION ABOUT PROCEDURES THAT COULD CAUSE IRREVERSIBLE DAMAGE TO THE CONTROL PANEL, IRREVERSIBLE LOSS OF PROGRAMMING DATA OR PERSONAL INJURY.
AFP-3030 Installation Manual — P/N DOC-01-037:B 25/08/2016 2

Section 2: System Overview

2.1 System Description

2.1.1 Standard Features

Connections to easily mount from one to ten Signalling Line Circuit (SLC) loops
Network operation
Uses Notifier’s VIEW® early warning fire detection and the FlashScan® or CLIP families of detectors and modules
Alarm, Fault, and Supervisory relays
Support for 32 annunciator addresses with either 64 or 96 points each (depending on the capability of the annunciator)
Supports Open (Style 4) and Closed (Style 6/7) SLC loops
Logic Equations
Multi-line display
Ability to activate local sounder or relay bases in alarm or pre-alarm
Supervisory duct and smoke detectors
Supports Intelligent Sensing algorithms
EIA-485 connections for wiring ACS annunciators (including LDM custom graphic annunciators), TM-4 transmitter
EIA-232 connection for printer
Autoprogram feature for faster programming of new devices
Easy connection to VeriFire® Tools programming utility
T he basic system power supply charges sealed lea d-acid batteries ranging in capacity from 7 to 85 amp hours, and provides up to 5 amps of power for use by the CPU.
Easy connection to auxiliary power supplies and battery chargers for custom design of very large systems.
Ground fault detection
Mass Notification System compatible
Provides LED mimic annunciator for up to 72 zones
Supports Type 5 Arrangements
1

2.1.2 Options

Refer to Section 2.3 “System Components” for descriptions of the various optional mo dul es.
Rubberised keypad with a standard “QWERTY” keyboard layout, a 640-character LCD display, indicator LEDs, and switches.
Separately ordered Loop Control Modules and Loop Expander Modules provide up to ten SLC loops.
Optional equipment includes: ACS devices, ACM-8RA remote relay module to provide additional relay points, and audio/voice components.

2.1.3 System Limitations

System expansion must take into consideration the following:
1. The physical limitations of the cabinet configuration.
2. The electrical limitations of the system power supply.
3. The capacity of the secondary power source (standby batteries).
1. Control Active LED is not supported.
Specifications System Overview

2.2 Specifications

2.2.1 Supply Rating

Supply Rating Parameter Details
Input Fuse Rating M205 Fuse - 250V, 8.0A Input Voltage Rating NPS-5CHS: 100-240 V AC, 50-60 Hz, 0.8-2.5 A
NPS-11CHS: 100-240 V AC, 50-60 Hz, 1.5-5.0 A
Output Ratings Details
Output Current NPS-5CHS: 5.6 A
NPS-11CHS: 11.7 A
Output Ratings (Charger) Details
Charger Voltage 27.3 V DC
*
@ 27.3 V DC
*
@ 27.3 V DC
*A total of 15 A can be drawn from the panel, with the difference in current being

2.2.2 Environmental Specifications

Environmental Specifications
Parameters
Environmental Limits 0°C to 49°C dry heat
IP Rating CAB650, CAB900: IP30

2.3 System Components

Central Processing Unit (CPU) with Power Supply. The central processing unit for the
AFP-3030 is a combination of the CPU and on board power supply (NPS-5CHS or NPS-11CHS). The power supply provides +24 V DC power and a battery charger for the basic system. Auxiliary power supplies and/or battery chargers are available to customize large systems.
Indicating Unit. The indicating unit acts as the primary display for the status of the Fire System. The ACM-ZM provides the status indications, with the AEM-ZM providing additional zonal indi­cations. The Indicating Unit also provides a Bulgin Switch for Trial Evacuation, a Bulgin Switch for Silence, and a Door Switch.
drawn from the panel batteries.
Details
40°C @ 93% relative humidity
18U, 28U, 40U: IP52
Keypad/Display. The keypad with built in LCD display serves as a secondary display for the AFP-3030.
Enclosures. Five cabinet sizes are available; CAB650, CAB900, 18U, 28U, and 40U. Refer to Section 2.5, “System Cabinets”, on page 8 for additional information.
SLC Loops: LCM-320, LEM-320 . To provide one SLC loop, connect one LCM-320 to the panel. Connect an LEM-320 to the LCM-320 to provide a second loop. Up to five pairs of modules can be installed on the panel to provide a maximum of ten SLC loops.
Network Connection. Connect a wire or fibre version of the NCM or the HS-NCM to provide a connection to the Noti•Fire•Net (network version 5.0 or higher) or High-Speed Noti•Fire•Net.
Annunciators. The AFP-3030 supports ACM-24A T/ACM-48A (and their expanders) with either 64 or 96 points at an address, as well as LDM-32 (and expanders) and Notifier’s other ACS devices. (See Section 2.6 “Compatible Equipment” if looking for specific ACS devices.)
NOTE: Annunciators for the AFP-2800 operate on a different baud rate and are not compatible with the AFP-3030.
AFP-3030 Installation Manual — P/N DOC-01-037:B 25/08/2016 4
System Overview System Components
Audio System. Voice evacuation applications are documented in the Audio System manuals:
DVC Digital Voice Command Manual, DAA2 and DAX Amplifiers Manual, DS-DB Digital Series Board Manual, DVC-RPU Manual and the AA-series Audio Amplifiers Manual.
Mass Notification System. The AFP-3030 supports Mass Notification applications. Installation, programming and operation information for Mass Notification systems are documented in the Mass Notification Manual. Refer to the AFP-3030 programming and operation manuals for additional information.
NOTE: The AFP-3030 does not support Control Active LED.

2.3.1 Replacement Kits

The system components that are available as replacement kits for the AFP-3030 are listed in Table 2.1.
Model Number Description
ASY-02-034 NPS-5CHS 5.6 A Power Supply Replacement Kit ASY-02-033 NPS-11CHS 11.7 A Power Supply Replacement
Kit
ASY-0 2-058 CPU2-3030NZ CPU Replacement Kit for New
Zealand AFP-3030
FG-50-012 DISP-3030NZ Keypad Replacement Kit for New
Zealand AFP-3030 ASY-01-035 Battery connection pack FG-65-016 3 V CR2477 24mm Lithium Battery ASY-02-023 ACM-ZM PCA Kit ASY-01-026 AEM-ZM Zone Mimic Expansion Card Kit ASY-01-048 SGD Assembly Kit ASY-01-055 SGD Inner Door Mounting Kit
Table 2.1 Available Kits
Product Diagram System Overview
Alarm Relay*
Fault Relay*
Supervisory Relay*
Alarm Relay*
Mini USB Connection
ACS (power-limited, supervised)
Printer (isolated)
CTX/CRX CRT-2 or Keltron printer supervision (TB5 CTX, REF No connection)
Lithium battery for backup of on-board memory (See Section 3.2.1 “Memory-Backup Battery”)
CPU Keypad Interface
LCM Interface
NAC connection
ASM-02-056Modified.wmf
LCD2-80: TOut pins
B-Type USB Connection
Battery Power Interface
Brigade Interface (A.R.E. Connection)
LCD2-80: RDP pins
24 V DC Power from PSU
for Door Holders
NAC connection
24 V DC connection
Field ACM Communications Connection
Field Power connection
Field Power connection
Local ACM Out
General Fault Input
NUP connection for HS-NCM network communications
24 V Power from PSU
Panel MCP Connection
4K7 EOL Resistors
* Relay may energise at power up and should not be used for Alarm Signalling Equipment. Alternative connections are available via
the Brigade Interface (A.R.E. Connection). See the A.R.E. Interface Board Installation Sheet for connection details.
†Door Holder Power must NOT be run directly to door holders in the field. This power must be fused
and must pass through a door holder relay to control when the doors are to be dropped.

2.4 Product Diagram

The control panel electronics are contained on one printed circuit board assembly that holds the central processing unit and power supply interface, collectively known as the CPU.
The following figure illustrates the location of the various connections, switches, jumpers and LEDs on the circuit board. See Section 3 “Installation” for more details.
AFP-3030 Installation Manual — P/N DOC-01-037:B 25/08/2016 6
Figure 2.1 CPU Connections
System Overview Product Diagram
NZCAB.wmf
Silence Buzzer Button
System Normal LED
Mute Alarm Devices Button
Alarm Routing Activated LED
Alarm Routing LEDs
QWERTY Keyboard
Fire LED
Alarm Scroll Button
Fault Scroll Button and LED
Reset Button
Disable Button
keypad-NZ-079.wmf
Alarm Devices Test &
Disable Buttons & LEDs
Program, Status
Supervisory Scroll Button and
LED
Other Scroll Button and LED
Door Holder Disable &
Auxiliary Disable Buttons &
LEDs
Delays On/Off Button
and LED
System Fault LED
Alarm Devices LEDs
Pre Alarm LED
Disable Scroll Button and LED
The keyboard/display assembly is shown in Figure 2.3.
Figure 2.2 AFP-3030 installed in a CAB650
Figure 2.3 AFP-3030 Keypad
System Cabinets System Overview

2.4.1 Main Power Supply

The NPS-5CHS or NPS-11CHS power supply provides a total of 5.6 A or 11.7 A to the CPU and has a built-in charger. During normal operation, the NPS can recharge batteries ranging in capacity from 7 to 85 amp-hours.
See Section 3.10, “Connecting Power Sources and Outputs”, on page 22 for basic power information.

2.5 System Cabinets

The CPU and modules are installed in a CAB650, CAB900 or U-Series backbox, holding up to four rows of equipment plus batteries (up to two 85AH batteries). Backboxes can be ordered with windowed or solid doors. The doors of the 28U and 40U can be mounted on the left or the right side of the cabinet. A trim ring option is available for semi-flush mounting.
External measurements for each cabinet backbox are provided in Appendix B, “Cabinet and Mounting Information”, on page 39. Refer to the CAB650, CAB900, or U-Series documentation for dimensions and door mounting specifications.

2.6 Compatible Equipment

Compatible Notifier and System Sensor equipment that connects directly to the CPU is listed below. These are the most common devices at time of publishing; the most complete list of compatible intelligent SLC loop devices is provided in the SLC Wiring Manual; for conventional non-addressable equipment see the Device Compatibility Document. Other control panels and their equipment can also be connected in a network, via Noti•Fire•Net version 5.0 or High-Speed Noti•Fire•Net; refer to the Noti•Fire•Net Version 5.0 Installation Manual or the High-Speed Noti•Fire•Net Installation Manual for details. Some products are documented in a separate manual; see Section 1.2 “Related Documents”.

Notifier Compatible Equipment

ACM-24AT Annunciator (Control) ACM-48A Annunciator (Control) ACM-8RA 8-way Relay Output Annunciator ACM-ZM Zone Mimic Annunciator AEM-24AT Annunciator (expander) AEM-48A Annunciator (expander) AEM-ZM Zone Mimic Annunciator Expansion ARM Agent Release Module Kit LCD2-80 LCD Annunciator Kit LDM-32 Lamp Driver Kit LDM-E32 Lamp Driver Expander Kit LDM-R32 Lamp Driver Relay Kit SCE-8A Smoke Control Annunciato r
SCS-8A Smoke Control Annunciator (Control) SCS-8LA Smoke Control Annunciator (Control) SGD Fire Brigade Alarm Signal Generating
HS-NCM-MF Network Control Module - Multi-mode HS-NCM-MFSF Network Control Module - Multi-mode/ HS-NCM-SF Network Control Module - Single-mode HS-NCM-W Network Control Module - Wire
HS-NCM-WMF Network Control Module - Wire/Multi- HS-NCM-WSF Network Control Module - Wire/ Single- NCA-2NZ Network Control Annunciator
NCM-F Network Control Module - Fibre NCM-W Network Control Module - Wire RPT-W NFN Wire-to-Wire Repeater RPT-WF NFN Wire-to-MMOF repeater
Annunciators
(Expander)
Device
Network Control Modules
optical fibre Single-mode optical fibre optical fibre
mode optical fibre mode optical fibre
BACNET-GW-3 Bacnet gateway DVC Digital Voice Command MODBUS-GW Modbus-GW NWS-3 NOTI-FIRE-NET WebServer NFN-GW-AU-EM-3 NFN gateway (Embedded) OnyxWorks OnyxWorks Workstation with and
VESDA-HLI-GW VESDA-Net gateway
AIBS32 Intelligent Base Sounder with B501 Addressable Detector Base
B524IEFT Short Circuit Isolator Base NFX-BF-IVR Addressable Strobe Base (NFX
NFX-BS-IV Addressable Sounder Base (NFX NFXI-BS-IV Addressable Sounder Base (NFX NFX-BSF-IVR Addressable Sounder/Strobe Base NFX-WF-RR Addressable Strobe (NFX Series)
NFX-WSF-RR Addressable Sounder/Strobe (NFX NFX-WS-R Addressable Sounder (NFX Series)
Gateways
without PC gateway
Detector/Sounder Base
integrated isolator
Series) Series) Series) (NFX Series)
Series)
AFP-3030 Installation Manual — P/N DOC-01-037:B 25/08/2016 8
System Overview Compatible Equipment
AAM Addressable Alarm Acknowledgement FCM-1 Single Intelligent Control Module
FDM-1 Dual Switch Input Module FDMR-1 Dual input/ output Module FMM-101 Single Switch Input Mini-Module FRM-1 Single Intelligent Relay Output Module FZM-1 Single Conventional Zone Interface
ISO-X Loop (SLC) Isolator Module SLC-IM Modbus Interface Module XP-10M 10-way Switch Input Module XP-6C 6-way Control output (NAC) Module XP-6MA 6-way Conventional Zone Interface
XP-6R 6-way relay output Module ZCM ZCM Conventional Zone Conversion
Module (HUSH)
Module
Module
Module
Detectors (FlashScan)
Field Modules (FlashScan)
FAPT-751AUS Intelligent Photo-Heat (Acclimate) FAPT-851AUS Intelligent Photo-Thermal multi-sensor
FSB-200 Beam Detector FSB-200S Beam Detector with built-in test facility FSC-851AUS IntelliQuad multi-criteria sensor FSD-751P Innovair DSU FSD-751PL Innovair Low-Flow DSU FSD-751RP Addressable Duct Detector with Relay FSI-851AUS Intelligent Ionization Sensor FSL-751 View™ High Sensitivity Laser Sensor FSP-751AUS Photoelectric Smoke Detector FSP-851AUS Intelligent Photo Sensor FST-851H Intelligent Flash Scan High Heat
FST-851RAUS Intelligent Thermal Sensor FST-851R-WP Intelligent Sealed Thermal Sensor FST-851-WP Type A2 Heat Detector (Addressable -
WCP5A­RP02SFM066-01C
(Acclimate)
(Addressable)
Sealed) Intelligent Weatherproof Red Manual
Call Point with isolator
Detectors (Clip)
FDX-851AUS Intelligent Thermal Sensor FDX-851RAUS Intelligent Thermal Sensor IDX-751AE Intrinsically Safe Addressable
SDX-851AUS Intelligent Photo Sensor
Photoelectric Detector
NOTE: This system is not intended for use by detectors incorporating eutectic alloys.

Section 3: Installation

!
!

3.1 Preparing for Installation

Choose a location for the fire alarm system that is clean, dry, and vibration-free with moderate temperature. The area should be readily accessible with sufficient room to easily install and maintain it. There should be sufficient space for cabinet door(s) to open completely.
Carefully unpack the system and inspect for shipping damage. Count the number of conductors needed for all devices and find the appropriate knockouts.
Before installing the fire alarm system, read the following:
Review the installation precautions at the front of this manual.
Installers should be familiar with the standards and codes specified in Section 1.1 “Agency Approvals”.
All wiring must comply with the National and Local codes for fire alarm systems.
Do not draw wiring into the bottom 25 cm of the cabinet except when using a separate battery cabinet; this space is for internal battery installation.
R ev i e w in stallation instructions in Section 3.2 “Installation Checklist”.
WARNING: RISK OF IRREPARABLE EQUIPMENT DAMAGE
MAKE SURE TO INSTALL SYSTEM COMPONENTS IN THE SEQUENCE LISTED BELOW. FAILURE TO DO SO CAN DAMAGE THE CONTROL PANEL AND OTHER SYSTEM COMPONENTS.
WARNING: RISK OF IRREPARABLE EQUIPMENT DAMAGE
WEAR A STATIC DISCHARGE STRAP ON WRIST TO PREVENT EQUIPMENT DAMAGE.

3.2 Installation Checklist

The checklist that follows contains references to information included in other manuals; see Section 1.2 “Related Documents” for document part numbers.
Task Refer to:
1. Mount the cabinet backbox to the wall. Appendix B, “Cabinet and Mounting Information”
2. Wire relays Section 3.6 “Form-C Relays on the CPU”
3. Attach & wire other system components
Audio/Voice equipment DVC Digital Voice Command Manual, DAA Digital Audio
Amplifiers Manual, DVC-RPU Manual
Annunciators and other ACS devices Installation document for the specific device (such as ACS
Manual, ACM-8RA Install Sheet, etc.)
Printer or other output device(s) Section 3.11 “Installing Printers” Network devices Noti•Fire•Net Version 5.0 & Higher Manual/High-Speed
Noti•Fire•Net Manual, and/or Installation document for specific device(s)
4. Wire the Signalling Line Circuits (Notification Appliance Circuits and Initiating Device Circuits)
5. Calculate the proper battery rating. Main Power Supply Manual
Section 3.12 “Wiring a Signalling Line Circuit (SLC)” and the SLC Wiring Manual
T able 3.1 Installation Checklist (1 of 2)
AFP-3030 Installation Manual — P/N DOC-01-037:B 25/08/2016 10
Installation Installation Checklist
!
Lift clip gently while
removing battery
Dotted line indicates
location of insulator
ASM-02-056-Battery.wmf
!
Task Refer to:
6. Install main power supply & batteries in
• Section 3.10 “Connecting Power Sources and Outputs”
separate enclosure. Run cable to main & optional power supplies, DC power outputs, relays, etc.
WARNING:
DO NOT ACTIVATE POWER AT THIS TIME. DO NOT CONNECT BATTERIES.
Main power supply.
NPS Installation Sheet
Auxiliary power supply and/or
external battery charger
7. Check that all mounting holes are secured to insure a proper Earth Ground connection.
8. Connect wire shielding to Earth Ground.
9. Remove insulator from lithium battery
Section 3.2.1 “Memory-Backup Battery”
on CPU
10. Apply AC power to the control panel by placing the external circuit breaker to the ON position. Do NOT connect batteries until AC power is checked (see next step).
11. Check AC power. Section 3.10.3 “Checking AC Power”
12. Connect the batteries using interconnect cable as described in Section 3.10.2 “Connecting Local and Remotely Powered Devices”.
13. Program the control panel. Programming Manual.
T able 3.1 Installation Checklist (2 of 2)

3.2.1 Memory-Backup Battery

The lithium battery on the CPU provides backup of the CPU’s on-board memory during power loss. The CPU ships with an insulator to prevent the battery from discharging. To preserve the battery, the insulating tube should be left in place as long as possible before applying AC power.
If the insulator is not removed before applying AC power, the control panel will show a fault situation.
This battery’s shelf-life should exceed 10 years, but if for some reason it fails, the control panel will show a fault when powered up. To replace the lithium battery:
1. Make a full backup of all system settings to prevent loss of all programming data.
2. Disconnect all power sources.
3. Lift clip gently using a hardware tool or screwdriver, and remove battery from under clip (use fingers, as screwdriver could damage components) before inserting new battery.
CAUTION:
THE BATTERY USED IN THIS DEVICE MAY PRESENT A RISK OF FIRE OR CHEMICAL BURN IF MISTREATED. DO NOT RECHARGE, DISASSEMBLE, HEAT ABOVE 100°C, OR INCINERATE. A REPLACEMENT CR2477 LITHIUM BATTERY CAN BE ORDERED FROM NOTIFIER BY QUOTING THE PART NUMBER FG-65-016. USE OF ANY OTHER BATTERY MAY PRESENT A RISK OF FIRE OR EXPLOSION.
4. Follow system power-up procedures.
5. Dispose of used battery promptly. Keep away from children. Do not disassemble and do not dispose of in fire.
Attaching Option Boards Installation
CHS-3L.jpg, CHS-4L.jpg
To mount option boards against
the CHS-3L or CHS-4L
backplate, attach stand-offs to
the chassis studs.
Figure 3.1 Mounting Option Boards in CHS-3L and CHS-4L
Slide tabs at bottom of
option boards into the
matching slot.

3.3 Attaching Option Boards

If installing option boards into a CAB650, CAB900, or U-Series backbox, mount & connect those boards at this time. This section contains general instructions for mounting an option board; see the documentation that shipped with your board for any product-specific instructions.
As described in Appendix B.6, “Laying Out Equipment in Cabinet and Chassis”, up to three option boards can be mounted in CHS-3L or four option boards can be mounted in the CHS-4L; additional modules can be mounted in other chassis.

Mounting procedures: Chassis mount

1. Install two 3/4 inch (19.05 mm) stand-offs onto the chassis as sho wn in Figure 3.1.
2. Place the first option board over the stand-offs so that holes line up.
3. If no more option boards will be mounted in that position, securely fasten all stand-offs with screws (provided with module). If mounting a second option board, attach another layer of stand-offs and repeat steps 2-3. Note: Set the switches on an option board before mounting another layer in front of it.
4. If mounting a pair of SLC loop modules, refer to Section 3.5 “Connecting the Loop Contro l and Expander Modules” and to Section 3.5.3 “Installing a Multi-layer Module into the Chassis”.
5. For the top (second) layer of option boards, slide the tab at the bottom of the board into the slots on the chassis, and lay the board back onto the top of the chassis so that the studs line up with mounting holes on the option board. Securely fasten all stand-offs with screws provided with module.
NOTE: Mounting two pairs of loop-control and -expander modules in one chassis position may cause intermittent electrical interference. If this occurs, move one pair to a separate chassis position.

Mounting procedures: Door mount

If mounting the option board in the door behind a blank dress plate, see Figure 3.2. This dress plate is suitable for option boards, which do not need to be visible or accessible when the door is closed.
AFP-3030 Installation Manual — P/N DOC-01-037:B 25/08/2016 12
Installation Attaching Option Boards
Fasten option board to the plate with four screws (included).
OptionBoard-Door.wmf, OptionBoardInstalled-Door.wmf
Mount option board onto stand-offs (included) to the blank plate
Mount single-space blank plate onto the door.
Figure 3.2 Door-Mounting Option Boards with a Single-space Blank Plate
Connecting the Network Communications Module Installation
Figure 3.3 Mounting an NCM/HS-NCM to the CPU Assembly
psi-network-card.jpg
CPU Assembly
NCM or HS-NCM
Fasten the NCM/HS-NCM to the CPU Assembly using the screws and standoffs included with your network card.
NUP Port connections: Connect NUP cable from NCM/HS­NCM to J1 on the fire panel

3.4 Connecting the Network Communications Module

If networking two or more control panels (or network control annunciators), each one requires a Network Communications Module; a wire version and a fibre version are available. The wire and fibre versions on the NCM or HS-NCM can be installed on the CPU and power supply assembly. The preferred position is on top of the CPU assembly, as shown in Figure 3.3.
1. Mount the NCM or HS-NCM in the selected position. (See Figure 3.3)
2. Connect J1 on the CPU to J3 on the NCM or J6 on the HS-NCM using the network cable provided (P/N 75556). Do not connect two NCMs via NUP ports (aka NUP to NUP).
3. When installing an NCM: Connect Channel A and/or Channel B as described in the NCM Installation Document.
When installing a HS-NCM: Connect Channel A to Channel B as described in the HS-NCM Installation Document.

3.5 Connecting the Loop Control and Expander Modules

AFP-3030 Installation Manual — P/N DOC-01-037:B 25/08/2016 14
NOTE: See the Noti•Fire•Net Version 5.0 & Higher Manual and the NCM Installation Document or the High-Speed Noti•Fire•Net Manual for system configuration information.
NOTE: Over-bending fibre-optic cable can damage it. Do not exceed a 8 cm minimum bend radius.
NOTE: NCM hardware is not compatible with HS-NCM hardware and should not be mixed on the same network.

3.5.1 Mounting Instructions

Mount loop control and expander modules within the cabinet with the CPU. Typical mounting positions are in the row immediately below the fire panel. Follow the basic chassis-mounting instructions given for option boards. Loop-expander modules are mounted first; Loop-control modules are mounted on top of those. Alternately, loop-control and loop-expander modules can be attached to each other and mounted as a pair to the chassis. See Figure 3.5 for connection instructions, connector locations and stand-off lengths.
If using loop control and expander modules in CHS-4L see Figure 3.6.
NOTE: Mounting two pairs of loop control and expander modules in one chassis position may cause intermittent electrical interference. If this occurs, move one pair to a separate chassis position.
Installation Connecting the Loop Control and Expander Modules
!
After all loop-control and loop-expander modules are mounted in the cabinet, connect the SLC loops to TB1 on each loop-control and loop-expander module as shown in Figure 3.8. Daisy-chain the loop-control modules as shown in Figure 3.7. The ribbon-cable connection runs from header J7 on the CPU to header J1 (“Data in”) on the first loop-control module, from J3 (“Data out”) on that unit to J1 on the next unit in the chain, and likewise for up to five loop-control modules. Each module should be assigned a unique SLC loop number (see below); loop number does not need to match the module’s location in this daisy-chain.
FlashScan devices can operate in either FlashScan or, for retrofit applications, CLIP mode. Each LCM-320 or LEM-320 running a FlashScan SLC can support up to 159 detectors and 159 modules. CLIP loops are limited to 99 detectors and 99 modules. These and other capacity restrictions for CLIP mode loops are discussed in Section 3.12 “Wiring a Signalling Line Circuit (SLC)”. Refer to the SLC Wiring Manual for wiring requirements and specific details.
CAUTION:
DO NOT PROGRAM MORE THAN 99 ADDRESSES ON A CLIP-MODE SLC LOOP, BECAUSE THIS WILL SLOW THE SYSTEM DOWN AND COMPROMISE THE RESPONSE TIME OF THE PANEL TO DISPLAY OFF-NORMAL EVENTS.

3.5.2 Setting SLC Loop Number

Assign a unique SLC loop number to the loop control module by setting SW1 on the module to 1, 3, 5, 7, or 9. The loop expander module which is mounted behind this loop control module will be assigned the next-higher even number. For example, if the LCM-320 is set to loop number 5, the LEM-320 mounted to it will be set to loop number 6.

3.5.3 Installing a Multi-layer Module into the Chassis

Follow the instructions illustrated in Figures 3.4 through 3.7 to install a pair of loo p control/expander modules.
1. Angle the module into the chassis so that the upper end of the rear board (or boards) fits into the top slot.
2. Bring the module back down so that the lower board edges slip into the bottom slots.
3. Secure the module to the chassis with the two module screws. Tighten securely.
4. Connect the ribbon cable to the module.
Connecting the Loop Control and Expander Modules Installation
SW1 Set to assign a unique SLC loop number
J3 Data Out to next LCM-320
J1 Data In from control panel or from previous LCM-320
Ground Fault LEDs: D32 Loop Expander
Module Ground Fault
D28 Loop Control Module
Ground Fault
J2 LEM-320 Connection
TB1 SLC Loop Connection
LCM-320 Connection
LCM-320 LEM-320
Note: Do not cut any jumpers on the LCM-320 or LEM-320.
TB1 SLC Loop Connection
LCM-320.wmf
LEM-320.wmf
Figure 3.4 LCM-320 and LEM-320 Diagram
JP2 See note.
Stand-off
locations
JP1 See note.
J2
SLC
B+ A+ B- A-
TB1
J1
J1
Figure 3.5 Connecting Loop Control Modules with Loop Expander Modules
Loop Expander Module
Loop
Control
Module
J1
J2
Loop Expander Module
Loop Control Module
The long-pin end plugs directly into the back of
the Loop Control
Module board.
The short-pin end plugs directly into the top of the
Loop Expander Module plug.
Stand-off
locations
J2 on LCM-320 “LEM-320 Data”
Loop Expander Module mounted
behind Loop Control Module
LEM-LCM.cdr
!
CAUTION:
IF THE STACKER-CONNECTOR IS INSTALLED UPSIDE-DOWN, THE SHORT-PIN END OF THE PLUG CAN FAIL TO MAKE A SECURE CONNECTION WHEN PLUGGED THROUGH THE LOOP CONTROL MODULE.
!
WARNING: RISK EQUIPMENT DAMAGE.
USE SPECIFIED STAND-OFF MOUNTING LOCATIONS ONLY. SEE FIGURES 3.4 AND 3.5. DO NOT USE CORNER HOLES FOR INSTALLATION PURPOSES.
AFP-3030 Installation Manual — P/N DOC-01-037:B 25/08/2016 16
Installation Connecting the Loop Control and Expander Modules
Angle tab on loop control module into slot on CHS-4L
Use a slimline screwdriver (3/32”) to fasten down LEM-320 through the hole in the LCM-320 board.
CHS-4L-LEM-LCM.cdr
Figure 3.6 Inserting Pair of Loop Control and Expander Modules into CHS-4L
For mounting in CHS-3L, see Figure 3.1
Figure 3.7 Connecting Multiple Pairs of Loop Control and Expander Modules
J22 on PSU
J1 on LCM-320
“Data in”
J3 on LCM-320
“Data out”
3030LCMchainrv2.wmf
Figure 3.7 Connecting Multiple Pairs of Loop Cont rol and Expander Modules
NOTE: The red stripe on the ribbon cable indicates position 1. Position 1 of the ribbon cable should line up with position 1 on J7 of the CPU and J1 and J3 of the LCM-320.
WARNING: INSTALL THE RIBBON CABLE AS SHOWN. DO NOT FORCE OR MODIFY THE CABLE TO FIT ANY OTHER WAY. EQUIPMENT DAMAGE CAN RESULT FROM INCORRECT ALIGNMENT.
!
The red stripe on the ribbon cable is indicated by the dark line
NOTE: Depending on system components, clearance may be tight. Do not force modules! Move the assembly around gently until you find the angle where components and mounting studs pass each other without scraping together.
Form-C Relays on the CPU Installation
LEM-SLC.cdr
LCM-SLC.cdr
LCM-320 (in front) LEM-320 (in back)
Figure 3.8 SLC Loop Connections on Loop-Control and Loop-Expander Modules
FormCRelays.jpg
Figure 3.9 Form-C Relay Connections
TB4 TB3 TB2 TB1
!

3.6 Form-C Relays on the CPU

The panel provides a set of Form-C relays. These are rated for 1 A at 30 V DC (resistive):
•Alarm - TB4
Fault - TB3
Supervisory - TB2
•Alarm - TB1
NOTE: Form-C Relays may energise at power up and should not be used for Alarm Signalling Equipment. See the A.R.E. Interface Board Installation Sheet for alternate connections for this purpose.

3.7 Installing the SGD Interface Board

The SGD assembly is used to transmit alarms and faults from the fire panel to the fire brigade.
CAUTION:
POWER DOWN THE FIRE PANEL BEFORE ADDING OR REMOVING THE SGD.
1. Affix two 3/4” 4-40 stand-offs to an empty slot on the CHS chassis.
2. Insert the tab at the bottom of the SGD assembly into the corresponding slot along the bottom of the CHS chassis, and slide the assembly into place.
AFP-3030 Installation Manual — P/N DOC-01-037:B 25/08/2016 18
Installation Installing a Replacement Zone Mimic (ACM-ZM)
Figure 3.10 Installing the SGD Interface Board
!
Figure 3.11 Setting the ACM-ZM address wheels
3. Secure the SGD assembly to the stand-offs using two 4-40 screws.
4. Connect the SGD assembly to the fire panel as specified in the SGD Schematic in Appendix C.
NOTE: The SGD Interface will need to be programmed into the panel to be operational. Consult the AFP-3030 Programming Manual for details.

3.8 Installing a Replacement Zone Mimic (ACM-ZM)

The Zone Mimic is a device that can be fitted away from a fire panel, permitting an operator to see the status of the available zones when the operator is working away from the panel.
CAUTION:
POWER DOWN THE FIRE PANEL BEFORE ADDING OR REMOVING THE ACM-ZM.
1. Unscrew and remove the existing ACM-ZM from the panel.
2. Set the address of the replacement card using the address wheels on the ACM-ZM.
3. Connect the replacement ACM-ZM to the fire panel as per the relevant drawing in Appendix C, “Schematics”, on page 46.
Installing a Replacement Zone Mimic (ACM-ZM) Installation
Figure 3.12 ACM-ZM termination jumper settings
Figure 3.13 Mounting the ACM-ZM
4. If the ACM-ZM is the last device on the line, set the Comms EOL Terminator jumper to the ON position; otherwise, leave the Comms EOL Terminator jumper in the OFF position.
5. Secure the ACM-ZM to the spacers on the NPS mounting bracket using two (2) M3 screws, as shown in Figure 3.13. Ensure that the ACM-ZM is mounted with the Comms/Power header at top right.

3.8.1 Installing a Zone Mimic Expansion Card (AEM-ZM)

The Zone Mimic Expansion card increases the number of feedback LEDs on the ACM-ZM. The additional LEDs can be programmed to represent the active state of any zones or outputs connected to the panel.
1. Screw the AEM-ZM to the vacant threaded spacers beneath the ACM-ZM card on the NPS Mounting Bracket, as shown in Figure 3.14.
2. Connect the replacement ACM-ZM to the fire panel as per the relevant drawing in Appendix C, “Schematics”, on page 46.
AFP-3030 Installation Manual — P/N DOC-01-037:B 25/08/2016 20
Installation Installing Replacement Bulgin Switches
Figure 3.14 Mounting a Zone Mimic Expansion Card
!
Figure 3.15 Bulgin switches and nuts, as viewed from inside the outer door

3.9 Installing Replacement Bulgin Switches

The Bulgin switches enable the evacuation and silent alarm functions of the panel to be operated more securely than with push button inputs, via the use of Bulgin switch keys. The fire brigade and service technicians are the only user groups that have access to the Bulgin switch keys.
CAUTION:
REMOVE ALL POWER SOURCES TO EQUIPMENT BEFORE CONNECTING THE BULGIN SWITCHES. LEAVE THE EXTERNAL, MAIN POWER BREAKER OFF UNTIL INSTALLATION OF THE BULGIN SWITCHES IS COMPLETE.
NOTE: The Bulgin switches require a Zone Mimic Card to be fitted before the switches can operate successfully.
1. Open the outer door of the cabinet.
2. Unscrew the nut on the outside of the outer door, and the hex nut on the inside of the outer door, to remove the Bulgin switches.
3. Remove the wires running from the Bulgin switches to the ACM-ZM.
Connecting Power Sources and Outputs Installation
!
!
4. Pass the threaded shafts of the replacement Bulgin switches through the Bulgin switch holes in the outer door, and secure with the provided nuts.
5. Wire the replacement Bulgin switches to the ACM-ZM. Bulgin switch wiring details can be found in the ACM-ZM wiring diagram in Appendix C, “Schematics”.

3.10 Connecting Power Sources and Outputs

WARNING:
REMOVE ALL POWER SOURCES TO EQUIPMENT WHILE CONNECTING ELECTRICAL COMPONENTS. LEAVE THE EXTERNAL, MAIN POWER BREAKER OFF UNTIL INSTALLATION OF THE ENTIRE SYSTEM IS COMPLETE.
WARNING:
SEVERAL SOURCES OF POWER CAN BE CONNECTED TO THE CONTROL PANEL. BEFORE SERVICING THE CONTROL PANEL, DISCONNECT ALL SOURCES OF INPUT POWER INCLUDING THE BATTERY. WHILE ENERGISED, THE CONTROL PANEL AND ASSOCIATED EQUIPMENT CAN BE DAMAGED BY REMOVING AND/OR INSERTING CARDS, MODULES, OR INTERCONNECTING CABLES.

3.10.1 Overview

Complete all mounting procedures and check all wiring before applying power. Electrical connections include the following:
Primary power source. +24 V DC, delivered through the NPS main power supply. For cabinet placement information see Appendix B.6 “Laying Out Equipment in Cabinet and Chassis” and the NPS Installation Sheet.
Secondary power source. +24 V DC from batteries, installed in the control panel (or in an optional battery cabinet). Secondary (battery) power is required to support the system during loss of primary power.
Exte rnal power sources. +24 V DC auxiliary power supplies.
Accessory power for peripheral devices. The NPS provides +24 V DC power to devices within the same enclosure as the CPU. If those devices have outputs, the outputs must be power-limited. Power rating is limited by the NPS primary power source, which is +24 V DC and 5.6 Amps (NPS-5CHS) or 11.7 Amps (NPS-11CHS) max.
NOTE: The CPU ships with an insulator to prevents its lithium battery from discharging. To preserve the battery, this insulator should be left in place as long as possible before applying AC power. Some installers may find it convenient to remove the insulator before mounting all equipment.
NOTE: If using multiple power supplies with one set of batteries, refer to main power supply documentation for connection requirements.
AFP-3030 Installation Manual — P/N DOC-01-037:B 25/08/2016 22
Installation Connecting Power Sources and Outputs
Red
Red Black Black
T o NPS Power Supply
To Battery
Black
Red
Main CPU
(Locally Powered)
Red (+)
Black (-)
Red (+)
Black (-)
Remote CPU

3.10.2 Connecting Local and Remotely Powered Devices

Refer to Figure 3.16 for power connections for a locally powered device. Refer to Figures 3.17 and
3.18 for power connections to a remote or secondary device from a locally powered device.
Figure 3.16 Connecting a Locally Powered CPU to power
Figure 3.17 Connecting a Remotely Powered CPU to the Main CPU
Connecting Power Sources and Outputs Installation
Main CPU
(Locally Powered)
Red (+)
Black (-)
Red (+)
Black (-)
Secondary CPU
PSU Switch
Figure 3.18 Connecting a Secondary CPU to the Main CPU within the same cabinet
NOTE: The Remote/Secondary CPU must be programmed with the Main PS Node number of
the CPU from which it is drawing power. This node number must be separate from its own node number. Refer to the ‘SUPERVISION’ section of the AFP-3030 Programming Manual for more information.

3.10.3 Checking AC Power

Power up the fire panel by switching on the PSU switch. The device will be on when the PSU switch is illuminated (red).
Figure 3.19 Location of the PSU Switch
AFP-3030 Installation Manual — P/N DOC-01-037:B 25/08/2016 24
Installation Installing Printers
!
6769cov.tif
Table 3.2 contains a checklist for checking the system with AC power applied to the main power supply:
CAUTION:
WHILE CHECKING AC POWER, MAKE SURE BATTERIES ARE NOT CONNECTED.
Component Status
CPU/PSU The green Operating indicator will come on when power is
coming from the main power supply.
Main power supply
Each auxiliary power supply
The green Operating indicator will come on when AC is supplied.
Refer to the panel’s LCD display for any auxiliary power supply issues.
Table 3.2 AC Power Checklist

3.10.4 Auxiliary Power Supply Connections

If an optional auxiliary power supply is installed in the cabinet, connect it at this time. Follow the connection procedures specified by your auxiliary power supply.

3.11 Installing Printers

This section contains information on connecting a printer to the CPU and for setting the printer options. The basic steps are as follows:
1. Make custom cable & connect it from printer to EIA-232 terminal on the CPU.
2. Connect printer’s power supply.
3. Configure printer settings as described in printer documentation.

Overview: PRN Printer

The PRN provides a printed record (80 columns on standard 9" x 11" tractor-feed paper) of all system events (alarm, trouble) and status changes within the system. The control panel can be configured to time-stamp the printout with the current time-of-day and date for each event. The printer can be located up to 15 metres from the control panel. Installation and configuration instructions follow.

3.11.1 Printer Installation Sequence

1. Fabricate a custom cable to connect a printer to the system. Length of the cable will vary with each installation, but should not exceed a maximum length of 15 metres. Printer must be installed in the same room as panel. Using overall foil/braided-shield twisted-pair cable, properly connect one end to the DB-25 Connector (provided) using the wiring specifications shown in Figure 3.20.
NOTE: Alternative wiring specifications are also shown in Figure 3.20 for a printer with a 9-pin connector. Refer to printer manual for detailed connection information.
2. Tighten clamp on connector to secure cable. Connect the four open leads of the custom cable to the TB5 terminal block on the CPU as shown in Figure 3.20.
Installing Printers Installation
Note: Outputs are power-limited
but are not supervised.
DB-25 connector on
PRN Series Printer
TB5 on Control Panel
Figure 3.20 Printer Connections
REF
PRX
PTX
3030-printer.wmf
DB-9 connector for alternative printers
3. If installing a PRN series printer, plug it into your AC power source. Note: PRN printers require a 240 V AC, 50 Hz primary power source. If required for the fire alarm system configuration (for example, a Proprietary Fire Alarm System), a remote printer requires a secondary power source (battery backup). Because a secondary power source is not provided, use a separate Uninterruptible Power Supply (UPS).
4. Plug the DB-25 connector end of the custom cable into the EIA-232 port of your printer. Tighten securely.
5. Configure the printer as described in Section 3.11.2 “Configuring the Printer”.
AFP-3030 Installation Manual — P/N DOC-01-037:B 25/08/2016 26
Installation Wiring a Signalling Line Circuit (SLC)
*Protocol: When printing in graphics mode, set I/O Serial Protocol to “Robust XON/OFF”.
Option Setting
L/R Adjust 0 Font HS Draft CPI 10 CPI LPI 6 LPI Skip 0.0 ESC Character ESC Emulate FX-850 Bidirectional Copy ON I/O
Interface Buffer Serial Baud Format Protocol *
Serial 40K
9600 8 Bit, None, 1 Stop
ENQ/STX CG-TAB Graphic Character Set Standard Country E-USA ASCII Select Zero ON Auto-CR OFF Auto-LF OFF
Option Setting
Menu Lock ON Language English Paper
Single Form Adjust Trac 1 Form Adjust Trac 2 Form Adjust Auto Sheet Feeder Form Adjust
12/72 12/72 12/72
12/72 Auto Tear OFF F-Eject OFF Form Length
Trac 1 Lines Standard Trac 2 Lines Standard
66
10.5”
66
10.5” Barcode Off Barmode Unsecured
Table 3.3 PRN Setup Options

3.11.2 Configuring the Printer

Refer to the documentation supplied with the printer for configuration instructions.
PRN Printer Settings
Set the printer options (under the menu area) according to the settings listed in Table 3.3.

3.12 Wiring a Signalling Line Circuit (SLC)

3.12.1 SLC Overview

Communication between the CPU and intelligent and addressable initiating, monitor, and control devices takes place through a Signalling Line Circuit (SLC). This manual provides requirements and performance details specific to this control panel; for installation information and general information, refer to the SLC Wiring Manual.
For electrical specifications, see Appendix A.2 “SLC Loops”. For additional notes on SLC resistance values, see Section 4.1 “Operational Checks”.

3.12.2 SLC Capacity

The AFP-3030 supports up to five pairs of LCM-320 and LEM-320 modules, providing from one to ten SLC loops. Loop capacity depends on operating mode:
Flash Scan: 01-159 intelligent detectors, 01-159 monitor and control modules
CLIP: 01-99 intelligent detectors, 01-99 monitor and control modules FlashScan devices can operate in either FlashScan or CLIP mode. Older models of CLIP devices
only support addresses up to address 99. CLIP loops are limited to 99 detectors and 99 modules.
NOTE: Response times for CLIP loops may vary. CLIP loops must be tested to assure that actuation of notification appliances occurs within 15 seconds after activation of an initiating device.
The following configuration guidelines may be used to improve the response times of CLIP loops:
1. All manual pull stations must be assigned addresses from 1-20.
Wiring a Signalling Line Circuit (SLC) Installation
TB1
B+ A+ B- A-
TB1
B+ A+ B- A-
T-Tapping is not allowed
on a four-wire SLC.
Channel B (output loop)
Channel A (loop return)
Open Wiring (Style 4)
SLC Loops
Closed Wiring (Style 6/7)
SLC Loops
SLC Loop #2 Connections on Loop Expander Module
SLC Loop Connections
on Loop Control Modules
SLC loop
connections are
the same for Loop
Expander and
Control Modules
Channel BChannel
A
3030-slcloops.cdr
Figure 3.21 SLC Loop Connections and Wiring
2. Loops must be programmed for Rapid Poll (refer to the programming manual for specific instructions).
3. Modules on a fully loaded loop must adhere to a ratio of two monitor modules to one control module.

3.12.3 SLC Installation

Install loop control and expander modules as described in Section 3.5 “Connect ing the Lo op Control and Expander Modules”. Note that the unique SLC loop number assigned to a module does not need to match the module’s location in the cabinet. For details on designing, installing and configuring SLC loops, see the SLC Wiring Manual.
B+ A+ B- A- B+ A+ B- A-
AFP-3030 Installation Manual — P/N DOC-01-037:B 25/08/2016 28
Installation Connecting a FAAST Intelligent Aspiration Detector
FAASTTermBlk.wmf
To Next SLC Device +
From FACP or Previous De vice +
To Next SLC Device -
From FACP or Previous Device -
Figure 3.22 FSA-8000A Connection to the FACP
To Next Device +
From Power Supply or Previous Device +
To Next Device -
SLC
Connection
24V External
Power
From Power Supply or Previous Device -

3.13 Connecting a FAAST Intelligent Aspiration Detector

The FAAST Intelligent Aspiration detector may be used to provide early warning fire protection using aspiration sensing technology.

FAAST Wiring:

Figure 3.22 shows the wiring for the FAA ST detect or to the AFP-
3030.
For additional installation information for the FAAST detector, refer the FSA-8000 FAAST
Installation and Maintenance Instruction document (I56-3903)
and the SLC Wiring Manual (51253).

3.14 Connecting a PC for Programming

A PC running the VeriFire® Tools programming utility can upload and download the operating program of the control panel when attached to J15 USB Connection, J1 Network/Service Connection (NUP) or to the second Network/Service connection on an attached wire or fibre version of the NCM or HS-NCM. Refer to the VeriFire® Tools CD for instructions.

Section 4: Testing the System

continued…

4.1 Operational Checks

Between formal periodic testing and servicing intervals, the following operation checks should be performed monthly.
Check that the green SYSTEM NORMAL LED lights. Check that all status LEDs are off. Press and hold the LAMP TEST key. Verify that all LEDs and all LCD display segments work. Before proceeding: a) notify the fire department and the central alarm receiving station if
transmitting alarm conditions; b) notify facility personnel of th e test so that alarm sounding devices are disregarded during the test period; and c) when necessary, disable activation of alarm notification appliances and speakers to prevent their sounding.
Activate an Initiating Device Circuit using an alarm initiating device or an addressable
initiating device on the SLC and check that all programmed active notification appliances function. Reset the alarm initiating device, the control panel, and any other associated equipment. In voice alarm applications, confirm that the proper tone(s) and/or messages sound during alarm conditions. Select the paging function and confirm that the message can be heard in the affected fire zones. Repeat the above step with each Initiating Device Circuit and each addressable device.
NOTE: SLC Resistance Valu es: The total DC resistance of the SLC pair cannot exceed 50 ohms. For instructions on how to measure the total DC resistance of a populated SLC pair, refer to the “Measuring Loop Resistance” section of the SLC Wiring Manual (P/N 51253). The minimum DC resistance between conductors of an unpopulated SLC pair cannot be less than 1 K ohms. Measure DC resistance on an unpopulated loop as shown in Figure 4.1 on page 31.
Zero Ohms to ground will cause a ground fault. On systems equipped with a firefighter’s telephone circuit, make a call from a telephone circuit
and confirm a ring indication. Answer the call and confirm communication with the incoming caller. End the call and repeat for each telephone circuit in the system.
Remove AC power, activate an Initiating Device Circuit through an alarm initiating device or
an addressable initiating device on the SLC, and check that programmed active notification appliances sound, and alarm indicators illuminate. Measure the battery voltage with notification appliances active. Replace any battery with a terminal voltage less than 21.6 V DC and reapply AC Power.
NOTE: The battery test requires fully charged batteri es. If batteries are new or discharged due to a recent power outage, allow the batteries to charge for 24 hours before testing.
Return all circuits to their pretest condition. Check that all status LEDs are off and the green POWER LED is on.
AFP-3030 Installation Manual — P/N DOC-01-037:B 25/08/2016 30
Testing the System Battery Checks and Maintenance
!
SLC-meas5.cdr
SLC Out
SLC Return
SLC Return
SLC Out
STEP 2
STEP 3
Step 1. Disconnect the SLC channel B (Out) and SLC channel A (Return) at the control panel. Step 2. Measure and record the resistance at SLC Out. Step 3. Measure and record the resistance at SLC Return.
The minimum resistance is the lesser of two and three.
Figure 4.1 Measuring DC Resistance on an Unpopulated SLC Loop
!
!
!
Notify fire, central station and/or building personnel when you finish testing the system.

4.2 Battery Checks and Maintenance

CAUTION:
The maximum current rating of the batteries is 15 A. The battery connection is fused. If the fuse needs to be replaced, it must be replaced with a 20A blade fuse.
Maintenance-free sealed lead-acid batteries used in the system do not require the addition of water or electrolyte. These batteries are charged and maintained in a fully charged state by the main power supply's float charger during normal system operation. A discharged battery typically reaches the float voltage of 27.3 V DC within 24 hours.
Follow the manufacturer recommendations for battery replacement intervals. Minimal replacement battery capacity appears on the control panel marking label. Immediately replace a leaking or damaged battery. You can get replacement batteries from the manufacturer.
WARNING: BATTERIES CONTAIN SULFURIC ACID,
WHICH CAN CAUSE SEVERE BURNS TO THE SKIN AND EYES AND DAMAGE TO FABRICS.
If a battery leaks and contact is made with the Sulfuric Acid, immediately flush skin and/or eyes with water for at least 15 minutes. Water and household baking soda provides a good neutralizing solution for Sulfuric Acid.
If Sulfuric Acid gets into eyes, seek immediate medical attention.
Ensure proper handling of the battery to prevent short circuits.
Take care to avoid accidental shorting of the leads from uninsulated work benches, tools, bracelets, rings, and coins.
CAUTION:
SHORTING THE BATTERY LEADS CAN DAMAGE THE BATTERY, EQUIPMENT, AND COULD CAUSE INJURY TO PERSONNEL.
CAUTION:
RISK OF EXPLOSION IF BATTERY IS REPLACED WITH INCORRECT TYPE. DISPOSE OF BATTERY ACCORDING TO MANUFACTURER’S INSTRUCTIONS.
Battery Checks and Maintenance Testing the System
PSI STATUS
PSU VOLTAGE: 27.3V BATTERY VOLTAGE: 24.2V
PSI CONTROL STATUS: PANEL RUNNING FROM PSI SUPPLY
START BATTERY TEST BACK

4.2.1 PSI Status

Pressing the PSI STATUS button will display the status of the local power supply. This informa­tion includes the supply voltage, battery voltage, PSI output voltage, which supply source the panel is running from (PSI or battery), whether a battery test is in progress and whether or not the battery test and charger have been disabled.
Figure 4.2 PSI Status Screen
AFP-3030 Installation Manual — P/N DOC-01-037:B 25/08/2016 32

Appendix A: Electrical Specifications

A.1 Operating Power

DC Power The control panel requires connection to NPS-5CHS or NPS-11CHS, which is a
27.3 V DC regulated, power-limited power supply, that can supply 0.1 amps continuous for the
CPU without the display (0.3 amps for CPU with the display).

A.2 SLC Loops

Listed below are specifications for a Signalling Line Circuit loop. Refer to the SLC Wiring Manual for more detailed specifications and specific device listings:
Item Value
Voltage 24 V DC nominal, 27.6 V DC maximum Maximum length The maximum wiring distance of an SLC using 12 AWG (3.25 mm
Maximum current 130 mA: LCM-320
Maximum resistance 50 ohms (supervised and power-limited). For additional notes on SLC
2
) twisted­pair wire is 3810 m. Note: Refer to Appendix A.5 “Wire Requirements” for limitations.
100 mA: LEM-320 400 mA max*: Single SLC loop; for battery calculations use 200 mA
*Max short circuit; circuit will shut down until short circuit condition is corrected.
resistance values, see Section 4.1 “Operational Checks”.

A.3 Notification Appliance Circuits

The power supply provides Notification Appliance Circuits. The maximum current rating for each NAC output is 1.0 A. Refer to the Device Compatibility Document for compatible devices and notification appliances.

A.4 Networks

Network Card Communication Para meters
NCM-W Supports twisted-pair wire medium, data is regenerated at each node. 312.5K
NCM-F Supports fibre-optic medium (62.5/125 or 50/125 micrometres – multimode).
HS-NCM High-speed data communications (12 Mb wire, 100 Mb MF/SF fibre). Multi-
baud transmission rate.
Single mode available. 312.5K baud transmission rate. Data is regenerated at each node.
mode fibre optic (MF), single-mode fibre optic (SF), wire (W), or a combination of W/MF/SF communications path.

A.5 Wire Requirements

Each type of circuit within the Fire Alarm Control System requires use of a specific wire type to ensure proper circuit operation. The wire gauge of a particular circuit depends on the length of that circuit and the current traveling through it. Use the table below to determine the specific wiring requirements for each circuit.
Use twisted-pair shielded wire for any non-SLC-loop wiring entering or exiting the cabinet that is not enclosed in conduit. Use twisted-pair unshielded wiring for SLC-loop wiring.
NOTE: If running an SLC in conduit with Notification Appliance Circuits, you can reduce problems by exclusively using electronic sounders (such as the MA/SS-24 Series) instead of more electronically noisy notification appliances (such as electromechanical bells or horns).
Power Supply Calculations Electrical Specifications
Circuit Type Circuit Function Wire Requirements
SLC (power limited)
EIA-485 ACS Connection (power limited)
EIA-485 RDP Connection (power limited)
EIA-232 (power limited)
IDC Initiating Device Circuit
NAC Notification Appliance Circuit
Releasing Module
Connects to intelligent and addressable modules.
or Twisted-shielded pair.
or Untwisted, unshielded wire, in conduit or
Connects to ACS devices such as annunciators and UDACT/UDACT-2
Connects to RDP devices
Connects to Printers or PC.
FMM-1, FMM-101 (power limited)
FCM-1 (power limited)
FCM-1-REL
Twisted-unshielded pair, 12 to 18 AWG (3.25 to 0.75mm per length of Closed (Style 6 & 7) loops. 50 ohms per branch maximum for Open (Style 4) loops.
NOTE:
• Shields must be isolated from ground.
• Shields should be broken at each device.
outside of conduit.
NOTE: Maximum total capacitance for all SLC wiring (both between conductors and from any conductor to ground) should not exceed 0.5 microfarads
Twisted-shielded pair with a characteristic impedance of 120 ohms. 18 AWG (0.75mm
Twisted-shielded pair with a characteristic impedance of 120 ohms. 18 AWG (0.75mm
Twisted-shielded pair . 18 A WG (0.75mm minimum.
12-18 AWG Maximum circuit resistance is 20 ohms.
12-18 AWG. MPS-24A: At alarm current level, no more than a 1.2 V drop at the end of the circuit, or sized to provide the minimum rated operating voltage of the appliances used.
12-18 AWG. 5 ohms maximum per circuit for class A or B, or sized to provide the minimum rated operating voltage of the appliances used.
2
2
) minimum.
2
) minimum.
). 50 ohms, maximum
Distance
(feet/meters)
3,810 m 2,896 m 1,829 m 1,128 m
1524 m
1,128 m
1524 m
1,128 m
1829 m (max) 16 AWG (1.31mm
1219 m (max) 16 AWG (1.31 mm
2
)
15.24 m without modem
To meet 1.2 V drop, or sized to provide the minimum rated operating voltage of the appliances used.
To meet 5 ohms maximum circuit resistance, or sized to provide the minimum rated operating voltage of the appliances used.
Typical Wire Type
12 AWG (3.31 mm 14 AWG (2.08 mm 16 AWG (1.31 mm 18 AWG (0.82 mm
12 to 16 AWG (3.31
2
mm
to 1.31 mm2)
18 AWG (0.82 mm
12 to 16 AWG (3.31
2
mm
to 1.31 mm2)
18 AWG (0.82 mm
16 AWG (1.31 mm2)
12 to 18 AWG (3.31 to 0.82 mm
12 to 18 AWG (3.31 to 0.82 mm
12 to 18 AWG (3.31 to 0.82 mm
2
)
2
)
2
)
2
)
2
)
2
)
2
)
2
)
2
)
2
)
2
)
24 VDC Power Runs (power­limited)
To TM-4 Transmitter, Annunciator and FCM-1 modules
12-18 AWG. Size wire so that no more than 1.2 V drop across wire run from supply source to end of any branch.
To meet 1.2 volt drop 12 to 18 AWG
(3.31 to 0.82 mm
Table A.1 Wire Requirements
Relay Output circuits are “Common” 30 V DC, 2 A (see Section 3.6 “Form-C Relays on the CPU”).

A.6 Power Supply Calculations

Calculations must be done to determine standby and alarm DC current loads. Ampere-hour requirements must be calculated as well to determine battery size.
The NPS power supply provides filtered 24 V DC (nominal) power that may be used for operating external devices. The power for operating external devices is limited. Use Table A.2 to determine if external loading is within the capabilities of the power supply.

A.6.1 Calculating the System Current Draws

The NPS must be able to power all devices in the panel in the quiescent condition as well as charge the batteries. The NPS does not need to provide enough current to run the panel when in the alarm condition, if the panel needs more current than the NPS can supply during alarm, the extra current
AFP-3030 Installation Manual — P/N DOC-01-037:B 25/08/2016 34
2
)
Electrical Specifications Power Supply Calculations
will be drawn from the batteries. Use column 1 in Table A.2 to calculate the Quiescent Load on the power supply . The alarm or quiescent current must not exceed 15A regardless of which NPS power supply is connected. Use column 2 in Table A.2 to calculate the additional current needed during alarm conditions.

A.6.2 How to Use the Calculating Tables

In the following section: The term “secondary” refers to the system’s backup batteries The term “primary” is reserved for the NPS’s primary source of power, 240 VAC 50 Hz The term “standby” refers to the output current required when no fire alarm is present. The term “alarm” refers to the output current required when a fire alarm is present.
The Primary Quiescent Current and Fire Alarm Current columns are DC current calculations. Use these calculations to confirm that the NPS can provide enough current to support the system during Primary Quiescent and Fire Alarm conditions.
Quantities List the number of devices powered by the MAIN 24 V Main Output on the NPS and any auxiliary 24 V Outputs. Use these quantities to calculate total current draw of each set of devices in calculation columns 1, 2, and 3.
Calculation Column 1 (Primary, Quiescent Current in amps) Add the contents of Column 1 to get the current drawn from the NPS during a quiescent condition, with AC power applied.
Calculation Column 2 (Primary, Fire Alarm Current in amps) Column 2 lets the system designer determine the current load that the NPS must support during a fire alarm.
Typically, a system should contain capacity to activate all output circuits and relays, and support fire alarms on no less than 10% of Initiating Device Circuits.
If the system provides power for Notification Appliance Circuits, refer to the Device Compatibility Document for 24 V DC notification appliances.
NOTE: A current calculation tool can also be found in the Download Centre on the Notifier website: http://www.notifier.com.au/
Power Supply Calculations Electrical Specifications

A.6.3 Calculation for Main Supply Current

Calculation Column 1
Quantities
AFP-3030/NCA-2 with display AFP-3030/NCA-2 without display LCM-320 (refer to Doc. 51330,52544) LEM-320 (refer to Doc. 51330,52544)
SLC Loop* NCM-W, NCM-F HS-NCM-W/MF/MFSF/WMF/WSF
DVC components (Refer to DVC manual) DVC-RPU components (Refer to DVC-RPU
manual) DA-30/DA-60/DA-120 (Refer to DOC-01-
004) FSD-751RPL (Duct Detector) [ ] x [0.025]= x [0.087]= FSA-8000/FSA-20000 (FAAST Detector) [ ] x [0.465]= x [0.493]= ACM-24AT ACM-48A AEM-24AT AEM-48A Maximum number of LEDs illuminated on these annunciators during quiescent conditions: SCS-8A (refer to Doc. 15712) [ ] x [ ]= x [ ]= LCD2-80 ACM-8RA LDM (refer to Doc. 15885) ACM-ZM AEM-ZM8 ARM (Refer to DOC-01-005) ARE Interface FZM-1, MMX-2 [ ]
Four-Wire Smoke Detectors
Compatible Devices not listed above Sub-totals Primary,
Battery [ ]
[ ] [ ]
[ ] [ ] [ ] [ ] [ ] [ ] [ ]
[ ] [ ] x [ ]= x [ ]=
[ ] [ ] [ ] [ ]
[ ] x [0.0054]=
[ ] [ ] [ ] [ ] [ ] [ ] [ ]
[ ] [ ] [ ] [ ]
Primary, Quiescent Current (amps) x [0.205]= x [0.140]= x [0.130]= x [0.100]= x [0.200]= x [0.200]= x [0.110]= x [0.400]= x [ ]= x [ ]=
x [ ]= x [ ]=
x [0.016]= x [0.016]= x [0.002]= x [0.002]=
x [0.100]= x [ 0.020]= x [ ]= x [0.020]= x [0.005]= x [ ]= x [0.020]= x [0.0094]= x [0.090]= x [ ]= x [ ]= x [ ]= x [ ]=
Quiescent: x [AH‡] x [0.1]=
Calculation Column 2 Primary, Fire Alarm Current (amps) x [0.225]= x [0.150]= x [0.130]= x [0.100]=
x [0.110]= x [0.400]= x [ ]= x [ ]=
x [0.070]= x [0.070]= x [0.056]= x [0.056]=
x [0.100]= x [0.035]= x [ ]= x [0.025]= x [0.025]= x [ ]= x [0.035]=
x [ ]= x [ ]= x [ ]= x [ ]= Primary, alarm:
Sum each column for totals Primary,
Quiescent:
Primary, alarm:
Table A.2 System Draw Current Calculations
* Value represents an SLC’s maximum current draw. Refer to device datasheets for individual current
draws. Total device current cannot exceed 200 mA. † Refer to manual and/or Device Compatibility Document. ‡ V alue represents battery size in amp hours. Refer to Appendix A.7, “Calculating the Battery Requirements”, on page 38
to determine battery size.
AFP-3030 Installation Manual — P/N DOC-01-037:B 25/08/2016 36
Electrical Specifications Power Supply Calculations
A.6.4 Calculating the Maximum Secondary Power Quiescent
Current Draw
Use the table below to determine the maximum current requirements of the secondary power source during quiescent conditions. The result obtained is the amount of current that the batteries must be able to supply to the fire alarm system. Use the result in Table A.3 to determine the size of the batteries needed for the fire alarm system.
Results taken from the table below assume that, while in a quiescent condition, batteries must feed the NPS (and any additional supplies) with the maximum rated power each supply can provide.
Alarm
Device Quantity
Current (in amps)
Alarm Current, from Table A.2, col 3 = Additional Load [ ] X =
Sum Column for Secondary Quiescent Load =
Total Current/Type
Table A.3 Maximum Secondary Power Quiescent Current Draw
A.6.5 Calculating the Maximum Secondary Power Fire Alarm
Current Draw
Use the table below to determine the maximum current requirements of the secondary power source during fire alarm conditions. The result obtained is the amount of current that the batteries must be able to supply to the fire alarm system. Use the result in Table A.4 to determine the size of the batteries needed for the fire alarm system.
Results taken from the table below assume that, while in a fire alarm condition, batteries must feed the NPS (and any additional supplies) with the maximum rated power each supply can provide.
Alarm
Device Quantity
Current (in amps)
Alarm Current, from Table A.2, col 2 = Additional Load [ ] X =
Sum Column for Secondary Fire Alarm Load =
Total Current/Type
Table A.4 Maximum Secondary Power Fire Alarm Current Draw
Calculating the Battery Requirements Electrical Specifications

A.7 Calculating the Battery Requirements

A.7.1 Battery Power Equations

For a remotely connected system:
Ah = (I
x 24) + I
Q
A
For a non-remotely-connected system:
Ah = (I
x 72) + I
Q
A
Where:
= The minimum rated battery capacity
Ah
= the non-alarm current from that battery (charger off) in amps
I
Q
= the alarm current drawn from the b attery (charger off) in amps
I
A
NOTE: A times 2 de-rating factor has been applied to the Alarm Capacity to compensate for battery conversion inefficiencies.

A.7.2 Recommended Standby Battery Sizes

When selecting and installing batteries, ensure that there is enough available current to charge the batteries while in quiescent mode. A list of available batteries and the minimum charging current required is shown in Table A.5, “Recommended Battery Specifications”.
NOTE: Connect only sealed lead acid batteries.
Battery Description Voltage Capacity (Ah)
Olympic, 12 AH 12 V Battery ­BATT/12 (CJ12-12)
Olympic, 18 AH 12 V Battery ­BATT/18 (CJ12-18)
Olympic, 26 AH 12 V Battery ­BATT/26 (CJ12-26)
Olympic, 33 AH 12 V Battery ­BATT/33 (CJ12-33)
Olympic 40 AH 12 V Battery ­BATT/40 (CJ12-40)
Olympic 85 AH 12 V Battery ­BATT/85 (CJ12-85)
12 12 0.55 2
12 18 0.83 2
12 26 1.19 2
12 33 1.51 2
12 40 1.83 2
12 85 3.89 2
Table A.5 Recommended Battery Specifications
Minimum Charging Current (A)
Quantity
AFP-3030 Installation Manual — P/N DOC-01-037:B 25/08/2016 38

Appendix B: Cabinet and Mounting Information

Figure B.1 CAB650 Mounting Details and Dimensions
NOTE: All dimensions in Millimeters

B.1 CAB650 Mounting Details

CAB900 Mounting Details Cabinet and Mounting Information
Figure B.2 CAB900 Mounting Details and Dimensions
NOTE: All dimensions in Millimeters

B.2 CAB900 Mounting Details

AFP-3030 Installation Manual — P/N DOC-01-037:B 25/08/2016 40
Cabinet and Mounting Information CAB 18U Cabinet Mounting Dimensions
Figure B.3 CAB 18U Mounting Details and Dimensions
NOTE: All dimensions in Millimeters

B.3 CAB 18U Cabinet Mounting Dimensions

CAB 28U Cabinet Mounting Dimensions Cabinet and Mounting Information
Figure B.4 CAB 28U Cabinet Mounting Details and Dimensions
NOTE: All dimensions in Millimeters
1330.0
376.0
70.0
380.0
550.0
343.0
1260.0
1210.0
175.1
8 x
50.0
Laser cut
Knockout
4 x
10.0
2 x
25.0
Laser cut
Knockout
610.0
70.0
380.0
540.0
35.0
115.0
16 x 50.0 Lasercut Knockout 8 on top, 8 on bottom
Mounting
Holes

B.4 CAB 28U Cabinet Mounting Dimensions

AFP-3030 Installation Manual — P/N DOC-01-037:B 25/08/2016 42
Cabinet and Mounting Information CAB 40U Cabinet Mounting Dimensions
Figure B.5 CAB 40U Cabinet Mounting Details and Dimensions
NOTE: All dimensions in Millimeters
70.0
380.0
343.0
550.0
1795.0
1745.0
707.5
1865.0
376.0
4 x
10.0
8 x 50.0
Laser cut
Knockout
2 x
25.0
Laser cut
Knockout
610.0
70.0
380.0
540.0
35.0
105.0
16 x 50.0 Lasercut Knockout 8 on top, 8 on bottom

B.5 CAB 40U Cabinet Mounting Dimensions

Laying Out Equipment in Cabinet and Chassis Cabinet and Mounting Information
!
Figure B.6 Chassis CHS-3L
1
2
3
Three positions on chassis CHS-3L
CHS-3L-NEW.wmf
Figure B.7 Chassis CHS-4L
Chs-4L.jpg
1
2
3
Four positions on chassis CHS-3L
4

B.6 Laying Out Equipment in Cabinet and Chassis

The AFP-3030 allows for flexible system design. It mounts in a CAB650 or CAB900 backbox using the CHS-3L or in a U-Series backbox using the CHS-4L. Follow these gui deli nes when deciding where to locate equipment in the backbox. The number of layers that can be mounted in each position of the chassis depends on the module size.
CAUTION:
IT IS CRITICAL THAT ALL MOUNTING HOLES OF THE FIRE ALARM CONTROL PANEL ARE SECURED WITH A SCREW OR STAND-OFF TO INSURE CONTINUITY OF EARTH GROUND.

CHS-3L

The CPU and power supply assembly mount in the top row of the CAB650 or CAB900 cabinet. The AFP-3030 keypad is door mounted in front of the CPU and power supply assembly . The CHS-3L Chassis is mounted below the CPU and power supply assembly.
In the CAB900, a second CHS-3L Chassis can be installed below the first for additional equipment.

CHS-4L

The CPU and power supply assembly mount in the top row of the U-Series cabinet. The AFP-3030 keypad is door mounted in front of the CPU and power supply assembly. The CHS-4L Chassis is mounted below the CPU and power supply assembly.
In the 28U and 40U cabinets, additional CHS-4L Chassis can be installed below the first for additional equipment.
AFP-3030 Installation Manual — P/N DOC-01-037:B 25/08/2016 44
Cabinet and Mounting Information Installing Replacement Equipment
!
Figure B.8 Removing the fire panel keypad
Ribbon cable connecting the keypad to the fire panel CPU.
Cabinet inner door
The AFP-3030 keypad
Door studs
Flanged nuts

B.7 Installing Replacement Equipment

B.7.1 Installing a replacement keypad

The keypad enables the user to operate and program the fire panel.
CAUTION: POWER DOWN THE FIRE PANEL BEFORE FITTING THE KEYPAD.
1. Open the cabinet inner door and unplug the ribbon cable connecting the keypad to the CPU board.
2. From the cabinet inner door, remove: a. The flanged nuts from the inner door studs. b. The keypad from the studs as per Figure B.8.
3. Replace keypad on door studs.
4. Replace the Flanged nuts, fastening the keypad to the door.

Appendix C: Schematics

The table below lists the relevant schematics found in this appendix.
Title Drawing Number
ACM-ZM Schematic DWG0919 SGD Schematic DWG0937
Table C.1
AFP-3030 Installation Manual — P/N DOC-01-037:B 25/08/2016 46

Index

A
Alarm Relays see Relays 18
B
Backboxes 4, 8 Battery
Battery Calculations Battery Checks Memory-Backup Battery
BMP-1
44
33, 35, 3738
31
11
C
Cabinets, also see Backboxes 4, 44 Chassis
CHS-3L Circuit Board, also see CPU Control Panel Circuit Board, also see CPU CPU
6
Drawing
Installation Steps
44
6
6
6
45
D
Doors 4, 8 Dress Panels DS-DB DVC-RPU
4
36
36
E
Electrical Connections 22 Electrical Specifications
33
H
HS-NCM-W/F
Mounting
14
I
Indicating Device Circuits, also see NACs 33 Indicating Unit Installation
Checklist
Preparation
4
10
10
L
LCM-320/LEM-320, see SLC Loop Modules
M
Main Power Supply 8 Maintenance Manual Pull Station Memory-Backup Battery
Insulator
31
27
11
N
NACs
Specifications
NCM-W/F
Mounting Networking Notification Appliance Circuits, also see NACs
33
14
14
O
Operating Power 33 Operational Checks Output Relays, also see Form-C Relays
Specifications
30
18
P
PC Connection 29 Power
AC Power Checklist
Auxiliary Power
Installation Steps
Locally Powered Devices
Main Power Supply
Power Supply Calculations
PSU Switch
Remote Device Powered By Local Device
Specifications Printers
27
Installation
PRN Printer Settings
24
25
24
25
22
23
8
33, 35, 3738
22
27
R
Related Documentation 1
S
SGD
Installing
Schematic Signalling Line Circuit, also see SLC SLC Loop Modules
SLC Loop Number SLC, also see SLC Wiring Manual
Specifications Specifications
Environmental Specifications
Supply Ratings Supervisory Relays, also see Relays Supplemental Documentation System
Features
Limitations
Options
System Description System Current Draws
18
46
27
15
33
33
4
4
18
1
3
3
3
3
33, 35, 3738
33
23
Index T–W
T
Testing 30 Trouble Relays, also see Relays
18
U
Upload/Download Software 29
V
VeriFire® Tools 29
W
Wiring, also see SLC 27
Wire Requirements
33
AFP-3030 Installation Manual — P/N DOC-01-037:B 25/08/2016 50
Notes
Notes
AFP-3030 Installation Manual — P/N DOC-01-037:B 25/08/2016 52
New South Wales (Head Office) 9 Columbia Way Baulkham Hills NSW 2153
New Zealand 264 Mt Eden Rd Mt Eden 1064
ph +61 (0)2 9899-4155 fax +61 (0)2 9899-4156
ph +64 (0)9 623-5050 fax +64 (0)9 623 5060
Loading...