Notifier AFP-200 Installation Manual

Analog Fire Panel
AFP-200
Installation Manual
Document 15511 10/14/2002 Rev:
H2
15511:H2 ECN 02-436
2 AFP-200 PN 15511:H2 10/14/2002
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system—typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control with remote notifica­tion capability—can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detec­tors be located throughout a protected premise following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommen­dations contained in the Guide for Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. A study by the Federal Emergency Man­agement Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are designed to pro­vide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a first-floor or basement fire.
Particles of combustion or “smoke” from a developing fire may not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow.
• Smoke particles may become “cold,” stratify, and not reach the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air outlets.
• Smoke particles may be drawn into air returns before reaching the detector.
The amount of “smoke” present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ion­izing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of flammable materials, etc.).
Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predeter­mined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire pro­tection specialist. Heat detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the sys­tem for the connection of alarm transmission wiring, communi­cations, signaling, and/or power. If detectors are not so located, a developing fire may damage the alarm system, crip­pling its ability to report a fire.
Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol or medica­tion. Please note that:
• Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property owner's responsi­bility to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.
Equipment used in the system may not be technically com­patible with the control. It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against tele­phone line failure, backup radio transmission systems are rec­ommended.
The most common cause of fire alarm malfunction is inade­quate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA stan­dards. At a minimum, the requirements of Chapter 7 of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent mainte­nance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled monthly or as required by National and/or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records of all inspections should be kept.
Precau-L-4-2002.fm
AFP-200 PN 15511:H2 10/14/2002 3
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associ­ated equipment may be damaged by removing and/or insert­ing cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software Changes. To ensure proper system operation, this product
must be tested in accordance with NFPA 72 Chapter 7 after any programming operation or change in site-specific soft­ware. Reacceptance testing is required after any change, addition or deletion of system components, or after any modifi­cation, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software func­tions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvert­ently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation ver­ified.
This system meets NFPA requirements for operation at 0-49° C/32-120° F and at a relative humidity of 85% RH - 93% per ULC - (non-condensing) at 30° C/86° F. However, the useful life of the system's standby batteries and the electronic com­ponents may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and all peripherals be installed in an environment with a nominal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and indi­cating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to light­ning-induced transients. Although no system is completely immune from lightning transients and interferences, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased sus­ceptibility to nearby lightning strikes. Consult with the Techni­cal Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifi­cations, verify that they will not interfere with battery, trans­former, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced ter­minal contact pressure and difficulty with screw terminal removal.
Though designed to last many years, system components can fail at any time. This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static-suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and pro­gramming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation by authorized personnel.
Precau-L-4-2002.fm
WARNING: This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause interference to radio communications. It has been tested and found to comply with the limits for class A com­puting device pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at his own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits radio­electriques depassant les limites applicables aux appar­eils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.
FCC Warning
Acclimate Plus™, HARSH™, NOTI•FIRE•NET™, ONYX™, and Ver iF ire™ are trademarks, and FlashScan® and VIEW® are registered trademarks of
NOTIFIER. NION™ and UniNet™ are trademarks of NIS. NIS™ and Notifier Integrated Systems™ are trademarks and NOTIFIER® is a registered trademark of Fire•Lite Alarms, Inc. Echelon® is a registered trademark and LonWorks™ is a trademark of Echelon Corporation. ARCNET® is a registered trademark of Datapoint Corporation. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. LEXAN® is a registered trademark of GE Plastics, a subsidiary of General Electric Company.
4 AFP-200 PN 15511:H2 10/14/2002
About This Manual..................................................................................................10
Section 1 System Overview .................................................................................. 14
1.1 General Description.............................................................................................................................. 14
1.2 Features ............................................................................................................................................... 14
1.3 Components........................................................................................................................................... 15
1.3.1 Membrane Switch Panel ..................................................................................................................................15
1.3.2 Panel Sounder .................................................................................................................................................. 16
1.3.3 Output Circuits (TB2) ......................................................................................................................................16
1.3.4 Relays (TB3) .................................................................................................................................................... 16
1.4 Main Assemblies ................................................................................................................................... 17
1.4.1 CPU Board ....................................................................................................................................................... 17
1.4.2 Cabinet .............................................................................................................................................................18
1.4.3 LCD Display .................................................................................................................................................... 18
1.4.4 Membrane Switch Panel ..................................................................................................................................18
1.4.5 Transformer Assembly ....................................................................................................................................18
1.4.6 Batteries ........................................................................................................................................................... 18
1.5 Optional Devices & Option Modules .................................................................................................. 19
1.5.1 Digital Communicator ..................................................................................................................................... 19
1.5.2 UDACT ............................................................................................................................................................ 19
1.5.3 Network Interface Board - NIB-96 ..................................................................................................................19
1.5.4 Field Charger/Power Supply - FCPS-24 ..........................................................................................................20
1.5.5 Battery Charger - CHG-120 .............................................................................................................................20
1.5.6 Liquid Crystal Display - LCD-80 .................................................................................................................... 20
1.5.7 Option Module: Transmitter Module - 4XTM ................................................................................................ 20
1.5.8 Option Module: Relay/Transmitter Module - RTM-8 ..................................................................................... 20
1.5.9 Meter Module ..................................................................................................................................................20
1.5.10 Trim Ring ....................................................................................................................................................... 21
1.5.11 Battery Box .................................................................................................................................................... 21
1.5.12 Dress Panel .................................................................................................................................................... 21
1.5.13 Expansion Power Supplies (AVPS-24 and APS-6R) .................................................................................... 21
1.5.14 Marine Cabinet .............................................................................................................................................. 21
1.6 Intelligent Detectors.............................................................................................................................. 21
1.7 Addressable Modules............................................................................................................................ 22
1.7.1 Overview ..........................................................................................................................................................22
1.7.2 Module Descriptions ........................................................................................................................................22
1.8 End-of-Line Devices.............................................................................................................................. 24
1.8.1 Overview ..........................................................................................................................................................24
1.9 Annunciation Modules ......................................................................................................................... 24
1.9.1 Overview ..........................................................................................................................................................24
1.9.2 Annunciator Control Module-8R (ACM-8R) .................................................................................................. 24
1.9.3 LDM Series Lamp Driver Modules ................................................................................................................. 24
1.9.4 Annunciator Control System (ACS) ................................................................................................................25
1.9.5 Annunciator Fixed Modules ............................................................................................................................ 25
1.10 EIA-232 Peripheral Devices (TB4).................................................................................................... 26
1.10.1 Overview ........................................................................................................................................................ 26
1.10.2 PRN Remote Printer ...................................................................................................................................... 26
1.10.3 Keltron Remote Printer (Model VS4095) ...................................................................................................... 26
1.10.4 CRT-2 Display Terminal ...............................................................................................................................26
1.11 Specifications....................................................................................................................................... 27
1.11.1 Primary AC Power (TB7) .............................................................................................................................. 27
1.11.2 Battery (lead-acid only) .................................................................................................................................27
1.11.3 Signaling Line Circuit (TB6) ......................................................................................................................... 27
1.11.4 Notification Appliance and Releasing Circuits (TB2) ...................................................................................27
1.11.5 Relays (TB3) .................................................................................................................................................. 28
1.11.6 24 VDC Power (TB1) .................................................................................................................................... 28
1.12 Cabinet Dimensions ............................................................................................................................ 28
1.12.1 Surface Mount with a BB-17 Battery Box ..................................................................................................... 28
AFP-200 PN 15511:H2 10/14/2002 5
1.12.2 Semi-flush Mount .......................................................................................................................................... 29
Section 2 Installation ............................................................................................. 30
2.1 Preparing for Installation..................................................................................................................... 30
2.1.1 Unpacking the System ..................................................................................................................................... 30
2.1.2 Installation Notes ............................................................................................................................................. 30
2.1.3 Standards and Codes ........................................................................................................................................30
2.2 Installation Checklist............................................................................................................................ 31
2.3 Backbox Mounting................................................................................................................................ 32
2.4 AC and DC Power Connections .......................................................................................................... 33
2.4.1 AC Power Connections (TB7) .........................................................................................................................33
2.4.2 Battery Power Connection (J3) ........................................................................................................................ 34
2.4.3 Expansion Power Supplies – AVPS-24 or APS-6R (Optional) .......................................................................34
2.5 DC Output Power Connections (TB1) ................................................................................................ 35
2.6 Output Circuits (TB2) .......................................................................................................................... 35
2.6.1 Notification Appliance Circuits ....................................................................................................................... 35
2.7 Standard Relays (TB3) ......................................................................................................................... 36
2.8 EIA-232 Devices – Remote Printers and CRTs (TB4) ....................................................................... 37
2.8.1 Overview ..........................................................................................................................................................37
2.8.2 Printer Configuration ....................................................................................................................................... 37
2.8.3 Installation .......................................................................................................................................................37
2.8.4 Keltron Printer ................................................................................................................................................. 38
2.8.5 CRT Connections .............................................................................................................................................39
2.9 Wiring a Signaling Line Circuit (SLC)............................................................................................... 41
2.9.1 Overview of SLC Wiring .................................................................................................................................41
2.9.2 SLC Devices ....................................................................................................................................................42
2.9.3 Control Panel Capacity .................................................................................................................................... 42
2.9.4 SLC Performance ............................................................................................................................................. 43
2.9.5 SLC Shield Termination .................................................................................................................................. 43
2.9.6 Setting an SLC Address for a Module ............................................................................................................. 44
2.9.7 Wire Requirements for a Two-wire SLC ......................................................................................................... 45
2.9.8 Wire Requirements for a Four-wire SLC ........................................................................................................ 46
2.9.9 Wiring an Isolator Module (ISO-X) ................................................................................................................49
2.9.10 Wiring an IDC with Monitor Modules ..........................................................................................................50
2.9.11 Wiring a Notification Appliance Circuit (NAC) or Control Circuit ..............................................................56
2.9.12 SLC Wiring with Control Modules ............................................................................................................... 57
2.9.13 SLC Wiring with an Intelligent Detector .......................................................................................................59
2.9.14 SLC Wiring with an NBG-12LX Addressable Manual Pull Station .............................................................60
2.10 Option Module Installation................................................................................................................ 61
2.10.1 Overview ........................................................................................................................................................ 61
2.10.2 Installing a 4XTM Module ............................................................................................................................62
2.10.3 Installing an RTM-8 Module ......................................................................................................................... 63
Section 3 Programming......................................................................................... 65
3.1 Overview ................................................................................................................................................ 65
3.1.1 Programming Methods ....................................................................................................................................65
3.1.2 In This Section ................................................................................................................................................. 65
3.2 Getting Started...................................................................................................................................... 66
3.2.1 How to Access Programming Options ............................................................................................................. 66
3.2.2 Programming Passwords .................................................................................................................................. 66
3.2.3 How to Use the Programming Keypad ...........................................................................................................67
3.2.4 Programming Shortcuts ................................................................................................................................... 68
3.2.5 Upload and Download ..................................................................................................................................... 68
3.2.6 Key Programming Terms ................................................................................................................................. 68
3.2.7 How to Avoid Programming Errors ................................................................................................................. 69
3.3 Program Change Options..................................................................................................................... 70
3.3.1 Overview ..........................................................................................................................................................70
3.4 How to Enter Program Change........................................................................................................... 71
3.4.1 Program Change Map ...................................................................................................................................... 72
6 AFP-200 PN 15511:H2 10/14/2002
3.4.2 How to Clear a Program from Memory (0=clr) ..............................................................................................73
3.4.3 How to Autoprogram the Control Panel (1=auto) ........................................................................................... 73
3.4.4 How to Edit or Delete a Point (2=point) .......................................................................................................... 78
3.4.5 How to Change a Programming Password (3=passwd) ...................................................................................85
3.4.6 How to Change a System Message (4=message) ............................................................................................ 86
3.4.7 How to Change a Zone Label (5=zones) ......................................................................................................... 86
3.4.8 How to Edit a Special Zone (6=spl zones) ......................................................................................................87
3.4.9 How to Edit System Functions (7=sys) ........................................................................................................... 89
3.4.10 How to Check the Program (8=check) .......................................................................................................... 92
3.5 Status Change Options ......................................................................................................................... 92
3.5.1 Overview ..........................................................................................................................................................92
3.5.2 Entering Status Change .................................................................................................................................... 93
3.5.3 Status Change Programming Map ................................................................................................................... 94
3.5.4 How to Disable or Enable a Point (1=disable) ................................................................................................95
3.5.5 How to Set Detector Selections (2=sens/comp) ..............................................................................................96
3.5.6 How to Clear Alarm Verification Counters (3=clr ver) ...................................................................................97
3.5.7 How to Clear the History Buffer (4=clr hist) ................................................................................................... 98
3.5.8 How to Set the System Time and Date (5=time) .............................................................................................98
3.5.9 How to do a Walk Test (6=walk test) ..............................................................................................................99
Section 4 Operation............................................................................................. 101
4.1 Overview .............................................................................................................................................. 101
4.2 The Membrane Panel ......................................................................................................................... 102
4.2.1 Overview ........................................................................................................................................................ 102
4.2.2 How to Use the Programming Keypad .......................................................................................................... 102
4.2.3 How to Use the Enter Key and Cursor Keys ................................................................................................. 103
4.2.4 How to Use the Operator Keys ...................................................................................................................... 103
4.2.5 How to Read System Status LED Indicators .................................................................................................105
4.3 How to Operate the Control Panel.................................................................................................... 106
4.3.1 How to Operate the Panel in Normal Operation ............................................................................................ 107
4.3.2 How to Operate a Panel with a Trouble Condition ........................................................................................ 107
4.3.3 How to Operate a Panel with a Trouble Monitor Point ................................................................................. 109
4.3.4 How to Operate a Panel with a Fire Alarm .................................................................................................... 109
4.3.5 How to Operate a Panel with a Supervisory Condition ................................................................................. 110
4.3.6 How to Operate a Panel with a Non-Alarm Condition ..................................................................................111
4.3.7 How to Operate the Panel with an Output Circuit Trouble ........................................................................... 111
4.3.8 How the Control Panel Indicates a Panel Circuit Trouble ............................................................................. 112
4.4 Control-By-Event Operation .............................................................................................................. 112
4.5 Releasing Functions ............................................................................................................................. 113
4.5.1 Overview ........................................................................................................................................................ 113
4.5.2 How to Select Cross Zone Options ................................................................................................................113
4.6 Releasing Functions ............................................................................................................................. 114
4.7 Intelligent Detector Functions ............................................................................................................ 115
4.7.1 Summary of Detector Functions .................................................................................................................... 115
4.7.2 Pre-Alarm Operation/Advanced Warning Addressable Combustion Sensing (AWACS™) ........................ 115
4.8 Time Functions..................................................................................................................................... 116
4.8.1 Overview ........................................................................................................................................................ 116
4.8.2 Coding Operation (NAC only) ...................................................................................................................... 117
4.8.3 Presignal/PAS Operation ...............................................................................................................................117
4.8.4 Special System Timers ................................................................................................................................... 118
4.8.5 Waterflow Circuits Operation ........................................................................................................................ 118
4.8.6 Disable/Enable Operation .............................................................................................................................. 118
4.8.7 Style 6 Operation ........................................................................................................................................... 118
4.9 Read Status........................................................................................................................................... 118
4.9.1 Overview ........................................................................................................................................................ 118
4.9.2 How to Enter Read Status ..............................................................................................................................119
4.9.3 Read Status Options .......................................................................................................................................119
4.9.4 Read Point ...................................................................................................................................................... 119
4.9.5 Using the History Buffer ................................................................................................................................124
AFP-200 PN 15511:H2 10/14/2002 7
Appendix A Power Supply Calculations........................................................... 126
A.1 Overview ............................................................................................................................................. 126
A.2 Calculating the AC Branch Circuit.................................................................................................. 126
A.3 The Main Power Supply.................................................................................................................... 127
Current Limitations in Standby ..............................................................................................................................127
Current Limitations in Alarm – System Operation on Primary Power ...................................................................127
A.4 Calculating the System Current Draw............................................................................................. 128
Overview .................................................................................................................................................................128
How to Use Table 47 to Calculate System Current Draws ..................................................................................... 128
A.5 Calculating the Battery Size.............................................................................................................. 130
A.6 Selecting and Locating Batteries ...................................................................................................... 131
A.7 NFPA Battery Requirements ............................................................................................................ 131
Appendix B NFPA Applications......................................................................... 132
B.1 Section Overview................................................................................................................................ 132
Specific Requirements ............................................................................................................................................ 132
Additional Requirements ........................................................................................................................................ 132
B.2 Central Station Fire Alarm Systems (Protected Premises) ............................................................ 133
Installing a Notifier 911AC ....................................................................................................................................133
Installing a UDACT ................................................................................................................................................ 134
B.3 NFPA 72 Auxiliary Fire Alarm System............................................................................................ 135
B.4 Wiring a Remote Station Fire Alarm System .................................................................................. 136
Overview .................................................................................................................................................................136
Using a 4XTM Module ...........................................................................................................................................137
Using an RTM-8 Module ........................................................................................................................................138
B.5 NFPA 72 Proprietary Fire Alarm Systems ...................................................................................... 138
Appendix C Annunciators.................................................................................. 140
C.1 LCD-80 Display.................................................................................................................................. 140
ACS Mode ..............................................................................................................................................................140
Terminal Mode ........................................................................................................................................................ 140
C.2 Terminal Mode (LCD-80) Annunciation Interface (TB5 on CPU) ............................................... 140
C.3 ACS Annunciation Interface (TB5 on CPU) ................................................................................... 141
Supported Modules ................................................................................................................................................. 141
C.4 Annunciator Capacity ....................................................................................................................... 141
Data Formats for Annunciator Address 1 ............................................................................................................... 141
Data Formats at Annunciator Address 2 ................................................................................................................. 141
C.5 Terminal Mode EIA-485 Connections (TB5)................................................................................... 144
C.6 LCD-80 ACS Mode EIA-485 Connections ...................................................................................... 145
C.7 Power Connections for LCD and ACS Series Annunciators ......................................................... 146
C.8 ACS and LDM Series EIA-485 Connections ................................................................................... 147
Appendix D Releasing Applications ................................................................. 148
D.1 NFPA Standards................................................................................................................................. 148
D.2 Programming Releasing Zones......................................................................................................... 148
Releasing Zone Functions .......................................................................................................................................149
Delay Timer ............................................................................................................................................................149
Cross Zoning .................................................................................................................. ......................................... 149
Soak Timer (NFPA 16 Applications Only) ............................................................................................................. 150
Abort Timer ............................................................................................................................................................ 151
Special Module Type Codes ................................................................................................................................... 151
Abort Switch ........................................................................................................................................................... 151
Man. Release ........................................................................................................................................................... 151
Rel Ckt ULC ........................................................................................................................................................... 152
Release Ckt .............................................................................................................................................................152
Initiating Devices ....................................................................................................................................................152
Warning Sounders ...................................................................................................................................................152
Auxiliary Control Relay Functions ......................................................................................................................... 153
ACS Annunciation .................................................................................................................................................. 153
Deluge/Pre-Action Release ..................................................................................................................................... 153
D.3 Connecting Releasing Devices........................................................................................................... 153
8 AFP-200 PN 15511:H2 10/14/2002
Connecting a Releasing Device to a Control Panel through an SLC Control or Relay Module ............................154
Connecting an NBG-12LRA Agent Releasing Abort Station ................................................................................154
Appendix E Combination Fire/Burglary Applications ..................................... 157
E.1 Overview ............................................................................................................................................. 157
E.2 Installation .......................................................................................................................................... 157
Installation Overview .............................................................................................................................................. 157
Installing a Tamper Switch .....................................................................................................................................157
Wiring for Proprietary Security Alarm Applications .............................................................................................. 158
Connecting to an AM2020/AFP1010 Receiving Unit ............................................................................................159
E.3 Programming...................................................................................................................................... 159
E.4 Operation ............................................................................................................................................ 160
Overview .................................................................................................................................................................160
Configuring the Keypad for a Security LED Indicator ........................................................................................... 160
Control Panel Operation in a Security Condition ................................................................................................... 160
Appendix F Wire Requirements......................................................................... 161
Appendix G Pre-Alarm (AWACS™) Applications ............................................ 162
G.1 Overview ............................................................................................................................................. 162
G.2 Pre-Alarm Applications..................................................................................................................... 162
Pre-Alarm Alert Level ............................................................................................................................................ 162
Action Level Pre-Alarm Function .......................................................................................................................... 163
G.3 Pre-Alarm Programming................................................................................................................... 163
Pre-Alarm Programming Screen ............................................................................................................................. 163
Selecting Pre-Alarm Application Levels ................................................................................................................ 164
Self-Optimizing Pre-Alarm Function ..................................................................................................................... 165
Audible Warning Applications for AWACS™ ....................................................................................................... 166
Appendix H Special Zones................................................................................. 167
H.1 Overview ............................................................................................................................................. 167
H.2 Presignal and Positive Alarm Sequence (PAS)................................................................................ 167
Presignal ..................................................................................................................................................................167
Positive Alarm Sequence (PAS) ............................................................................................................................. 167
H.3 Time Control ...................................................................................................................................... 168
H.4 NAC Code Types................................................................................................................................ 168
Appendix I Terminal Interface Protocol ............................................................ 169
I.1 General Description ............................................................................................................................ 169
I.2 Operating Modes ................................................................................................................................. 169
Local Terminal Mode (LocT) .................................................................................................................................169
Local Monitor Mode (LocM) ................................................................................................................................. 170
Remote Terminal Mode (RemT) .............................................................................................................................170
I.3 Using the CRT-2 for Read Status....................................................................................................... 171
Overview .................................................................................................................................................................171
Accessing Read Status Options ..............................................................................................................................171
Read Point ...............................................................................................................................................................172
Display Devices in Alarm or Trouble .....................................................................................................................172
Display the Status of all Programmed Points .........................................................................................................172
View the History Buffer .......................................................................................................................................... 173
Send the History Buffer to the CRT-2 .....................................................................................................................173
I.4 Using the CRT-2 for Alter Status....................................................................................................... 173
Overview .................................................................................................................................................................173
Accessing Alter Status Options ..............................................................................................................................174
Enable or Disable Detectors, Modules, or Bell Circuits .........................................................................................174
Change Detector Sensitivity Levels ........................................................................................................................ 175
Clear the Verification Counter ................................................................................................................................175
Clear the Entire History Buffer ............................................................................................................................... 175
Set the Pre-Alarm for Alert or Action Level .......................................................................................................... 176
CRT-2 Configuration .............................................................................................................................................. 176
Appendix J Expansion Power Supplies............................................................ 177
J.1 Overview .............................................................................................................................................. 177
AFP-200 PN 15511:H2 10/14/2002 9
AVPS-24 Audio/Visual Power Supply ....................................................................................................................177
APS-6R Auxiliary Power Supply ...........................................................................................................................177
J.2 Programming....................................................................................................................................... 179
J.3 Supply Calculations ............................................................................................................................ 179
AVPS-24/AVPS-24E Calculations .......................................................................................................................... 179
APS-6R Calculations .............................................................................................................................................. 180
J.4 Installation........................................................................................................................................... 180
Installing the AVPS-24/AVPS-24E .........................................................................................................................180
Installing the APS-6R ............................................................................................................................................. 183
Appendix K UL Power-limited Wiring Requirements ...................................... 186
K.1 Overview ............................................................................................................................................. 186
K.2 Typical Circuit with Nonpower-limited and Power-limited Wiring ............................................. 186
Appendix L U.S. Coast Guard & Lloyd’s Register ........................................... 187
Appendix M CBE Programming......................................................................... 189
M.1 Purpose............................................................................................................................................... 189
M.2 Software Zones .................................................................................................................................. 189
M.3 How to Program CBE....................................................................................................................... 189
CBE Example 1 ......................................................................................................................................................189
CBE Example 2 ......................................................................................................................................................190
Appendix N External Battery Charger............................................................... 191
N.1 Overview ............................................................................................................................................. 191
N.2 Installation Requirements ................................................................................................................. 191
N.3 Mounting the CHG-120..................................................................................................................... 191
Mounting the Charger into a CAB-X3 Series Cabinet ...........................................................................................191
Mounting the Charger into a Battery Box .............................................................................................................. 192
N.4 Connecting the CHG-120 .................................................................................................................. 194
Connecting a CHG-120 to the AFP-200 ................................................................................................................. 194
10 AFP-200 PN 15511:H2 10/14/2002
About This Manual
Scope of this Manual
This manual contains the following:
Section 1 “System Overview” provides a description of the control panel and system components, a list of related system documentation, electrical specifications, and cabinet dimensions.
Section 2 “Installation” provides instructions for installing the basic and optional system components, and provides a checklist for testing an installed system and the batteries.
Section 3 “Programming” provides instructions for customizing the fire alarm system by selecting and setting program options for addressable SLC devices, NACs, and Panel Circuits.
Section 4 “Operation” provides instructions for operator use of the fire alarm system.
Appendix A “Power Supply Calculations” provides current draws for system components and calculation tables for determining the power required to operate the control panel during fire alarm and AC loss of power conditions.
Appendix B “NFPA Applications” provides information and wiring diagrams for setting up the control panel for NFPA applications.
Appendix C “Annunciators” provides information about annunciating control panel points and contains instructions and wiring diagrams for connecting annunciators to the control panel.
Appendix D “Releasing Applications” provides information and wiring diagrams for setting up the control panel for releasing applications.
Appendix E “Combination Fire/Burglary Applications” provides information and wiring diagrams for setting up the control panel for security applications.
Appendix F “Wire Requirements” provides wire requirements for circuits connected to the control panel.
Appendix G “Pre-Alarm (AWACS™) Applications” provides information and wiring diagrams for setting up the control panel for AWACs applications.
Appendix H “Special Zones” provides descriptions and options for Special Zones used to define presignal and PAS selections, Time Control selection, Holiday selections, and NAC Code Types.
Appendix I “Terminal Interface Protocol” provides detailed information about the terminal operating modes: Local Terminal Mode (LocT), Local Monitor Mode (LocM), and Remote Terminal Mode (RemT). The appendix also contains instructions for using a CRT-2 for Read Status and Alter Status (Change Status) operations.
Appendix J “Expansion Power Supplies” provides information and wiring diagrams for setting up the panel to use external power supplies.
Appendix K “UL Power-limited Wiring Requirements” provides UL wiring requirements and sample wiring diagrams for power-limited and nonpower-limited wiring.
Appendix L “U.S. Coast Guard & Lloyd’s Register” provides a list of equipment suitable for use in marine and shipyard applications as compatible with this control panel.
AFP-200 PN 15511:H2 10/14/2002 11
Appendix M “CBE Programming” provides information and programming examples to set up the fire alarm system to use Control-by-Event.
Appendix N “External Battery Charger” provides information and wiring diagrams for setting up an external battery charger for use with the panel.
Notes, Cautions, and Warnings
This manual contains notes, cautions, and warnings to alert the reader to as follows:
Note – Supplemental information for a topic, such as tips and references, that
typically appear in the left margin.
Caution – information about procedures that could cause programming errors, runtime errors, or equipment damage.
WA R NI N G – indicates information about procedures that could cause irreversible damage to the control panel, irreversible loss of programming data or personal injury.
Typographic Conventions
For presentation and printing, this manual uses different typeface characters, in place of the actual LCD letters that you see on the LCD display. This manual uses the following conventions for entering data and pressing control panel keys, as listed in Table 1:
Table 1 Typographic Conventions in this Manual
General Terms
Unless noted, general terms reference the specific part numbers listed Table 2:
Table 2 General Terms
!
!
When you see Specifies Example
text in small caps the way the text
appears in the LCD display
MARCH TIME is a selection that
appears in the LCD display
TAMPER shows a Type Code
selection as it appears in the LCD display
text in quotes a reference to a
section
“Program Change” specifies the Program Change section.
bold text In body text, a key
on the control panel
Press the Enter key Press the 1 key
a graphic of the key In a graphic, a key
as it appears on the control panel
Press
General Term Specific Part Number(s)
Auxiliary Power Supply APS-6R
AVPS-24 AVPS-24/AVPS-24E
Control module FCM-1
CPU AFP-200 circuit board
CRT CRT-2
LCD display 80-character LCD (liquid crystal display)
Monitor Module FMM-1 or FMM-101
PRN PRN-5
Relay module FRM-1
12 AFP-200 PN 15511:H2 10/14/2002
Supplemental Information
Table 3 contains a list of documents that contain additional information on the AFP-200:
Table 3 Supplemental Documentation
For information on Refer to Part Number
All features AFP-200 Data Sheet DN-3783
System Connections AFP-200 Basic System Drawing 51265
Compatible Devices Device Compatibility Document 15378
Off-line programming and installation Veri•Fire Medium Systems CD: AFP-200 Upload/Download Utility Verifire-CD
Networking applications NAM-232 Network Adaptor Module Manual 50038
Networking applications Noti•Fire•Net Manual
Noti•Fire•Net Manual, Network Version 4.0 & Higher
50257 51584
SLC Wiring Instructions SLC Wiring Manual 51253
Annunciators Annunciator Control System
Annunciator Fixed Module ACM-8R Annunciator Control Module LDM Series Lamp Driver Annunciator LCD-80 Manual LCD-80TM Manual RPT-485W/RPT-485WF EIA-485 Annunciator Loop Repeater
15842 15048 15342 15885 15037 51082 15640
Auxiliary Power Supplies and Battery Chargers
APS-6R Installation Manual ACPS-2406 Auxiliary Power Supply Manual CHG-120 Battery Charger Manual FCPS-24 Field Charger/Power Supply
50702 51304 50641 50059
Cabinets CAB-3 Installation Drawing 15330
Network Interface NIB-96 Network Interface Board 15666
Transponders XP5 Series Manual
DPI-232 Manual RFX Wireless Interface System
50786 51499 51012
Universal Digital Alarm Communicator/Transmitter
The UDACT Manual 911AC Manual 411UD 411 411UDAC
50050 74-06200-005 50759 50921 51073
Universal Zone Coder UZC-256 Universal Zone Coder
UZC-256 Programming
15216 15976
Voice Alarm Systems VEC-25/50 Voice Alarm System Manual
RM-1 Series Remote Microphone - PID
50686 51138
AFP-200 PN 15511:H2 10/14/2002 13
Agency Standards and Compliance
This control panel complies with the following NFPA standards:
NFPA 12 CO
2
Extinguishing Systems (High Pressure Only)
NFPA 12A Halon 1301 Extinguishing Systems
NFPA 12B Halon 1211 Extinguishing Systems
NFPA 13 Sprinkler Systems
NFPA 15 Water Spray Systems
NFPA 16 Foam/Water Deluge and Foam/Water Spray Systems
NFPA 17 Dry Chemical Extinguishing Systems
NFPA 17A Wet Chemical Extinguishing Systems
NFPA 72 Central Station Signaling Systems (Automatic, Manual, and Waterflow). Protected Premises Unit (Requires 411UDAC or NOTI•FIRE 911AC DACT or MS-5012 Slave Communicator)*
NFPA 72 Local Fire Alarm Systems
NFPA 72 Auxiliary Fire Alarm Systems. (Requires 4XTM or RTM-8)
NFPA 72 Remote Station Fire Alarm Systems. (Requires 4XTM or 411UDAC DACT or NOTI•FIRE 911AC DACT*)
NFPA 72 Proprietary Fire Alarm Systems (Protected Premises Unit) (Requires Potter #EFT-C McCulloh Transmitter)*
NFPA 2001 Clean Agent Fire Extinguishing Systems
United States Coast Guard–Fire Protection System. (Marine Approvals require CAB-AM.)
Lloyd’s Register –Marine, Offshore and Industrial Category ENV1 and ENV2*
* Applications which require the 411UDAC, the NOTI-FIRE 911AC, or the Potter EFT-C are not FM approved.
The installer should also be familiar with the following documents and standards:
NFPA Standards
NFPA 72 Automatic Fire Detectors
NFPA 72 Installation, Maintenance, and Use of Notification Appliances for Fire Alarm Systems
NFPA 72 Testing Procedures for Signaling Systems
NFPA 2001 Clean Agent Fire Extinguishing Systems
Underwriters Laboratories Documents:
UL 38 Manual Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers - Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Alarm systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power supplies for Fire Protective Signaling Systems
UL 1638 Visual Signaling Appliances
UL 1076 Proprietary Burglar Alarm Systems
Standard CAN/ULC-S527-M87 Standard for Control Units for Fire Alarm Systems
Other:
EIA-485 and EIA-232 Serial Interface Standards
NEC Article 300 Wiring Methods
NEC Article 760 Fire Alarm Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction
Notifier Device Compatibility Document
ADA Americans with Disabilities Act
System Overview General Description
14 AFP-200 PN 15511:H2 10/14/2002
Section 1 System Overview
1.1 General Description
The AFP-200 is a compact, cost-effective, intelligent fire alarm control panel with an extensive list of powerful features. The power supply and all electronics are contained on a single circuit board, providing a complete fire control system for most applications. Optional modules which plug into the main circuit board are available for special functions.
1.2 Features
Figure 1 identifies major features of the control panel.
Single standard communication (SLC) loop, meets NFPA Style 4, 6, or 7 requirements
198 intelligent device capacity
Four Notification Appliance Circuits standard
Optional RTM-8 eight-zone relay module with transmitter
Optional 411, 411UD, 411UDACT, or 911AC Digital Alarm Communicator/Transmitter
Optional UDACT Universal Digital Alarm Communicator/Transmitter
LCD-80 liquid crystal display, mounts up to 6,000 feet (1,828.8 m) from panel
ACS annunciators, including LDM custom graphic annunciators
ACM-8R remote relay module, increases point capacity
Printer interface
Real time clock, with European format option
History file with 650 event capacity
Intelligent features
Sensitivity display in percent
Manual sensitivity adjustment
Day/Night automatic sensitivity adjustment
Drift compensation (U.S. patent pending)
Auto detector test (meets NFPA 72)
Maintenance Alert
Pre-Alarm (AWACS™ — 2 levels)
LED blink control
Releasing features
Four independent hazards
Cross zone (three methods)
Delay timer
Soak timer
Abort — four options
Manual release
Waterflow (non-silenceable) selection per module point
Supervisory selection per point with separate LED
Alarm Verification
•Walk Test
Positive alarm sequence (PAS) pre-signal per NFPA 72
Silence Inhibit timer option
Auto silence timer option
March time/temporal code
Two-stage option for Canada
California code
Tornado warning code
Remote Ack/Silence/Reset/Drill via Monitor Modules
Automatic time control functions, with holiday exceptions
Autoprogram (learn mode) reduces installation time
Password- and key-protected nonvolatile memory.
Programmable from a PC with a Windows®-based programming utility
Rapid poll algorithm for manual stations (U.S. patent pending)
Operates up to 1,000 feet (304.8 m) with untwisted, unshielded wire (U.S. Patent 5,210,523)
Operates sounder base on Action Pre-Alarm level with general evacuation on alarm level.
Burglar alarm point option.
Read status on program via modem using dial-up phone lines.
Marine cabinet option (CAB-AM)
Components System Overview
AFP-200 PN 15511:H2 10/14/2002 15
:
Figure 1 AFP-200 System Features
1.3 Components
1.3.1 Membrane Switch Panel
Figure 2 shows the membrane switch panel which includes the following:
Windows for the Liquid Crystal Display (LCD) and six system status indicator LEDs.
Programming keys, including a 12-key alphanumeric pad (similar to a telephone keypad) an
ENTER key, and four arrow movement keys.
Slide-in labels, which provide switch and LED description for the six system status indicator LEDs and the four operator keys.
Figure 2 Membrane Switch Panel
LCD-80 Remote Display/Control
(up to 32 devices)
Signaling Line Circuit (SLC) up to 198 devices
XP Transponder
Monitor Control Module Module
NBG-12LXFSP-751 FSI-751 FST-751
IDC NAC
Annunciator control points Up to 68 fully programmable output circuits
Dual phone lines to Central Station
To oth e r
FAC P
CRT terminal
LDM-32 custom graphics
ACM-8R
EIA-232 terminal
ACM/AEM-16AT annunciator
Optional 396-channel UDACT
ACS EIA-485
EIA-485
PRN printer
AFP-200
ENTER
ACKNOWLEDGE
STEP
ALARM
SILENCE
DRILL
HOLD 2 SECONDS
SYSTEM
RESET
AC POWER
FIRE ALARM
PRE-ALARM WAR NING
SUPERVISORY
ALARM SILENCE
SYSTEM TROUBLE
DET MOD
12
3
4
5
6
7
89
#
ABC
DEF
GHI
JKL
MNO
PRS
TUV
WXY
Q
Z
­/
.
ALL SYSTEMS NORMAL 09:45A THU 06/18/97
Membrn
e
Slide-in labels
System status indicator LEDs
Four operator keys
ENTER switch
Cursor movement keys
12-key alphanumeric programming keypad
Liquid Crystal Display
System Overview Components
16 AFP-200 PN 15511:H2 10/14/2002
System Status Indicator LEDs
Figure 2 shows the location of the control panel system status indicator LEDs.
AC Power (green)
System Alarm (red)
Pre-Alarm Warning (yellow)
Supervisory/Security (yellow)
Alarm Silence (yellow)
System Trouble (yellow)
For descriptions of each System Status LED Indicator, refer to Section 4 “Operation”.
Operator Keys
Figure 2 shows the location of the following operator keys:
Acknowledge/Step
Alarm Silence
Drill
System Reset (lamp test)
For descriptions of each operator key, refer to Section 4 “Operation”.
Programming Keypad
Figure 2 shows the location of the control panel keypad switches, the cursor keys, and the
ENTER key.
Twelve-key pad with 0-9, *, #
Four cursor keys (up, down, right, left)
ENTER key
1.3.2 Panel Sounder
The control panel provides audio signals for alarm, trouble, and supervisory/security conditions through an onboard panel sounder. For more information on the panel sounder, refer to Section 4 “Operation”.
1.3.3 Output Circuits (TB2)
Output circuits consist of four Class B (Style Y) Notification Appliance Circuits (NACs) or releasing circuits (fully programmable). For installation instructions, refer to “Output Circuits (TB2)” on page 35.
1.3.4 Relays (TB3)
The control panel includes three dry contact relays for system alarm, system trouble, and supervisory. Contacts are rated 2 A at 30 VDC and 0.5 A at 30 VAC (resistive). For installation instructions, “Standard Relays (TB3)” on page 36.
Main Assemblies System Overview
AFP-200 PN 15511:H2 10/14/2002 17
1.4 Main Assemblies
The AFP-200 main assemblies include the CPU board, the cabinet for enclosing the control panel, the transformer assembly, and the batteries.
1.4.1 CPU Board
The control panel circuit board contains the system’s central processing unit (CPU), power supply, and other primary components. The CPU is delivered pre-mounted in the cabinet. Figure 3 shows the components of the CPU board, such as terminals, LEDs, and connectors. For details of the membrane switch panel, see Figure 2 on page 15.
Figure 3 Connections and Controls (Shown Without Dress Panel)
Afp2incab
JP2
JP7
JP5
SW3
SW2
JP3
JP9
JP1
JP6
JP2 External charger (cut if using CHG-120 external charger)
Battery Trouble LED (yellow)
High Rate Charge LED (green)
JP1 Ammeter option (cut if ammeter installed)
CB1 Circuit Breaker
J3 battery – refer to 2.4.2 “Battery
Power Connection (J3)”.
4XMM Meter Module option (refer to “Meter Module” on page
20)
SW2 EIA-485 Select switch (left =Terminal; right =ACS)
SW3 AC Delay Reporting
TB3 Relays – refer to “Standard Relays (TB3)” on page 36
TB2 Notification Appliance Circuits– refer to “Output Circuits (TB2)” on page 35
TB1 DC power – refer to “DC Output Power Connections (TB1)” on page 35
TB7 AC Power (refer to “AC Power Connections (TB7)” on page 33)
J4 Ammeter connector
J11 APS Supervisory/Tamper Switch
J2 Voltmeter connector
JP5 Option board
(cut jumper if option board installed)
JP9 Ground fault (cut jumper to disable ground fault detector)
Ground Fault LED (yellow)
JP3 Tamper – cut jumper to enable supervision for expansion power supply (Appendix J “Expansion Power Supplies”) or for tamper switch
JP6, JP7 External power – cut jumpers if AVPS-24 or APS-6R installed (refer to Appendix J “Expansion Power Supplies”)
J10 External power supply connection for AVPS-24 or APS-6R (refer to Appendix J “Expansion Power Supplies”)
Batteries (two 12 AH batteries shown)
J6-J-8 Option module slot (refer to “Option Module: Transmitter Module - 4XTM” on page 20
TB4 EIA-232 connections – refer to “EIA-232 Devices – Remote Printers and CRTs (TB4)” on page 37
TB5 EIA-485 connections – refer to Appendix C “Annunciators” Annunciators
TB6 SLC connections – refer to “Wiring a Signaling Line Circuit (SLC)” on page 41
System Overview Main Assemblies
18 AFP-200 PN 15511:H2 10/14/2002
1.4.2 Cabinet
The CPU board mounts in a compact (16.125" x 14.5" x 5.5") cabinet with a front dress plate. The cabinet provides space for two batteries (up to 12 AH).
1.4.3 LCD Display
The control panel uses an 80-character LCD display (4 rows of 20 characters each). The display includes a long-life LED backlight that remains on unless AC power is lost while the system is not in alarm:
Figure 4 LCD Display
1.4.4 Membrane Switch Panel
The membrane switch panel provides LED Status Indicators, operator keys, and programming keys. The operator keys and LEDs are visible with the cabinet door closed. The programming keys are visible only with the door open. Slide-in labels are provided for switch and LED descriptions. Refer to “Membrane Switch Panel” on page 15.
1.4.5 Transformer Assembly
The transformer assembly includes two 100 VA transformers and a connector.
1.4.6 Batteries
The cabinet provides space for 7 AH or 12 AH batteries (for 18 AH batteries use the BB-17 battery box). Batteries must be ordered separately.
AFP-200
ANALOG@FIRE@PANEL
ALL@SYSTEMS@NORMAL
11:00@MON@5/19/98
ENTER
ACKNOWLEDGE
STEP
ALARM
SILENCE
DRILL
HOLD 2 SECONDS
SYSTEM
RESET
AC POWER
FIRE ALARM
PRE-ALARM WARNING
SUPERVISORY
ALARM SILENCE
SYSTEM TROUBLE
DET MOD
12
3
4
5
6
789
#
ABC
DEF
GHI
JKL
MNO
PRS
TUV
WXY
Q
Z
­/
.
ALL SYSTEMS NORMAL 09:45A THU 06/18/97
Membrn
e
Optional Devices & Option Modules System Overview
AFP-200 PN 15511:H2 10/14/2002 19
1.5 Optional Devices & Option Modules
Several optional components can be installed within this fire alarm control system, including external devices and “option modules” that plug directly into the CPU. The CPU board includes an option module slot located on the right side of the board. When an option module is installed, jumper JP5 (Figure 3 on page 17) must be cut. The option slot supports a 4XTM or RTM-8 module.
For instructions on installing an option module, refer to 2.10 “Option Module Installation”.
Figure 5 Option Module Slot (Shown with RTM-8 Module)
Further information and installation instructions for specific devices are provided in those product manuals; for part numbers of manuals refer to Table 3, “Supplemental Documentation,” on page 12.
1.5.1 Digital Communicator
The 911AC Digital Alarm Communicator/Transmitter transmits three zones of information (System Alarm, System Trouble, Supervisory) to the central station or remote station receiver. Fully UL-listed for fire operation (NFPA 72), the 911AC requires two standard dial-up telephone lines to operate. For details, refer to the 911AC Manual.
1.5.2 UDACT
The UDACT transmits system status for up to 99 zones to UL-listed Central Station Receivers over a public switched telephone network. It mounts remotely in the ABS-8R enclosure. The unit connects to the EIA-485 annunciator port and 24 VDC (nominal) power; software PN 73609 or higher must be installed. Some NFPA applications are provided in Appendix B. For further details, refer to the UDACT manual.
1.5.3 Network Interface Board - NIB-96
A microprocessor- controlled module that connects slave control panels to a master control panel. The board can be installed in each slave FACP. Each slave FACP can contain as many as 96 input/output points, or as few as eight points. Refer to the NIB-96 Network Interface Board manual for further information and installation instructions.
RTM-8 module installed in option slot
J5
UDACTassy.cdr
SIZE
SIZE
CONFIG
TENS
ONES
SWITCH SETTINGS
1
2 3 4
6
7
8 9
0
8
16
24 32
40 48
56
64 80
96
5
NO OF POINTS
SLC P5
P2
SLC ONLINE
RS485 ONLINE
TROUBLE
P3
P1
SW4
SW3
SW2
SW1
RS485 P4
NIB-96assy.cdr
System Overview Optional Devices & Option Modules
20 AFP-200 PN 15511:H2 10/14/2002
1.5.4 Field Charger/Power Supply - FCPS-24
A compact, cost-effective remote power supply and battery charger. It consists of a filtered, 24 VDC output that can drive up to four Notification Appliance Circuits (NACs). Refer to the FCPS-24 Field Charger/Power Supply manual for further information and installation instructions.
1.5.5 Battery Charger - CHG-120
Designed to charge lead-acid batteries that provide emergency standby power for a Fire Alarm Control Panel. Provides two (2) output circuits for connection to multiple loads. Can be mounted into a CAB-3 Series cabinet or a BB-55 or NFS-LBB Battery Box. For details, refer to the CHG-120 Battery Charger manual.
1.5.6 Liquid Crystal Display - LCD-80
An alphanumeric display module that is an ancillary device which has two basic modes of operation. In
Terminal Mode it acts as a display interface and in ACS Mode as an alphanumeric annunciator. The LCD-80TM is
also available and provides Term i na l Mod e only. Refer to the LCD-80 manual or LCD-80TM Liquid Crystal Display manual.
1.5.7 Option Module: Transmitter Module - 4XTM
The 4XTM provides connections to municipal box and remote station transmitters meeting NFPA 72 Auxiliary and Remote Station requirements. The 4XTM is mounted on the control panel’s CPU and includes a Disable switch and an LED indicator. Refer to 2.10.2 “Installing a 4XTM Module”.
1.5.8 Option Module: Relay/Transmitter Module - RTM-8
The Relay/Transmitter Module (RTM-8) provides eight Form-C relays (5A contacts) that track software zones 1 through 8. The RTM-8 also provides Municipal Box and Remote Station transmitters NFPA 72 Auxiliary and Remote Station requirements. In remote station applications, the RTM-8 transmits alarm only and does not transmit trouble or supervisory status. Disable switches and indicators are included. Refer to 2.10.3 “Installing an RTM-8 Module”.
1.5.9 Meter Module
The 4XMM Meter Module provides a voltmeter to measure voltage across the batteries and an ammeter to measure charging current to the batteries. A single assembly containing both meters mounts in the lower-left corner of the AFP-200 cabinet as shown in Figure 3 on page 17.
++ + +
+ + + + +
++ +++++
+ +++
+
+ +
TB2
P3
TB1
TB3
TB4
1
2
3
4
5
6
7
8
9
30
1.0
2520.815.610.45.20
0
D.C. VOLTS
D.C. AMPERES
FCPS-24assy.cdr
TB2
JP4 JP5 JP6
F3 F2 F1
SW1
R100
R104
JP8
JP9
JP3
JP7
TB3
TB1
CHG120pc.cdr
LCD80-outline.tif
4XTMassy.cdr
rtm-8.cdr
Intelligent Detectors System Overview
AFP-200 PN 15511:H2 10/14/2002 21
1.5.10 Trim Ring
The TR-4XG gray trim ring is available for semi-flush mounting of the control panel cabinet. See Figure 7 on page 29 for an illustration of the trim ring installed.
1.5.11 Battery Box
The BB-17 battery box may be used to mount two 18 AH batteries. The box mounts directly below the control panel cabinet. See Figure 6 on page 28 for an illustration of the battery box dimensions.
1.5.12 Dress Panel
A dead front dress panel (DP-AFP200) is available as an option (required for Canadian and FM installations).
1.5.13 Expansion Power Supplies (AVPS-24 and APS-6R)
Power supply model AVPS-24/AVPS-24E provides an additional 3 amps of notification appliance power (Appendix J “Expansion Power Supplies”) and the APS-6R provides 6 amps of additional notification appliance power. Refer to the Device Compatibility Document for compatible notification appliances.
1.5.14 Marine Cabinet
Cabinet CAB-AM is required for applications requiring United States Coast Guard or Lloyd’s Register approvals. Refer to Appendix L “U.S. Coast Guard & Lloyd’s Register” on page 187.
1.6 Intelligent Detectors
Intelligent, addressable detectors provide analog information to the control panel on a Signaling Line Circuit (SLC). This allows the control panel to continually process this information to determine the status of each detector (alarm, trouble, maintenance, or normal). Each detector responds to an SLC address that is set in the detector head using built-in rotary decimal switches. The sensitivity of each intelligent detector can be programed at the control panel. (Refer to Section 3 “Programming” for details.) Detector heads mount to a separate base for ease of installation and replacement, as described below.
A blinking LED on an intelligent detector indicates communication between the detector and the control panel.
Detectors
FSI-751. Analog, addressable, low profile intelligent smoke detector that incorporates an ionization sensing chamber. Designed to provide open area protection.
FSP-751. Same as FSI-751, but uses a photoelectric sensing chamber. The FSP-751T adds thermal sensors that will alarm at a fixed temperature of 135° F. Designed to provide open area protection.
FSI-751, FSP-751
System Overview Addressable Modules
22 AFP-200 PN 15511:H2 10/14/2002
FST-751. Intelligent thermistor sensing circuit for fast response. Designed to provide open area protection with 50 foot spacing capability. The FST-751R incorporates a thermal rate of rise of 15°F (9.4°C).
FSD-751P. Photoelectric Duct Detector. The FSD-751RP includes an alarm relay.
HPX-751. A special smoke detector that provides early warning smoke detection in hostile environments where traditional smoke detectors are not practical.
Detector Bases
Several bases, to which the detectors are affixed, are available:
B710LP. Standard U.S. Low-Profile base
B501. Standard European flangeless base
B501BH. Sounder base, includes B501
B524RB. Intelligent relay base
B524BI. Intelligent isolator base
B224RB. Low Profile Intelligent relay base
B224BI. Low Profile Intelligent isolator base
B710HD. HARSH detector base
Accessories
The following is available:
RA400Z. A Remote Single LED Annunciator that can be wired directly off of an addressable detector for annunciation of that detector's alarm status.
1.7 Addressable Modules
1.7.1 Overview
Addressable modules include:
Control modules. Provide an interface between the control panel and conventional notification appliances such as horns and bells.
Relay modules. Route power to relays under specified conditions; relays can control non-resistive loads within power supply limitations.
Monitor modules. Provide an interface between the control panel and initiating devices, such as pull stations.
You can set each control, relay and monitor module to respond to an address with built-in rotary decimal switches.
Note: A blinking LED on a monitor, control or relay module indicates communication between the module and the control panel.
1.7.2 Module Descriptions
The monitor, control and relay modules and other addressable modules described below can be used with the control panel:
Control Modules. FCM-1 control modules are used as Notification Appliance Circuits (NACs) to power and supervise compatible, UL-listed notification appliances. Wire supervised circuits as NFPA Style Y or Style Z. Comes with a thermoplastic cover for mounting to a 4-inch (10.16 cm) square mounting box.
FST-751
8
9
10
11 12 13
14
150
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
TENS
ONES
LOOP
LOOP ADDRESS
ADDRESS
8
9
7
6
5
9
8
7
6
5
0
1
2
3
4
4
3
2
1
0
TENS
ONES
8
9
0
1
2
3
4
5
6
7
8
9 10
11 12 13
14
15
0
1
2
3
4
5
6
7
FMM-1.cdr
FCM-1
Addressable Modules System Overview
AFP-200 PN 15511:H2 10/14/2002 23
Monitor Modules: FMM-1, FZM-1, FMM-101.
Addressable modules used to monitor conventional initiating devices. Use the FMM-1 for normally open contact alarm initiating devices, such as manual pull stations, four-wire smoke detectors, heat detectors, waterflow, security contacts, and supervisory devices. Use the FZM-1 for specific two-wire smoke detectors in addition to normally open contacts. Wire supervised circuits as NFPA Style B or Style D circuits. Use the FMM-101 when mounting directly in the electrical box of the device being monitored; this smaller package is limited to Style B circuits only and does not include a blinking LED or a magnetic test switch.
Relay Module. FRM-1 serves as a Form-C control relay. It resembles an FCM-1 and also comes with a thermoplastic cover for mounting to a 4-inch (10.16 cm) square mounting box.
XP5-C Modules. XP5-C Modules allow the AFP-200 to control a maximum of five individual circuits. These modules can be configured as NACs/telephone or relay circuits. Their function is similar to that of the control or relay modules described above.
XP5-M Modules. XP5-M Modules allow the AFP-200 to monitor a maximum of five individual circuits. Their function is similar to those of the monitor modules described above.
Loop Isolator Module (ISO-X). The ISO-X module is an automatic switch that opens the circuit voltage to a communications loop branch(es) whenever a fault is detected on that circuit. The remainder of the communications loop leading up to the ISO-X continues to operate, unaffected by the fault.
NBG-12LX. A dual action addressable manual pull station featuring a key-lock reset. The pull station includes a mini-monitor module and responds to an address set with built-in rotary decimal switches.
NBG-12LRA. A dual-action agent release station featuring an abort switch, release LED, normal LED, and a key-lock reset. The release station includes a mini-monitor module and responds to an address set with built-in rotary decimal switches.
8
9
10
11 12 13
14
150
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
TENS
ONES
LOOP
LOOP ADDRESS
ADDRESS
8
9
7
6
5
9
8
7
6
5
0
1
2
3
4
4
3
2
1
0
TENS
ONES
8
9
0
1
2
3
4
5
6
7
8
9 10
11 12 13
14
15
0
1
2
3
4
5
6
7
FMM-1.cdr
0
10
11
12
13
14
15
ADDRESS
LOOP
1
2
3 4
TENS
ONES
6
7
8
9
5
0
1
2
3 4
6
7
8
9
5
FMM-101.cdr
FMM-1, FZM-1
FMM-101
8
9
8
8
9
9
10
11 12 13
14
15
0
0
1
1
2
2
3
3
4
4
5
5
6
6
7
7
0
1
2
3
4
7
6
5
TENS
ONES
ADDRESS
LOOP
FMM-1.cdr
FRM-1
SYSTEM
NORMAL
SYSTEM
A
CTIVATED
System Overview End-of-Line Devices
24 AFP-200 PN 15511:H2 10/14/2002
1.8 End-of-Line Devices
1.8.1 Overview
Table 4 contains a list of the end-of-line devices that you can install in an AFP-200 system:
Table 4 End-of-Line Devices
1.9 Annunciation Modules
1.9.1 Overview
For instructions on installing annunciation modules, refer to Appendix C “Annunciators” on page 140.
This section contains brief descriptions and the model numbers of annunciator modules that can be connected to the control panel. Communication between the control panel and annunciators takes place over a two-wire serial interface connected to an EIA-485 connector (TB5) on the CPU. For detailed wiring requirements, refer to the appropriate annunciator manuals.
Canadian Requirement: The ACM Series annunciator modules must be used to annunciate the fire alarm input points/zones only. For Canadian applications, the following LED colors must be employed:
• Red must be used to indicate active alarm inputs
• Yellow must be used to indicate supervisory, burglary or trouble signals
• Green must be used to indicate the presence of power or an activated output
1.9.2 Annunciator Control Module-8R (ACM-8R)
The ACM-8R provides the AFP-200 with a mappable relay control module. ACM-8R relays can be selected for mapping anywhere in the system memory map (in groups of eight). Features of the ACM-8R include the following:
Provides eight Form-C relays with 5 A contacts.
Tracks any group of eight zones within the system.
1.9.3 LDM Series Lamp Driver Modules
The LDM-32 Lamp Driver Annunciator Module provides 32 alarm lamp driver outputs for connection to a custom graphic annunciator. You can also set the LDM-32 with a DIP switch for 16 alarm, 16 trouble and 16 switch inputs for control of such system functions as Signal Silence and System Reset.
Lamp Driver Annunciator Expander Module
Option Description Notes
A2143-00 (System Sensor)
A 47K End-Of-Line Resistor (ELR) Assembly ELR used in the supervision of monitor, control and relay module circuits.
Supplied with monitor, control and relay modules.
A2143-10 (System Sensor)
The 3.9K End-Of-Line Resistor (ELR) Assembly used with two-wire detector modules.
Supplied with two-wire detector modules.
N-ELR Resistor plate (Notifier)
An N-ELR, required for Canadian installations, provides connection for a resistor to mount to an ELR plate.
• Use 4.7K for the NAC circuits.
• Use 47K for monitor, control and relay modules.
Annunciation Modules System Overview
AFP-200 PN 15511:H2 10/14/2002 25
(LDM-E32) – Expands the LDM-32 by 32 system points, to a maximum of 64 points.
Relay Expander Module (LDM-R32) – Provides the LDM-32 or LDM-E32 with 32 dry Form-A (normally open) contacts.
1.9.4 Annunciator Control System (ACS)
The ACS series annunciator and control system provides the control panel with up to 32 remote annunciators, each with a capacity of 64 points. Table 5 contains brief descriptions of ACS annunciators. For detailed information, refer to the ACS Manual.
Table 5 ACS Modules
1.9.5 Annunciator Fixed Modules
Annunciator Fixed Modules (AFM-16AT and AFM-32A) provide the control panel with discrete display and control points. AFMs turn their LEDs on and off as directed by the CPU, and also report switch activations to the CPU for action. You can only use one AFM in a system. Each annunciator’s address is fixed at address 1.
AFM-16AT – The AFM-16AT contains 16 red alarm and 16 yellow trouble LEDs, a system trouble LED, an On-line/Power LED, and a local sounder, and switches for control panel Acknowledge, Alarm Silence, and System Reset. Use the AFM-16AT for systems that require 16 or fewer annunciation points.
AFM-32A – The AFM-32A contains 32 red alarm LEDs, a system trouble LED, an ON LINE/POWER LED, and a local panel sounder with a silence/acknowledge switch. The AFM-32A is fixed at address 1, and will not accept expander modules.
Module Features
Annunciator Control Module-16AT (ACM-16AT)
The ACM-16AT provides features for audible and visual indication of alarm and trouble conditions at each annunciator. These features include: 1) 16 red alarm LEDs; 2) 16 yellow trouble LEDs; 3) 16 momentary touch-pad switches for controlling each point; 4) a system trouble LED; 5) an Online/Power LED; 6) a local sounder; 7) a Silence/Acknowledge switch; and remote functions.
Annunciator Expander Module (AEM-16AT)
The AEM-16AT, identical in size and appearance to the ACM-16AT, expands the ACM-16AT by 16 system points. An ACM-16AT can support up to three AEM-16ATs, to a provide a maximum of 64 system points. Note: An AEM-16AT cannot be used to expand an ACM-32A.
Annunciator Control Module-32A (ACM-32A)
The ACM-32A provides features for audible and visual indication of alarm and trouble conditions at each annunciator. These features include: 1) 32 red alarm LEDs; 2) a system trouble LED; 3) an Online/Power LED; 4) a local sounder; and 5) a Silence/Acknowledge switch.
Annunciator Expander Module-32A (AEM-32A)
The AEM-32A, identical in size and appearance to the ACM-32A, expands the ACM-32A by 32 system points. An ACM-32 can support one AEM-32A, providing a maximum of 64 system points. Note: An AEM-32A cannot be used to expand an ACM-16AT.
anunc16.tif
anunc32.tif
System Overview EIA-232 Peripheral Devices (TB4)
26 AFP-200 PN 15511:H2 10/14/2002
1.10 EIA-232 Peripheral Devices (TB4)
1.10.1 Overview
The control panel is compatible with the following printers and display devices that connect through the EIA-232 interface on CPU terminal TB4:
PRN printer
Keltron remote printer
CRT-2 display terminal
For installation instructions for these devices, refer to “EIA-232 Devices – Remote Printers and CRTs (TB4)” on page 37.
1.10.2 PRN Remote Printer
The PRN is an optional printer that connects directly to the control panel through TB1 on the CPU and can be located up to 50 feet (15.24 m) from the control panel. It features the following:
Provides a printed record (80 columns of data on standard 9" x 11" tractor-feed paper) of all system events (alarm, trouble) and status changes within the system.
Time-stamps the printout with the current time-of-day and date. Note: Time stamping is a function of the AFP-200 panel.
1.10.3 Keltron Remote Printer (Model VS4095)
The VS4095 is a two-color (red and black), 40-column, 24 VDC printer that can print up to 50 messages in 90 seconds. This printer connects to the EIA-232 TB4 in the control panel through TB1 on the CPU, from which it gets its power, and mounts in a separate cabinet next to the control panel. The VS4095 meets UL fire and security requirements for an ancillary device. For more information on the Keltron printer, contact the manufacturer (Keltron Corp., Waltham, MA). Refer to “Keltron Printer” on page 38 for installation instructions.
1.10.4 CRT-2 Display Terminal
The optional CRT-2 Display Terminal connects to the control panel via the EIA-232 serial interface (TB4) and can be located up to 50 feet (15.24 m) from the control panel. The CRT-2 displays data on 26 lines by 80 columns and allows you to do the following:
Control and view events, points, and event history
Control the system (Acknowledge, Alarm Silence, and System Reset).
Change important system operating parameters, such as enable/disable of addressable points, change alarm and pre-alarm sensitivities, clear verification counters, clear history, and set the pre-alarm action level.
Specifications System Overview
AFP-200 PN 15511:H2 10/14/2002 27
1.11 Specifications
This section contains electrical specifications for the control panel.
1.11.1 Primary AC Power (TB7)
Primary AC connections are made through TB7 on the AFP-200. Wire size: minimum 14 AWG with 600 VAC insulation.
AFP-200. 120 VAC, 50/60 Hz, 3.0 A
AFP-200E. 220/240 VAC, 50/60 Hz, 1.5 A
1.11.2 Battery (lead-acid only)
Maximum Charging Circuit Dual Rate High Charge is 29.1 V @ 0.7 A
Normal Flat Charge is 27.6 V @ 0.5 A
Maximum Battery Capacity 18 AH. (Batteries larger than 12 AH require a BB-17
or other UL-listed battery cabinet.)
1.11.3 Signaling Line Circuit (TB6)
Connections between the control panel and the Signaling Line Circuit (SLC) are supervised and power-limited.
Voltage 24 VDC nominal, 27.6 VDC Max.
Maximum length 10,000 ft. (3048 m) per channel (NFPA Style 4) or
10,000 ft. (3048 m) total twisted-pair length (NFPA Style 6 and 7)
Maximum loop current is 250 mA (max short circuit) or 100 mA (normal)
Maximum loop resistance 40 ohms
1.11.4 Notification Appliance and Releasing Circuits (TB2)
The following contains specifications for NACs and releasing circuits available on the AFP-200 (all circuits are power-limited).
Max. wiring voltage drop 2 VDC
Normal Operating Voltage 24 VDC.
NAC circuit 1 2.5 A
NAC circuits 2-4 2.5 A shared total
Current for all external devices 5.0 A
Optional AVPS-24/AVPS-24E Additional 3.0 A of notification appliance power (see
Appendix J “Expansion Power Supplies”)
Optional APS-6R Additional 6.0 A of notification appliance power (see
Appendix J “Expansion Power Supplies”)
Max. signaling current/circuit 2.5 A
End-of-line resistor 4.7K, 1/2-Watt (PN 71252 UL-listed) for NACs)
Releasing circuits REL-4.7K; for control module — REL-47K
System Overview Cabinet Dimensions
28 AFP-200 PN 15511:H2 10/14/2002
1.11.5 Relays (TB3)
Relays for Alarm, Trouble, Security, and Supervisory are available on terminal TB3 for power-limited circuits only. Contact ratings for relays through TB3 are:
2.0 A at 30 VDC (resistive), 0.5 A at 30 VAC (resistive)
Alarm and Trouble: Form-C
Supervisory: Form-A
1.11.6 24 VDC Power (TB1)
Terminal Block (TB1) provides 24 VDC power as follows:
1.12 Cabinet Dimensions
1.12.1 Surface Mount with a BB-17 Battery Box
Figure 6 shows dimensions for mounting a cabinet with a BB-17 Battery Box.
Figure 6 AFP-200 Cabinet and BB-17 Battery Box Dimensions
Four-wire Smoke Detector Power (24 VDC ± 5%) – TB1-5 and TB1-6
• Max. ripple voltage: 10 mVrms
• Up to 500 mA is available for powering four-wire
smoke detectors
1,2
Non-resettable 24 V Power (24 VDC ± 5%) – TB1-3 and TB1-4
• Max. ripple voltage: 10 mVrms
• Total DC current available from this output is up to
500 mA (subtracted from four-wire smoke power)
2
High Ripple Regulated 24 V Power (24 VDC ±10%) – TB1-1 and TB1-2
• Max. ripple voltage: 2 Vrms
• Total DC current available for powering external
devices is 1.0 A standby and 1.5 A alarm2. This power is not recommended for LCD-80 or ACS annunciators except for an ACM-8R.
1
For power supply calculations, refer to Appendix A.
2
Total current for regulated power, non-resettable power, four-wire smoke power, and four Notification Appliance Circuits must not exceed 5 A or 8 A if using an AVPS-24 (refer to Appendix J “Expansion Power Supplies”) or APS-6R. Total external system current in excess of
2.5 A requires 12 AH or 18 AH batteries—not 7 AH.
Door = 16.125"
(40.9575 cm)
Backbox = 16.0"
(40.64 cm)
Battery Box = 8.25"
(20.955 cm)
(Optional BB-17)
Door = 14.625" (37.1475 cm)
Backbox = 14.5" (36.83 cm)
Depth = 4.75" (12.065 cm)
Battery Box = 14.5" (36.83 cm)
(Optional BB-17)
Depth = 5.5" (13.97 cm)
afp2cab-surface.cdr
Cabinet Dimensions System Overview
AFP-200 PN 15511:H2 10/14/2002 29
1.12.2 Semi-flush Mount
Figure 7 shows dimensions for semi-flush mounting of the AFP-200 cabinet using a TR-4XG Trim Ring.
Figure 7 Dimensions with TR-4XG Trim Ring
Trim Ring = 17.62"
(44.7548 cm)
Trim Ring = 19.12"
(48.564 cm)
1.5" (3.8 cm) typical
for 4" (10.16 cm) wall
Installation Preparing for Installation
30 AFP-200 PN 15511:H2 10/14/2002
Section 2 Installation
2.1 Preparing for Installation
2.1.1 Unpacking the System
Carefully unpack the system and inspect for shipping damage.
Select a location for the control panel in a clean, dry, vibration-free area with moderate temperature.
2.1.2 Installation Notes
Before installing the fire alarm system, read the following:
Install the system in a readily accessible area with sufficient room to easily install and maintain the control panel.
Locate the top of the cabinet approximately 60 inches (1.524 m) above the floor with the hinge mounting on the left.
Count the number of conductors needed for all devices and find the appropriate knockouts.
Review the installation precautions at the front of this manual.
All wiring must comply with the National and/or Local codes for fire alarm systems.
Do not draw wiring into the bottom 9 inches (22.86 cm) of the cabinet, except when using the BB-17. This prevents interference between the power supply and batteries.
2.1.3 Standards and Codes
In addition, installers should be familiar with the following standards:
NEC Article 300 Wiring Methods.
NEC Article 760 Fire Protective Signaling Systems.
Applicable Local and State Building Codes.
Requirements of the Local Authority Having Jurisdiction.
Loading...
+ 166 hidden pages