Notifier AFP-200 Installation Manual

Page 1
Analog Fire Panel
AFP-200
Installation Manual
Document 15511 10/14/2002 Rev:
H2
15511:H2 ECN 02-436
Page 2
2 AFP-200 PN 15511:H2 10/14/2002
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system—typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control with remote notifica­tion capability—can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detec­tors be located throughout a protected premise following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommen­dations contained in the Guide for Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. A study by the Federal Emergency Man­agement Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are designed to pro­vide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a first-floor or basement fire.
Particles of combustion or “smoke” from a developing fire may not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow.
• Smoke particles may become “cold,” stratify, and not reach the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air outlets.
• Smoke particles may be drawn into air returns before reaching the detector.
The amount of “smoke” present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ion­izing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of flammable materials, etc.).
Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predeter­mined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire pro­tection specialist. Heat detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the sys­tem for the connection of alarm transmission wiring, communi­cations, signaling, and/or power. If detectors are not so located, a developing fire may damage the alarm system, crip­pling its ability to report a fire.
Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol or medica­tion. Please note that:
• Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property owner's responsi­bility to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.
Equipment used in the system may not be technically com­patible with the control. It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against tele­phone line failure, backup radio transmission systems are rec­ommended.
The most common cause of fire alarm malfunction is inade­quate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA stan­dards. At a minimum, the requirements of Chapter 7 of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent mainte­nance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled monthly or as required by National and/or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records of all inspections should be kept.
Precau-L-4-2002.fm
Page 3
AFP-200 PN 15511:H2 10/14/2002 3
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associ­ated equipment may be damaged by removing and/or insert­ing cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software Changes. To ensure proper system operation, this product
must be tested in accordance with NFPA 72 Chapter 7 after any programming operation or change in site-specific soft­ware. Reacceptance testing is required after any change, addition or deletion of system components, or after any modifi­cation, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software func­tions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvert­ently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation ver­ified.
This system meets NFPA requirements for operation at 0-49° C/32-120° F and at a relative humidity of 85% RH - 93% per ULC - (non-condensing) at 30° C/86° F. However, the useful life of the system's standby batteries and the electronic com­ponents may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and all peripherals be installed in an environment with a nominal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and indi­cating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to light­ning-induced transients. Although no system is completely immune from lightning transients and interferences, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased sus­ceptibility to nearby lightning strikes. Consult with the Techni­cal Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifi­cations, verify that they will not interfere with battery, trans­former, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced ter­minal contact pressure and difficulty with screw terminal removal.
Though designed to last many years, system components can fail at any time. This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static-suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and pro­gramming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation by authorized personnel.
Precau-L-4-2002.fm
WARNING: This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause interference to radio communications. It has been tested and found to comply with the limits for class A com­puting device pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at his own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits radio­electriques depassant les limites applicables aux appar­eils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.
FCC Warning
Acclimate Plus™, HARSH™, NOTI•FIRE•NET™, ONYX™, and Ver iF ire™ are trademarks, and FlashScan® and VIEW® are registered trademarks of
NOTIFIER. NION™ and UniNet™ are trademarks of NIS. NIS™ and Notifier Integrated Systems™ are trademarks and NOTIFIER® is a registered trademark of Fire•Lite Alarms, Inc. Echelon® is a registered trademark and LonWorks™ is a trademark of Echelon Corporation. ARCNET® is a registered trademark of Datapoint Corporation. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. LEXAN® is a registered trademark of GE Plastics, a subsidiary of General Electric Company.
Page 4
4 AFP-200 PN 15511:H2 10/14/2002
About This Manual..................................................................................................10
Section 1 System Overview .................................................................................. 14
1.1 General Description.............................................................................................................................. 14
1.2 Features ............................................................................................................................................... 14
1.3 Components........................................................................................................................................... 15
1.3.1 Membrane Switch Panel ..................................................................................................................................15
1.3.2 Panel Sounder .................................................................................................................................................. 16
1.3.3 Output Circuits (TB2) ......................................................................................................................................16
1.3.4 Relays (TB3) .................................................................................................................................................... 16
1.4 Main Assemblies ................................................................................................................................... 17
1.4.1 CPU Board ....................................................................................................................................................... 17
1.4.2 Cabinet .............................................................................................................................................................18
1.4.3 LCD Display .................................................................................................................................................... 18
1.4.4 Membrane Switch Panel ..................................................................................................................................18
1.4.5 Transformer Assembly ....................................................................................................................................18
1.4.6 Batteries ........................................................................................................................................................... 18
1.5 Optional Devices & Option Modules .................................................................................................. 19
1.5.1 Digital Communicator ..................................................................................................................................... 19
1.5.2 UDACT ............................................................................................................................................................ 19
1.5.3 Network Interface Board - NIB-96 ..................................................................................................................19
1.5.4 Field Charger/Power Supply - FCPS-24 ..........................................................................................................20
1.5.5 Battery Charger - CHG-120 .............................................................................................................................20
1.5.6 Liquid Crystal Display - LCD-80 .................................................................................................................... 20
1.5.7 Option Module: Transmitter Module - 4XTM ................................................................................................ 20
1.5.8 Option Module: Relay/Transmitter Module - RTM-8 ..................................................................................... 20
1.5.9 Meter Module ..................................................................................................................................................20
1.5.10 Trim Ring ....................................................................................................................................................... 21
1.5.11 Battery Box .................................................................................................................................................... 21
1.5.12 Dress Panel .................................................................................................................................................... 21
1.5.13 Expansion Power Supplies (AVPS-24 and APS-6R) .................................................................................... 21
1.5.14 Marine Cabinet .............................................................................................................................................. 21
1.6 Intelligent Detectors.............................................................................................................................. 21
1.7 Addressable Modules............................................................................................................................ 22
1.7.1 Overview ..........................................................................................................................................................22
1.7.2 Module Descriptions ........................................................................................................................................22
1.8 End-of-Line Devices.............................................................................................................................. 24
1.8.1 Overview ..........................................................................................................................................................24
1.9 Annunciation Modules ......................................................................................................................... 24
1.9.1 Overview ..........................................................................................................................................................24
1.9.2 Annunciator Control Module-8R (ACM-8R) .................................................................................................. 24
1.9.3 LDM Series Lamp Driver Modules ................................................................................................................. 24
1.9.4 Annunciator Control System (ACS) ................................................................................................................25
1.9.5 Annunciator Fixed Modules ............................................................................................................................ 25
1.10 EIA-232 Peripheral Devices (TB4).................................................................................................... 26
1.10.1 Overview ........................................................................................................................................................ 26
1.10.2 PRN Remote Printer ...................................................................................................................................... 26
1.10.3 Keltron Remote Printer (Model VS4095) ...................................................................................................... 26
1.10.4 CRT-2 Display Terminal ...............................................................................................................................26
1.11 Specifications....................................................................................................................................... 27
1.11.1 Primary AC Power (TB7) .............................................................................................................................. 27
1.11.2 Battery (lead-acid only) .................................................................................................................................27
1.11.3 Signaling Line Circuit (TB6) ......................................................................................................................... 27
1.11.4 Notification Appliance and Releasing Circuits (TB2) ...................................................................................27
1.11.5 Relays (TB3) .................................................................................................................................................. 28
1.11.6 24 VDC Power (TB1) .................................................................................................................................... 28
1.12 Cabinet Dimensions ............................................................................................................................ 28
1.12.1 Surface Mount with a BB-17 Battery Box ..................................................................................................... 28
Page 5
AFP-200 PN 15511:H2 10/14/2002 5
1.12.2 Semi-flush Mount .......................................................................................................................................... 29
Section 2 Installation ............................................................................................. 30
2.1 Preparing for Installation..................................................................................................................... 30
2.1.1 Unpacking the System ..................................................................................................................................... 30
2.1.2 Installation Notes ............................................................................................................................................. 30
2.1.3 Standards and Codes ........................................................................................................................................30
2.2 Installation Checklist............................................................................................................................ 31
2.3 Backbox Mounting................................................................................................................................ 32
2.4 AC and DC Power Connections .......................................................................................................... 33
2.4.1 AC Power Connections (TB7) .........................................................................................................................33
2.4.2 Battery Power Connection (J3) ........................................................................................................................ 34
2.4.3 Expansion Power Supplies – AVPS-24 or APS-6R (Optional) .......................................................................34
2.5 DC Output Power Connections (TB1) ................................................................................................ 35
2.6 Output Circuits (TB2) .......................................................................................................................... 35
2.6.1 Notification Appliance Circuits ....................................................................................................................... 35
2.7 Standard Relays (TB3) ......................................................................................................................... 36
2.8 EIA-232 Devices – Remote Printers and CRTs (TB4) ....................................................................... 37
2.8.1 Overview ..........................................................................................................................................................37
2.8.2 Printer Configuration ....................................................................................................................................... 37
2.8.3 Installation .......................................................................................................................................................37
2.8.4 Keltron Printer ................................................................................................................................................. 38
2.8.5 CRT Connections .............................................................................................................................................39
2.9 Wiring a Signaling Line Circuit (SLC)............................................................................................... 41
2.9.1 Overview of SLC Wiring .................................................................................................................................41
2.9.2 SLC Devices ....................................................................................................................................................42
2.9.3 Control Panel Capacity .................................................................................................................................... 42
2.9.4 SLC Performance ............................................................................................................................................. 43
2.9.5 SLC Shield Termination .................................................................................................................................. 43
2.9.6 Setting an SLC Address for a Module ............................................................................................................. 44
2.9.7 Wire Requirements for a Two-wire SLC ......................................................................................................... 45
2.9.8 Wire Requirements for a Four-wire SLC ........................................................................................................ 46
2.9.9 Wiring an Isolator Module (ISO-X) ................................................................................................................49
2.9.10 Wiring an IDC with Monitor Modules ..........................................................................................................50
2.9.11 Wiring a Notification Appliance Circuit (NAC) or Control Circuit ..............................................................56
2.9.12 SLC Wiring with Control Modules ............................................................................................................... 57
2.9.13 SLC Wiring with an Intelligent Detector .......................................................................................................59
2.9.14 SLC Wiring with an NBG-12LX Addressable Manual Pull Station .............................................................60
2.10 Option Module Installation................................................................................................................ 61
2.10.1 Overview ........................................................................................................................................................ 61
2.10.2 Installing a 4XTM Module ............................................................................................................................62
2.10.3 Installing an RTM-8 Module ......................................................................................................................... 63
Section 3 Programming......................................................................................... 65
3.1 Overview ................................................................................................................................................ 65
3.1.1 Programming Methods ....................................................................................................................................65
3.1.2 In This Section ................................................................................................................................................. 65
3.2 Getting Started...................................................................................................................................... 66
3.2.1 How to Access Programming Options ............................................................................................................. 66
3.2.2 Programming Passwords .................................................................................................................................. 66
3.2.3 How to Use the Programming Keypad ...........................................................................................................67
3.2.4 Programming Shortcuts ................................................................................................................................... 68
3.2.5 Upload and Download ..................................................................................................................................... 68
3.2.6 Key Programming Terms ................................................................................................................................. 68
3.2.7 How to Avoid Programming Errors ................................................................................................................. 69
3.3 Program Change Options..................................................................................................................... 70
3.3.1 Overview ..........................................................................................................................................................70
3.4 How to Enter Program Change........................................................................................................... 71
3.4.1 Program Change Map ...................................................................................................................................... 72
Page 6
6 AFP-200 PN 15511:H2 10/14/2002
3.4.2 How to Clear a Program from Memory (0=clr) ..............................................................................................73
3.4.3 How to Autoprogram the Control Panel (1=auto) ........................................................................................... 73
3.4.4 How to Edit or Delete a Point (2=point) .......................................................................................................... 78
3.4.5 How to Change a Programming Password (3=passwd) ...................................................................................85
3.4.6 How to Change a System Message (4=message) ............................................................................................ 86
3.4.7 How to Change a Zone Label (5=zones) ......................................................................................................... 86
3.4.8 How to Edit a Special Zone (6=spl zones) ......................................................................................................87
3.4.9 How to Edit System Functions (7=sys) ........................................................................................................... 89
3.4.10 How to Check the Program (8=check) .......................................................................................................... 92
3.5 Status Change Options ......................................................................................................................... 92
3.5.1 Overview ..........................................................................................................................................................92
3.5.2 Entering Status Change .................................................................................................................................... 93
3.5.3 Status Change Programming Map ................................................................................................................... 94
3.5.4 How to Disable or Enable a Point (1=disable) ................................................................................................95
3.5.5 How to Set Detector Selections (2=sens/comp) ..............................................................................................96
3.5.6 How to Clear Alarm Verification Counters (3=clr ver) ...................................................................................97
3.5.7 How to Clear the History Buffer (4=clr hist) ................................................................................................... 98
3.5.8 How to Set the System Time and Date (5=time) .............................................................................................98
3.5.9 How to do a Walk Test (6=walk test) ..............................................................................................................99
Section 4 Operation............................................................................................. 101
4.1 Overview .............................................................................................................................................. 101
4.2 The Membrane Panel ......................................................................................................................... 102
4.2.1 Overview ........................................................................................................................................................ 102
4.2.2 How to Use the Programming Keypad .......................................................................................................... 102
4.2.3 How to Use the Enter Key and Cursor Keys ................................................................................................. 103
4.2.4 How to Use the Operator Keys ...................................................................................................................... 103
4.2.5 How to Read System Status LED Indicators .................................................................................................105
4.3 How to Operate the Control Panel.................................................................................................... 106
4.3.1 How to Operate the Panel in Normal Operation ............................................................................................ 107
4.3.2 How to Operate a Panel with a Trouble Condition ........................................................................................ 107
4.3.3 How to Operate a Panel with a Trouble Monitor Point ................................................................................. 109
4.3.4 How to Operate a Panel with a Fire Alarm .................................................................................................... 109
4.3.5 How to Operate a Panel with a Supervisory Condition ................................................................................. 110
4.3.6 How to Operate a Panel with a Non-Alarm Condition ..................................................................................111
4.3.7 How to Operate the Panel with an Output Circuit Trouble ........................................................................... 111
4.3.8 How the Control Panel Indicates a Panel Circuit Trouble ............................................................................. 112
4.4 Control-By-Event Operation .............................................................................................................. 112
4.5 Releasing Functions ............................................................................................................................. 113
4.5.1 Overview ........................................................................................................................................................ 113
4.5.2 How to Select Cross Zone Options ................................................................................................................113
4.6 Releasing Functions ............................................................................................................................. 114
4.7 Intelligent Detector Functions ............................................................................................................ 115
4.7.1 Summary of Detector Functions .................................................................................................................... 115
4.7.2 Pre-Alarm Operation/Advanced Warning Addressable Combustion Sensing (AWACS™) ........................ 115
4.8 Time Functions..................................................................................................................................... 116
4.8.1 Overview ........................................................................................................................................................ 116
4.8.2 Coding Operation (NAC only) ...................................................................................................................... 117
4.8.3 Presignal/PAS Operation ...............................................................................................................................117
4.8.4 Special System Timers ................................................................................................................................... 118
4.8.5 Waterflow Circuits Operation ........................................................................................................................ 118
4.8.6 Disable/Enable Operation .............................................................................................................................. 118
4.8.7 Style 6 Operation ........................................................................................................................................... 118
4.9 Read Status........................................................................................................................................... 118
4.9.1 Overview ........................................................................................................................................................ 118
4.9.2 How to Enter Read Status ..............................................................................................................................119
4.9.3 Read Status Options .......................................................................................................................................119
4.9.4 Read Point ...................................................................................................................................................... 119
4.9.5 Using the History Buffer ................................................................................................................................124
Page 7
AFP-200 PN 15511:H2 10/14/2002 7
Appendix A Power Supply Calculations........................................................... 126
A.1 Overview ............................................................................................................................................. 126
A.2 Calculating the AC Branch Circuit.................................................................................................. 126
A.3 The Main Power Supply.................................................................................................................... 127
Current Limitations in Standby ..............................................................................................................................127
Current Limitations in Alarm – System Operation on Primary Power ...................................................................127
A.4 Calculating the System Current Draw............................................................................................. 128
Overview .................................................................................................................................................................128
How to Use Table 47 to Calculate System Current Draws ..................................................................................... 128
A.5 Calculating the Battery Size.............................................................................................................. 130
A.6 Selecting and Locating Batteries ...................................................................................................... 131
A.7 NFPA Battery Requirements ............................................................................................................ 131
Appendix B NFPA Applications......................................................................... 132
B.1 Section Overview................................................................................................................................ 132
Specific Requirements ............................................................................................................................................ 132
Additional Requirements ........................................................................................................................................ 132
B.2 Central Station Fire Alarm Systems (Protected Premises) ............................................................ 133
Installing a Notifier 911AC ....................................................................................................................................133
Installing a UDACT ................................................................................................................................................ 134
B.3 NFPA 72 Auxiliary Fire Alarm System............................................................................................ 135
B.4 Wiring a Remote Station Fire Alarm System .................................................................................. 136
Overview .................................................................................................................................................................136
Using a 4XTM Module ...........................................................................................................................................137
Using an RTM-8 Module ........................................................................................................................................138
B.5 NFPA 72 Proprietary Fire Alarm Systems ...................................................................................... 138
Appendix C Annunciators.................................................................................. 140
C.1 LCD-80 Display.................................................................................................................................. 140
ACS Mode ..............................................................................................................................................................140
Terminal Mode ........................................................................................................................................................ 140
C.2 Terminal Mode (LCD-80) Annunciation Interface (TB5 on CPU) ............................................... 140
C.3 ACS Annunciation Interface (TB5 on CPU) ................................................................................... 141
Supported Modules ................................................................................................................................................. 141
C.4 Annunciator Capacity ....................................................................................................................... 141
Data Formats for Annunciator Address 1 ............................................................................................................... 141
Data Formats at Annunciator Address 2 ................................................................................................................. 141
C.5 Terminal Mode EIA-485 Connections (TB5)................................................................................... 144
C.6 LCD-80 ACS Mode EIA-485 Connections ...................................................................................... 145
C.7 Power Connections for LCD and ACS Series Annunciators ......................................................... 146
C.8 ACS and LDM Series EIA-485 Connections ................................................................................... 147
Appendix D Releasing Applications ................................................................. 148
D.1 NFPA Standards................................................................................................................................. 148
D.2 Programming Releasing Zones......................................................................................................... 148
Releasing Zone Functions .......................................................................................................................................149
Delay Timer ............................................................................................................................................................149
Cross Zoning .................................................................................................................. ......................................... 149
Soak Timer (NFPA 16 Applications Only) ............................................................................................................. 150
Abort Timer ............................................................................................................................................................ 151
Special Module Type Codes ................................................................................................................................... 151
Abort Switch ........................................................................................................................................................... 151
Man. Release ........................................................................................................................................................... 151
Rel Ckt ULC ........................................................................................................................................................... 152
Release Ckt .............................................................................................................................................................152
Initiating Devices ....................................................................................................................................................152
Warning Sounders ...................................................................................................................................................152
Auxiliary Control Relay Functions ......................................................................................................................... 153
ACS Annunciation .................................................................................................................................................. 153
Deluge/Pre-Action Release ..................................................................................................................................... 153
D.3 Connecting Releasing Devices........................................................................................................... 153
Page 8
8 AFP-200 PN 15511:H2 10/14/2002
Connecting a Releasing Device to a Control Panel through an SLC Control or Relay Module ............................154
Connecting an NBG-12LRA Agent Releasing Abort Station ................................................................................154
Appendix E Combination Fire/Burglary Applications ..................................... 157
E.1 Overview ............................................................................................................................................. 157
E.2 Installation .......................................................................................................................................... 157
Installation Overview .............................................................................................................................................. 157
Installing a Tamper Switch .....................................................................................................................................157
Wiring for Proprietary Security Alarm Applications .............................................................................................. 158
Connecting to an AM2020/AFP1010 Receiving Unit ............................................................................................159
E.3 Programming...................................................................................................................................... 159
E.4 Operation ............................................................................................................................................ 160
Overview .................................................................................................................................................................160
Configuring the Keypad for a Security LED Indicator ........................................................................................... 160
Control Panel Operation in a Security Condition ................................................................................................... 160
Appendix F Wire Requirements......................................................................... 161
Appendix G Pre-Alarm (AWACS™) Applications ............................................ 162
G.1 Overview ............................................................................................................................................. 162
G.2 Pre-Alarm Applications..................................................................................................................... 162
Pre-Alarm Alert Level ............................................................................................................................................ 162
Action Level Pre-Alarm Function .......................................................................................................................... 163
G.3 Pre-Alarm Programming................................................................................................................... 163
Pre-Alarm Programming Screen ............................................................................................................................. 163
Selecting Pre-Alarm Application Levels ................................................................................................................ 164
Self-Optimizing Pre-Alarm Function ..................................................................................................................... 165
Audible Warning Applications for AWACS™ ....................................................................................................... 166
Appendix H Special Zones................................................................................. 167
H.1 Overview ............................................................................................................................................. 167
H.2 Presignal and Positive Alarm Sequence (PAS)................................................................................ 167
Presignal ..................................................................................................................................................................167
Positive Alarm Sequence (PAS) ............................................................................................................................. 167
H.3 Time Control ...................................................................................................................................... 168
H.4 NAC Code Types................................................................................................................................ 168
Appendix I Terminal Interface Protocol ............................................................ 169
I.1 General Description ............................................................................................................................ 169
I.2 Operating Modes ................................................................................................................................. 169
Local Terminal Mode (LocT) .................................................................................................................................169
Local Monitor Mode (LocM) ................................................................................................................................. 170
Remote Terminal Mode (RemT) .............................................................................................................................170
I.3 Using the CRT-2 for Read Status....................................................................................................... 171
Overview .................................................................................................................................................................171
Accessing Read Status Options ..............................................................................................................................171
Read Point ...............................................................................................................................................................172
Display Devices in Alarm or Trouble .....................................................................................................................172
Display the Status of all Programmed Points .........................................................................................................172
View the History Buffer .......................................................................................................................................... 173
Send the History Buffer to the CRT-2 .....................................................................................................................173
I.4 Using the CRT-2 for Alter Status....................................................................................................... 173
Overview .................................................................................................................................................................173
Accessing Alter Status Options ..............................................................................................................................174
Enable or Disable Detectors, Modules, or Bell Circuits .........................................................................................174
Change Detector Sensitivity Levels ........................................................................................................................ 175
Clear the Verification Counter ................................................................................................................................175
Clear the Entire History Buffer ............................................................................................................................... 175
Set the Pre-Alarm for Alert or Action Level .......................................................................................................... 176
CRT-2 Configuration .............................................................................................................................................. 176
Appendix J Expansion Power Supplies............................................................ 177
J.1 Overview .............................................................................................................................................. 177
Page 9
AFP-200 PN 15511:H2 10/14/2002 9
AVPS-24 Audio/Visual Power Supply ....................................................................................................................177
APS-6R Auxiliary Power Supply ...........................................................................................................................177
J.2 Programming....................................................................................................................................... 179
J.3 Supply Calculations ............................................................................................................................ 179
AVPS-24/AVPS-24E Calculations .......................................................................................................................... 179
APS-6R Calculations .............................................................................................................................................. 180
J.4 Installation........................................................................................................................................... 180
Installing the AVPS-24/AVPS-24E .........................................................................................................................180
Installing the APS-6R ............................................................................................................................................. 183
Appendix K UL Power-limited Wiring Requirements ...................................... 186
K.1 Overview ............................................................................................................................................. 186
K.2 Typical Circuit with Nonpower-limited and Power-limited Wiring ............................................. 186
Appendix L U.S. Coast Guard & Lloyd’s Register ........................................... 187
Appendix M CBE Programming......................................................................... 189
M.1 Purpose............................................................................................................................................... 189
M.2 Software Zones .................................................................................................................................. 189
M.3 How to Program CBE....................................................................................................................... 189
CBE Example 1 ......................................................................................................................................................189
CBE Example 2 ......................................................................................................................................................190
Appendix N External Battery Charger............................................................... 191
N.1 Overview ............................................................................................................................................. 191
N.2 Installation Requirements ................................................................................................................. 191
N.3 Mounting the CHG-120..................................................................................................................... 191
Mounting the Charger into a CAB-X3 Series Cabinet ...........................................................................................191
Mounting the Charger into a Battery Box .............................................................................................................. 192
N.4 Connecting the CHG-120 .................................................................................................................. 194
Connecting a CHG-120 to the AFP-200 ................................................................................................................. 194
Page 10
10 AFP-200 PN 15511:H2 10/14/2002
About This Manual
Scope of this Manual
This manual contains the following:
Section 1 “System Overview” provides a description of the control panel and system components, a list of related system documentation, electrical specifications, and cabinet dimensions.
Section 2 “Installation” provides instructions for installing the basic and optional system components, and provides a checklist for testing an installed system and the batteries.
Section 3 “Programming” provides instructions for customizing the fire alarm system by selecting and setting program options for addressable SLC devices, NACs, and Panel Circuits.
Section 4 “Operation” provides instructions for operator use of the fire alarm system.
Appendix A “Power Supply Calculations” provides current draws for system components and calculation tables for determining the power required to operate the control panel during fire alarm and AC loss of power conditions.
Appendix B “NFPA Applications” provides information and wiring diagrams for setting up the control panel for NFPA applications.
Appendix C “Annunciators” provides information about annunciating control panel points and contains instructions and wiring diagrams for connecting annunciators to the control panel.
Appendix D “Releasing Applications” provides information and wiring diagrams for setting up the control panel for releasing applications.
Appendix E “Combination Fire/Burglary Applications” provides information and wiring diagrams for setting up the control panel for security applications.
Appendix F “Wire Requirements” provides wire requirements for circuits connected to the control panel.
Appendix G “Pre-Alarm (AWACS™) Applications” provides information and wiring diagrams for setting up the control panel for AWACs applications.
Appendix H “Special Zones” provides descriptions and options for Special Zones used to define presignal and PAS selections, Time Control selection, Holiday selections, and NAC Code Types.
Appendix I “Terminal Interface Protocol” provides detailed information about the terminal operating modes: Local Terminal Mode (LocT), Local Monitor Mode (LocM), and Remote Terminal Mode (RemT). The appendix also contains instructions for using a CRT-2 for Read Status and Alter Status (Change Status) operations.
Appendix J “Expansion Power Supplies” provides information and wiring diagrams for setting up the panel to use external power supplies.
Appendix K “UL Power-limited Wiring Requirements” provides UL wiring requirements and sample wiring diagrams for power-limited and nonpower-limited wiring.
Appendix L “U.S. Coast Guard & Lloyd’s Register” provides a list of equipment suitable for use in marine and shipyard applications as compatible with this control panel.
Page 11
AFP-200 PN 15511:H2 10/14/2002 11
Appendix M “CBE Programming” provides information and programming examples to set up the fire alarm system to use Control-by-Event.
Appendix N “External Battery Charger” provides information and wiring diagrams for setting up an external battery charger for use with the panel.
Notes, Cautions, and Warnings
This manual contains notes, cautions, and warnings to alert the reader to as follows:
Note – Supplemental information for a topic, such as tips and references, that
typically appear in the left margin.
Caution – information about procedures that could cause programming errors, runtime errors, or equipment damage.
WA R NI N G – indicates information about procedures that could cause irreversible damage to the control panel, irreversible loss of programming data or personal injury.
Typographic Conventions
For presentation and printing, this manual uses different typeface characters, in place of the actual LCD letters that you see on the LCD display. This manual uses the following conventions for entering data and pressing control panel keys, as listed in Table 1:
Table 1 Typographic Conventions in this Manual
General Terms
Unless noted, general terms reference the specific part numbers listed Table 2:
Table 2 General Terms
!
!
When you see Specifies Example
text in small caps the way the text
appears in the LCD display
MARCH TIME is a selection that
appears in the LCD display
TAMPER shows a Type Code
selection as it appears in the LCD display
text in quotes a reference to a
section
“Program Change” specifies the Program Change section.
bold text In body text, a key
on the control panel
Press the Enter key Press the 1 key
a graphic of the key In a graphic, a key
as it appears on the control panel
Press
General Term Specific Part Number(s)
Auxiliary Power Supply APS-6R
AVPS-24 AVPS-24/AVPS-24E
Control module FCM-1
CPU AFP-200 circuit board
CRT CRT-2
LCD display 80-character LCD (liquid crystal display)
Monitor Module FMM-1 or FMM-101
PRN PRN-5
Relay module FRM-1
Page 12
12 AFP-200 PN 15511:H2 10/14/2002
Supplemental Information
Table 3 contains a list of documents that contain additional information on the AFP-200:
Table 3 Supplemental Documentation
For information on Refer to Part Number
All features AFP-200 Data Sheet DN-3783
System Connections AFP-200 Basic System Drawing 51265
Compatible Devices Device Compatibility Document 15378
Off-line programming and installation Veri•Fire Medium Systems CD: AFP-200 Upload/Download Utility Verifire-CD
Networking applications NAM-232 Network Adaptor Module Manual 50038
Networking applications Noti•Fire•Net Manual
Noti•Fire•Net Manual, Network Version 4.0 & Higher
50257 51584
SLC Wiring Instructions SLC Wiring Manual 51253
Annunciators Annunciator Control System
Annunciator Fixed Module ACM-8R Annunciator Control Module LDM Series Lamp Driver Annunciator LCD-80 Manual LCD-80TM Manual RPT-485W/RPT-485WF EIA-485 Annunciator Loop Repeater
15842 15048 15342 15885 15037 51082 15640
Auxiliary Power Supplies and Battery Chargers
APS-6R Installation Manual ACPS-2406 Auxiliary Power Supply Manual CHG-120 Battery Charger Manual FCPS-24 Field Charger/Power Supply
50702 51304 50641 50059
Cabinets CAB-3 Installation Drawing 15330
Network Interface NIB-96 Network Interface Board 15666
Transponders XP5 Series Manual
DPI-232 Manual RFX Wireless Interface System
50786 51499 51012
Universal Digital Alarm Communicator/Transmitter
The UDACT Manual 911AC Manual 411UD 411 411UDAC
50050 74-06200-005 50759 50921 51073
Universal Zone Coder UZC-256 Universal Zone Coder
UZC-256 Programming
15216 15976
Voice Alarm Systems VEC-25/50 Voice Alarm System Manual
RM-1 Series Remote Microphone - PID
50686 51138
Page 13
AFP-200 PN 15511:H2 10/14/2002 13
Agency Standards and Compliance
This control panel complies with the following NFPA standards:
NFPA 12 CO
2
Extinguishing Systems (High Pressure Only)
NFPA 12A Halon 1301 Extinguishing Systems
NFPA 12B Halon 1211 Extinguishing Systems
NFPA 13 Sprinkler Systems
NFPA 15 Water Spray Systems
NFPA 16 Foam/Water Deluge and Foam/Water Spray Systems
NFPA 17 Dry Chemical Extinguishing Systems
NFPA 17A Wet Chemical Extinguishing Systems
NFPA 72 Central Station Signaling Systems (Automatic, Manual, and Waterflow). Protected Premises Unit (Requires 411UDAC or NOTI•FIRE 911AC DACT or MS-5012 Slave Communicator)*
NFPA 72 Local Fire Alarm Systems
NFPA 72 Auxiliary Fire Alarm Systems. (Requires 4XTM or RTM-8)
NFPA 72 Remote Station Fire Alarm Systems. (Requires 4XTM or 411UDAC DACT or NOTI•FIRE 911AC DACT*)
NFPA 72 Proprietary Fire Alarm Systems (Protected Premises Unit) (Requires Potter #EFT-C McCulloh Transmitter)*
NFPA 2001 Clean Agent Fire Extinguishing Systems
United States Coast Guard–Fire Protection System. (Marine Approvals require CAB-AM.)
Lloyd’s Register –Marine, Offshore and Industrial Category ENV1 and ENV2*
* Applications which require the 411UDAC, the NOTI-FIRE 911AC, or the Potter EFT-C are not FM approved.
The installer should also be familiar with the following documents and standards:
NFPA Standards
NFPA 72 Automatic Fire Detectors
NFPA 72 Installation, Maintenance, and Use of Notification Appliances for Fire Alarm Systems
NFPA 72 Testing Procedures for Signaling Systems
NFPA 2001 Clean Agent Fire Extinguishing Systems
Underwriters Laboratories Documents:
UL 38 Manual Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers - Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Alarm systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power supplies for Fire Protective Signaling Systems
UL 1638 Visual Signaling Appliances
UL 1076 Proprietary Burglar Alarm Systems
Standard CAN/ULC-S527-M87 Standard for Control Units for Fire Alarm Systems
Other:
EIA-485 and EIA-232 Serial Interface Standards
NEC Article 300 Wiring Methods
NEC Article 760 Fire Alarm Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction
Notifier Device Compatibility Document
ADA Americans with Disabilities Act
Page 14
System Overview General Description
14 AFP-200 PN 15511:H2 10/14/2002
Section 1 System Overview
1.1 General Description
The AFP-200 is a compact, cost-effective, intelligent fire alarm control panel with an extensive list of powerful features. The power supply and all electronics are contained on a single circuit board, providing a complete fire control system for most applications. Optional modules which plug into the main circuit board are available for special functions.
1.2 Features
Figure 1 identifies major features of the control panel.
Single standard communication (SLC) loop, meets NFPA Style 4, 6, or 7 requirements
198 intelligent device capacity
Four Notification Appliance Circuits standard
Optional RTM-8 eight-zone relay module with transmitter
Optional 411, 411UD, 411UDACT, or 911AC Digital Alarm Communicator/Transmitter
Optional UDACT Universal Digital Alarm Communicator/Transmitter
LCD-80 liquid crystal display, mounts up to 6,000 feet (1,828.8 m) from panel
ACS annunciators, including LDM custom graphic annunciators
ACM-8R remote relay module, increases point capacity
Printer interface
Real time clock, with European format option
History file with 650 event capacity
Intelligent features
Sensitivity display in percent
Manual sensitivity adjustment
Day/Night automatic sensitivity adjustment
Drift compensation (U.S. patent pending)
Auto detector test (meets NFPA 72)
Maintenance Alert
Pre-Alarm (AWACS™ — 2 levels)
LED blink control
Releasing features
Four independent hazards
Cross zone (three methods)
Delay timer
Soak timer
Abort — four options
Manual release
Waterflow (non-silenceable) selection per module point
Supervisory selection per point with separate LED
Alarm Verification
•Walk Test
Positive alarm sequence (PAS) pre-signal per NFPA 72
Silence Inhibit timer option
Auto silence timer option
March time/temporal code
Two-stage option for Canada
California code
Tornado warning code
Remote Ack/Silence/Reset/Drill via Monitor Modules
Automatic time control functions, with holiday exceptions
Autoprogram (learn mode) reduces installation time
Password- and key-protected nonvolatile memory.
Programmable from a PC with a Windows®-based programming utility
Rapid poll algorithm for manual stations (U.S. patent pending)
Operates up to 1,000 feet (304.8 m) with untwisted, unshielded wire (U.S. Patent 5,210,523)
Operates sounder base on Action Pre-Alarm level with general evacuation on alarm level.
Burglar alarm point option.
Read status on program via modem using dial-up phone lines.
Marine cabinet option (CAB-AM)
Page 15
Components System Overview
AFP-200 PN 15511:H2 10/14/2002 15
:
Figure 1 AFP-200 System Features
1.3 Components
1.3.1 Membrane Switch Panel
Figure 2 shows the membrane switch panel which includes the following:
Windows for the Liquid Crystal Display (LCD) and six system status indicator LEDs.
Programming keys, including a 12-key alphanumeric pad (similar to a telephone keypad) an
ENTER key, and four arrow movement keys.
Slide-in labels, which provide switch and LED description for the six system status indicator LEDs and the four operator keys.
Figure 2 Membrane Switch Panel
LCD-80 Remote Display/Control
(up to 32 devices)
Signaling Line Circuit (SLC) up to 198 devices
XP Transponder
Monitor Control Module Module
NBG-12LXFSP-751 FSI-751 FST-751
IDC NAC
Annunciator control points Up to 68 fully programmable output circuits
Dual phone lines to Central Station
To oth e r
FAC P
CRT terminal
LDM-32 custom graphics
ACM-8R
EIA-232 terminal
ACM/AEM-16AT annunciator
Optional 396-channel UDACT
ACS EIA-485
EIA-485
PRN printer
AFP-200
ENTER
ACKNOWLEDGE
STEP
ALARM
SILENCE
DRILL
HOLD 2 SECONDS
SYSTEM
RESET
AC POWER
FIRE ALARM
PRE-ALARM WAR NING
SUPERVISORY
ALARM SILENCE
SYSTEM TROUBLE
DET MOD
12
3
4
5
6
7
89
#
ABC
DEF
GHI
JKL
MNO
PRS
TUV
WXY
Q
Z
­/
.
ALL SYSTEMS NORMAL 09:45A THU 06/18/97
Membrn
e
Slide-in labels
System status indicator LEDs
Four operator keys
ENTER switch
Cursor movement keys
12-key alphanumeric programming keypad
Liquid Crystal Display
Page 16
System Overview Components
16 AFP-200 PN 15511:H2 10/14/2002
System Status Indicator LEDs
Figure 2 shows the location of the control panel system status indicator LEDs.
AC Power (green)
System Alarm (red)
Pre-Alarm Warning (yellow)
Supervisory/Security (yellow)
Alarm Silence (yellow)
System Trouble (yellow)
For descriptions of each System Status LED Indicator, refer to Section 4 “Operation”.
Operator Keys
Figure 2 shows the location of the following operator keys:
Acknowledge/Step
Alarm Silence
Drill
System Reset (lamp test)
For descriptions of each operator key, refer to Section 4 “Operation”.
Programming Keypad
Figure 2 shows the location of the control panel keypad switches, the cursor keys, and the
ENTER key.
Twelve-key pad with 0-9, *, #
Four cursor keys (up, down, right, left)
ENTER key
1.3.2 Panel Sounder
The control panel provides audio signals for alarm, trouble, and supervisory/security conditions through an onboard panel sounder. For more information on the panel sounder, refer to Section 4 “Operation”.
1.3.3 Output Circuits (TB2)
Output circuits consist of four Class B (Style Y) Notification Appliance Circuits (NACs) or releasing circuits (fully programmable). For installation instructions, refer to “Output Circuits (TB2)” on page 35.
1.3.4 Relays (TB3)
The control panel includes three dry contact relays for system alarm, system trouble, and supervisory. Contacts are rated 2 A at 30 VDC and 0.5 A at 30 VAC (resistive). For installation instructions, “Standard Relays (TB3)” on page 36.
Page 17
Main Assemblies System Overview
AFP-200 PN 15511:H2 10/14/2002 17
1.4 Main Assemblies
The AFP-200 main assemblies include the CPU board, the cabinet for enclosing the control panel, the transformer assembly, and the batteries.
1.4.1 CPU Board
The control panel circuit board contains the system’s central processing unit (CPU), power supply, and other primary components. The CPU is delivered pre-mounted in the cabinet. Figure 3 shows the components of the CPU board, such as terminals, LEDs, and connectors. For details of the membrane switch panel, see Figure 2 on page 15.
Figure 3 Connections and Controls (Shown Without Dress Panel)
Afp2incab
JP2
JP7
JP5
SW3
SW2
JP3
JP9
JP1
JP6
JP2 External charger (cut if using CHG-120 external charger)
Battery Trouble LED (yellow)
High Rate Charge LED (green)
JP1 Ammeter option (cut if ammeter installed)
CB1 Circuit Breaker
J3 battery – refer to 2.4.2 “Battery
Power Connection (J3)”.
4XMM Meter Module option (refer to “Meter Module” on page
20)
SW2 EIA-485 Select switch (left =Terminal; right =ACS)
SW3 AC Delay Reporting
TB3 Relays – refer to “Standard Relays (TB3)” on page 36
TB2 Notification Appliance Circuits– refer to “Output Circuits (TB2)” on page 35
TB1 DC power – refer to “DC Output Power Connections (TB1)” on page 35
TB7 AC Power (refer to “AC Power Connections (TB7)” on page 33)
J4 Ammeter connector
J11 APS Supervisory/Tamper Switch
J2 Voltmeter connector
JP5 Option board
(cut jumper if option board installed)
JP9 Ground fault (cut jumper to disable ground fault detector)
Ground Fault LED (yellow)
JP3 Tamper – cut jumper to enable supervision for expansion power supply (Appendix J “Expansion Power Supplies”) or for tamper switch
JP6, JP7 External power – cut jumpers if AVPS-24 or APS-6R installed (refer to Appendix J “Expansion Power Supplies”)
J10 External power supply connection for AVPS-24 or APS-6R (refer to Appendix J “Expansion Power Supplies”)
Batteries (two 12 AH batteries shown)
J6-J-8 Option module slot (refer to “Option Module: Transmitter Module - 4XTM” on page 20
TB4 EIA-232 connections – refer to “EIA-232 Devices – Remote Printers and CRTs (TB4)” on page 37
TB5 EIA-485 connections – refer to Appendix C “Annunciators” Annunciators
TB6 SLC connections – refer to “Wiring a Signaling Line Circuit (SLC)” on page 41
Page 18
System Overview Main Assemblies
18 AFP-200 PN 15511:H2 10/14/2002
1.4.2 Cabinet
The CPU board mounts in a compact (16.125" x 14.5" x 5.5") cabinet with a front dress plate. The cabinet provides space for two batteries (up to 12 AH).
1.4.3 LCD Display
The control panel uses an 80-character LCD display (4 rows of 20 characters each). The display includes a long-life LED backlight that remains on unless AC power is lost while the system is not in alarm:
Figure 4 LCD Display
1.4.4 Membrane Switch Panel
The membrane switch panel provides LED Status Indicators, operator keys, and programming keys. The operator keys and LEDs are visible with the cabinet door closed. The programming keys are visible only with the door open. Slide-in labels are provided for switch and LED descriptions. Refer to “Membrane Switch Panel” on page 15.
1.4.5 Transformer Assembly
The transformer assembly includes two 100 VA transformers and a connector.
1.4.6 Batteries
The cabinet provides space for 7 AH or 12 AH batteries (for 18 AH batteries use the BB-17 battery box). Batteries must be ordered separately.
AFP-200
ANALOG@FIRE@PANEL
ALL@SYSTEMS@NORMAL
11:00@MON@5/19/98
ENTER
ACKNOWLEDGE
STEP
ALARM
SILENCE
DRILL
HOLD 2 SECONDS
SYSTEM
RESET
AC POWER
FIRE ALARM
PRE-ALARM WARNING
SUPERVISORY
ALARM SILENCE
SYSTEM TROUBLE
DET MOD
12
3
4
5
6
789
#
ABC
DEF
GHI
JKL
MNO
PRS
TUV
WXY
Q
Z
­/
.
ALL SYSTEMS NORMAL 09:45A THU 06/18/97
Membrn
e
Page 19
Optional Devices & Option Modules System Overview
AFP-200 PN 15511:H2 10/14/2002 19
1.5 Optional Devices & Option Modules
Several optional components can be installed within this fire alarm control system, including external devices and “option modules” that plug directly into the CPU. The CPU board includes an option module slot located on the right side of the board. When an option module is installed, jumper JP5 (Figure 3 on page 17) must be cut. The option slot supports a 4XTM or RTM-8 module.
For instructions on installing an option module, refer to 2.10 “Option Module Installation”.
Figure 5 Option Module Slot (Shown with RTM-8 Module)
Further information and installation instructions for specific devices are provided in those product manuals; for part numbers of manuals refer to Table 3, “Supplemental Documentation,” on page 12.
1.5.1 Digital Communicator
The 911AC Digital Alarm Communicator/Transmitter transmits three zones of information (System Alarm, System Trouble, Supervisory) to the central station or remote station receiver. Fully UL-listed for fire operation (NFPA 72), the 911AC requires two standard dial-up telephone lines to operate. For details, refer to the 911AC Manual.
1.5.2 UDACT
The UDACT transmits system status for up to 99 zones to UL-listed Central Station Receivers over a public switched telephone network. It mounts remotely in the ABS-8R enclosure. The unit connects to the EIA-485 annunciator port and 24 VDC (nominal) power; software PN 73609 or higher must be installed. Some NFPA applications are provided in Appendix B. For further details, refer to the UDACT manual.
1.5.3 Network Interface Board - NIB-96
A microprocessor- controlled module that connects slave control panels to a master control panel. The board can be installed in each slave FACP. Each slave FACP can contain as many as 96 input/output points, or as few as eight points. Refer to the NIB-96 Network Interface Board manual for further information and installation instructions.
RTM-8 module installed in option slot
J5
UDACTassy.cdr
SIZE
SIZE
CONFIG
TENS
ONES
SWITCH SETTINGS
1
2 3 4
6
7
8 9
0
8
16
24 32
40 48
56
64 80
96
5
NO OF POINTS
SLC P5
P2
SLC ONLINE
RS485 ONLINE
TROUBLE
P3
P1
SW4
SW3
SW2
SW1
RS485 P4
NIB-96assy.cdr
Page 20
System Overview Optional Devices & Option Modules
20 AFP-200 PN 15511:H2 10/14/2002
1.5.4 Field Charger/Power Supply - FCPS-24
A compact, cost-effective remote power supply and battery charger. It consists of a filtered, 24 VDC output that can drive up to four Notification Appliance Circuits (NACs). Refer to the FCPS-24 Field Charger/Power Supply manual for further information and installation instructions.
1.5.5 Battery Charger - CHG-120
Designed to charge lead-acid batteries that provide emergency standby power for a Fire Alarm Control Panel. Provides two (2) output circuits for connection to multiple loads. Can be mounted into a CAB-3 Series cabinet or a BB-55 or NFS-LBB Battery Box. For details, refer to the CHG-120 Battery Charger manual.
1.5.6 Liquid Crystal Display - LCD-80
An alphanumeric display module that is an ancillary device which has two basic modes of operation. In
Terminal Mode it acts as a display interface and in ACS Mode as an alphanumeric annunciator. The LCD-80TM is
also available and provides Term i na l Mod e only. Refer to the LCD-80 manual or LCD-80TM Liquid Crystal Display manual.
1.5.7 Option Module: Transmitter Module - 4XTM
The 4XTM provides connections to municipal box and remote station transmitters meeting NFPA 72 Auxiliary and Remote Station requirements. The 4XTM is mounted on the control panel’s CPU and includes a Disable switch and an LED indicator. Refer to 2.10.2 “Installing a 4XTM Module”.
1.5.8 Option Module: Relay/Transmitter Module - RTM-8
The Relay/Transmitter Module (RTM-8) provides eight Form-C relays (5A contacts) that track software zones 1 through 8. The RTM-8 also provides Municipal Box and Remote Station transmitters NFPA 72 Auxiliary and Remote Station requirements. In remote station applications, the RTM-8 transmits alarm only and does not transmit trouble or supervisory status. Disable switches and indicators are included. Refer to 2.10.3 “Installing an RTM-8 Module”.
1.5.9 Meter Module
The 4XMM Meter Module provides a voltmeter to measure voltage across the batteries and an ammeter to measure charging current to the batteries. A single assembly containing both meters mounts in the lower-left corner of the AFP-200 cabinet as shown in Figure 3 on page 17.
++ + +
+ + + + +
++ +++++
+ +++
+
+ +
TB2
P3
TB1
TB3
TB4
1
2
3
4
5
6
7
8
9
30
1.0
2520.815.610.45.20
0
D.C. VOLTS
D.C. AMPERES
FCPS-24assy.cdr
TB2
JP4 JP5 JP6
F3 F2 F1
SW1
R100
R104
JP8
JP9
JP3
JP7
TB3
TB1
CHG120pc.cdr
LCD80-outline.tif
4XTMassy.cdr
rtm-8.cdr
Page 21
Intelligent Detectors System Overview
AFP-200 PN 15511:H2 10/14/2002 21
1.5.10 Trim Ring
The TR-4XG gray trim ring is available for semi-flush mounting of the control panel cabinet. See Figure 7 on page 29 for an illustration of the trim ring installed.
1.5.11 Battery Box
The BB-17 battery box may be used to mount two 18 AH batteries. The box mounts directly below the control panel cabinet. See Figure 6 on page 28 for an illustration of the battery box dimensions.
1.5.12 Dress Panel
A dead front dress panel (DP-AFP200) is available as an option (required for Canadian and FM installations).
1.5.13 Expansion Power Supplies (AVPS-24 and APS-6R)
Power supply model AVPS-24/AVPS-24E provides an additional 3 amps of notification appliance power (Appendix J “Expansion Power Supplies”) and the APS-6R provides 6 amps of additional notification appliance power. Refer to the Device Compatibility Document for compatible notification appliances.
1.5.14 Marine Cabinet
Cabinet CAB-AM is required for applications requiring United States Coast Guard or Lloyd’s Register approvals. Refer to Appendix L “U.S. Coast Guard & Lloyd’s Register” on page 187.
1.6 Intelligent Detectors
Intelligent, addressable detectors provide analog information to the control panel on a Signaling Line Circuit (SLC). This allows the control panel to continually process this information to determine the status of each detector (alarm, trouble, maintenance, or normal). Each detector responds to an SLC address that is set in the detector head using built-in rotary decimal switches. The sensitivity of each intelligent detector can be programed at the control panel. (Refer to Section 3 “Programming” for details.) Detector heads mount to a separate base for ease of installation and replacement, as described below.
A blinking LED on an intelligent detector indicates communication between the detector and the control panel.
Detectors
FSI-751. Analog, addressable, low profile intelligent smoke detector that incorporates an ionization sensing chamber. Designed to provide open area protection.
FSP-751. Same as FSI-751, but uses a photoelectric sensing chamber. The FSP-751T adds thermal sensors that will alarm at a fixed temperature of 135° F. Designed to provide open area protection.
FSI-751, FSP-751
Page 22
System Overview Addressable Modules
22 AFP-200 PN 15511:H2 10/14/2002
FST-751. Intelligent thermistor sensing circuit for fast response. Designed to provide open area protection with 50 foot spacing capability. The FST-751R incorporates a thermal rate of rise of 15°F (9.4°C).
FSD-751P. Photoelectric Duct Detector. The FSD-751RP includes an alarm relay.
HPX-751. A special smoke detector that provides early warning smoke detection in hostile environments where traditional smoke detectors are not practical.
Detector Bases
Several bases, to which the detectors are affixed, are available:
B710LP. Standard U.S. Low-Profile base
B501. Standard European flangeless base
B501BH. Sounder base, includes B501
B524RB. Intelligent relay base
B524BI. Intelligent isolator base
B224RB. Low Profile Intelligent relay base
B224BI. Low Profile Intelligent isolator base
B710HD. HARSH detector base
Accessories
The following is available:
RA400Z. A Remote Single LED Annunciator that can be wired directly off of an addressable detector for annunciation of that detector's alarm status.
1.7 Addressable Modules
1.7.1 Overview
Addressable modules include:
Control modules. Provide an interface between the control panel and conventional notification appliances such as horns and bells.
Relay modules. Route power to relays under specified conditions; relays can control non-resistive loads within power supply limitations.
Monitor modules. Provide an interface between the control panel and initiating devices, such as pull stations.
You can set each control, relay and monitor module to respond to an address with built-in rotary decimal switches.
Note: A blinking LED on a monitor, control or relay module indicates communication between the module and the control panel.
1.7.2 Module Descriptions
The monitor, control and relay modules and other addressable modules described below can be used with the control panel:
Control Modules. FCM-1 control modules are used as Notification Appliance Circuits (NACs) to power and supervise compatible, UL-listed notification appliances. Wire supervised circuits as NFPA Style Y or Style Z. Comes with a thermoplastic cover for mounting to a 4-inch (10.16 cm) square mounting box.
FST-751
8
9
10
11 12 13
14
150
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
TENS
ONES
LOOP
LOOP ADDRESS
ADDRESS
8
9
7
6
5
9
8
7
6
5
0
1
2
3
4
4
3
2
1
0
TENS
ONES
8
9
0
1
2
3
4
5
6
7
8
9 10
11 12 13
14
15
0
1
2
3
4
5
6
7
FMM-1.cdr
FCM-1
Page 23
Addressable Modules System Overview
AFP-200 PN 15511:H2 10/14/2002 23
Monitor Modules: FMM-1, FZM-1, FMM-101.
Addressable modules used to monitor conventional initiating devices. Use the FMM-1 for normally open contact alarm initiating devices, such as manual pull stations, four-wire smoke detectors, heat detectors, waterflow, security contacts, and supervisory devices. Use the FZM-1 for specific two-wire smoke detectors in addition to normally open contacts. Wire supervised circuits as NFPA Style B or Style D circuits. Use the FMM-101 when mounting directly in the electrical box of the device being monitored; this smaller package is limited to Style B circuits only and does not include a blinking LED or a magnetic test switch.
Relay Module. FRM-1 serves as a Form-C control relay. It resembles an FCM-1 and also comes with a thermoplastic cover for mounting to a 4-inch (10.16 cm) square mounting box.
XP5-C Modules. XP5-C Modules allow the AFP-200 to control a maximum of five individual circuits. These modules can be configured as NACs/telephone or relay circuits. Their function is similar to that of the control or relay modules described above.
XP5-M Modules. XP5-M Modules allow the AFP-200 to monitor a maximum of five individual circuits. Their function is similar to those of the monitor modules described above.
Loop Isolator Module (ISO-X). The ISO-X module is an automatic switch that opens the circuit voltage to a communications loop branch(es) whenever a fault is detected on that circuit. The remainder of the communications loop leading up to the ISO-X continues to operate, unaffected by the fault.
NBG-12LX. A dual action addressable manual pull station featuring a key-lock reset. The pull station includes a mini-monitor module and responds to an address set with built-in rotary decimal switches.
NBG-12LRA. A dual-action agent release station featuring an abort switch, release LED, normal LED, and a key-lock reset. The release station includes a mini-monitor module and responds to an address set with built-in rotary decimal switches.
8
9
10
11 12 13
14
150
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
TENS
ONES
LOOP
LOOP ADDRESS
ADDRESS
8
9
7
6
5
9
8
7
6
5
0
1
2
3
4
4
3
2
1
0
TENS
ONES
8
9
0
1
2
3
4
5
6
7
8
9 10
11 12 13
14
15
0
1
2
3
4
5
6
7
FMM-1.cdr
0
10
11
12
13
14
15
ADDRESS
LOOP
1
2
3 4
TENS
ONES
6
7
8
9
5
0
1
2
3 4
6
7
8
9
5
FMM-101.cdr
FMM-1, FZM-1
FMM-101
8
9
8
8
9
9
10
11 12 13
14
15
0
0
1
1
2
2
3
3
4
4
5
5
6
6
7
7
0
1
2
3
4
7
6
5
TENS
ONES
ADDRESS
LOOP
FMM-1.cdr
FRM-1
SYSTEM
NORMAL
SYSTEM
A
CTIVATED
Page 24
System Overview End-of-Line Devices
24 AFP-200 PN 15511:H2 10/14/2002
1.8 End-of-Line Devices
1.8.1 Overview
Table 4 contains a list of the end-of-line devices that you can install in an AFP-200 system:
Table 4 End-of-Line Devices
1.9 Annunciation Modules
1.9.1 Overview
For instructions on installing annunciation modules, refer to Appendix C “Annunciators” on page 140.
This section contains brief descriptions and the model numbers of annunciator modules that can be connected to the control panel. Communication between the control panel and annunciators takes place over a two-wire serial interface connected to an EIA-485 connector (TB5) on the CPU. For detailed wiring requirements, refer to the appropriate annunciator manuals.
Canadian Requirement: The ACM Series annunciator modules must be used to annunciate the fire alarm input points/zones only. For Canadian applications, the following LED colors must be employed:
• Red must be used to indicate active alarm inputs
• Yellow must be used to indicate supervisory, burglary or trouble signals
• Green must be used to indicate the presence of power or an activated output
1.9.2 Annunciator Control Module-8R (ACM-8R)
The ACM-8R provides the AFP-200 with a mappable relay control module. ACM-8R relays can be selected for mapping anywhere in the system memory map (in groups of eight). Features of the ACM-8R include the following:
Provides eight Form-C relays with 5 A contacts.
Tracks any group of eight zones within the system.
1.9.3 LDM Series Lamp Driver Modules
The LDM-32 Lamp Driver Annunciator Module provides 32 alarm lamp driver outputs for connection to a custom graphic annunciator. You can also set the LDM-32 with a DIP switch for 16 alarm, 16 trouble and 16 switch inputs for control of such system functions as Signal Silence and System Reset.
Lamp Driver Annunciator Expander Module
Option Description Notes
A2143-00 (System Sensor)
A 47K End-Of-Line Resistor (ELR) Assembly ELR used in the supervision of monitor, control and relay module circuits.
Supplied with monitor, control and relay modules.
A2143-10 (System Sensor)
The 3.9K End-Of-Line Resistor (ELR) Assembly used with two-wire detector modules.
Supplied with two-wire detector modules.
N-ELR Resistor plate (Notifier)
An N-ELR, required for Canadian installations, provides connection for a resistor to mount to an ELR plate.
• Use 4.7K for the NAC circuits.
• Use 47K for monitor, control and relay modules.
Page 25
Annunciation Modules System Overview
AFP-200 PN 15511:H2 10/14/2002 25
(LDM-E32) – Expands the LDM-32 by 32 system points, to a maximum of 64 points.
Relay Expander Module (LDM-R32) – Provides the LDM-32 or LDM-E32 with 32 dry Form-A (normally open) contacts.
1.9.4 Annunciator Control System (ACS)
The ACS series annunciator and control system provides the control panel with up to 32 remote annunciators, each with a capacity of 64 points. Table 5 contains brief descriptions of ACS annunciators. For detailed information, refer to the ACS Manual.
Table 5 ACS Modules
1.9.5 Annunciator Fixed Modules
Annunciator Fixed Modules (AFM-16AT and AFM-32A) provide the control panel with discrete display and control points. AFMs turn their LEDs on and off as directed by the CPU, and also report switch activations to the CPU for action. You can only use one AFM in a system. Each annunciator’s address is fixed at address 1.
AFM-16AT – The AFM-16AT contains 16 red alarm and 16 yellow trouble LEDs, a system trouble LED, an On-line/Power LED, and a local sounder, and switches for control panel Acknowledge, Alarm Silence, and System Reset. Use the AFM-16AT for systems that require 16 or fewer annunciation points.
AFM-32A – The AFM-32A contains 32 red alarm LEDs, a system trouble LED, an ON LINE/POWER LED, and a local panel sounder with a silence/acknowledge switch. The AFM-32A is fixed at address 1, and will not accept expander modules.
Module Features
Annunciator Control Module-16AT (ACM-16AT)
The ACM-16AT provides features for audible and visual indication of alarm and trouble conditions at each annunciator. These features include: 1) 16 red alarm LEDs; 2) 16 yellow trouble LEDs; 3) 16 momentary touch-pad switches for controlling each point; 4) a system trouble LED; 5) an Online/Power LED; 6) a local sounder; 7) a Silence/Acknowledge switch; and remote functions.
Annunciator Expander Module (AEM-16AT)
The AEM-16AT, identical in size and appearance to the ACM-16AT, expands the ACM-16AT by 16 system points. An ACM-16AT can support up to three AEM-16ATs, to a provide a maximum of 64 system points. Note: An AEM-16AT cannot be used to expand an ACM-32A.
Annunciator Control Module-32A (ACM-32A)
The ACM-32A provides features for audible and visual indication of alarm and trouble conditions at each annunciator. These features include: 1) 32 red alarm LEDs; 2) a system trouble LED; 3) an Online/Power LED; 4) a local sounder; and 5) a Silence/Acknowledge switch.
Annunciator Expander Module-32A (AEM-32A)
The AEM-32A, identical in size and appearance to the ACM-32A, expands the ACM-32A by 32 system points. An ACM-32 can support one AEM-32A, providing a maximum of 64 system points. Note: An AEM-32A cannot be used to expand an ACM-16AT.
anunc16.tif
anunc32.tif
Page 26
System Overview EIA-232 Peripheral Devices (TB4)
26 AFP-200 PN 15511:H2 10/14/2002
1.10 EIA-232 Peripheral Devices (TB4)
1.10.1 Overview
The control panel is compatible with the following printers and display devices that connect through the EIA-232 interface on CPU terminal TB4:
PRN printer
Keltron remote printer
CRT-2 display terminal
For installation instructions for these devices, refer to “EIA-232 Devices – Remote Printers and CRTs (TB4)” on page 37.
1.10.2 PRN Remote Printer
The PRN is an optional printer that connects directly to the control panel through TB1 on the CPU and can be located up to 50 feet (15.24 m) from the control panel. It features the following:
Provides a printed record (80 columns of data on standard 9" x 11" tractor-feed paper) of all system events (alarm, trouble) and status changes within the system.
Time-stamps the printout with the current time-of-day and date. Note: Time stamping is a function of the AFP-200 panel.
1.10.3 Keltron Remote Printer (Model VS4095)
The VS4095 is a two-color (red and black), 40-column, 24 VDC printer that can print up to 50 messages in 90 seconds. This printer connects to the EIA-232 TB4 in the control panel through TB1 on the CPU, from which it gets its power, and mounts in a separate cabinet next to the control panel. The VS4095 meets UL fire and security requirements for an ancillary device. For more information on the Keltron printer, contact the manufacturer (Keltron Corp., Waltham, MA). Refer to “Keltron Printer” on page 38 for installation instructions.
1.10.4 CRT-2 Display Terminal
The optional CRT-2 Display Terminal connects to the control panel via the EIA-232 serial interface (TB4) and can be located up to 50 feet (15.24 m) from the control panel. The CRT-2 displays data on 26 lines by 80 columns and allows you to do the following:
Control and view events, points, and event history
Control the system (Acknowledge, Alarm Silence, and System Reset).
Change important system operating parameters, such as enable/disable of addressable points, change alarm and pre-alarm sensitivities, clear verification counters, clear history, and set the pre-alarm action level.
Page 27
Specifications System Overview
AFP-200 PN 15511:H2 10/14/2002 27
1.11 Specifications
This section contains electrical specifications for the control panel.
1.11.1 Primary AC Power (TB7)
Primary AC connections are made through TB7 on the AFP-200. Wire size: minimum 14 AWG with 600 VAC insulation.
AFP-200. 120 VAC, 50/60 Hz, 3.0 A
AFP-200E. 220/240 VAC, 50/60 Hz, 1.5 A
1.11.2 Battery (lead-acid only)
Maximum Charging Circuit Dual Rate High Charge is 29.1 V @ 0.7 A
Normal Flat Charge is 27.6 V @ 0.5 A
Maximum Battery Capacity 18 AH. (Batteries larger than 12 AH require a BB-17
or other UL-listed battery cabinet.)
1.11.3 Signaling Line Circuit (TB6)
Connections between the control panel and the Signaling Line Circuit (SLC) are supervised and power-limited.
Voltage 24 VDC nominal, 27.6 VDC Max.
Maximum length 10,000 ft. (3048 m) per channel (NFPA Style 4) or
10,000 ft. (3048 m) total twisted-pair length (NFPA Style 6 and 7)
Maximum loop current is 250 mA (max short circuit) or 100 mA (normal)
Maximum loop resistance 40 ohms
1.11.4 Notification Appliance and Releasing Circuits (TB2)
The following contains specifications for NACs and releasing circuits available on the AFP-200 (all circuits are power-limited).
Max. wiring voltage drop 2 VDC
Normal Operating Voltage 24 VDC.
NAC circuit 1 2.5 A
NAC circuits 2-4 2.5 A shared total
Current for all external devices 5.0 A
Optional AVPS-24/AVPS-24E Additional 3.0 A of notification appliance power (see
Appendix J “Expansion Power Supplies”)
Optional APS-6R Additional 6.0 A of notification appliance power (see
Appendix J “Expansion Power Supplies”)
Max. signaling current/circuit 2.5 A
End-of-line resistor 4.7K, 1/2-Watt (PN 71252 UL-listed) for NACs)
Releasing circuits REL-4.7K; for control module — REL-47K
Page 28
System Overview Cabinet Dimensions
28 AFP-200 PN 15511:H2 10/14/2002
1.11.5 Relays (TB3)
Relays for Alarm, Trouble, Security, and Supervisory are available on terminal TB3 for power-limited circuits only. Contact ratings for relays through TB3 are:
2.0 A at 30 VDC (resistive), 0.5 A at 30 VAC (resistive)
Alarm and Trouble: Form-C
Supervisory: Form-A
1.11.6 24 VDC Power (TB1)
Terminal Block (TB1) provides 24 VDC power as follows:
1.12 Cabinet Dimensions
1.12.1 Surface Mount with a BB-17 Battery Box
Figure 6 shows dimensions for mounting a cabinet with a BB-17 Battery Box.
Figure 6 AFP-200 Cabinet and BB-17 Battery Box Dimensions
Four-wire Smoke Detector Power (24 VDC ± 5%) – TB1-5 and TB1-6
• Max. ripple voltage: 10 mVrms
• Up to 500 mA is available for powering four-wire
smoke detectors
1,2
Non-resettable 24 V Power (24 VDC ± 5%) – TB1-3 and TB1-4
• Max. ripple voltage: 10 mVrms
• Total DC current available from this output is up to
500 mA (subtracted from four-wire smoke power)
2
High Ripple Regulated 24 V Power (24 VDC ±10%) – TB1-1 and TB1-2
• Max. ripple voltage: 2 Vrms
• Total DC current available for powering external
devices is 1.0 A standby and 1.5 A alarm2. This power is not recommended for LCD-80 or ACS annunciators except for an ACM-8R.
1
For power supply calculations, refer to Appendix A.
2
Total current for regulated power, non-resettable power, four-wire smoke power, and four Notification Appliance Circuits must not exceed 5 A or 8 A if using an AVPS-24 (refer to Appendix J “Expansion Power Supplies”) or APS-6R. Total external system current in excess of
2.5 A requires 12 AH or 18 AH batteries—not 7 AH.
Door = 16.125"
(40.9575 cm)
Backbox = 16.0"
(40.64 cm)
Battery Box = 8.25"
(20.955 cm)
(Optional BB-17)
Door = 14.625" (37.1475 cm)
Backbox = 14.5" (36.83 cm)
Depth = 4.75" (12.065 cm)
Battery Box = 14.5" (36.83 cm)
(Optional BB-17)
Depth = 5.5" (13.97 cm)
afp2cab-surface.cdr
Page 29
Cabinet Dimensions System Overview
AFP-200 PN 15511:H2 10/14/2002 29
1.12.2 Semi-flush Mount
Figure 7 shows dimensions for semi-flush mounting of the AFP-200 cabinet using a TR-4XG Trim Ring.
Figure 7 Dimensions with TR-4XG Trim Ring
Trim Ring = 17.62"
(44.7548 cm)
Trim Ring = 19.12"
(48.564 cm)
1.5" (3.8 cm) typical
for 4" (10.16 cm) wall
Page 30
Installation Preparing for Installation
30 AFP-200 PN 15511:H2 10/14/2002
Section 2 Installation
2.1 Preparing for Installation
2.1.1 Unpacking the System
Carefully unpack the system and inspect for shipping damage.
Select a location for the control panel in a clean, dry, vibration-free area with moderate temperature.
2.1.2 Installation Notes
Before installing the fire alarm system, read the following:
Install the system in a readily accessible area with sufficient room to easily install and maintain the control panel.
Locate the top of the cabinet approximately 60 inches (1.524 m) above the floor with the hinge mounting on the left.
Count the number of conductors needed for all devices and find the appropriate knockouts.
Review the installation precautions at the front of this manual.
All wiring must comply with the National and/or Local codes for fire alarm systems.
Do not draw wiring into the bottom 9 inches (22.86 cm) of the cabinet, except when using the BB-17. This prevents interference between the power supply and batteries.
2.1.3 Standards and Codes
In addition, installers should be familiar with the following standards:
NEC Article 300 Wiring Methods.
NEC Article 760 Fire Protective Signaling Systems.
Applicable Local and State Building Codes.
Requirements of the Local Authority Having Jurisdiction.
Page 31
Installation Checklist Installation
AFP-200 PN 15511:H2 10/14/2002 31
2.2 Installation Checklist
CAUTION: Make sure to install system components in the precise order in the checklist. Failure to do so can damage the control panel and other system components
Table 6 contains an installation checklist for installing, wiring, and testing an AFP-200 system:
Table 6 Installation Checklist
Table 7 contains a checklist for checking the system with AC power applied:
CAUTION: While checking AC power, make sure batteries are not connected.
Table 7 AC Power Checklist
Task Refer to
Mount the cabinet backbox to the wall. “Backbox Mounting” on page 32
If using expansion power supplies, mount the expansion power supply to the backbox.
Appendix J “Expansion Power Supplies”
CAUTION: Connect the AC power cable and DC battery cables. CAUTION: Do not connect power at this time!
“AC and DC Power Connections” on page 33
Mount an optional module (RTM-8 or 4XTM). “Option Module Installation” on
page 61
Install optional peripheral devices, such as a printer, personal computer, or CRT-2 terminal.
“EIA-232 Devices – Remote Printers and CRTs (TB4)” on page 37
Wire the Signaling Line Circuits. “Wiring a Signaling Line Circuit
(SLC)” on page 41
Connect AC power to control panel — but do not connect batteries.
“AC Power Connections (TB7)” on page 33
Check AC power—but do not connect batteries. Table 7
Program the control panel. Section 3 “Programming”
Connect the batteries. “Battery Power Connection (J3)”
on page 34
Walk test the system. “How to do a Walk Test (6=walk
test)” on page 99
Component Status
The CPU The green AC Power indicator on; the system Trouble indicator
on because of no battery power.
option module The yellow Trouble indicator may come on for approximately 10
seconds after applying AC power. (This only applies to an unconfigured system.)
AVPS-24/AVPS-24E or APS-6R
The yellow Trouble indicator comes on because batteries are not connected.
!
!
!
Page 32
Installation Backbox Mounting
32 AFP-200 PN 15511:H2 10/14/2002
2.3 Backbox Mounting
Figure 8 shows the dimensions of the cabinet backbox:
Figure 8 Backbox Dimensions
1. Remove the CPU board assembly by unscrewing the four screws in the corners of the board. Set the CPU board aside in a safe, clean place. Avoid static discharge which may damage the board.
2. Mark and predrill the four mounting bolts using dimensions shown in Figure 8.
3. Install two upper fasteners in wall with screw heads protruding.
4. Using upper keyholes, mount the backbox over the two screws. Tighten the screws.
5. Install and tighten the lower two screws.
6. When location is dry and free of construction dust, reinstall the CPU board.
afpcabdim.cdr
16.0"
(40.64 cm)
9.5"
(23.495 cm)
0.5"
(1.27 cm)
12.5" (31.75 cm)
14.5" (36.83 cm)
1.0"
(2.54 cm)
Page 33
AC and DC Power Connections Installation
AFP-200 PN 15511:H2 10/14/2002 33
2.4 AC and DC Power Connections
This section contains illustrations and instructions for connecting AC and DC power to the control panel.
WARNING: Several different sources of power can be connected to the control panel. Disconnect all sources of power before servicing. The control panel and associated equipment may be damaged by removing and/or inserting cards, modules, or connecting cables while this control panel is energized.
WARNING: Use extreme caution when connecting power—high voltage and AC line-connected circuits are present in the control panel. Turn off and remove all power sources. To reduce the risk of electric shock—make sure to properly ground the control panel.
2.4.1 AC Power Connections (TB7)
Primary power required for the AFP-200 is 120 VAC, 50/60 Hz, 3 A and primary power required for the AFP-200E is 220/240 VAC, 50/60 Hz, 1.5 A. Overcurrent protection for this circuit must comply with Article 760 of the National Electrical Code (NEC) and/or local codes. Use 14 AWG or larger wire with 600 VAC rating. Connect AC power, using a grounded power cord, to the TB7 on the control panel as follows:
1. Turn off all power sources to the control panel.
2. Insert the stripped ends of the power cord through the knockout on the bottom of the control panel (Figure 9).
3. Connect the earth ground (green) wire to the TB7 terminal labeled “GND”.
4. Connect the neutral wire to the TB7 terminal labeled “NEUT”.
5. Connect the hot wire to the TB7 terminal labeled “HOT”.
Figure 9 AC Power Connections (TB7)
!
!
TB7 – AC power
connector
AC power cord
Knockout in bottom of cabinet
Page 34
Installation AC and DC Power Connections
34 AFP-200 PN 15511:H2 10/14/2002
2.4.2 Battery Power Connection (J3)
WARNING: Battery contains sulfuric acid which can cause severe burns to the skin and eyes, and can destroy fabrics. If contact is made with sulfuric acid, immediately flush skin or eyes with water for 15 minutes and seek immediate medical attention.
Observe polarity when connecting the battery to the control panel. To connect the battery to the control panel, follow these steps:
1. Calculate the battery rating and size required for your installation. For instructions, refer to Appendix A.
2. Connect the battery cable to J3 on the CPU board using the plug-in connector provided.
Figure 10 AC and Battery Power Connections
2.4.3 Expansion Power Supplies – AVPS-24 or APS-6R
(Optional)
Expansion power supplies can provide additional notification appliance power for Notification Appliance Circuits 3 and 4 (TB2) on the control panel. The control panel can accommodate one of the following expansion power supplies:
the Audio/Visual Power Supply (AVPS-24); or
the Auxiliary Power Supply (APS-6R).
For detailed information, including installation instructions, refer to Appendix J “Expansion Power Supplies”.
!
J3 Battery Power
Battery cable
Page 35
DC Output Power Connections (TB1) Installation
AFP-200 PN 15511:H2 10/14/2002 35
2.5 DC Output Power Connections (TB1)
Figure 11 shows the outputs for DC voltage connections from TB1 on the CPU:
Note: All DC power outputs are power-limited.
Figure 11 DC Output Power Output Connections
2.6 Output Circuits (TB2)
Output circuits consist of Notification Appliance Circuits (NACs) connected through TB2 on the control panel. When connecting output circuits, note the following:
Use UL-listed 24 VDC notification appliances only. Refer to the Device Compatibility Document for a list of compatible devices.
Circuits are supervised and power-limited.
Figure 12 shows typical connections for NACs connected to TB2.
2.6.1 Notification Appliance Circuits
The control panel provides four Notification Appliance Circuits (Style Y). Each NAC can supply up to 2.5 A of current. Total current drawn from these as well as DC power outputs cannot exceed 5.0 A. An additional 3.0 A are available when using an expansion power supply (AVPS-24/AVPS-24E or APS-6R). For details on expansion power supplies, refer to Appendix J “Expansion Power Supplies”.
Non-resettable Power 24 VDC filtered, regulated, non-resettable power can be drawn from TB1 terminals 3 (+) and 4 (–).
Four-wire Smoke Detector Power 24 VDC filtered,
regulated, resettable power for four-wire smoke detectors can be obtained from TB1 terminals 5 (+) and 6 (–).
High Ripple Regulated Power 24 VDC power for notification appliances. TB1 terminal 1 (+) and 2 (–). Note: This power is unsuitable for all EIA-485 annunciation devices, except the ACM-8R.
Page 36
Installation Standard Relays (TB3)
36 AFP-200 PN 15511:H2 10/14/2002
Figure 12 Output Circuit Connections (TB2)
2.7 Standard Relays (TB3)
The control panel provides a set of Form-C alarm and a set of Form-C trouble contacts rated for 2.0 A @ 30 VDC (resistive). The control panel also provides a Form-A supervisory contact rated for 2.0 A @ 30 VDC (resistive).
Figure 13 Relay Connections (TB3)
T B 3
T B 2
T B 1
1
1
2233445566778
8
+ -
+ -
Polarized Horn
Polarized Strobe
Style Y Notification Appliance Circuit
(supervised and power-limited)
Dummy Load all unused Circuits 4.7K, 1/2-Watt
4.7K, 1/2-Watt (PN 71252 UL-listed)
+ –
Note: Notification circuit polarity shown in alarm state.
Polarized Bell
afpoca.cdr
Form-C contacts
Form-A contact
Page 37
EIA-232 Devices – Remote Printers and CRTs (TB4) Installation
AFP-200 PN 15511:H2 10/14/2002 37
2.8 EIA-232 Devices – Remote Printers and CRTs (TB4)
2.8.1 Overview
The PRN remote printer provides a hardcopy printout of all status changes within the system and time-stamps the printout with the current time and date from the panel. The PRN provides 80 columns of data on standard 9-inch by 11-inch (22.86 cm by 27.94 cm) tractor-feed paper.
2.8.2 Printer Configuration
Refer to the documentation supplied with the PRN for instructions on the printer’s menu controls. Set the printer’s options as listed in Table 8.
Table 8 PRN Remote Printer Options
2.8.3 Installation
Remote printers require 120 VAC, 50/60 Hz primary power. A secondary power source (battery backup) is not provided. The use of a separate uninterruptable power supply (UPS), UL-listed for Fire Protective Signaling is recommended.
Option Setting
L/R Adjust 0
Font Draft
LPI 6 LPI
ESC Character Esc
Bidirectional Copy On
CG-Tab Graphic
Country E–US ASCII
Auto CR ON
Color Option Not installed
Formlen:
Lines
Standard
6 LIP-60 Executive 10.5
CPI 10 CPI
Skip 0.0"
Emulate Epson
I/O:
Baud Format Protocol
40KB
2400 7 bit, Even, 1 Stop XON/XOFF
Character Extended
S1. Zero On
Auto LF Off
Menlock All
Paper:
Bin 1 Bin 2 Single Pull Tra Pap Roll Paport
12/72" 12/72" 12/72" 12/72" 12/72" No
Page 38
Installation EIA-232 Devices – Remote Printers and CRTs (TB4)
38 AFP-200 PN 15511:H2 10/14/2002
Connection between the control panel and the PRN is via an EIA-232 interface. A custom cable must be assembled for connection to the printer's EIA-232 port.
Figure 14 Remote Printer Connections
2.8.4 Keltron Printer
Figure 15 shows typical connections between the control panel and a Keltron printer.
Figure 15 Keltron Printer Connections
Notes on Figure 15:
1. Outputs are power-limited, but are not supervised.
2. Connections must be made with overall foil/braided-shield twisted paired cable
7 321
TB4
TB5 TB6
TX REF RX REF
OUT OUT IN IN
1 2 3 4 5 6
A B B + A+ B- A-
DB-25 Connections:
Connect TX (Pin 3) to TB4 terminal 1 Connect REF (Pin 7) to TB4 terminal 2 Connect RX (Pin 2) to TB4 terminal 3
Note: When using a DB-25 for Upload/Download connect a jumper between pin 6 and pin 20.
DB-9 Connections:
Connect TX (Pin 2) to TB4 terminal 1 Connect REF (Pin 5) to TB4 terminal 2 Connect RX (Pin 3) to TB4 terminal 3
Note: If also using a DB-9 connector for upload/download connect a jumper between pin 4 and pin 6.
Plug the DB-9 or DB-25 connector into the EIA-232 port of the printer.
The EIA-232 printer interface may also be used with EDP UL-listed equipment, such as personal computers, to monitor the control panel for supplementary purposes.
afp2rprn.cdr
TB4
TB5 TB6
TB1
TB2 TB3
7 321
Keltron Printer
Model number VS4095/5 (see note 3)
Plug this DB-25 connector into the EIA-232 port of the printer
Keltron Remote Printer
DC IN+
DC IN -
24VDC (14 AWG)
af
p
2kltn.cdr
Page 39
EIA-232 Devices – Remote Printers and CRTs (TB4) Installation
AFP-200 PN 15511:H2 10/14/2002 39
suitable for EIA-232 applications. Typically, 50 feet (15.24 m) is the maximum recommended wiring distance between printer and control panel.
3. The printer communicates using the following protocol:
4. Set DIP switches SP1 and SP2 on the Keltron printer as follows:
2.8.5 CRT Connections
For terminal interface and protocol information, refer to Appendix I.
This section shows how to connect a CRT to the control panel and how to connect a combination of CRTs and printers (daisy chain). Figure 16 shows typical connections for a CRT to the control panel:
Figure 16 CRT Connections
Baud rate 2400
Parity Even
Data Bits Seven
Stop B its One
SP1-1: OFF SP1-2: ON SP1-3: OFF SP1-4: ON SP1-5: OFF
SP1-7: ON SP1-8: OFF SP2-1: OFF SP2-2: OFF SP2-3: OFF
SP2-4: OFF SP2-5: OFF SP2-7: ON SP2-8: OFF
7 321
TB4
TB5 TB6
TX REF R X REF
OUT OUT IN IN
1 2 3 4 5 6
A B B+ A+ B- A-
Connect TX (Pin 3) to TB4 terminal 1 Connect REF (Pin 7) to TB4 terminal 2 Connect RX (Pin 2) to TB4 terminal 3
afp2rprn.cdr
Page 40
Installation EIA-232 Devices – Remote Printers and CRTs (TB4)
40 AFP-200 PN 15511:H2 10/14/2002
Figure 17 shows typical connections for daisy chaining multiple CRTs, printers, or both. (Refer to CRT configuration in Appendix I.)
Figure 17 Connections For Multiple CRTs or Combined CRTs and Printers
7
321
EIAportcrt.cdr
Twist ed P air
To AUX Port of CRT
To EIA Port of CRT
with keyboard
To EIA Port of next
CRT or PRN
To T B 4 - 2 To T B 4 - 1
To T B 4 - 3
7
321
7
321
Page 41
Wiring a Signaling Line Circuit (SLC) Installation
AFP-200 PN 15511:H2 10/14/2002 41
2.9 Wiring a Signaling Line Circuit (SLC)
2.9.1 Overview of SLC Wiring
Communication between the control panel and intelligent and addressable initiating, monitor, and control devices takes place through a Signaling Line Circuit (SLC). You can wire an SLC to meet the requirements of NFPA Style 4, Style 6, or Style 7 circuits. This section covers the topics outlined in Table 9:
Table 9 SLC Wiring Topics
Top i c s Refer to
Setting an Address for a monitor, control, or relay module
Figure 22.
Methods for terminating wiring leaving the control panel
“SLC Shield Termination” on page 43.
Wire Requirements for a Two-wire SLC
“Wire Requirements for a Two-wire SLC” on page 45, which covers:
• Loop resistance for a Two-wire SLC.
• Total wiring length for a Two-wire SLC.
• Typical Wiring for a Two-wire SLC.
Wire Requirements for a Four-wire SLC
“Wire Requirements for a Four-wire SLC” on page 46, which covers:
• Loop resistance for a Four-wire SLC.
• Total wiring length for a Four-wire SLC.
• Typical Wiring for a Four-wire SLC.
Wiring an ISO-X Isolator Module
“Wiring an Isolator Module (ISO-X)” on page 49, which covers:
• Description of an ISO-X Module
• Isolating a Branch of a Two-wire SLC
Wiring a Conventional Initiating Device Circuit (IDC)
“Wiring an IDC with Monitor Modules” on page 50, which covers:
• Description of Monitor Modules
• Wiring a Two-wire or Four-wire IDC.
Wiring Notification Appliance Circuits (NACs)
“SLC Wiring with Control Modules” on page 57, which covers:
• Description of control/relay modules
• Wiring a Relay Module
• Wiring a Control Module
• Wiring a Two-wire NAC (Style Y)
• Wiring a Four-wire NAC (Style Z)
Wiring an Intelligent Detector
“SLC Wiring with an Intelligent Detector” on page 59
Wiring an Addressable Manual Pull Station
“SLC Wiring with an NBG-12LX Addressable Manual Pull Station” on page 60
Page 42
Installation Wiring a Signaling Line Circuit (SLC)
42 AFP-200 PN 15511:H2 10/14/2002
2.9.2 SLC Devices
Communication with intelligent and addressable initiating, monitor, and control devices takes place through a Signaling Line Circuit (SLC). You can wire an SLC to meet the requirements of NFPA Style 4, Style 6, or Style 7 circuits. Table 10 contains descriptions of devices connected to an SLC:
Table 10 SLC Devices
Maximum wiring distance of an SLC:
Style 4. 10,000 ft. (3048 m) (12 AWG)
Style 6, 7. 10,000 ft. (3048 m) (12 AWG) total twisted-pair.
2.9.3 Control Panel Capacity
Refer to the installation drawings supplied with each loop device for rating and specification information.
AFP-200 capacity includes up to 99 intelligent detectors and an additional combination of up to 99 addressable pull stations, and monitor, control and relay modules. In addition, the control panel also supports four Notification Appliance Circuits and up to 99 programmable relays.
Figure 18 AFP-200 Capacity
Type of Device SLC Function
Isolator Modules (ISO-X)
Allows a zone of detectors and modules to be electrically isolated from the remainder of the loop, which lets critical loop components function if a circuit fails. ISO-X modules are required for NFPA Style 7 circuits.
Addressable Monitor Modules
Allows the control panel to monitor entire circuits of conventional alarm-initiating devices, such as manual pull stations, detectors, waterflow and supervisory devices.
Control Modules Allows the control panel to selectively activate Notification Appliance
Circuits (NACs).
Relay Modules Allows the control panel to selectively activate Form-C output relays.
XP5-M Allows the control panel to monitor up to five Initiating Device Circuits
(IDCs). Each XP5-M occupies five consecutive addresses on the SLC.
XP5-C Allows the control panel to control a maximum of five individual
notification appliance/telephone circuits or Form-C relays. Each XP5-C occupies five consecutive addresses on the SLC.
Intelligent Detectors Allows the control panel to communicate with intelligent ionization,
photoelectric, and thermal detectors on the SLC.
Addressable Pull Station
The NBG-12LX provides a manual method of creating an alarm activation.
A
fp2incab
JP2
JP7
JP5
SW3
SW2
JP3
JP9
JP1
JP6
SLC – Up to 198 intelligent/addressable devices
Page 43
Wiring a Signaling Line Circuit (SLC) Installation
AFP-200 PN 15511:H2 10/14/2002 43
2.9.4 SLC Performance
SLC performance depends on the type of circuit: Style 4, Style 6, or Style 7. Table 11 lists the trouble conditions that result when a fault exists on an SLC.
Table 11 SLC Performance
2.9.5 SLC Shield Termination
Overview
All wiring leaving the control panel must be shielded. Figure 19, Figure 20, and Figure 21 show three methods of wiring termination, depending on the type of conduit used: a) no-conduit, b) full-conduit, and c) partial-conduit.
No-Conduit Shield Termination
Do not allow the shield drain wire to enter the system cabinet. Connect the drain wire to the outside of the cabinet using a cable connector as shown in Figure 19:
Figure 19 Shield Termination – No Conduit
Full-Conduit Shield Termination
For Style 6 or Style 7 field-wiring of the SLC, connect each end of the shield to the negative side of the respective channel as shown in Figure 20:
Figure 20 Shield Termination – Full Conduit
Fault in SLC Style 4 Style 6 Style 7
Open Trouble Alarm/Trouble Alarm/Trouble
Ground Alarm/Trouble Alarm /Trouble Alarm/Trouble
Short Trouble Trouble Alarm/Trouble
Short and open Trouble Trouble Trouble
Short and ground Trouble Trouble Alarm/Trouble
Open and ground Trouble Alarm /Trouble Alarm/Trouble
Communications loss
Trouble Trouble Trouble
Trouble indicates a trouble signal will be generated at the control panel during the abnormal
condition.
Alarm/Trouble indicates an alarm signal can be transmitted to the control panel during the
abnormal condition.
• SLC operation meeting Style 7 requirements isolates entire physical zones on the SLC from faults that occur within other areas of the SLC.
Shield Drain Wire
Scrape paint away from the cabinet to make good electrical connections.
shield1.wmf
SLC +
SLC -
Cabinet
Shield Drain Wire: The shield must not be connected to earth ground at any point.
The shield drain wire must be connected to the negative (–) side of the loop. Do not let the shield drain wire or the shield foil touch the system cabinet.
Cabinet
shield2.wmf
SLC +
SLC -
Page 44
Installation Wiring a Signaling Line Circuit (SLC)
44 AFP-200 PN 15511:H2 10/14/2002
Partial-Conduit Shield Termination
Do not allow the shield drain wire to enter the system cabinet or the conduit. Connect the drain wire to the termination point of the conduit run.
Figure 21 Shield Termination – Partial Conduit
2.9.6 Setting an SLC Address for a Module
Each module can be set to one of 99 addresses (01-99) and is factory preset with an address of “00”. Addresses past 99 are not recognized by this system.
To set an SLC address, use a common screwdriver to adjust the rotary switches on the module to the desired address. The unit below is set at “35”. When finished, mark the address on the module face in the place provided.
Figure 22 Setting SLC Address on Module
If the length of conduit from the control panel cabinet exceeds 20 feet (6.096 m), terminate the shield as shown. If using a metal box, you must use a metal conduit.
Cabinet
Shield Drain Wire
SLC +
SLC -
TENS
ONES
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
SLC-setadd.cdr
Rotary Switches
Breakaway Tab - Devices come with a raised breakaway tab on the TENS rotary switch. This tab must be left intact for this system.
Page 45
Wiring a Signaling Line Circuit (SLC) Installation
AFP-200 PN 15511:H2 10/14/2002 45
2.9.7 Wire Requirements for a Two-wire SLC
Measuring Loop Resistance for a Two-wire SLC
The total DC resistance from panel to branch end cannot exceed 40 ohms. Measure DC resistance as shown in Figure 23:
Figure 23 Measuring DC Resistance of a Two-wire SLC
1. Short the termination point of one branch at a time. Measure the DC resistance from the beginning of the loop to the end of that particular branch.
2. Repeat this procedure for all remaining branches in the SLC.
Measuring Total Wire Length for a Two-wire SLC
The total length of wire (12 AWG) in a two-wire SLC cannot exceed 10,000 feet (3048 m). Find the total length of wire in the SLC by summing the wire lengths on each branch of the SLC. Figure 24 shows how to find the total length wire in a typical two-wire SLC.
CAUTION: Terminate shield drain wire according to the instructions in “SLC Shield Termination” on page 43.
Figure 24 Measuring the Total Length of Wire in a Two-wire SLC
For detailed wiring requirements, refer to Appendix F.
SLC Out
Branch
!
(Branch A) +(Branch B) +(Branch C) +(Branch D) + (Branch E) =10,000 feet (3048 m) or less (12 AWG)
Branch B
Branch E
Branch C
Branch D
Loop Out Branch A
no connection
CPU
TB6
Page 46
Installation Wiring a Signaling Line Circuit (SLC)
46 AFP-200 PN 15511:H2 10/14/2002
2.9.8 Wire Requirements for a Four-wire SLC
Measuring Loop Resistance for a Four-wire SLC
The total DC resistance of the SLC pair cannot exceed 40 ohms. Measure DC resistance as shown in Figure 25. For detailed UL wiring requirements, refer to Appendix F.
1. Disconnect the SLC Out and SLC Return at the control panel.
2. Short the two leads of SLC Return.
3. Measure the resistance across the SLC Out leads (Figure 25).
Figure 25 Meter Leads for Measuring a Four-wire SLC
Measuring Total Wire Length for a Four-wire SLC
The total length of wire (12 AWG) in a four-wire SLC cannot exceed 10,000 feet (3048 m). Figure 26 identifies the output and return loops from SLC terminal TB5 on the CPU:
Figure 26 Measuring the Wire Length – Four-wire SLC
SLC Out
SLC Return
T-Tapping is not allowed on a four-wire SLC.
CPU
SLC A (loop return)
SLC B (output loop)
no connection
TB5
Page 47
Wiring a Signaling Line Circuit (SLC) Installation
AFP-200 PN 15511:H2 10/14/2002 47
Figure 27 shows typical wiring of a supervised and power-limited two-wire SLC that meets NFPA 72 Style 4 requirements.
CAUTION: Terminate shield drain wire according to the instructions in “SLC Shield Termination” on page 43.
Note: ISO-X devices are not required to meet NFPA Style 4. You can install a maximum of 25 devices, detectors, and modules between isolator modules, or isolator detector mounting base.
Figure 27 Two-wire SLC (Style 4)
!!
1 2 3 4
TB4
TB5 TB6
TX REF RX REF
OUT OUT IN IN
1 2 3 4 5 6
A B B+ A+ B- A-
2(+)
1(-)
3
LOOP ADDRESS
TYPE
Low Med High
1
2
3
4
1
2
3
4
90 81 72 63 54
­+
+-
90 81 72 63 54
-
+
+
-
CPU
Connect (+) to TB 6-3 Connect (–) to TB 6-5
B710LP Detector Base
Use with FSP, FSI, and FST
Series intelligent detectors
Separate T-Tap to other SLC devices
no connection
NBG-12LX
Monitor ModuleControl or Relay
Module
Loop Isolator Module Loop Isolator Module
AFP200-SLC-6.cdr
Page 48
Installation Wiring a Signaling Line Circuit (SLC)
48 AFP-200 PN 15511:H2 10/14/2002
Figure 28 shows typical wiring for a supervised and power-limited four-wire SLC that meets NFPA 72 Style 6 requirements.
CAUTION: Terminate shield drain wire according to the instructions in “SLC Shield Termination” on page 43.
Figure 28 Typical Four-wire SLC Circuit (Style 6)
!!
TB4
TB5 TB6
TX REF RX REF
OUT OUT IN IN
1 2 3 4 5 6
A B B+ A+ B- A-
2(+)
1(-)
3
LOOP ADDRESS
TYPE
Low Med High
1
2
3
4
1
2
3
4
1 2 3 4
90 81 72 63 54
-
+
+
-
90 81 72 63 54
-
+
+-
CPU
Connect SLC Out to TB 6-3 (+) and TB 6-5 (–). Connect SLC Return to TB 6-4 (+) and 6-6 (–).
B710LP Detector Base
Use with FSP, FSI, and FST
Series intelligent detectors
no connection
NBG-12LX
Monitor ModuleControl or Relay
Module
Loop Isolator Module Loop Isolator Module
AFP200-SLC-6.cdr
Page 49
Wiring a Signaling Line Circuit (SLC) Installation
AFP-200 PN 15511:H2 10/14/2002 49
Style 7 Wiring Overview
Figure 29 shows typical wiring of a four-wire SLC that meet NFPA Style 7 requirements. As shown in Figure 29, flanking each SLC device with a pair of ISO-X isolator modules protects each device from short circuit faults that may occur on other SLC devices. For example, a fault on zone 2 will not affect zones 1 and 3. ISO-X modules on either side of zone 2 will open the SLC. Zone 1 will still operate from power on loop out and zone 3 will operate from SLC return. Because the control panel cannot communicate with zone 2, a trouble signal(s) will be generated for that device.
Note: Do not T-Tap or branch a Style 7 four-wire SLC. Ratings and characteristics are identical to a NFPA Style 6 four-wire SLC.
Figure 29 Four-wire SLC (Style 7)
2.9.9 Wiring an Isolator Module (ISO-X)
ISO-X Module Overview
You can connect a maximum of 25 devices between isolator modules. During a fault condition, the control panel registers a trouble condition for each addressable device which is isolated on the SLC segment or branch.
Refer to 2.9.6 “Setting an SLC Address for a Module” for instructions on addressing the modules.
Addressable Manual Pull Station (flanked by ISO-X modules)
Note: All wiring between a manual pull station and ISO-X modules should be enclosed in conduit.
Note: If a non ISO base is used, install ISO-X modules on both sides of devices within 20 feet (6.096 m) in rigid conduit.
Note: Locate ISO-X module near detector. Enclose wiring between detector and ISO-X in conduit.
CPU
Connect SLC Out to TB 6-3 (+) and TB 6-5 (–). Connect SLC Return to TB 6-4 (+) and TB 6-6 (–).
SLC Out
SLC Return
Addressable Detector (Zone 1)
Two-wire Isolator Detector Base
(Zone 2)
Addressable
Pull Station
(Zone 3)
Control Panel
ISO-X
ISO-X
ISO-X
ISO-X
ISO-X
_
+
_
+
1
2
3
4
5
6
A+BB+ B-A-A
1
2
34
1
2
34
1
234
1
2
3
4
1
2
3
1
2
3
4
Page 50
Installation Wiring a Signaling Line Circuit (SLC)
50 AFP-200 PN 15511:H2 10/14/2002
Figure 30 ISO-X Module Terminal Connections
Isolating a Branch of a Two-wire SLC
A short circuit on the SLC Style 4 branch (connected to ISO-X terminals 3 and 4) causes the branch to be disconnected and isolated from the remainder of the SLC. This prevents a communication problem with all other addressable devices on the branches (labeled “Continuation of the SLC” in Figure 31) and all addressable devices on the isolated branch will report a trouble condition at the CPU.
Figure 31 Wiring an ISO-X (Style 4)
2.9.10 Wiring an IDC with Monitor Modules
Overview of Monitor Modules
The FMM-1, FZM-1, and FMM-1 Monitor Modules are addressable modules that monitor conventional contact-type, alarm, supervisory, security, alert, or trouble initiating devices. You can wire a supervised monitor-module circuit as an NFPA Style B or Style D Initiating Device Circuit (refer to Figure 34 and Figure 35 for Style B; refer to Figure 36 and Figure 37 for Style D).
Refer to 2.9.6 “Setting an SLC Address for a Module” for instructions on addressing the modules.
FMM-1. Use for wiring Style B and Style D IDCs.
FZM-1. The FZM-1 Monitor Module is an addressable module used to monitor a single Initiating Device Circuit of smoke detectors. Use FZM-1 modules to monitor conventional, two-wire smoke detectors. The FZM-1 requires an
SLC In (–)
SLC In (+)
SLC Out (–)
SLC Out (+)
SLC
Continuation of the SLC
T-Tapped branch off the SLC
Page 51
Wiring a Signaling Line Circuit (SLC) Installation
AFP-200 PN 15511:H2 10/14/2002 51
additional connection of 24 VDC filtered, low-noise and resettable power on FZM-1 Terminals 3 (–) and 4 (+).
Figure 32 Standard Monitor Module (FMM-1)
and Two-wire Detector Module (FZM-1)
FMM-101 (Style B circuits only). The FMM-101 is a miniature addressable module that is functionally and electrically identical to an FMM-1 module. Because of the smaller size, an FMM-101 is suitable for mounting directly in the electrical box of a monitored contact-type device.
Figure 33 Miniature Monitor Module (FMM-101)
Wiring a Monitor Module
Connect the SLC wiring to terminals 1 (–) and 2 (+) of FMM-1 and/or FZM-1. SLC wiring on the FMM-101 are the red and black wires identified in Figure 33. The monitor module takes one module address on the SLC.
When installing FMM-1 and FMM-101 modules, note the following:
1. With these modules, the IDC provides the following services (do not mix):
• Fire Alarm Service.
• Automatic/Manual Waterflow Alarm Service with normally open contact
devices.
• Sprinkler Supervision with normally open contact devices.
• Security Service.
2. Maximum IDC wiring resistance is 20 ohms.
Note: Refer to Installation Document shipped with each two-wire detector monitor module for specific installation notes for this variety of module.
8
9
10
11 12
13
14
150
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
TENS
ONES
LOOP
LOOP
A
DDRESS
A
DDRESS
8
9
7
6
5
9
8
7
6
5
0
1
2
3
4
4
3
2
1
0
TENS
ONES
8
9
0
1
2
3
4
5
6
7
8
9
10
11 12
13
14
15
0
1
2
3
4
5
6
7
FMM-1.cdr
Rotary Switches
Areas used to record the device address and SLC number.
SLC-
SLC+
24 VDC
- (FZM-1 only)
24 VDC + (FZM-1 only)
IDC Return +
IDC Return
-
IDC Out +
IDC Out
-
0
10
11
12
13
14
15
ADDRESS
LOOP
1
2
3 4
TENS
ONES
6
7
8
9
5
0
1
2
3 4
6
7
8
9
5
Labels – Use to record the device address and SLC number.
SLC + (Red)
SLC - (Black)
IDC + (Violet)
IDC - (Yellow)
Page 52
Installation Wiring a Signaling Line Circuit (SLC)
52 AFP-200 PN 15511:H2 10/14/2002
Wiring an NFPA Style B IDC with Standard Monitor Modules
Figure 34 shows typical wiring using FMM-1 modules to wire a Style B IDC. Maximum IDC resistance is 20 ohms. Refer to Device Compatibility Document for detector and power supervision relays.
Figure 34 Typical Style B (Class B) IDC Wiring with FMM-1 Modules
TB4
TB5 TB6
TX REF RX REF
OUT O UT IN IN
1 2 3 4 5 6
A B B+ A+ B- A-
TB1
TB2 TB3
+ - + - + -
B+ B- B+ B- B+ B- B+ B- NO C NO NC C NO NC C
++-
-
+
+
-
-++
-
-
+
+
-
-
90 81 72 63 54
-
+
+
-
- +
UL-listed power supervision relay (shown energized)
To next device on the SLC
Manual pull station
Heat detector
24 VDC four-wire smoke detector
24 VDC four-wire detector resettable power:
24 VDC (+) TB1-5 24 VDC (–) TB1-6
SLC out
SLC (+) TB6-3 SLC (–) TB6-5
End-of-Line Resistor 47K, 1/2-watt PN SSD A2143-00 (N-ELR in Canada)
afp200-IDC-B-FMM1.cdr
CPU
Page 53
Wiring a Signaling Line Circuit (SLC) Installation
AFP-200 PN 15511:H2 10/14/2002 53
Wiring an NFPA Style B IDC with Two-wire Detector Modules
Note: Figure 35 shows typical wiring for a supervised and power-limited NFPA Style B IDC using FZM-1 modules. Refer to Installation Document shipped with each two-wire detector monitor module for specific installation notes for this variety of module.
Wiring guidelines for this IDC are:
Refer to the Device Compatibility Document for detector and power supervision relays.
Maximum Initiating Device Circuit (IDC) resistance is 25 ohms.
Maximum alarm current is 90 mA.
Maximum detector standby current is 2.4 mA.
Figure 35 Typical Style B (Class B) IDC Wiring with FZM-1
+
+
-
-
+
+
-
-
TB4
TB5 TB6
TX REF RX REF
OUT OUT IN IN
1 2 3 4 5 6
A B B+ A+ B- A-
TB1
TB2 TB3
+ - + - + -
B+ B- B+ B- B+ B- B+ B- NO C NO NC C NO NC C
90 81 72 63 54
-
+
+
-
- +
3.9K ELR – supplied with monitor module
To the next device on the SLC
24 VDC filtered, regulated and resettable power:
24 VDC (+) TB1-5 24 VDC (–) TB1-6
SLC out
SLC (+) TB 6-3 SLC (–) TB 6-5
FZM-1
Compatible two-wire smoke detectors
AFP200-IDC-B-FZM1.CDR
CPU
Page 54
Installation Wiring a Signaling Line Circuit (SLC)
54 AFP-200 PN 15511:H2 10/14/2002
Wiring an NFPA Style D IDC with Standard Monitor Modules
Figure 36 shows typical wiring for a supervised and power-limited NFPA Style D (Class A) IDC using monitor modules. Maximum IDC resistance is 20 ohms.
Figure 36 Typical Style D (Class A) IDC Wiring with FMM-1
TB4
TB5 TB6
TX REF RX REF
OUT O UT IN IN
1 2 3 4 5 6
A B B+ A+ B- A-
TB1
TB2 TB3
+ - + - + -
B+ B- B+ B- B+ B- B+ B- NO C NO NC C NO NC C
90 81 72 63 54
-
+
+
-
- +
Heat detector
UL-listed power supervision relay (shown energized)
To the next device on the SLC
Manual pull station
24 VDC filtered, low-noise and resettable power:
24 VDC (+) to TB1-5 24 VDC (–) to TB1-6
SLC out
SLC (+) to TB6-3 SLC (–) to TB6-5
Refer to the Device Compatibility Document for detector and power supervision relays.
24 VDC four-wire smoke detector
CPU
AFP200-IDC-B-FZM1.CDR
Monitor Module
Page 55
Wiring a Signaling Line Circuit (SLC) Installation
AFP-200 PN 15511:H2 10/14/2002 55
Wring an NFPA Style D IDC with FZM-1 Modules
Note: Figure 37 shows typical wiring for a supervised and power-limited NFPA Style D (Class A) IDC using FZM-1 modules. Refer to Installation Document shipped with each two-wire detector monitor module for specific installation notes for this variety of module.
Wiring guidelines for this IDC are:
Refer to the Device Compatibility Document for detector and power supervision relays.
Maximum Initiating Device Circuit (IDC) resistance is 25 ohms.
Maximum alarm current is 90 mA.
Maximum detector standby current is 2.4 mA.
Figure 37 Typical Style D (Class A) IDC Wiring with FZM-1 Modules
TB4
TB5 TB6
TX REF RX REF
OUT O UT IN IN
1 2 3 4 5 6
A B B+ A+ B- A-
TB1
TB2 TB3
+ - + - + -
B+ B- B+ B- B+ B- B+ B- NO C NO NC C NO NC C
- +
+
+
-
-
+
+
-
-
90 81 72 63 54
-
+
+
-
To the next device on the SLC
24 VDC filtered, low-noise and resettable power:
24 VDC (+) to TB1-5 24 VDC (–) to TB1-6
3.9K ELR – supplied with FZM-1 module
Compatible two-wire smoke detectors
SLC out:
SLC (+) to TB6-3 SLC (–) to TB6-5
CPU
Page 56
Installation Wiring a Signaling Line Circuit (SLC)
56 AFP-200 PN 15511:H2 10/14/2002
2.9.11 Wiring a Notification Appliance Circuit (NAC) or
Control Circuit
Control and Relay Module Overview
The FCM-1 is an addressable module that controls a Notification Appliance Circuit (NAC). Use the FCM-1 to route 24 VDC NAC Power for NFPA Style Y (Class B) and NFPA Style Z (Class A) notification circuits. Figure 38 shows control module connections.
Figure 38 FCM-1 Control Module Connections
The FRM-1 is an addressable module which includes a Form-C dry contact relay which can be used to activate a variety of output circuits. Figure 39 shows relay module connections.
Figure 39 FRM-1 Relay Module Connections
Ratings for the dry contacts on a Form-C relay module are:
Resistive: 3.0 A @ 30 VDC max Non-coded application
Further rating information is available in the module document and data sheet.
90 81 72 63 54
Style D NAC (+) Style D NAC (–) Style B NAC (–) Style B NAC (+)
no connection
no connection SLC (–) SLC (+) 24 VDC Power (–) 24 VDC Power (+)
Note: Polarity shown in alarm condition
8
9
10
11 12
13
14
15
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
TENS
ONES
LOOP
LOOP ADDRES S
ADDRES S
8
9
7
6
5
9
8
7
6
5
0
1
2
3
4
4
3
2
1
0
TENS
ONES
8
9
0
1
2
3
4
5
6
7
8
9
10
11 12
13
14
150
1
2
3
4
5
6
7
8
9
7
6
5
9
8
7
6
5
0
1
2
3
4
4
3
2
1
0
LOOP
LOOP
SLC
SLC-frmC.cdr
FRM-1
NO
C
NC
NO
C
NC
To next device on SLC
From FACP or previous device on SLC loop
SLC (+) TB6-3 SLC (–) TB6-5
Refer to the installation instruction sheet supplied with the control module for additional information.
Page 57
Wiring a Signaling Line Circuit (SLC) Installation
AFP-200 PN 15511:H2 10/14/2002 57
Installing a Relay Module
Install a relay module by following the instructions below:
1. Connect the SLC from the CPU to relay module terminals 1 (-) and 2 (+) as shown in Figure 39.
2. Set the rotary switches on the relay module to the required SLC address. (The FRM-1 takes one module address on the SLC. Refer to 2.9.6 “Setting an SLC Address for a Module” for instructions on addressing the modules.)
3. Wire the common and the normally-open or normally-closed contacts to the relay module (Figure 39).
2.9.12 SLC Wiring with Control Modules
This section contains instructions and wiring diagrams for wiring a control module to polarized alarm notification appliances. Figure 40 provides a diagram for two-wire appliances wired according to NFPA Style Y NAC. Figure 41 provides a diagram for four-wire appliances wired according to NFPA Style Z.
Style Y NAC Circuits (Two-wire)
Figure 40 shows a supervised and power-limited NFPA Style Y NAC using a control module. This shows polarized alarm notification appliances connected to control modules in a two-wire configuration. A control module can control 3 A of resistive load (on non-coded electronic devices). Further rating information is available in the module document and data sheet. If installing more than one control module NAC, install the power supervision relay on the 24 VDC power bus after the last control module.
Refer to Device Compatibility Document for compatible notification appliances and relays.
Do not T-Tap or branch a Style Y circuit.
Terminate the circuit across the last device using a 47K, 1/2-watt ELR (PN ELR-47K).
Do not run wiring under any terminals. To maintain supervision, break the wire run.
Wiring Diagram and Instructions
Connect the NAC as follows:
1. Connect the SLC to FCM-1 terminals 1 (–) and 2 (+).
2. Connect 24 VDC power (Figure 40).
3. Set the control module rotary switches to the required SLC address. (The control module takes one module address on the SLC.) Refer to 2.9.6 “Setting an SLC
Page 58
Installation Wiring a Signaling Line Circuit (SLC)
58 AFP-200 PN 15511:H2 10/14/2002
Address for a Module” for instructions on addressing the modules.
Figure 40 Typical Wiring for an NFPA Style Y NAC
- +
-
+
+
-
TB4
TB5 TB6
TX REF RX REF
OUT OUT IN IN
1 2 3 4 5 6
A B B+ A+ B- A-
TB1
TB2 TB3
+ - + - + -
B+ B- B+ B- B+ B- B+ B- NO C NO NC C NO NC C
90 81 72 63 54
-
+
+
+
-
-
+
+--
UL-listed Power Supervision Relay
End-of-Line Resistor 47K, 1/2-watt PN SSD A2143-00 (Use an N-ELR in Canada)
24 VDC notification appliances
To next device
on SLC
SLC out
SLC (+) to TB6-3 SLC (–) to TB6-5
24 VDC filtered, regulated, nonresettable
24 VDC (+) to TB1-1 24 VDC (–) to TB1-2
CPU
AFP200-NAC-Y-CMXa.cdr
Control
Module
Page 59
Wiring a Signaling Line Circuit (SLC) Installation
AFP-200 PN 15511:H2 10/14/2002 59
Style Z NAC
Figure 41 shows an NFPA Style Z NAC with notification appliances connected to a control module.
Refer to the Device Compatibility Document for compatible notification appliances.
Connect the NAC as follows:
1. Connect the SLC to control module terminals 1 (–) and 2 (+).
2. Connect 24 VDC power from TB1 to control module terminals 3 and 4.
3. Set the control module rotary switches to the required loop address. (The control module takes one module address on the SLC.) Refer to 2.9.6 “Setting an SLC Address for a Module” for instructions on addressing the modules.
Do not loop wiring under any terminals. Break wire run to maintain supervision. The NAC is supervised and power-limited.
Figure 41 NFPA Style Z Notification Appliance Circuit
2.9.13 SLC Wiring with an Intelligent Detector
Overview for Wiring Intelligent Detectors
The B501 or B710LP base provides the connection between the SLC and the following intelligent detectors: FSP-751, FSI-751, FST-751, and FST-751R.
1. Connect the communications loop to terminal 1 (–) and terminal 2 (+) on the detector mounting base.
2. If using an RA400Z Remote LED Annunciator: (a) connect the RA400Z positive terminal to base terminal 3; and (b) connect the RA400Z negative terminal to base terminal 1.
TB4
TB5 TB6
TX REF RX REF
OUT OUT IN IN
1 2 3 4 5 6
A B B+ A+ B- A-
TB1
TB2 TB3
+ - + - + -
B+ B- B+ B- B+ B- B+ B- NO C NO NC C NO NC C
- +
90 81 72 63 54
-
-
+
+
+
+--
+
+
-
-
UL-listed Power Supervision Relay
24 VDC notification appliances
To next device on SLC
SLC out
SLC (+) to TB6-3 SLC (–) to TB6-5
24 VDC filtered, regulated, nonresettable
24 VDC (+) to TB1-1 24 VDC (–) to TB1-2
CPU
AFP200-NAC-Z-CMXa.cdr
Control Module
Page 60
Installation Wiring a Signaling Line Circuit (SLC)
60 AFP-200 PN 15511:H2 10/14/2002
3. Set the detector address on the head with a small, slotted screwdriver. Mark this address on the base and on the head.
4. Install the intelligent detector head.
Wiring an Intelligent Detector to an SLC
Figure 42 shows typical wiring of a detector (wired to a RA400Z remote annunciator) connected to an SLC:
Figure 42 Typical Wiring of a Detector Base to an SLC
2.9.14 SLC Wiring with an NBG-12LX Addressable Manual
Pull Station
The NBG-12LX is an addressable manual pull station with a key-lock reset feature. Figure 43 shows typical wiring and provides instructions for setting the SLC address.
1. Connect the SLC to terminal screws (+) and (–).
2. Connect the NBG-12LX to the CPU as shown in Figure 43.
3. Set the SLC address of the pull station. Rotary switches are located on the interior of the pull station, as shown in Figure 43. The address is set the same way as for control, monitor & relay modules (refer to “Setting an SLC Address for a Module” on page 44). Factory preset is address 00. Record the device address and SLC number on the label inside the pull station.
Note: In the sample shown below, the switches are set to address 12.
Detector Base
Channel (+)
Channel (–)
to next device on SLC
Channel (+)
Channel (–)
RA400Z Remote LED Annunciator
SLC
Page 61
Option Module Installation Installation
AFP-200 PN 15511:H2 10/14/2002 61
Figure 43 Typical SLC Wiring of an NBG-12LX Pull Station
2.10 Option Module Installation
2.10.1 Overview
The control panel has an option module slot, using connectors J6, J7, and J8 on the CPU board. Two optional modules are available for the control panel: the 4XTM Transmitter Module and the RTM-8 Relay Module. To enable module supervision, you must cut jumper JP5 before installing an option module. Figure 44 shows the location of the connectors and jumper J5.
Figure 44 Optional Module Location
1 2 3 4
TB6
1
23456
+
-
CPU of Control Panel
SLC (+) TB 6-3 SLC (–) TB 6-5
NBG-12LX (rear view)
(+)
(-)
To next device on SLC loop
N
O
R
M
A
L
A
C
T
I
V
A
T
E
D
4 3 2 1
0
0
10
11
12
13
14
15
1
1
2
2
3
3
4
4
TENS
ONES
6
6
7
788
9
9
5
5
LOOP
M
A
DDRESS
PRODUCT IDENTIFICATION LABEL
A
DDRESS
LOOP
NBG-12LX (front view)
Afp2incab
JP2
JP7
JP5
SW3
SW2
JP3
JP9
JP1
JP6
Jumper JP5
J6
J7
J8
Page 62
Installation Option Module Installation
62 AFP-200 PN 15511:H2 10/14/2002
2.10.2 Installing a 4XTM Module
Install the 4XTM module onto the CPU board as follows:
1. Insert the two nylon standoffs (provided) into the holes located on the right-side edge of the main circuit board.
2. Carefully align the pins on the circuit board with the connector on the option board; then, press firmly on the option board until it locks in place on the standoffs.
3. Stick the provided labels on the 4XTM module.
4. Push the disconnect switch (Figure 45) down to prevent unwanted activation of the municipal box during testing of the control panel.
The Disconnect LED remains lighted while the municipal box is disconnected. The System Trouble LED will indicate disconnected and/or open circuit conditions on the municipal box. During trouble conditions, it is possible to obtain the circuit condition on the alarm reverse-polarity output. If this operation is desired, cut the TBL jumper (shown in Figure 45)
Figure 45 shows 4XTM module components with polarities shown in activated positions.
Figure 45 4XTM Module Connections and Components
Standoffs
4XTM Option Board
CPU Board
Polarities are shown in activated positions.
Page 63
Option Module Installation Installation
AFP-200 PN 15511:H2 10/14/2002 63
2.10.3 Installing an RTM-8 Module
Install the RTM-8 module onto the CPU board according to the following directions. If the FACP is in a high vibration area where additional support is desired, install the RTM-8 with a DP-AFP200 Dress Panel, using every step in Figure 46 below. Steps 4 and 8 are not necessary if a dress panel is not installed.
Figure 46 RTM-8 Relay Module Installation
AFP-200 CPU
1. Remove screw from lower right corner of the AFP-200 CPU board. Reserve the screw for later use. Note: Remember that jumper JP5 must be cut to enable module supervision (See Figure 44 on page 61. )
2. Replace the screw with one of the three short (1/2 in, 12.7 mm) metal standoffs supplied with the RTM-8 module.
AFP-200 CPU
3. Place the other two short metal standoffs into the AFP-200 CPU holes as indicated. Fasten them with two of the nuts supplied with the RTM-8 module.
4. Note: Use this step only when using a DP-AFP200 dress panel.
Attach one of the two long (15/16 in, 23.8 mm) metal standoffs to the upper left corner of the RTM-8 as indicated. Fasten with the third nut supplied.
5. Carefully align the pins on the circuit board with the connector on the RTM-8 module; then press firmly on the module until it locks in place and rests on the standoffs installed in steps 2 and 3 above.
6. Secure the upper right corner of the RTM-8 with the (remaining) long metal standoff.
7. Using the screw removed from the AFP-200 CPU and the screw supplied with the RTM-8, secure the module to the CPU at the points indicated.
8. Note: Use this step only when using a DP-AFP200 dress panel.
Install the DP-AFP200 Dress Panel per instruction document supplied with the dress panel. This installation provides extra mounting support for the module in areas of high vibration.
AFP2ptla.cdr
AFP2ptlb.cdr
AFP2RTM8lngstdoff.cdr
AFP200i
nsta
ll
e
d
rtm
8
.c
d
r
Page 64
Installation Option Module Installation
64 AFP-200 PN 15511:H2 10/14/2002
Figure 47 shows electrical connections for the RTM-8 module.
Figure 47 RTM-8 Module Connections
Notes on the RTM-8 module
1. Zone Relay Contact Ratings – 6 A @ 30 VDC or 300 VAC. Material: Silver Nickel.
2. Refer to the power-limited label located on the AFP-200 cabinet door. Make a notation on the label for each circuit used as a nonpower-limited circuit. (Refer to the example on the label).
The RTM-8 module is not suitable for separate transmission of both alarm and trouble signals to remote station.
3. Polarity Reversal Output – 24 VDC (nominal), 10 mA maximum rated current. Internal resistance: 1200 ohms (nominal). Intended for connection to the polarity reversal circuit of a remote station receiving circuit (Fire•Lite RS-82) having compatible ratings. Output is power-limited. Wiring can exit the protected premises.
4. Municipal Box output – Supervised for open circuit. Nonpower-limited. Maximum short current circuit: 0.6 A. Maximum open circuit voltage: 27.6 VDC. Maximum wire resistance: 3 ohms. Wiring can exit the protected premises.
C NO NC
Local Energy Municipal Box LED (yellow)
Relay Disconnect Switch
Transmitter Disconnect Switch
Transmitter Disabled LED (yellow) Relay Disabled LED (yellow)
Zone 5
Zone 6
Zone 7
Zone 8
Transmitter Output (-) normal (+) normal
Alarm/Trouble Polarity Reversal Remote Station JP1 must be cut
Alarm only Polarity Reversal Remote Station JP1 must be cut
Local Energy Municipal Box Jumper JP1 is optional
Disconnected
Normal
JP-2 Jumper Settings
Switch Settings
Typical Form-C Relay Configuration
JP2 - Transmitter Module Select
JP1 - Cut for polarity
reversal remote station operation
Zone 1
Zone 2
Zone 3
Zone 4
AFP200-RTM-8.cdr
Place jumper over pins as indicated
Jumper
Jumper
Jumper
Page 65
Overview Programming
AFP-200 PN 15511:H2 10/14/2002 65
Section 3 Programming
3.1 Overview
The AFP-200 is an intelligent, field-programmable Fire Alarm Control Panel. Field-programming the control panel lets you customize the fire alarm system by selecting and setting program options for addressable SLC devices (intelligent detectors, monitor modules, relay modules, and control modules), NACs, and Panel Circuits. There are two levels of programming—Program Change and Status Change. Each requires a password to restrict programming access to authorized personnel. For more details on Program Change and Status Change options, see Table 12.
3.1.1 Programming Methods
The control panel is completely field-programmable and requires no special software skills. You can program the control panel in one of two ways:
1. Using the Autoprogram feature and the control panel keypad is a convenient way to quickly bring the system on-line and to make changes to an existing system program. This chapter provides detailed instructions for programming the control panel using the keypad.
2. Veri•Fire™ is an off-line programming utility that lets you create site-specific programming information using a Windows®-based computer. It is the preferred method for programs requiring a large amount of data entry. For detailed instructions, refer to Veri•Fire’s on-line help program.
3.1.2 In This Section
For details on panel operation, refer to Section 4 “Operation”.
This section provides information for programming the control panel, divided into the main sections that are listed in Table 12.
Table 12 Programming Topics
Section Topic(s) covered Refer to page
Getting Started Programming Passwords
How to Use the Programming Keypad Programming Shortcuts Upload and Download
66 67 68 68
Program Change Options
Instructions and sample screens for Program Change options used to configure and program operation of the control panel, such as: Autoprogramming, programming points, special zones, and system defaults; changing a program password; and checking the program for errors.
70
Status Change Options
Instructions and sample screens for Status Change options that do not affect configuration or basic operation of the control panel, such as: disabling/enabling points, setting system time/date, clearing counters, setting detector sensitivity, and walk-testing the system.
92
Page 66
Programming Getting Started
66 AFP-200 PN 15511:H2 10/14/2002
3.2 Getting Started
3.2.1 How to Access Programming Options
To enter Program Change mode or Status Change mode, follow these steps:
1. Press the
ENTER key to enter programming mode and the LCD display shows the
Programming Entry screen:
Figure 48 Programming Entry Screen
2. Press the 1 key and the following screen appears in the LCD display:
Figure 49 Password Entry Screen
3. Enter the Program Change or Status Change password.
3.2.2 Programming Passwords
There are two programming passwords: Program Change and Status Change:
Program Change password – The password used to access Program Change functions. The Program Change factory-set password is 00000.
Status Change password – The password used to access Status Change functions. The Status Change factory-set password is 11111.
Passwords are user-definable (refer to “How to Change a Programming Password (3=passwd)” on page 85). If you enter an invalid password (or press the
ENTER key
without entering a password), the LCD display shows the Incorrect Password screen, like the one shown in Figure 50:
Figure 50 Sample Incorrect Password Screen
From the Incorrect Password screen (Figure 50), press the
BACKSPACE key and enter the
correct Program Change or Status Change password or contact the manufacturer for assistance.
1=PROGRAMMING 2=READ@STATUS@ENTRY (BACKSPACE@TO@ABORT)
ENTER@PROG@OR@STATUS PASSWORD,@THEN@ENTER. (BACKSPACE@TO@ABORT)
INCORRECT PASSWORD PROGRAM: 0000000 STATUS: 0880880 BACKSPACE@TO@ABORT
Page 67
Getting Started Programming
AFP-200 PN 15511:H2 10/14/2002 67
3.2.3 How to Use the Programming Keypad
The programming keypad lets you enter numeric and alphabetic characters. Entering alphabetic characters is necessary for functions such as changing the LCD display message (“How to Change a System Message (4=message)” on page 86) and custom zone labels (“How to Change a Zone Label (5=zones)” on page 86). Table 13 shows examples of how to enter alphanumeric characters.
Table 13 Entering Alphanumeric Characters
To enter Do this
10
1. Press , then press
2. Press , then press
D16
1. Press two times; then press
2. Press , then press
3. Press , then press
Smoke 1
1. Press four times, then press
2. Press two times, then press
3. Press four times, then press
4. Press three times, then press
5. Press three times, then press
6. Press two times, then press
7. Press , then press then press
ENTER
DET MOD
1
6
8
9
#
2
ABC
3
DEF
4
GHI
5
JKL
MNO
7
PRS
TUV
W
X
Y
Q
Z
-
/
.
Programming keys (12)
cursor keys (4) and ENTER key
right cursor key
left cursor key (BACKSPACE key)
Page 68
Programming Getting Started
68 AFP-200 PN 15511:H2 10/14/2002
3.2.4 Programming Shortcuts
During programming, the control panel automatically returns to normal operation after two minutes of inactivity.
“Programming Shortcuts” on page 68 lists shortcuts that you can use when programming the control panel.
Table 14 Programming Shortcuts
3.2.5 Upload and Download
An upload/download of the control panel may be done at any time by connecting a personal computer to the EIA-232 port and running the off-line programming routine. Refer to the Veri•Fire on-line help program for more information.
3.2.6 Key Programming Terms
Here is a list of terms that apply to control panel programming.
All Systems Normal message The message (up to 40 characters) in first two lines of the LCD display during normal system operation.
Autoprogram A control panel programming function that automatically detects new devices connected to the SLC, assigns default programming information, and also determines the total number of programmed devices.
CBE (Control-by-Event) A software function that provides a means to program a variety of output responses based on various initiating events.
Control module Addressable module that switches power to a Style Y or Style Z NAC.
CPU memory (Central Processing Unit) The nonvolatile element of the CPU that
contains programming information for the control panel.
custom label A custom label is a user-defined message in an LCD display that identifies a device.
detector sensitivity A detector setting for an ionization or photoelectric detector that determines the level at which a detector will activate.
installed device An intelligent, addressable detector, control, monitor or relay module properly addressed and installed in a fire alarm system.
missing device A missing device is a detector or module removed from the SLC (TB6) that exists in the current program.
Monitor module An addressable monitor module that monitors conventional alarm-initiating devices.
To Do this
To save a point’s program into memory during Autoprogram or point programming
Press the
ENTER key. After pressing the ENTER key, the autoprogram
routine displays the next new detector or module.
To exit from Program Change or Status Change operations
Press the
BACKSPACE key until the All Systems Normal screen appears,
or press the
SYSTEM RESET key.
To display the last 19-character label
When the blinking cursor is over the first letter of the label field, press the zero key twice to display the label entered for the previous point. If the last character of the label is a number, pressing the zero key a third time will increment this number. Once you recall the label, you can edit each character of the label.
Page 69
Getting Started Programming
AFP-200 PN 15511:H2 10/14/2002 69
NAC (Notification Appliance Circuit) A circuit or path directly connected to a notification appliance. (Notification appliances include bells, strobes, and horns that produce an audible signal, visual signal, or both.) You can use an NAC for coding functions (March Time, California Code, Temporal, and Two Stage).
new device New devices include detectors and modules connected to the SLC (TB6) that do not exist in the current program.
obscuration A smoke measurement, usually expressed in percent per foot (30.48 cm), that calculates reduction in the atmospheric transparency caused by smoke.
panel circuit One of four NACs (B01, B02, B03, or B04) available through TB2 on the control panel that connects to a notification appliance (such as a bell, strobe, horn, and so on). Each NAC can be programmed with CBE.
point A detector, module, or panel circuit properly installed, addressed, and programmed into the control panel.
Programming Keypad A set of keys on the membrane panel used for data entry and selection while programming the control panel.
Relay Module An addressable module that controls a Form-C relay.
SLC device An addressable detector, control, monitor or relay module connected to
the control panel through TB6.
Type Code is a control panel software entity that defines the function of a detector, control, monitor or relay module, or panel circuit.
3.2.7 How to Avoid Programming Errors
You can avoid programming errors by making sure to follow these guidelines:
General Alarm (Z00)
If programming general alarm (Z00), note the following:
Do not program a general alarm (Z00) to a releasing function.
Do not program a general alarm (Z00) without an input point.
Releasing Zone (91–94)
If programming releasing zones (91–94), note the following:
Do not program a releasing zone input (91–94) without at least one mapped
RELEASE CKT output.
Do not program a
RELEASE CKT output without programming at least one releasing
zone input (91–94).
Do not program a releasing zone input (91–94) without programming at least one
MAN. RELEASE zone.
Do not program an Abort timer selected with Delay=00.
Cross Zones
If programming cross zones, a programming error will occur with any of the following conditions:
A releasing zone, cross-zoned as type H, without at least one smoke detector and one heat detector mapped to the same releasing zone.
A missing releasing input on cross-zoning function
A missing different zone on releasing cross zone Z.
A missing associated zone on releasing cross zoning.
Time Control (Z95, Z96)
Do not program a time control function (Z95, Z96) as a releasing function.
Do not program a heat detector to a time control zone (Z95, Z96).
Page 70
Programming Program Change Options
70 AFP-200 PN 15511:H2 10/14/2002
3.3 Program Change Options
3.3.1 Overview
This section covers the following Program Change options:
Table 15 Program Change Topics
Top i c Re f e r t o
Clear programming memory
“How to Clear a Program from Memory (0=clr)” on page 73
Autoprogram the control panel
“How to Autoprogram the Control Panel (1=auto)” on page 73
Program a point for a:
• detector
• monitor module
• control or relay module
• panel circuit
“How to Program an Intelligent Detector” on page 80 “How to Program a Monitor Module” on page 81 “How to a Program a Control or Relay Module” on page 83 “How to Program a Panel Circuit” on page 84
Change a programming password (Program Change or Status Change)
“How to Change a Programming Password (3=passwd)” on page 85
Create or change the system message on the display
“How to Change a System Message (4=message)” on page 86
Create or change a custom zone label
“How to Change a Zone Label (5=zones)” on page 86
Change the program for special Zones 90 through 99
“How to Edit a Special Zone (6=spl zones)” on page 87
Change system functions
“How to Edit System Functions (7=sys)” on page 89
Check the program for errors
“How to Check the Program (8=check)” on page 92
Page 71
How to Enter Program Change Programming
AFP-200 PN 15511:H2 10/14/2002 71
3.4 How to Enter Program Change
To enter Program Change mode, follow these steps:
1. Press the
ENTER key to enter programming mode and the LCD display shows the
Programming Entry screen:
Figure 51 Programming Entry Screen
2. Press the 1 key and the following screen appears in the LCD display:
Figure 52 Password Entry Screen
3. Enter your Program Change password. The control panel enters Program Change. The Program Change options appear in the LCD display as shown in Figure 53:
Figure 53 Program Change Screen
In Program Change, the control panel trouble relay activates—but the panel sounder does not activate, and the System Trouble LED flashes.
The System Trouble LED remains flashing throughout all Program Change operations.
4. Select a Program Change option by pressing the numeric key (0-8) that matches the option. To exit Program Change and return to the Program Entry screen, press the
BACKSPACE key.
1=PROGRAMMING 2=READ@STATUS@ENTRY (BACKSPACE@TO@ABORT)
ENTER@PROG@OR@STATUS PASSWORD,@THEN@ENTER. (BACKSPACE@TO@ABORT)
0=CLR@1=AUTO@2=POINT 3=PASSWD@4=MESSAGE 5=ZONES@6=SPL@ZONES 7=SYS@8=CHECK@PRG
Page 72
Programming How to Enter Program Change
72 AFP-200 PN 15511:H2 10/14/2002
3.4.1 Program Change Map
Figure 54 shows a map of the Program Change options. For each option (0-8) the map shows the main screen, a reference to the section, and a brief overview of the option.
Figure 54 Map of Program Change Options
Password Entry Screen
Programming Entry Screen
Program Change Screen
0
1
2
3
4
5
6
7
8
Clear existing program information from CPU memory
Clear Screen
Autoprogram Screen
Point Programming Screen
Password Change Screen
Message Change Screen
Zone Change Screen
Special Zone Change Screen
System Function Change Screen
Check Program Screen
0=CLR@1=AUTO@2=POINT 3=PASSWD@4=MESSAGE 5=ZONES@6=SPL@ZONES 7=SYS@8=CHECK@PRG
PRESS ENTER TO CLEAR ENTIRE PROGRAM OR BACKSPACE TO ESCAPE
AUTOPROGRAM PLEASE@WAIT
1=PROGRAMMING 2=READ@STATUS@ENTRY (BACKSPACE@TO@ABORT)
ENTER@PROG@OR@STATUS PASSWORD,@THEN@ENTER. (BACKSPACE@TO@ABORT)
For details, refer to “How to Clear a Program from Memory (0=clr)” on page 73
For details, refer to “How to Autoprogram the Control Panel (1=auto)” on page 73
For details, refer to “How to Change a Programming Password (3=passwd)” on page 85
For details, refer to “How to Edit or Delete a Point (2=point)” on page 78
For details, refer to “How to Change a System Message (4=message)” on page 86
For details, refer to “How to Change a Zone Label (5=zones)” on page 86
For details, refer to “How to Edit a Special Zone (6=spl zones)” on page 87
For details, refer to “How to Edit System Functions (7=sys)” on page 89
For details, refer to “How to Check the Program (8=check)” on page 92
POINT@PROG.ENTER: 1 = MODIFY POINT 2 = DELETE POINT
CHANGE@PASSWORD *,NNNNN,E=PROGRAM #,NNNNN,E=STATUS AREA FOR NEW PASSWORD
SYS@NORMAL@MESSAGE
CHANGE@ZONE@LABEL SELECT@ZONE@01-89: ENTER@UP@TO@19@CHAR:
SPECIAL@ZONE@PROGRAM 90=PRESIG@91-94=REL 95-96=TIME@97=HOL 98=CODING@99=PREALM
SIL@INH=060@AUTO=600 VERIFY=30@@@USA@TIME ANNUN=ACS(1+2)@@LocT BLINK=Y@ST=4@AVPS=N
PROGRAM CHECK OK.
RE-TEST PANEL NOW 05:31P MON 11/03/97
Display New Device
Edit or Delete Point
Change Password
Edit Message
Edit Zone Label
Edit Zone Label
Edit Zone Label
Edit Zone Label
Confirm Screen
Accept or reject new detectors and modules
Select an installed and programmed point to edit or delete
Change the Program or Status Change password
Edit the 40-character message that displays on the first two lines
Edit the 19-character custom zone label for zones 01-89
Program releasing zones and special zones
Program global system functions
Check the new or current program for errors
Page 73
How to Enter Program Change Programming
AFP-200 PN 15511:H2 10/14/2002 73
3.4.2 How to Clear a Program from Memory (0=CLR)
The Clear option erases all programming information from the CPU memory of the control panel. You typically use the Clear function to erase data from the control before autoprogramming the control panel for the first time or if you remove one or more devices from the system. For more information on removing devices, refer to “How to Remove a Device from the Program” on page 76.
1. From the Program Change screen (Figure 53), press the 0 key. The Clear Program screen displays a verification prompt as shown in Figure 55:
Figure 55 Clear Program Screen
CAUTION: Pressing the ENTER key causes the system to erase all existing programming data from CPU memory.
2. To erase existing programming data, press the ENTER key. To exit and return to the Program Change screen without erasing data, press the
BACKSPACE key.
3.4.3 How to Autoprogram the Control Panel (1=AUTO)
Purpose
The Autoprogram option directs the control panel to identify all detectors and modules connected to the SLC. You can use the Autoprogram option to create a new program and add or delete addressable detectors and modules connected to the SLC. Table 16 contains a summary of the Autoprogram functions, when to use the functions, and where to find information on using the functions.
Table 16 Autoprogram Functions
Autoprogram Function
Control Panel Configuration Refer to
Create a new program
for the control panel
A new control panel or a control panel with no existing program in memory.
“Create a New Program for the Control Panel” on page 74
Add one or more SLC-connected detectors and modules to an existing program
A program exists in memory and you want to add a detector or module to the existing program—without modifying information for existing detectors and modules.
“How to Add a Device to the Program” on page 75
Remove one or more SLC-connected detectors and modules from an existing program
A program exists in memory and you want to remove an installed detector or module from the existing program—without modifying information for existing detectors and modules.
“How to Remove a Device from the Program” on page 76
View system defaults A program exists in memory and
you want to view system settings assigned during autoprogram, such as custom labels, passwords, and so on.
“How to Change Autoprogram System Defaults” on page 77
Program Change Password
PRESS ENTER TO CLEAR ENTIRE PROGRAM OR BACKSPACE TO ESCAPE
!
Program Change Password
Page 74
Programming How to Enter Program Change
74 AFP-200 PN 15511:H2 10/14/2002
Create a New Program for the Control Panel
This section covers how to use the Autoprogram option to create a new program for the control panel. The control panel will identify all addressable detectors and modules connected to the SLC then display default program information for each installed device.
Note: If your system includes a relay module, you must manually set this from “control” to “relay” after completing autoprogram. Refer to “How to a Program a Control or Relay Module” on page 83 for details.
To create a new program for the control panel, follow these steps:
1. Use the Clear option to clear program information from memory. For instructions on doing this, refer to “How to Clear a Program from Memory (0=clr)” on page 73.
2. From the Program Change screen, press the 1 key to start Autoprogram. The control panel scans the system to identify all detectors and modules connected to the SLC and displays the following screen:
Figure 56 Autoprogram Prompt
3. When finished identifying SLC devices, the LCD displays the first detector or module in the following order: detectors in address order (D01, D02, and so on), monitor modules in address order, and control or relay modules in address order. For example, Figure 57 shows a sample screen for a new device identified by the control program during autoprogram.
Figure 57 Sample New Device Screen
Program Change Password
AUTOPROGRAM PLEASE@WAIT
PROGRM@SMOKE(PHOTO) DETECTOR@ADDRESS@01 ZO3@Z@@@Z@@@Z@@@Z@@
2.0%@@@@@@*P*@@@@D01
Default Autoprogram information for the device. To edit this information, refer to “How to Edit or Delete a Point (2=point)” on page 78 for instructions.
Device address (detector at SLC address 01 shown)
Type Code for the device which you can only edit using the Point Programming option. For details, refer to “How to Edit or Delete a Point (2=point)” on page 78.
Default label for the device. To edit, refer to “How to Edit or Delete a Point (2=point)” on page 78.
Page 75
How to Enter Program Change Programming
AFP-200 PN 15511:H2 10/14/2002 75
4. When a New Device screen displays, you can take one of the following actions:
Table 17 Autoprogram Options for New Devices
5. Continue displaying and acting on each device. When the control panel completes displaying new devices, the Autoprogram Summary screen is displayed. The Autoprogram Summary screen—see Figure 58—displays the total number of detectors, modules, and panel circuits connected to the control panel.
Figure 58 Sample Autoprogram Summary Screen
6. Press the
ENTER key, then press the BACKSPACE key to save the program in memory
and return to the Program Change screen (Figure 53 on page 71); or
Press the
BACKSPACE key to exit without saving and return to the Program Change
screen (Figure 53 on page 71).
How to Add a Device to the Program
You can also use the Autoprogram option to add addressable detectors and modules to the existing control panel program.
When using the Autoprogram option with an existing program, the control panel does not change program information for installed and programmed devices.
The following steps describe how to add a new detector at SLC address 04 with 10 detectors in the existing program:
1. Install the addressable detector to the SLC at address 04 (for instructions, refer to Section 2 “Installation”).
2. From the Program Change screen (Figure 53), press the 1 key to start autoprogram. The Autoprogram Prompt screen (Figure 56 on page 74) appears in the LCD display as the control panel identifies addressable devices connected to the SLC.
3. When finished identifying SLC devices, the control panel displays information for the new detector at SLC address 04 on the LCD display as shown in Figure 59.
You can Do this
Accept default program information for the device
Press the ENTER key to save the default program information in memory for the device and display the next device.
Reject the device
Press the BACKSPACE key to reject the device (which prevents storing the device in memory) and display the next device.
Edit program information for the device
Use the programming keypad to edit program information for the device. For instructions on editing program information, refer to “How to Edit or Delete a Point (2=point)” on page 78). When finished
editing device information, press the ENTER key to save the program information in memory for the device and display the next device.
DETECTORS :10 MODULES :02 PANEL CKTS :04
SLC devices (detectors and modules) identified during Autoprogram
The number of panel circuits shown in the Autoprogram Summary screen always equals “04.”
Page 76
Programming How to Enter Program Change
76 AFP-200 PN 15511:H2 10/14/2002
Figure 59 Sample New Device Screen
4. Press the
ENTER key to add detector 04 to the program with the default program
information. If you want to change the default information, use the programming keys to do so, then press the
ENTER key to add detector 04 to the program. To reject
the new device, press the
BACKSPACE key to return to the Program Change screen.
5. The Autoprogram Summary screen appears. You can verify addition of the detector to the program by noting the new count of detectors as shown in Figure 60.
Figure 60 Sample Autoprogram Summary Screen
6. Press the
ENTER key, then press the BACKSPACE key to save the program in memory
and return to the Program Change screen (Figure 53 on page 71).
How to Remove a Device from the Program
You can also use the Autoprogram option to remove addressable detectors and modules from the control panel program.
The following steps describe how to delete a detector at SLC address 04 with 10 detectors in the existing program:
When using the Autoprogram option with an existing program, the control panel does not change program information for installed and programmed devices.
1. Disconnect and remove the detector from the SLC at address 04.
2. From the Program Change screen (Figure 53), press the 1 key to start Autoprogram. The Autoprogram Prompt screen (Figure 56 on page 74) while the control panel identifies addressable devices connected to the SLC.
3. When finished identifying SLC devices, the control panel displays a screen, indicating a missing detector at SLC address 04 as shown in Figure 61.
Figure 61 Sample Missing Device Screen
4. Press the
ENTER key to delete detector 04 from the program and return to the
Program Change screen (Figure 53 on page 71).
PROGRM@SMOKE(PHOTO) DETECTOR@ADDRESS@01 ZO3@Z@@@Z@@@Z@@@Z@@
2.0%@@@@@@*P*@@@@D04
Default Autoprogram information for the device. To edit this information, refer to “How to Edit or Delete a Point (2=point)” on page 78 for instructions.
Device address (detector at SLC address 04 shown)
Type Code for the device which you can only edit using the Point Programming option. For details, refer to “How to Edit or Delete a Point (2=point)” on page 78.
Default label for the device. To edit, refer to “How to Edit or Delete a Point (2=point)” on page 78.
DETECTORS :11 MODULES :02 PANEL CKTS :04
Note that the number of detectors increases (from 10 to 11) to show the addition of the detector.
PROGRM@SMOKE(PHOTO) FLOOR1@MAIN@LOBBY DEVICE@NOT@ANSWERING DELETE@FROM@MEM?@D04
D04 – the address of the device removed from the SLC.
Page 77
How to Enter Program Change Programming
AFP-200 PN 15511:H2 10/14/2002 77
The Autoprogram Summary screen appears. You can verify removal of the detector from the program by noting the new count of detectors as shown in Figure 60.
Figure 62 Sample Autoprogram Summary Screen
5. Press the
ENTER key, then press the BACKSPACE key to save the program in memory
and return to the Program Change screen (Figure 53 on page 71).
How to Change Autoprogram System Defaults
The Autoprogram option automatically selects default system functions during initial programming of the control panel. You can change the default system functions. If you change any system default, then autoprogram the control panel, any new system values that you enter, do not change. For example, if you change a Program Change password, install new devices, and run the Autoprogram option, the new Program Change password remains unchanged. Table 18 contains default system functions and value.
Table 18 Default Parameters for System Functions
DETECTORS :10 MODULES :02 PANEL CKTS :04
Note that the number of detectors decreases (from 11 to
10) to show the removal of the detector.
System Function Default Value For more information, refer to
Zone 00
Custom label = GENERAL
ALARM ZONE
“How to Edit or Delete a Point (2=point)” on page 78
Zones 01 through 89 Custom label is blank “How to Change a Zone Label (5=zones)” on
page 86
Zone 90
Label = PRESIGNAL
/PAS DELAY,
DELAY=180, PAS=N
“Programming a Presignal Zone (Z90)” on page 87
Zones 91-94
Label = RELEASE
ZONE 91 DELAY=00,
ABORT-ULI CROSS=N SOAK=00
“Releasing Control Zones (Zones 91-94)” on page 88
Zones 95 and 96
Label = TIME
CONTROL ZONE 96,
ON=00:00, OFF=00:00, DAYS=SMTWTFSH
“Time Control Change (Zones 95, 96)” on page 88
Zone 97
Label = HOLIDAY
ZONE 97, all days are
00/00
“Holiday Change (Zone 97)” on page 88
Zone 98
Label = all blanks, CODE TYPE
=MARCH
TIME
“Code Type (Zone 98)” on page 89
Zone 99
Label = PRE
-ALARM ZONE 99,
ALERT=70% OF ALARM, ACTION=00% OF
ALARM
“Pre-Alarm (Zone 99)” on page 89
System Parameters
SIL
INH=000, AUTO=000, VERIFY=00,
USA TIME, ANNUN=NON SUPV, LocT
BLINK
=Y, ST=4, AVPS=N
“How to Edit System Functions (7=sys)” on page 89
Programming Passwords Program Change 00000
Status Change 11111
“Programming Passwords” on page 66 “How to Change a Programming Password (3=passwd)” on page 85
All Systems Normal Custom Message
Custom message label = 40 blanks “How to Change a System Message
(4=message)” on page 86
Page 78
Programming How to Enter Program Change
78 AFP-200 PN 15511:H2 10/14/2002
3.4.4 How to Edit or Delete a Point (2=POINT)
Purpose
A point is a detector or module connected to the SLC or a device connected to one of the four panel circuits. The Point Programming (Point) option lets you do the following:
Modify program information for a detector, module, or panel circuit point
Delete a detector or module point from the program
This section contains instructions using the Point Programming option to do the following tasks:
Table 19 Point Programming Topics
How to Select a Point
To select a point, follow these steps:
1. From the Program Change screen (Figure 53 on page 71), press the 2 key (Point) to display the Point Programming Entry screen (Figure 64).
Figure 63 Point Programming Screen
Task Covers the following
Refer to page
How to Select a Point to modify or delete
a How to display a detector, module, or
panel circuit point so you can modify or delete it
75
How to Program an Intelligent Detector
a
a. To do this task, the device must be installed and programmed using the Autoprogram
option.
How to modify program information for an addressable, intelligent detector
80
How to Program a Monitor Module
a How to modify program information
for a monitor module
81
How to a Program a Control or Relay
Module
a
How to modify program information for a control or relay module
83
How to Program a Panel Circuit How to modify program information
for any of the four NAC or Panel Circuits
84
How to Delete a Detector or Module
Point
b
b. Deleting a point only deletes the point from program memory—not the device. For
instructions on removing a device, refer to “How to Remove a Device from the Program” on page 76.
How delete a detector or module point from the program
84
Program Change Password
POINT@PROG.ENTER: 1 = MODIFY POINT 2 = DELETE POINT
Page 79
How to Enter Program Change Programming
AFP-200 PN 15511:H2 10/14/2002 79
2. From the Point Programming screen, press the 1 key to display the Modify Point Selection screen or press the 2 key to display the Delete Point Selection screen (Figure 64).
Figure 64 Modify and Delete Point Selection Screen
3. From the Modify Point screen or the Delete Point screen, use the programming keys to display a device as shown in Table 20.
Table 20 How to Display a Point
To Display a Do this Refer to
Detector Press the * key, press the numeric keys
that represent the detector SLC address (01-99), then press the ENTER key.
• “How to Program an Intelligent Detector” on page 80 or
• “How to Delete a Detector or Module Point” on page 84
monitor, relay, or control module
Press the # key, press the numeric keys that represent the module SLC address
(01-99), then press the ENTER key.
• “How to a Program a Control or Relay Module” on page 83
or
• “How to Program a Monitor Module” on page 81
• “How to Delete a Detector or Module Point” on page 84
Panel circuit Press the * key, press the # key, press the
numeric key which represents the circuit address (01-04), then press the ENTER key.
“How to Program a Panel Circuit” on page 84
Notes:
• If you enter the address of a detector or module that is not installed, the control panel displays the point with the next highest address.
• Press the Up arrow key to display the point at the previous address or press the Down arrow key to select the point at the next address.
• You cannot delete a panel circuit.
POINT@PROG.ENTER: DETECTOR=*,AA,E MODULE=#,AA,E BELLCKT=*#,A,E
DELETE POINT.ENTER: DETECTOR=*,AA,E MODULE=#,AA,E
Modify Point screen
Delete Point screen
Page 80
Programming How to Enter Program Change
80 AFP-200 PN 15511:H2 10/14/2002
How to Program an Intelligent Detector
You can change program information for an addressable detector that is installed and programmed using the Autoprogram option. Figure 65 shows a sample display for a programmed detector. If editing the detector while using the Point: Modify option, you can modify all fields as shown in Figure 65.
Figure 65 Typical Detector Point: Modify Screen
Notes for Figure 65:
1. Default Zone Selection Default zones are: Zone 01 (heat detectors), Zone 02 (ionization detectors), and Zone 03 (photo detectors).
2. CBE selection Four additional zones can be selected for the device’s CBE.
3. Detector Sensitivity If this is an FSI-751 ionization detector used in a duct application, the sensitivity must be set to HIGH. Refer to Section 4 “Operation” for details on selecting detector sensitivity.
4. Pre-Alarm To deselect Pre-Alarm, press the * key. For more information on selecting Pre-Alarm, refer to “Pre-Alarm (Zone 99)” on page 89 and Appendix G.
5. Alarm Verification Make sure to record detectors programmed for Alarm Verification on the Protected Premises Label located inside the cabinet door. To select Alarm Verification, replace the * with the a “V”. For more information on Alarm Verification, refer to Section 4 “Operation”.
6. Drift Compensation To select Drift Compensation, position the cursor over the first * and press the D (3) key. For more information on Drift Compensation, refer to Section 4 “Operation”
A Type Code defines the function of the detector. Table 21 contains a list of detector Type Codes:
Table 21 Detector Type Codes
PROGRM@SMOKE(PHOTO) DETECTOR@ADDRESS@01 ZO3@Z@@@Z@@@Z@@@Z@@
2.0%@@@@@@*P*@@@@D01
Type Code (For selections, refer to Table
21)
The default custom label
Z03 is the default zone selection (note 1)
2.0% obscuration per foot is the sensitivity setting. Ion detectors show HIGH, MED, or LOW (note 3)
P indicates that the AWACS™ Pre-Alarm function is operational. The default setting is Alert level at 70% of alarm level. See note 4.
* Indicates Alarm Verification option not set (note 5)
* Indicates drift compensation option not set (note 6)
Four additional zones for the device’s CBE (note 2).
Type Code Detector Type
SMOKE (ION) Ionization smoke detector (FSI-751)
SMOKE (PHOTO) Intelligent smoke detector (FSP-751)
HEAT (ANALOG) Intelligent thermal detector (FST-751)
Page 81
How to Enter Program Change Programming
AFP-200 PN 15511:H2 10/14/2002 81
How to Program a Monitor Module
Figure 66 shows a sample display of a typical monitor module Point: Modify screen. If editing the module while using the Point: Modify option, you can modify all fields as shown in Figure 65.
Figure 66 Sample Monitor Module Programming Display
Edit any field in the LCD display by following these steps:
1. Move the blinking cursor with the right cursor key to the field you want to edit.
2. Change the blinking fields by pressing the up cursor key, or by pressing a numeric key.
The primary programming task for editing monitor modules is selecting the Type Code. To do so, move the cursor to the Type Code field (the Type Code field blinks when selected). Select a Type Code by pressing the up cursor key until your Type Code selection appears (Table 23 contains a list of monitor module Type Codes).
Selection of a Type Code may change the functional operation of the monitor module point. For example, selecting the Type Code “Tamper” can define the monitor module to indicate an alarm for a security application
You can change the default zone (listed in Ta ble 2 2) and add up to four zones for the CBE of each monitor module. Tab l e 22 contains the Autoprogram default zone selection for monitor modules.
Table 22 Monitor Module Default Zone Selection
PROGRM@MONITOR MODULE@ADDRESS@08 Z04@Z@@Z@@Z@@Z @@@@@@@@@@@@@ M08
“M” (Module) identifies the type of device
Default zone selection is Z04. See Table 22 for a list of default zone selections.
Type Code (For explanations, refer to Table 23)
Custom label for this device, which you can edit using the programming keys.
Four additional CBE selections
Two-digit address (01-99)
Monitor module Address Zone Default
01 through 19 Z04
20 through 39 Z05
40 through 59 Z06
60 through 79 Z07
80 through 99 Z08
Page 82
Programming How to Enter Program Change
82 AFP-200 PN 15511:H2 10/14/2002
Table 23 contains a list of monitor module Type Codes:
Table 23 Monitor Module Type Codes
Type Code Special function when activated
Nonlatching or Latching
Activate CBE?
MONITOR
(default)
Monitor module used to monitor normally open contact, shorting-type devices.
latching yes
PULL
STATION
NBG-12LX addressable manual pull station latching yes
SMOKE
DETECT
None latching yes
HEAT DETECT
None latching yes
Blank None, select when no other Type Code
applies.
latching yes
WATERFLOW
Causes a non-silenceable alarm. latching yes
SUPERVISORY
Becomes a supervisory point (Refer to Section 4 “Operation”).
latching yes
TAMPER
Becomes a supervisory point (Refer to Section 4 “Operation”).
latching yes
NON
FIRE
A special non-alarm point used for energy management or other non-fire situations (Refer to Section 4 “Operation”)
nonlatching yes
HAZARD
ALERT
A special non-alarm point used for monitoring hazardous situations, such as a tornado (Refer to Section 4 “Operation”).
latching yes
FIRE
CONTROL
A special non-alarm point used for air handler shutdown and are intended to override normal operating automatic functions (Refer to Section 4 “Operation”).
nonlatching yes
ABORT
SWITCH
Aborts activation of a releasing zone (Refer to Appendix D “Releasing Applications.”)
nonlatching yes
MAN
.
RELEASE
Provide a manual release function and overrides the abort switch (Refer to Appendix D “Releasing Applications.”)
latching yes
SILENCE
Functions like the Alarm Silence switch. latching no
SYSTEM
RESET
Functions like the System Reset switch. nonlatching no
EVACUATE
Functions like the Drill switch latching yes
PAS
INHIBIT
Overrides a Presignal selection (Refer to Appendix H “Special Zones.”)
nonlatching no
TROUBLE
MON
Short = Trouble (Refer to Section 3 “Programming” & Section 4 “Operation”).
latching yes
BURGLAR
ALA
Causes Security Alarm on open or short (Refer to Appendix E “Combination Fire/Burglary Applications.”)
latching yes
Page 83
How to Enter Program Change Programming
AFP-200 PN 15511:H2 10/14/2002 83
How to a Program a Control or Relay Module
A sample display of a typical control module Modify Point screen appears in Figure 67. If editing the module while using the Modify Point option, you can modify all fields as shown in Figure 67.
Figure 67 Sample Control or Relay Module Programming Screen
Press the
ENTER key to accept default program information or press the BACKSPACE key
to reject the default autoprogram information. Edit any field in the LCD display by following these steps:
1. Move the blinking cursor with the right cursor key to the field you want to edit.
2. Change blinking fields by pressing the up cursor key, or by pressing a numeric key.
Selection of control or relay module Type Code may change their function. Table 24 contains descriptions of the control or relay module Type Codes.
Table 24 Control or Relay Module Type Codes
Type Code Label Special Function
CONTROL
None (default)
RELAY
Ignore open circuit
STROBE
CKT
None
BELL
None
HORN
CIRCUIT
None
AUDIBLE
CKT
None
BLANK
None, select when no other Type Code applies
RELEASE
CKT
Short = Normal (nonpower-limited, see Appendix D)
REL
CKT ULC
Short = Trouble (supervised and power-limited, see Appendix D)
RELEASE
FORM_C
Contacts operated upon release
Note: A releasing circuit is always non-silenceable.
PROGRM@CONTROL MODULE@ADDRESS@08 Z00@Z@@Z@@Z@@Z @@@@@@@@@@@@@S*M08
“M” (Module) prefix to device SLC address
Default zone selection is Z00 (general alarm)
Walk Test (*) is not selected by default. (To select, change to “W”)
Type Code (For explanations, refer to Table 24)
CBE selections
Two-digit SLC address (01-99)
Silenceable (S) selected by default. (* = not selected).
Custom label for this device, which you can edit using the programming keys.
Page 84
Programming How to Enter Program Change
84 AFP-200 PN 15511:H2 10/14/2002
How to Program a Panel Circuit
Panel circuit program functions and Type Codes are similar to control modules, with the exception that they can not be used for agent release applications.
Because the four Panel Circuits are always installed, the autoprogram feature does not display Panel Circuits. Figure 68 shows a sample edit screen for Panel Circuit point programming:
Figure 68 Sample Panel Circuit Edit Screen
To edit a Panel Circuit point select the Type Code. To do so, move the cursor to the Type Code field (the Type code field will blink when selected). Select a Type Code by pressing the up key until your desired Type Code appears. Table 25 contains a list of the Notification Appliance Circuits (NACs) Type Codes.
Table 25 contains Type Code selections for the four Notification Appliance Circuits:
Table 25 Notification Appliance Circuit Type Codes
How to Delete a Detector or Module Point
You can use the Delete Point option to temporarily delete an intelligent detector or module point from program memory. Selecting option 2 from the Point Programming screen (Figure 63) lets you choose a detector or module point to delete. Figure 69 shows the Delete Point Selection screen and contains instructions for accessing a point.
Type Code Label Special Function
BELL
CIRCUIT
None (default)
STROBE
CKT
None
HORN
CIRCUIT
None
AUDIBLE
CKT
None
blank Use when no other Type Code applies
PROGRM@BELL@CIRCUIT PANEL@CIRCUIT@NO.@1 Z00@Z@@@@Z@@@Z@@@Z @@@@@@@@@@@@SW@BO1
“B” (bell circuit) in the address
Default zone selection is Z00 (general alarm)
Walk Test (W) is selected by default. (* = not selected). For details on Walk Test, refer to “How to do a Walk Test (6=walk test)” on page 99.
Type Code (For explanations, refer to Table 25)
Custom label for this device.
CBE selections
Two-digit address (01-04)
Silenceable (S) is selected by default. (* = not selected).
Page 85
How to Enter Program Change Programming
AFP-200 PN 15511:H2 10/14/2002 85
Figure 69 Delete Point Selection Screen
Instead of reentering the next point number or if you do not know the SLC address, you can press the up or down key to display the next lower or higher point.
From the Delete Point Selection screen, select a detector or module SLC address. If the selected point number is not installed, the control panel displays the next higher installed point.
Figure 70 shows a sample Delete Point screen for a smoke detector at SLC address 38:
Figure 70 Sample Delete Point Screen
From the Delete Point screen, you can do the following:
Press the
ENTER key to delete the point and return to the Delete Point Selection
screen; or
Press the left cursor (backspace) key to keep the point in memory and return to the Delete Point Selection screen.
3.4.5 How to Change a Programming Password (3=PASSWD)
The Password Change function lets you enter the Program Change and Status Change passwords. A password must contain at least five numeric characters, no spaces allowed. To change a password, follow these steps:
1. From the Program Change screen (Figure 53 on page 71), select option 3 (Password). The LCD display shows the Password Change screen (Figure 71).
Figure 71 Password Change Screen
2. Follow the instructions in Figure 71. To return to the Program Change screen without changing the password, press the left cursor (backspace) key. When finished changing the password, press the
ENTER key to return to the Program
Change screen.
DELETE POINT.ENTER: DETECTOR=*,AA,E MODULE=#,AA,E
NORMAL SMOKE (ION): ENTER TO DELETE OR BACKSPACE TO ABORT 00%/HIGH *P* D38
Program Change Password
CHANGE@PASSWORD *,NNNNN,E=PROGRAM #,NNNNN,E=STATUS AREA FOR NEW PASSWORD
To change the Program Change password, press *, key in the new password, then press the
ENTER key.
To change the Status Change password, press #, key in the new password, then press the
ENTER key.
As the new Program Change or Status Change password is entered it displays on the fourth line.
Page 86
Programming How to Enter Program Change
86 AFP-200 PN 15511:H2 10/14/2002
3.4.6 How to Change a System Message (4=MESSAGE)
The Message Change screen lets you change the 40-character “All Systems Normal” message.
1. From the Program Change screen (Figure 53 on page 71), select option 4 (Message) to display the Message Change screen (Figure 72).
Figure 72 Message Change Screen
For instructions on using the programming key, refer to “How to Use the Programming Keypad” on page 67.
2. Use the programming keypad to enter or edit the system message (up to 40 characters).
3. When finished entering characters, press the
ENTER key to save the new message
and return to the Program Change screen.
3.4.7 How to Change a Zone Label (5=ZONES)
The Zone Change function lets you add or modify a zone label. A zone label is a text entry that you can key in to describe a zone between 01–89. To change a zone label, follow these instructions:
1. From the Program Change screen (Figure 53 on page 71), select option (5=Zones) to display the Change Zone Label screen. Figure 73 shows the Change Zone Label screen:
Figure 73 Zone Change Label Screen
For instructions on using the programming keys, refer to “How to Use the Programming Keypad” on page 67.
2. Select a zone to change by entering the zone number (01-89) in character positions 19 and 20 on the second line. For single-digit numbers, enter a leading zero before the digit (for example, enter “07” for zone 7).
3. The existing (if any) zone label displays on line 4 of the LCD display, characters 2 through 20. Character 1 on line 4 is blank to force a space between the device and zone labels when they are linked on the printer.
4. Add or change the zone label, then press the
ENTER key. The zone label changes in
memory and the LCD display returns to the Change Zone Label screen.
5. If the zone is out of range, the software ignores the
ENTER key. To return to the
Program Change screen, press the
BACKSPACE key.
Program Change Password
SYS@NORMAL@MESSAGE
The first character on the third line blinks and may be changed to any alphabetic character by using the keypad, then pressing the right cursor to move to the next position.
Message entry area for entering up to 40 characters. Type a blank space in character position 20 or 21 so the words do not run together on an 80-character printer.
Program Change Password
CHANGE@ZONE@LABEL SELECT@ZONE@01-89: ENTER@UP@TO@19@CHAR:
Line 2, character positions 19 and 20, for entering a zone number.
Line 4 – display area for existing zone label.
Page 87
How to Enter Program Change Programming
AFP-200 PN 15511:H2 10/14/2002 87
3.4.8 How to Edit a Special Zone (6=SPL ZONES)
Purpose of Special Zones (90-99)
Special zones include ten special software zones that you can program to do the following:.
Table 26 Special Software Zones 90-99
How to Select Special Zones
The Special Zone Change option you change the program for special Zones 90 through
99. From the Program Change screen (Figure 53 on page 71), select 6=SPL ZONES to
display the Special Zone Change screen. Figure 74 shows the Special Zone Change screen:
Figure 74 Special Zone Change Screen
From the Special Zone Change screen, you can select one of the options listed in Table
26. To select an option from the Special Zone Change screen, key in the number of the
option. For example, to select the coding software zone, key in “98”; to select the releasing software zone 92, key in “92”. The following subsections show each screen that can be selected from the Special Zone Change screen (Figure 74).
Programming a Presignal Zone (Z90)
What is a Presignal Zone? You can use Presignal zone 90 when you want to
delay control points for human verification. If zone 90 is included in a control or relay module or Notification Appliance Circuit CBE list, it inhibits all other CBE. Detectors and monitor modules must call out Zone 90 in their program to be included in the pre-signal/PAS operation.
When any alarm occurs and no PAS inhibit type monitor module is activated, Zone 90 activates. If a second alarm activates, or the Drill switch is pressed, Zone 90 goes false. If PAS is selected, and the Acknowledge switch is not pressed within 15 seconds, Zone 90 goes false. At the first alarm, a programmable 0–180 second timer starts. If an Alarm Silence occurs, the timer stops. If the delay timer expires, manual activation will activate outputs mapped to zone F0. The System Alarm relay, the 4XTM Polarity Reversal Alarm Output, and the 4XTM Municipal Box Output delay if PAS is selected, but do not delay for Presignal operations.
Special Zone
Description
90 A software zone used to select Presignal options.
91-94 Four software zones used to control releasing applications.
95, 96 Two software zones used to assign time control functions.
97 A software zone used to select holiday time controls.
98 A software zone used to select the type of coding for Panel Circuits.
99 A zone used to select the Pre-Alarm function.
Program Change Password
SPECIAL@ZONE@PROGRAM 90=PRESIG@91-94=REL 95-96=TIME@97=HOL 98=CODING@99=PREALM
Page 88
Programming How to Enter Program Change
88 AFP-200 PN 15511:H2 10/14/2002
From the Special Zone Change screen (Figure 74), key in “90” to display the Presignal screen. Figure 75 shows a typical Presignal screen.
Figure 75 Presignal Screen
From the Presignal screen, you can change the delay time or the PAS selection. Refer to Appendix H for a detailed explanation of Presignal and PAS.
Releasing Control Zones (Zones 91-94)
From the Special Zone Change screen (Figure 74), you can key in 91, 92, 93, or 94 to display the Release Control screen (Figure 76). You can change delay times (0-60 seconds), abort type (ULI, IRI, NYC or AHJ), cross zoning (N,Y, H, or Z) or soak time (00, 10-15 minutes). Figure 76 shows a typical display:
Figure 76 Release Control Screen
For descriptions and options for releasing zones, refer to Appendix D “Releasing Applications”
.
Time Control Change (Zones 95, 96)
Time Control lets you change the start time, stop time, or days of the week. From the Special Zone Change screen (Figure 74), you can key in 95 or 96 to display the Time Control Change screen. Figure 77 shows a typical screen for changing the time using software zone 95:
Figure 77 Time Control Change Screen
For descriptions and options for Time Control zones, refer to Appendix H “Special Zones”.
Holiday Change (Zone 97)
Software zone 97 (Holiday Change) lets you select up to nine holiday dates. Any device programmed to Software Zone 97 will be active on the holiday dates listed. From the Special Zone Change screen (Figure 74), key in 97 to display the Holiday Change screen. Figure 78 shows a typical Holiday Change screen:
Figure 78 Holiday Change Screen
PRG@SOFTWARE@ZONE PRESIGNAL@DELAY DELAY=180 PAS=YES Z90
PRG@SOFTWARE@ZONE RELEASE@@@CONTROL DELAY=00@@ABORT=ULI CROSS=Y@@@SOAK=00 Z91
PRG@SOFTWARE@ZONE TIME@CONTROL ON=08:00@@@OFF=17:00 DAYS=SMTWTFSH@@@@@@@Z95
PRG@HOLIDAY@ZONE 97 01/01@@04/10@@05/26 07/04@@09/07@@11/26 11/27@@12/24@@12/25
Page 89
How to Enter Program Change Programming
AFP-200 PN 15511:H2 10/14/2002 89
For descriptions and options for Holiday Zones, refer to Appendix H “Special Zones”.
Code Type (Zone 98)
Software zone 98 (code type), lets you select one of four code types: March Time, Temporal, California, or Two Stage. Selection of coding only has an effect if one or more Notification Appliance Circuits call out zone 98. From the Special Zone Change screen (Figure 74), you key in 98, to display the Code Type screen. Figure 79 shows a sample Code Type screen with a code type of March Time.
Figure 79 Code Type Screen
For descriptions and options for Code Types, refer to Appendix H “Special Zones”.
Pre-Alarm (Zone 99)
Use software zone 99 to program the Alert or Action Pre-Alarm. From the Special Zone Change screen (Figure 74), enter 99 to display the Pre-Alarm screen. Figure 80 shows a sample Pre-Alarm screen.
Figure 80 Pre-Alarm Screen
For descriptions and options for Pre-Alarm, refer to Appendix G “Pre-Alarm (AWACS™) Applications”.
3.4.9 How to Edit System Functions (7=SYS)
Purpose
You can select global settings for nine system functions, which appear in the System Function Selection screen. Figure 81 shows a System Function Selection screen with default values in each system function field. The next section contains descriptions of each field and contains instructions for editing system functions.
Figure 81 System Function Default Values
Understanding System Functions
This section contains descriptions of the nine system functions, with the field name in parentheses, and the selections for each function.
SIL INH= Lets you program a Silence Inhibit Timer that disables the Alarm
Silence switch function when a fire alarm occurs. You can enter a timer value between 0-300 seconds or enter 000 for no timer. The timer starts at the first alarm and restarts with each new alarm.
PRG@SOFTWARE@ZONE CODE@TYPE: MARCH@TIME Z98
PRG PRE-ALARM ZONE ALERT=70% OF ALARM ACTION=00% OF ALARM Z99
Program Change Password
SIL@INH=000@AUTO=000 VERIFY=00@@@USA@TIME ANNUN=NON SUPV@@REMT BLINK=Y@ST=4@AVPS=N
Page 90
Programming How to Enter Program Change
90 AFP-200 PN 15511:H2 10/14/2002
AUTO= Lets you program an Auto Silence Timer that functions like pressing the
Alarm Silence switch. For example, select 600. When the timer reaches 600 seconds (10 minutes), the control panel turns all active outputs that are programmed as silenceable.
An Alarm Verification Timer can reduce the amount of nuisance alarms caused by dirt and dust in a detector
VERIFY= Lets you program an Alarm Verification timer that tells the control
panel to ignore a smoke detector alarm while the timer is counting. (The control panel ignores the Alarm Verification Timer if it detects another alarm during the alarm verification period.) If the time elapses and a smoke detector alarm still exists, the control panel performs all standard functions. If the timer expires and a smoke detector alarm no longer exists, the control panel increments the verification counter (up to 99) for the device and returns to normal operation.
USA TIME Lets you specify the format for system time and date that appears on
the LCD display, terminal mode LCD-80s, and printouts. USA Time displays 12 hour clock with month/day/year. EUR displays a 24 hour clock with day/month/year and changes
TROUBL to FAULT, and DISABL to ISOLAT in the Display Status field.
ANNUN= The Annunciation field lets you select the type of remote annunciation:
No Supv, LCD-80, ACS Addr 1, ACS (1+2), or UDACT. Table 27 contains descriptions of each type:
Table 27 Annunciation Selections
You cannot program an AVPS-24 or APS-6R for a combination Fire/Burglary application because the AVPS-24 Trouble input is also used to monitor the door tamper switch.
AV P S= You can program the control panel to supervise an installed AVPS-24 or
APS-6R expansion power supply. For details on programming and installation of an AVPS-24/AVPS-24E or APS-6R, refer to Appendix J “Expansion Power Supplies”
.
Blink= You can program the blink function of SLC-connected device LEDs
during normal operation (selecting “Y” means devices blink and selecting “N” means devices do not blink). An SLC-addressable detector only blinks when the detector is tested (every three to four hours) but does not blink each time the control panel polls the detector.
ST= You can specify the wiring style used on the SLC: Style 4 (default) or Style 6
operation. Wiring and programming the SLC for Style 6 and a single fault occurs, the control panel detects a fault and drives both ends of the line, fully recovering from the fault. The control panel latches the trouble and displays the trouble until System Reset. Style 7 operation is the same as Style 6—but requires using ISO-X modules for isolating faults.
LocT You can specify the operating mode for a computer or terminal connected
through the EIA-232 port (TB4) on the control panel. For detailed information configuring the control panel with a computer or terminal, refer to Appendix I “Terminal Interface Protocol”. Table 28 lists the operating mode selections.
Selection Specifies
NO SUPV (default)
Terminal mode on; no annunciation used.
LCD 80 (T) Select terminal mode interface (TB5 on the CPU; set SW2 to TERM) to
annunciate all point information to a remote LCD-80.
ACS ADDR 1 Select ACS mode (TB5 on the CPU; set SW2 to ACS) to communicate with
ACS mode devices, on Annunciator Address 1, which displays software zones 1-64
ACS (1+2) EIA-485 port (TB5 on CPU-200) programmed for point annunciation (SW2 set
to ACS) to communicate with ACS mode devices, on Annunciator Address 1, which displays the eight system points and software zones 1-64 and Annunciator Address 2, which displays software zones 57-99.
UDACT Annunciate panel status to a UDACT which is connected and programmed to
the control panel.
Page 91
How to Enter Program Change Programming
AFP-200 PN 15511:H2 10/14/2002 91
Table 28 EIA-232 Operating Mode Selections
How To Edit System Functions
This section contains instructions for editing system function fields. To do so, follow these steps:
1. From the Program Change screen (Figure 53 on page 71), select 7=SYSTEM to display the System Function screen. Figure 82 shows a System Function screen with default system values.
2. Edit the system function values as shown in Figure 82. For additional information on each value, refer to “Understanding System Functions” on page 89.
3. When finished editing, press the
ENTER key to return to the Program Change
screen.
Figure 82 Editing System Functions
Selection Specifies
LocT (default) A local CRT terminal or computer in the same room as the control panel that
provides Read Status, Alter Status, Acknowledge, Silence, Drill, and System Reset functions.
LocM Functions in the same manner as LocT except that it requires a password to
execute the Acknowledge, Silence, Drill, and System Reset functions.
RemT A remote terminal located away from the control panel that only allows the
user to execute the Read Status function.
SIL@INH=000@AUTO=000 VERIFY=30@@@USA@TIME ANNUN=NONE SUPV@@LOCT BLINK=Y@ST=4@AVPS=N
LocT (default) To change, press the Up or Down key to scroll through the selections: LocT, LocM, or RemT.
Verif y=
To change, enter a timer value as follows: 0–30 seconds (for systems with Release 1.2 software or higher) or 0 to 60 seconds (only permitted in systems with Release 1.0 and 1.1 software)
ST=4
To switch the value between ST=4 and ST=6, press the Up or Down key.
ANNUN=
To change, press the Up or Down key to scroll through the selections (See Table 27 on page 90).
USA TIME (default) To switch the value between USA and EUR, press the Up or Down key.
Auto=
To change the timer value, enter 000 none (default) or 600–900 seconds.
Sil Inh=000
To change the timer value, enter a timer value between 000–300 seconds.
AVPS=4 (or APS-6R) To switch the value between Y and N, press the Up or Down key.
BLINK=Y
To change the value between Y and N, press the Up or Down key.
Page 92
Programming Status Change Options
92 AFP-200 PN 15511:H2 10/14/2002
3.4.10 How to Check the Program (8=CHECK)
When finished programming the control panel, use the Check option to search program entries for possible errors. From the Program Change screen (Figure 53 on page 71), select option 8, (Check). The control panel software searches the program for the following conditions:
Output points mapped to a zone with no inputs mapped.
A zone with programmed input point(s) without programmed output point(s), including Z00 (general alarm) outputs.
Releasing zone inputs (91, 92, 93, and 94) with no
RELEASE CKT outputs
programmed to them; or
RELEASE CKT outputs with no releasing zone (91-94)
inputs programmed to them.
RELEASE CKT inputs not mapped to MAN RELEASE.
If multiple devices fail the check, use the up or down keys to step through the devices. To correct any errors detected by the Check routine, return to point programming and correct the program errors.
Figure 83 shows a sample screen that appears when the system successfully completes a Program Check.
Figure 83 Program Check Screen
3.5 Status Change Options
3.5.1 Overview
Even though control program parameters may display in Status Change, the operator cannot access functions that affect basic operation of the control panel.
Status Change provides a second set of options accessed using the Status Change password (“Programming Passwords” on page 66). The Status Change options only allow change of operating parameters (listed in Table 29) that do not affect the basic configuration or control program. For instance, assign the Status Change password to persons who do not need to program applications or use the Autoprogram option.
This section covers the following Status Change topics:
Table 29 Status Change Topics
Program Change Password
PROGRAM CHECK OK.
RE-TEST PANEL NOW 05:31P MON 11/03/97
Topic Refer to
Disable or enable a detector, module, or Panel Circuit point.
“How to Disable or Enable a Point (1=disable)” on page 95
Change detector sensitivity for an intelligent photo or ion detector
“How to Set Detector Selections (2=sens/comp)” on page 96
Clear verification counters used with the Alarm Verification feature
“How to Clear Alarm Verification Counters (3=clr ver)” on page 97
Clear history from memory
“How to Clear the History Buffer (4=clr hist)” on page 98
Set system time and date “How to Set the System Time and Date (5=time)” on page 98
Walk test the system “How to do a Walk Test (6=walk test)” on page 99
Page 93
Status Change Options Programming
AFP-200 PN 15511:H2 10/14/2002 93
3.5.2 Entering Status Change
For more information on programming passwords, refer to “Programming Passwords” on page 66.
You access all Status Change options from the Status Change screen (Figure 84). From the Program Entry screen (Figure 48 on page 66), enter your Status Change password to display the Status Change screen (Figure 84).
Figure 84 Status Change Screen
Status Change operations (except for Walk Test) have a two-minute timer. (The Walk Test feature has a 1-hour timer.) If no keys are pressed for two minutes, the control panel exits Status Change and returns to normal operation.
STATUS@CHANGE@PRESS: 1=DISABLE@2=SENS/COMP 3=CLR@VER@4=CLR@HIST 5=TIME@6=WALK@TEST
Page 94
Programming Status Change Options
94 AFP-200 PN 15511:H2 10/14/2002
3.5.3 Status Change Programming Map
Figure 85 shows a map of the Status Change programming options. For each programming option (1-6) the map shows the main screen, a reference to the section with the instructions, and a brief overview of the option
Figure 85 Map of Status Change Programming Options
Press the ENTER key, test the system. Press the
BACKSPACE key to
stop.
Password Entry Screen
Programming Entry Screen
Program Change Screen
1
2
3
4
5
6
Disable or Enable a point or press the
BACKSPACE key to exit.
Disable Screen
Detector Sens/Comp Screen
Clear Verification Screen
Clear History Screen
Time and Date Screen
Walk Test Screen
STATUS@CHANGE@PRESS: 1=DISABLE@2=SENS/COMP 3=CLR@VER@4=CLR@HIST 5=TIME@6=WALK@TEST
DISABLE/ENABLE DETECTOR=*,AA,E MODULE=#,AA,E BELL@CKT=*#,AA,E
DET.@SENS/COMP ENTER@POINTS:@AA,E
1=PROGRAMMING 2=READ@STATUS@ENTRY (BACKSPACE@TO@ABORT)
ENTER@PROG@OR@STATUS PASSWORD,@THEN@ENTER. (BACKSPACE@TO@ABORT)
For details, refer to “How to Disable or
Enable a Point (1=disable)” on page 95
For details, refer to “How to Set Detector
Selections (2=sens/comp)” on page 96
For details, refer to “How to Clear the
History Buffer (4=clr hist)” on page 98
For details, refer to
“How to Clear Alarm Verification Counters
(3=clr ver)” on page 97
For details, refer to
“How to Set the System Time and
Date (5=time)” on page 98
For details, refer to “How to do a Walk
Test (6=walk test)” on page 99
PRESS@ENTER@TO@CLEAR VERIFICATION COUNTS OR@BACKSPACE@TO ESCAPE
PRESS@ENTER@TO@CLEAR HISTORY@FILE OR@BACKSPACE@TO ESCAPE
CHANGE@TIME/DATE
09:45A@MON@10/31/97
WALK@TEST@PRESS ENTER@TO@START BACKSPACE@TO@STOP
Make detector sensitivity, drift comp. selections or press the
BACKSPACE key to exit.
Press the
ENTER key
to clear or the
BACKSPACE key to exit.
Press the
ENTER key
to clear or the
BACKSPACE key to exit.
Edit the system time and date or press the
BACKSPACE key to exit.
Page 95
Status Change Options Programming
AFP-200 PN 15511:H2 10/14/2002 95
3.5.4 How to Disable or Enable a Point (1=DISABLE)
WARNING: Disable is a software function. Do not use as a lockout in releasing applications.
The Disable/Enable option lets you disable or enable a programmed SLC point or panel circuit—except for an initiating device in alarm or a output/control point that is on. To disable or enable a programmed point or panel circuit, follow these instructions:
1. From the Status Change screen (Figure 84 on page 93), press the 1 key to display the Disable/Enable screen as shown in Figure 86.
Figure 86 Disable/Enable Screen
2. Enter the type of point to be disabled or enabled (* for detectors, # for modules, or * and # for panel circuits), enter the two-digit SLC address of the point or the panel circuit number; then press the
ENTER key. The control panel displays an edit screen
for the point. For example, Figure 87 shows an edit screen for the NAC at address B01.
Figure 87 Sample Edit Screen for Disabling or Enabling a Point
3. Toggle the status banner to
DISABL or ENABLE by pressing the up or down key.
4. When finished selecting the Enable/Disable status banner, press the
ENTER key.
The control panel updates memory to the selected status and returns to the Disable/Enable screen (Figure 86).
5. To continue with the Enable/Disable option, you can select another point. Do so by entering a new point number or pressing the up key to go to the next address point, or press the down key to go to the previous address point.
6. When finished selecting Enable/Disable selections, press the
BACKSPACE key to
return to the Status Change screen (Figure 84 on page 93).
!
!
Status Change Password
DISABLE/ENABLE DETECTOR=*,AA,E MODULE=#,AA,E BELL@CKT=*#,A,E
To s e l e c t a detector: a) press the * key, press the numeric keys that represent the detector SLC address (01-99), then press the
ENTER key.
To select a module: a) press the # key, press the numeric keys that represent the module SLC address (01-99), then press the
ENTER
key.
To s e l ec t a panel circuit: a) press the * key, press the # key, then enter the address of the panel circuit (1, 2, 3, or 4), then press the
ENTER key.
ENABLE BELL CIRCUIT PANEL CIRCUIT NO. 1 Z00 Z Z Z Z SW B01
Blinking status banner showing the current ENABLE/DISABL selection.
For explanations of lines 3 and 4, refer to Figure 63 on page 78.
Page 96
Programming Status Change Options
96 AFP-200 PN 15511:H2 10/14/2002
3.5.5 How to Set Detector Selections (2=SENS/COMP)
Purpose
The Sens/Comp option lets you select detector sensitivity and drift compensation for photoelectric and ionization detectors.
You can select drift compensation for any intelligent detector on the SLC. Drift compensation provides accurate and stable readings of smoke, counteracting long-term drift caused by dust contamination and other long-term environmental factors. Drift compensation quickly detects true fires, rejects false signals—while allowing a detector to remain within performance specifications throughout its life span. Table 30 lists the three drift compensation measurements performed for each ionization or photoelectric detector.
Table 30 Drift Compensation Measurement
The control panel converts the present reading to percent per foot obscuration or percent of alarm, based on its position between the known clean air and test values. The accuracy of this measurement method is sufficient to meet the NFPA 72 requirements as a calibrated smoke test instrument.
What are Detector Sensitivity Selections?
You can set the sensitivity level for an ionization or a photoelectric detector. Table 31 contains a list of UL-approved detector sensitivity settings for intelligent detectors.
Table 31 Ionization and Photoelectric Detector Sensitivity Selections
How to Select Detector Sensitivity and Drift Compensation
To change detector sensitivity, drift compensation both, follow these steps:
1. From the Status Change screen (Figure 84 on page 93), press the 2 key to display the Detector Sensitivity/Comp screen (Figure 88).
Figure 88 Detector Sensitivity/Comp Screen
Feature Description
long-term measurement of location’s clear air
An average reading which adjusts to gradual buildup of dust contamination, unaffected by true smoke, even from smoldering fires.
alarm test level measurement
A periodic detector test that commands each detector to simulate an alarm level reading from the sensing chamber.
current chamber reading Under normal conditions, this reading is close to the stored air
clear value. If smoke occurs, the reading moves toward the alarm test level.
Type of Detector Sensitivity Selection
Ionization (FSI series) H (high) M (medium), or L (low)
Note: If using older (DH500 series) ionization detectors for duct applications, set the detector sensitivity to “H”.
Photoelectric (FSP series) 2.0, 1.5, of 1.0 percent obscuration per foot
Status Change Password
DET.@SENS/COMP ENTER@POINTS:@AA,E
Page 97
Status Change Options Programming
AFP-200 PN 15511:H2 10/14/2002 97
If you enter an address for an analog heat detector (FST) or other invalid address, the LCD display returns to Detector Sensitivity/Comp screen.
2. Enter a valid detector SLC address and the control panel displays information for the detector on a screen similar to sample screen shown in Figure 89 with the current detector sensitivity selection blinking.
Figure 89 Sample Screen for Changing Detector Selections
3. To change the detector sensitivity, move the cursor to the current detector selection. Press the Up or Down key to change the detector sensitivity. For selections, see Table 31 on page 96.
To exit the screen and return to the Detector Sensitivity/Comp screen,
press the BACKSPACE key from the Detector Sensitivity selection.
4. To enable or disable drift compensation, move the cursor to the drift compensation selection. Press the Up or Down key to toggle the detector sensitivity between D (enabled) or * (disabled).
5. When finished making selections, press the
ENTER key to return to the Detector
Sensitivity/Comp screen.
6. To change selections for another detector, press the up key to display the installed detector at the next highest SLC address or press the down key to display the installed detector at the next lowest SLC address.
3.5.6 How to Clear Alarm Verification Counters (3=CLR VER)
Purpose
The control panel provides a verification counter for each photoelectric and ionization detector programmed for Alarm Verification. (Alarm Verification time is a global program selection, covered in “How to Edit System Functions (7=sys)” on page 89.) The verification counter displays the number of times that a detector entered Alarm Verification but did not time out to alarm. The verification counter increments to 99 and holds. For instructions on viewing the verification counter, refer to 4.9 “Read Status”.
Clearing the Alarm Verification Counters
The Clear Verification Count screen (Figure 90) lets you clear all verification counters for detectors selected for Alarm Verification. To clear all verification counters, follow these steps:
1. From the Status Change screen (Figure 84 on page 93), press the 3 key to display the Verification Count Clear screen as shown in Figure 90:
Figure 90 Verification Count Clear Screen
2. Press the
ENTER key to clear the verification counters or press the BACKSPACE key
to return to the Status Change screen (Figure 84) without clearing the verification
NORMAL SMOKE (ION) DETECTOR ADDRESS 30 Z02 Z Z Z ZZ HIGH *P* D30
Detector sensitivity selection (for a list of detector selections, see Table 31).
Drift compensation selection (* indicates option not set; D indicates drift compensation set).For details on drift compensation, “How to Set Detector Selections (2=sens/comp)” on page 96.
Status Change Password
PRESS@ENTER@TO@CLEAR VERIFICATION COUNTS OR@BACKSPACE@TO ESCAPE
Page 98
Programming Status Change Options
98 AFP-200 PN 15511:H2 10/14/2002
counters.
3.5.7 How to Clear the History Buffer (4=CLR HIST)
Purpose
The History buffer is an electronic record of the last 650 events recorded by the control panel. Events in the History buffer include all alarms, troubles, and operator actions, such as Acknowledge, System Reset, Signal Silence, Manual Evacuate (Drill), and Walk Test. The control panel also records each programming entry, which includes a number indicating the programming submenu (0-9). All events are time and date stamped. For information on reading or printing the History buffer, refer to 4.9.5 “Using the History Buffer”.
Clearing the History Buffer
The Clear History option lets you clear the entire contents of the History buffer from the control panel memory. For more details on the History buffer, refer to Section 4 “Operation”.
1. From the Status Change screen (Figure 84 on page 93), press the 4 key to display the Clear History as shown in Figure 91.
Figure 91 Clear History Screen
2. Press the
ENTER key to clear the contents of the History buffer or press the
BACKSPACE key to return to the Status Change screen (Figure 84) without clearing.
3.5.8 How to Set the System Time and Date (5=TIME)
Purpose
The Change Time and Date option lets you set the system time and date, which also appears on the LCD display. For instructions on selecting the time and date format (USA or European), refer to “How to Edit System Functions (7=sys)” on page 89.
Setting the System Time and Date
To set the system time and date, follow these instructions:
1. From the Status Change screen (Figure 84 on page 93), press the 5 key to display the Time and Date screen. Figure 92 shows a sample Time and Date screen:
Figure 92 Time and Date Screen (USA time format shown)
2. Use the programming keypad to change the time and date, using the cursor keys to move the cursor as needed.
3. When finished entering the time and date, press the
ENTER key to change the time
and date in system memory and return to the Status Change screen.
Status Change Password
PRESS@ENTER@TO@CLEAR HISTORY@FILE OR@BACKSPACE@TO ESCAPE
Status Change Password
CHANGE@TIME/DATE
09:45A@MON@10/31/97
The first digit of the hours flashes. Change digits by keying in digits with the programming keys. Pressing the right cursor moves to the next digit, and so on.
Page 99
Status Change Options Programming
AFP-200 PN 15511:H2 10/14/2002 99
3.5.9 How to do a Walk Test (6=WALK TEST)
WARNING: A Walk Test can deactivate fire protection. When conducting a Walk Test, make sure to do the following:
Secure all protected buildings, and notify the building owner/operator, fire
department, and other persons that testing of the system is in progress.
When finished doing a Walk Test, exit Walk Test immediately and return the
system to normal operation.
Notify the building owner/operator, fire department, and other persons that
testing is complete and the system is operating normally.
Purpose
The Walk Test option lets one person test the entire system without returning to the control panel. Typically, you do a Walk Test by activating a set of devices in a planned sequence. When you finish a Walk Test, you can compare the History buffer against the planned test sequence.
There are two types of Walk Test, Standard and Silent, which are determined by the way the outputs are programmed:
A Standard Walk Test is a test that sounds each output programmed for Walk Test for 3 seconds. Program outputs for Walk Test.
A Silent Walk Test is a test that sends test information to a printer but does not sound outputs. Do not program any outputs for Walk Test.
Figure 93 shows a sample programming screen with a control module selected for a Standard Walk Test. For more information on selecting outputs for Walk Test, refer to “How to a Program a Control or Relay Module” on page 83 or “How to Program a Panel Circuit” on page 84.
Figure 93 Sample Control Module Programmed for Silent Walk Test
The Control Panel in Walk Test
When in Walk Test, the control panel does the following:
Accepts each new alarm and activates its programmed outputs for approximately 3 seconds. For details on programming points for Walk Test activation, refer to “How to Edit or Delete a Point (2=point)” on page 78).
Saves and stores each test in the History buffer.
Sends a TEST Axx (xx is the number of tests for a detector with this SLC address) status banner for each alarm to the printer. The “TEST Axx” message may be used to find installation errors. After walk-testing the entire system and setting each device into alarm once, if two devices are set to the same SLC address, a “TEST 02” will be reported for that SLC address. The installer should verify that no “TEST 02” or higher entries exist in the History buffer.
Turns on the System Trouble LED and the System Trouble relay. If a new trouble occurs, all control modules programmed for Walk Test activate for 8 seconds and
!
PROGRM@CONTROL MODULE@ADDRESS@08 Z00@Z@@Z@@Z@@Z @@@@@@@@@@@@@SW M08
Walk Test selected for the module. (To select for Silent Walk Test, change the “W” to an asterisk (*)
Page 100
Programming Status Change Options
100 AFP-200 PN 15511:H2 10/14/2002
the control panel sends a trouble banner (“TEST Txx”) to the History buffer and optional printer.
Turns off the System Alarm relay.
Doing a Walk Test
This section contains instructions for performing a Standard and Silent Walk Test. Follow these procedures for doing both types of Walk Test. The difference between a Standard and Silent Walk Test is the programming of the outputs as shown in“How to Edit or Delete a Point (2=point)” on page 78.
To do a Standard Walk Test, follow these steps:
1. From the Status Change screen (Figure 84 on page 93), press the 6 key to display the Walk Test Entry screen as shown in Figure 94:
Figure 94 Walk Test Entry Screen
To stop Walk Test at any time, press the BACKSPACE key and the control panel returns
to the Status Change screen. A 1-hour timer automatically returns the control panel to normal operation after 1 hour of inactivity.
2. From the Walk Test Entry screen, press the ENTER key. The control panel goes into Walk Test and the Walk Test screen appears as shown in Figure 95:
Figure 95 The LCD Display in Walk Test
3. Test your output devices.
4. When finished with the Walk Test, press the
BACKSPACE key to return the control
panel to normal operation as shown in the sample screen in Figure 96.
Figure 96 Sample LCD Display in Normal Operation
5. View the History buffer and printer output (if installed) to check the results of the Walk Te s t .
WARNING: When finished doing a Walk Test:
Exit Walk Test immediately and return the system to normal operation.
Notify the building owner/operator, fire department, and other persons that
testing is complete and the system is operating normally.
Status Change Password
WALK@TEST@PRESS ENTER@TO@START BACKSPACE@TO@STOP
WALK@TEST@PRESS
BACKSPACE@TO@STOP
Second line goes blank in Walk Test
ALL@SYSTEMS@NORMAL 11:13A@@SUN@12/25/97
!
Loading...