ACPS-610(E)
Addressable Charger/Power Supply
General
The ACPS-610(E) is an auxiliary power supply with a battery
charging option and a host of special features. Selectable
charging options allow the ACPS-610(E) to provide 6 amps of
shared power to four outputs while charging batteries from
12 to 200 AH, or 10 amps of shared power when the unit is
configured for use with an external battery charger. Four individually addressable outputs can be independently configured
for auxiliary power or Notification Appliance Circuits (NAC).
NAC outputs support notification appliance synchronization for
devices manufactured by System Sensor®, Wheelock, and
Gentex. An option to disable battery charging allows the system designer to use the four built-in circuits to distribute
10 amps of power for general purposes, excluding NAC applications.
The ACPS-610(E) is compatible with NOTIFIER intelligent fire
alarm control panels using CLIP and FlashScan® protocol.
Features
• Certified for seismic applications when used with the appropriate seismic mounting kit.
• Approved for Marine applications when used with listed
compatible equipment (see DN-60688).
• Provides 6.0 A of NAC power or 10 A of general purpose
power.
• Four Class B (Style Y) or four Class A (Style Z) outputs,
individually addressable by the FACP.
• When built-in outputs are configured for NAC operation,
each circuit supports strobe synchronization with the following manufacturers' audio/visual devices: System Sensor®
(SpectrAlert® and SpectrAlert Advance Series) or Wheelock or Gentex.
• Each circuit can be software-selected for use as: a Notification Appliance Circuit, general purpose 24 VDC power, fourwire detector power, or door holder.
• Steady, March Time (120 PPM), Two Stage, Temporal, or
UZC Zone-Coded and Non-Coded devices - softwareselectable by circuit.
• Universal Zone Coder (UZC-256) option supports for programmable coded outputs. Up to 256 different codes.
• Auxiliary Outputs: 24V @ 0.5A and 5V @ 0.15A.
• Charges 12 to 200 AH batteries with full supervision. The
charger on the ACPS may be disabled via software. When
disabled, a separate, external charger is required, for example a CHG-120.
• May be used to provide battery backup for multiple ACPS
supplies.
• AC loss detection, brownout detection, and AC loss delay
reporting.
• Power-limited outputs.
• Isolated Signaling Line Circuit (SLC) interface.
• Selectable ground fault detection.
• Canadian two stage operation.
DN-60244:C3
Power Supplies
Specifications
• Primary (AC) power:
– ACPS-610: 120 VAC, 50/60 Hz input, 5.0 A maximum.
– ACPS-610E: 220/240 VAC, 50/60 Hz input, 2.5 A maxi-
mum.
• Output voltage: 24 VDC electrically regulated and power
limited (under primary AC mains). Under secondary power,
20.4 to 26.4 VDC.
• Output circuits - TB3, TB4, TB5, TB6 on Main Board: 1.5 A
maximum for any NAC output circuit. 2.5 A maximum for
any Power output with battery charger disabled.
• Secondary power (battery) charging circuit - lead-acid battery charger which will charge 12 to 200 AH batteries. Maximum charger current - 5.0 A.
• Secondary power auxiliary outputs - TB2 on CPS-24 Board:
– 24V @ 0.5A, power limited.
– 5V @ 0.15A, power limited.
• Wiring: utilizes wire sizes 12 to 18 AWG (3.1 to 0.78 mm²).
• SLC specifications: Average SLC current is 1.287 mA. SLC
data is transmitted between 24.0 VDC, 5 VDC, and 0 VDC
at approximately 3.33 Kbaud.
• Battery fuse (F2): 15A, Fast-acting.
• Weight: 4.5 lb.
ACPS Programming
The ACPS-610(E) is programmable via the simple-to-use
PK-PPS programming utility, which requires a Windows® PC
with a USB port and cable. Programming may be performed
during an on-line session with the ACPS-610(E), or previously
saved programs may be downloaded to individual ACPS610(E) units. The ACPS-610(E) requires the use of a minimum
of 5 SLC address points, and will use up to 14 SLC address
points to fulfill requirements for Canadian supervision and two
stage operation.
NOTE: PK-PPS is available for download from www.magnifire.com.
DN-60244:C3 • 4/23/2012 — Page 1 of 2
Listings and Approvals
Example of Programming
for the ACPS-610 Using 6 Addresses
60244scrn1.jpg
Example for ACPS-610
Using Canadian Reporting with Two Stage
60244scrn2.jpg
These listings and approvals apply to the modules specified in
this document. In some cases, certain modules or applications
may not be listed by certain approval agencies, or listing may
be in process. Consult factory for latest listing status.
• UL Listed: S635.
• ULC Listed: S635.
• FM Approved.
• CSFM: 7315-0028:0248, 7165-0028:0224, 7165-
0028:0243.
• MEA #30-08-E.
• FDNY: COA #6085, #6098.
When used with the MARINE-EQ, appropriate seismic
bracket, and marine approved devices, the ACPS-610(E) is
approved by the following agencies:
• US Coast Guard: 161.002/50/0 (Standard 46 CFR).
• Lloyd's Register: 11/600013 (ENV 3 category).
• American Bureau of Shipping (ABS).
Product Line Information
ACPS-610: Addressable charger power supply, with selectable
built-in synchronization, and four built-in control modules. Several mounting options available (see below).
ACPS-610E: Same as ACPS-610, but configured for 220/240
VAC operation.
CAB-PS1: The CAB-PS1 can house one ACPS-610(E) and
two 12 AH batteries. Dimensions: 15.218" (38.654 cm) high x
14.5" (36.83 cm) wide x 3.562" (9.048 cm) deep with door.
SEISKIT-PS/2/4: Seismic kit for mounting ACPS-610 in a
CAB-PS1. Includes bracket for two 12 AH batteries.
DR-PS1: When installing an ACPS-610(E) into an older version of the CAB-PS1 used for an ACPS-2406(E), the new
wider door must be ordered for use with the older version
cabinet.
BB-25: The BB-25 can house one ACPS-610(E) and two 12
volt, 26 AH batteries.
BB-100: The BB-100 can house one ACPS-610(E) and two 12
volt, 55 AH or 100 AH AH batteries.
BB-200: The BB-200 can house one ACPS-610(E) and four
12 volt, 100 AH batteries.
CAB-4 Series: The ACPS-610(E) can mount in any of the
CAB-4 Series cabinets with
6857.
EQ Cabinet Series: The ACPS-610(E) can mount in any of
the EQ Cabinet Series cabinets using CHS-6. See DN-60229.
MARINE-EQ System: Protects equipment in shipboard and
waterfront applications. For a full list of required and optional
equipment, see DN-60688.
CHS-PS/CHS-6: Chassis used to mount the ACPS-610(E) in
row 1, 2, or 3 of the CAB-4 or EQ series enclosure.
CHS-BH: Battery mounting chassis that holds up to two 12AH
batteries on a CHS-PS.
Batteries: ACPS-610(E) battery charging circuit range is 12 200 AH. See DN-6933.
Notifier®, FlashScan®, System Sensor®, and SpectrAlert® are registered
trademarks of Honeywell International Inc. Windows® is a registered
trademark of Microsoft.
©2012 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
CHS-PS or CHS-BH. See DN-
Page 2 of 2 — DN-60244:C3 • 4/23/2012
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com