Notifier ACPS-2406 User Manual

July 20, 2004
DN-6834 • E-50
ACPS-2406
Addressable Charger/Power Supply
with built-in synchronization
Section: Power Supplies
GENERAL
The ACPS-2406 is an auxiliary power supply and battery charger with a host of unique features. Each of the four Notification Appli­ance Circuits (NAC) is individually addressable, eliminating the need for control modules. In addition, each circuit can provide notification appliance synchronization without an additional mod­ule, normally required when non-coded devices are installed. De­vice manufacturers supported are System Sensor, Wheelock, and Gentex. The ACPS-2406 is compatible with all NOTIFIER intelli­gent Fire Alarm Control Panels (FACPs).
S635
FEATURES
• Each NAC can be synchronized with any of the following manufacturers’ audio/visual devices:
— System Sensor (SpectrAlert® Series) — or Wheelock — or Gentex
• Four NACs individually addressable by the FACP: — 6.0 A of output power for NAC or 5.0 A of general pur-
pose power.
— Each circuit can be DIP-switch-selected as general pur-
pose 24 VDC power, four-wire detector power, or a No­tification Appliance Circuit.
— Steady, March Time (120 PPM), Dual Stage, Temporal,
or UZC Zone-Coded and Non-Coded devices — all DIP­switch-selectable by circuit.
• Universal Zone Coder (UZC-256)/supervised output option allows for programmable coded outputs. Up to 256 different codes.
• Charges 7 to 25 AH batteries with full supervision.
• The charger on the ACPS may be disabled via a DIP switch. When disabled, a remote charger, for example a CHG-120, may be used to battery-back multiple ACPS supplies.
• AC loss detection and AC loss delay reporting.
• Brownout detection.
• Power-limited outputs.
• Isolated Signaling Line Circuit (SLC) interface.
• Selectable ground fault detection.
• Canadian dual-stage operation.
• Two Class A/B and two Class B (Style Y) only.
• A total of five (or less) ACPS power supplies may be con­nected together to synchronize multiple power supplies (con­nect to any NAC output from one ACPS to sync signal input — single pair required).
INSTALLATION STANDARDS & CODES
The ACPS-2406 complies with the following standards:
• NFPA 72 National Fire Alarm Code.
• Underwriters Laboratories: — UL 864 Standard for Control Units for Fire Alarm Systems. — CAN/ULC – S527-M87.
In addition, the installer should be familiar with the following standards:
NOTIFIER® is a Honeywell company. This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information, contact NOTIFIER. Phone: (203) 484-7161 FAX: (203) 484-7118
12 Clintonville Road, Northford, Connecticut 06472
• NEC Article 760 Fire Protective Signaling Systems.
• Applicable Local and State Building Codes.
• Requirements of the Local Authority Having Jurisdiction.
SPECIFICATIONS
Primary (AC) power: 110 – 120 VAC, 50/60 Hz input, 2.7 A maximum.
Output voltage: 24 VDC electrically regulated and power­limited (under primary AC mains). Under secondary power,
20.4 to 26.4 VDC.
Output circuits – TB4, TB5, TB6: 2.5 A maximum for any one output circuit. For the entire supply, 5.0 A (continuous),
6.0 A during a fire alarm (1 hour UL rating).
Auxiliary power output: J1 – 24 VDC @ 0.5 A general pur­pose power (when auxiliary power is used, fourth output rated for 2.0 A).
Secondary power (battery) charging circuit – TB2, TB3: lead-acid battery charger which will charge 7 to 25 AH bat­teries. Maximum charger current – 1.1 A.
Wiring: utilizes wire sizes 12 to 18 AWG (3.1 to 0.78 mm²).
SLC specifications: Average SLC current is 1.287 mA. SLC data is transmitted between 24.0 VDC, 5 VDC, and 0 VDC at approximately 3.33 Kbaud.
Battery fuse (F2): 15A, 3AB.
MEA
173-01-E 345-02-E 317-01-E
CS118
(shown without cabinet)
California State Fire Marshal
7315-0028:213
DN-6834 • 07/20/04 — Page 1 of 4
6834pho1.jpg
Made in the U.S.A.
ACPS ADDRESS SELECTION
The ACPS addresses MUST start at an address ending with either “0” or “5”. DO NOT start the ACPS at address “000”.
Examples of effective start addresses are 5, 10, 15 ... 120; start addresses can go up to 145 (with 0 – 158 on loop; 13 addresses utilized by programming options), or 85 on CLIP systems (0 – 99 on loop; 13 ACPS addresses). Dependent upon the programming options selected (by DIP switches), the ACPS takes 5 (minimum) to 13 addresses on the SLC loop.
Address functions:
Address 1 = ACPS Trouble; tells FACP the ACPS is in
Trouble.
Address 2 = Activates NAC 1. Address 3 = Activates NAC 2. Address 4 = Activates NAC 3. Address 5 = Activates NAC 4. Address 6 = Silence Address (activation silences System
Sensor, Wheelock, or Gentex sync strobes).
Address 7 = Monitor AC Fail (Canadian requirement). Address 8 = Monitor Battery (Canadian requirement). Address 9 = Monitor Earth Fault (Canadian requirement). Address 10 = Dual Stage (changes NAC 1 from 20 PPM to
Temporal).
Address 11 = Dual Stage (changes NAC 2 from 20 PPM to
Temporal).
Address 12 = Dual Stage (changes NAC 3 from 20 PPM to
Temporal).
Address 13 = Dual Stage (changes NAC 4 from 20 PPM to
Temporal).
ARCHITECTURAL/ ENGINEERING SPECIFICATIONS
For specifications on the ACPS-2406 addressable power supply, please contact NOTIFIER.
ORDERING INFORMATION
ACPS-2406: Remote charger power supply, with selectable built-in synchronization, and four built-in control modules. In­cludes power supply circuit board, transformers, and installa­tion instructions. Several mounting options available (see be- low).
CAB-PS1: The CAB-PS1 can house one ACPS-2406 and two 7 AH batteries. Dimensions: 15.218" (38.654 cm) high x 14.5" (36.83 cm) wide x 3.562" (9.048 cm) deep with door; backbox
2.875" (7.303 cm) deep; 1.125" (2.858 cm) knockouts. Bottom knockouts for use only when batteries are externally mounted. Four mounting holes: two at 9.1" (23.114 cm) width apart from each other (at centers) at upper left and right of backbox; another two holes 10.625" (26.988 cm) below them (at centers).
BB-25: The BB-25 can house one ACPS-2406 and two 7 – 25 AH batteries.
CAB-3/-4 Series: The ACPS-2406 can mount in any of the CAB-3/-4 Series cabinets. This can be in the bottom of the cabinet or a tier via a CHS-PS and CHS-BH. See CAB-3 (DN-
3549) and CAB-4 Series (DN-6857) data sheets for model and ordering information.
CHS-PS/CHS-6: Power supply mounting kit. Optional kit used to mount the ACPS-2406 in a location other than the bottom of the CAB-3/-4 cabinet (e.g., second tier).
CHS-BH: Battery mounting kit. Optional kit used to mount the ACPS-2406 batteries in a location other than the bottom of the CAB-3/-4 cabinet (e.g., second tier).
Batteries: ACPS-2406 battery charging circuit range is 7 – 25 AH. See PS Series (DN-1109) or BAT Series (DN-6933) for
models and ordering information.
LED INDICATORS
(L to R on board)
SLC LEDs:
D74 SLCTXA ( D73 SLCRXA (
GRN)
GRN)
Output LEDs:
D54 NAC 4 Output ( D47 NAC 3 Output ( D40 NAC 2 Output ( D32 NAC 1 Output (
GRN) GRN) GRN) GRN)
D81 Monitor Polling LED (
D19 Ground Fault LED (
YEL)
• Polling LEDs:
D66 NAC 1 Polling ( D67 NAC 2 Polling ( D68 NAC 3 Polling ( D69 NAC 4 Polling (
GRN) GRN) GRN) GRN)
D70 Common Trouble LED (
D71 Bat/Chg Trouble LED (
D72 UC Failure LED (
D75 AC LED (
Page 2 of 4 — DN-6834 • 07/20/04
YEL)
GRN)
GRN)
YEL)
YEL)
AC Input on ACPS-2406:
120 VAC, 50/60 Hz,
2.7 A maximum.
JP2 Ground Fault Disable: Cut this
jumper to disable ground fault detection.
F2 Battery Fuse: 15A, 3AB. Battery: 7 AH to 25 AH, 24 VDC.
Float voltage 27.0 – 27.8 VDC. Maximum charger current 1.1 A. Maximum load current 6.0 A.