Notifier 8100A User Manual

8100(A)
Conventional FAAST Fire Alarm Aspiration Sensing Technology®
General
The FAAST 8100(A) conventional aspirating smoke detector combines dual-source (blue LED and infrared laser) optical smoke detection with advanced algorithms to detect a wide range of fires while maintaining enhanced immunity to nui­sance particulates. This enables the 8100 to accurately detect incipient fire conditions as early as 30 to 60 minutes before a fire actually starts for Early Warning Fire Detection and Very Early Warning Fire Detection. For initial system creation, the PipeIQ
® software guides users through pipe layout. The soft-
ware also provides intuitive control over system configuration and ongoing system monitoring. An installed device can be monitored through its integral display, from a computer con­nected to the device, or remotely through a computer browser or mobile device when the detector is connected to a network, or by Modbus/TCP protocol over Ethernet. When Internet-con­nected, the 8100 can also e-mail status updates to appropriate personnel. The detector can communicate alarm levels, urgent and minor faults, and isolate inputs via eight form C relays. To enable a full detection strategy, the 8100combines its advanced communications capabilities with an extensive range of customizable settings. The detector provides five alarm levels that can be programmed for latching or non-latch­ing relays. To accommodate specific codes or environments, alarm delays can be set anywhere between 0 to 60 seconds. The 8100 also supports two sensitivity modes: In Acclimate™ mode, the detector automatically adjusts itself to current envi­ronmental conditions to reduce nuisance alarms. Day/Night/ Weekend mode enables technicians to preset alarm thresh­olds based on routine changes in the environment.
Features
• Detection as precise as 0.00046%/ft obscuration.
• Five alarm levels and two sensitivity modes provide applica­tion flexibility.
• Dual flow detection including both ultrasonic and electronic sensing for pipe and chamber air flow measurement.
• A single device protects up to 8,000 square feet.
• Advanced detection algorithms reject common nuisance conditions.
• Patented particle separator and field-replaceable filter remove contaminants from the system.
• PipeIQ™ software provides intuitive system layout, configu­ration, and monitoring all in one package.
• Using the onboard Ethernet interface, you can monitor the detector from any Internet browser, smart phone or mobile device with VPN capability. You can also configure the detector to e-mail status updates to appropriate personnel.
• Monitoring and configuration can also be accomplished using Modbus/TCP protocol over Ethernet.
• Fault indicators exhibit a broad spectrum of events.
• Unique air flow pendulum graph verifies pipe network func­tionality.
• Particulate graph displays subtle environmental changes for early problem indications.
• 5 programmable alarm levels for latching or non-latching as well as a 0 to 60 second delay to best accommodate local codes or environments.
DN-60791:A
Conventional Smoke Detector
• At startup 8100 self-adapts to its environment in just 24 hours, not weeks. The exclusive Acclimate mode automati­cally adjusts within your specified parameters to reduce nui­sance alarms and adjust to current conditions.
• Comprehensive, simple and intuitive display has real-time, quick-read information at the device including five alarm levels, ten particulate levels, air flow, power and a wide range of faults to quickly identify the problem for prompt correction.
Specifications
ELECTRICAL SPECIFICATIONS
External Supply Voltage: 18-30 VDC.
Remote Reset Time: External monitor must be pulled low for
a minimum of 100 ms.
Power Reset: 1 sec.
Avg. Operating Current: 500 mA @ 24 VDC.
Alarm: 650 mA – All relays active, all alarm levels displayed.
Voltage @ 24 VDC.
Relay Contact Ratings: 3.0 A @ 30 VDC, 0.5 A @ 125 VAC.
ENVIRONMENTAL RATINGS
Operating Temperature: 32°F (0°C) to 100°F (38°C).
Sampled Air Temperature: -4°F (-20°C) to 140°F (60°C).
Humidity Range: 10 to 95% (non-condensing).
IP Rating: IP30.
Coverage Area: 8,000 sq. ft. (743 sq. m).
Air Movement: 0-4,000 ft./min (0-1,219 m/min).
DN-60791:A • 10/1/13 — Page 1 of 2
Made in the U.S. A.
PHYSICAL SPECIFICATIONS
User Interface Display
Height: 13.25 inches (33.7 cm).
Width: 13.0 inches (33 cm).
Depth: 5.0 inches (12.7 cm).
SLC Connection: Standard SLC connections. Class B (for-
merly Style 4) or Class A (formerly Style 6/7).
Relays: 8 Form C, 3 AMP, programmable latching or non­latching.
Communication Network: Ethernet monitoring, 6 E-mail address alerts, Modbus/TCP.
Cable Access: 4 1-inch (2.54 cm) cable entry holes on top and bottom of unit.
Wire Gauge: 12 AWG (2.05 mm) max. to 24 AWG (0.5 mm) min.
Maximum Single Pipe Length: 262 ft. (80 m).
Maximum Branched (2) Pipe Length: 165 ft. (50 m) each
branch.
Maximum Air Inlet Holes: 40 holes.
Network Outside Pipe Diameter: 1.050 inches, IPS (25 mm).
Internal Pipe Diameter: 0.591 to 0.827 inches (15-21 mm).
Sensitivity Range: 0.00046%/ft. obs – 4.0%/ft. obs.
Event Log: 18,000 events stored.
Shipping Weight: 11.6 lbs. (5.26 kg), includes packing mate-
rial.
User Interface Display:
• Five alarm levels (Alert, Action 1, Action 2, Fire 1, and Fire 2).
• Ten particulate levels.
• Ten bi-color flow.
• Fault graph.
Agency Listings and Approvals
The listings and approvals below apply to Intelligent FAAST Series components. In some cases, certain modules or applica­tions may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status.
UL Listed: S911.
ULC Listed: S911.
FM approved.
Maryland State Fire Marshal: Permit # 2244.
Product Line Information
8100 Intelligent FAAST: Conventional aspirating smoke detector. For Canadian applications, order 8100A.
F-A3384-000: Replacement Air Filter.
F-LCARD-SP: Language Card - Spanish.
P-PIPE-210: CPVC Pipe (210 feet total).
P-COUPLING: Coupling (15 each).
P-ELB-45: 45° Elbow (10 each).
P-ELB-90: 90° Elbow (20 each).
P-ENDCAP: End Cap (25 each).
P-TEE: Tee (15 each).
P-UNION: Union (10 each).
P-LABEL-P: Pipe Label (100 each).
P-LABEL-T: Sampling Point Labels (100 each).
P-SAMP-KT: Sampling Point Kit (10 sets).
HP300ULX: Power Supply, 12/24VDC, 2.4 A DC.
Page 2 of 2 — DN-60791:A • 10/1/13
NOTIFIER®, FlashScan®, PipeIQ®, and FAAST Fire Alarm Aspiration Sensing Technology® are registered trademarks of and Acclimate™is a trademark of Honeywell International Inc. ©2013 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com