Notifier 5600 User Manual

5600 Series
Mechanical Heat Detectors
GENERAL
System Sensor’s 5600 Series mechanical heat detectors offer property protection against fire and for non-life-safety installa­tions, where smoke detectors are inappropriate.
Multiple configurations. The 5600 Series offers a full line of configurations to accommodate a broad range of applications. Both single- and dual-circuit models are offered, each avail­able for low- and high-temperature ratings with either fixed­temperature or combination fixed-temperature/rate-of-rise (ROR) activation. The ROR element of the fixed/ROR models is restorable, to accommodate field-testing the unit.
Installation flexibility. To satisfy a variety of installations, the 5600 Series easily mounts to single-gang and octagonal back­boxes. These models also accommodate 4" (101.6 mm) square backboxes when used with a plaster ring. The mount­ing bracket is reversible to allow for flush- and surface-mount backbox installations.
Visual identification. The 5600 Series provides clear mark­ings on the exterior of the unit to ensure that the proper detec­tor is being used. Alphanumeric characters identify the activation method, as well as the temperature rating, in degrees Fahrenheit and Celsius. Fixed temperature models are identified “FX”, while combination fixed/rate-of-rise units are marked “FX/ROR”. The 5600 Series also provides a col­lector as a post-activation indicator. Once the detector has been activated, the collector drops from the unit to allow easy identification of the specific unit in alarm.
FEATURES
• Multiple configurations available: – Fixed-temperature (non-resettable) or combination fixed
(non-resettable)/rate-of-rise (self-restoring). – Low-temperature and high-temperature ratings. – Single-circuit and dual-circuit.
• Easy-to-read alphanumeric identification of detector type and temperature rating.
• External collector provides visual indication of activation.
• Reversible mounting bracket for flush- and surface-mount installations.
• Flexible mounting capabilities: single-gang, 3.5" or 4" octag­onal, 4" (101.6 mm) square with plaster ring.
• Easy-to-use terminal screws provide a more positive wiring connection.
• Low-profile design to coordinate with room aesthetics.
AGENCY LISTINGS AND APPROVALS
These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status.
UL Listed: S2101
ULC Listed: S2101 (all with “A” suffix)
MEA: 199-03-E
CSFM: 7270-1209:227, 7270-1653:167
• FM Approved
DN-6931:A1 • I-304
Conventional Initiating Devices
6931pho1.jpg
SPECIFICATIONS
PHYSICAL SPECIFICATIONS
Maximum installation temperature:
For models 5601P, 5603, 5621, 5623: 100°F (38°C).
For models 5602, 5604, 5622, 5624: 150°F (65.6°C).
Alarm temperature:
For models 5601P, 5603, 5621, 5623: 135°F (57°C).
For models 5602, 5604, 5622, 5624: 194°F (90°C).
Rate-of-Rise Threshold: 15°F (8.3°C) per minute (models 5601, 5602, 5621, 5622 only).
Operating Humidity Range: 5% to 95% RH noncondensing.
Input Terminals: non-polarized, accept 14 to 22 AWG (2.0 to
0.33 mm²).
Dimensions: diameter with mounting bracket: 4.57" (116 mm); height with mounting bracket: 1.69" (43 mm).
Weight: 6 oz. (170 grams).
Mounting Options: 3.5" (88.9 mm) octagonal backbox; 4"
(101.6 mm) octagonal backbox; single-gang backbox; 4" (101.6 mm) square backbox with a square-to-round plaster ring.
ELECTRICAL SPECIFICATIONS
Operating Voltage Contact Ratings (resistive)
6 - 125 VAC 3.0 A
6 - 28 VDC 1.0 A
125 VDC 0.3 A 250 VDC 0.1 A
Mechanical heat detector shall be a System Sensor 5600 Series model number ______, Listed to Underwriters Labora­tories UL 521 for Heat Detectors for Fire Protective Signaling Systems. The detector shall be either a single-circuit or a dual­circuit type, normally open. The detector shall be rated for acti­vation at either 135°F (57°C) or 194°F (90°C), and shall acti­vate by means of a fixed-temperature thermal sensor, or a combination fixed-temperature/rate-of-rise thermal sensor. The rate-of-rise element shall be activated by a rapid rise in temperature, approximately 15°F (8.3°C) per minute. The detector shall include a reversible mounting bracket for mount-
DN-6931:A1 • 2/9/10 — Page 1 of 2
ing to 3.5-inch (88.9 mm) octagonal, 4-inch (101.6 mm) octag­onal, single gang, and 4-inch (101.6 mm) square backboxes with a square-to-round plaster ring. Wiring connections shall be made by means of SEMS screws that shall accommodate 14 – 22 AWG wire. The detector shall contain alphanumeric markings on the exterior of the housing to identify its tempera-
ORDERING INFORMATION
ture rating and activation method. The rate-of-rise element of combination fixed-temperature/rate-of-rise models shall be restorable, to allow for field-testing. The detectors shall include an external collector that shall drop upon activation to identify the unit in alarm.
Model*
Method on
Circuit
Exterior
5601P None Single 135°F (57°C) Fixed-Temperature/Rate-of-Rise 50 ft. x 50 ft. (15.24 m x 15.24 m)
5602 Lettering Single 194°F (90°C) Fixed-Temperature/Rate-of-Rise 50 ft. x 50 ft. (15.24 m x 15.24 m) 5603 Lettering Single 135°F (57°C) Fixed-Temperature 25 ft. x 25 ft. (7.62 m x 7.62 m) 5604 Lettering Single 194°F (90°C) Fixed-Temperature 25 ft. x 25 ft. (7.62 m x 7.62 m) 5621 Lettering Dual 135°F (57°C) Fixed-Temperature/Rate-of-Rise 50 ft. x 50 ft. (15.24 m x 15.24 m) 5622 Lettering Dual 194°F (90°C) Fixed-Temperature/Rate-of-Rise 50 ft. x 50 ft. (15.24 m x 15.24 m) 5623 Lettering Dual 135°F (57°C) Fixed-Temperature 25 ft. x 25 ft. (7.62 m x 7.62 m) 5624 Lettering Dual 194°F (90°C) Fixed-Temperature 25 ft. x 25 ft. (7.62 m x 7.62 m)
NOTE: Refer to NFPA 72 guidelines for spacing reductions when ceiling heights exceed 10 feet (3.048 m).
Identification
Temperature
Rating
Activation
UL Protected Spacing,
10’ (3.048 m) Ceiling*
* Add an “A” to part number for ULC model.
WIRING DIAGRAMS
Single-Circuit Models
6931wir1.wmf
Dual-Circuit Models
Page 2 of 2 — DN-6931:A1 • 2/9/10
6931wir2.wmf
©2010 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Made in the U.S. A.