USING THE 1010/2020 DISPLAY INTERFACE ASSEMBLY (DIA)...................................................................................................................................5
The Keypad....................................................................................................................................................................................................5
The “ACK NEXT” Button.............................................................................................................................................................................. 5
The “EXT Bell ISOLATE” Button .................................................................................................................................................................5
The “RESET’ Button......................................................................................................................................................................................6
The “TEST MENU” Button...........................................................................................................................................................................6
The “ISOLATE” Button.................................................................................................................................................................................6
EXPLANATION OF LOOP BOARDS...........................................................................................................................................................................14
RS-485 AND RS-232 CIRCUITS....................................................................................................................................... 16
CONNECTING A PRINTER DIRECTLY TO THE DISPLAY (DIA) ....................................................................................................................................17
CONNECTING A PRINTER TO THE SIB BOARD .......................................................................................................................................................17
CONNECTING A LAPTOP IN TERMINAL MODE TO EMULATE A PRINTER.....................................................................................................................18
TERMINAL MODE PROGRAMMING FROM A LAPTOP COMPUTER...............................................................................................................................18
RS-485 FROM SIB CARD TO ANNUNCIATORS........................................................................................................................................................ 19
RS-485 TO AN LCD-80TM...................................................................................................................................................................................19
CONNECTING AND PROGRAMMING AN LCD-80 (ACS MODE) FROM A LAPTOP................................................................. 20
LAPTOP TO LCD-80 TERMINATIONS......................................................................................................................................................................20
ENTERING CUSTOM POINT LABELS........................................................................................................................................................................22
CPU TERMINATIONS ........................................................................................................................................................23
POWER SUPPLY TERMINATIONS........................................................................................................................................ 23
TERMINATING THE LOOP AND DEVICES ON THE LOOP.........................................................................................................24
TERMINATING THE ANALOGUE LOOP TO THE LIB CARDS.........................................................................................................................................24
WIRING CONTROL MODULES (CMX-2).................................................................................................................................................................. 26
WIRING SHORT CIRCUIT ISOLATOR MODULES (ISO-X)...........................................................................................................................................26
1668 FAN CONTROLS....................................................................................................................................................... 28
TERMINATION OF MODULES .................................................................................................................................................................................28
APPLICATION OF FAN CONTROL MODULES.............................................................................................................................................................28
SCS-8 FAN CONTROL MODULE ANNUNCIATOR......................................................................................................................................................29
ACM-16AT PUSHBUTTON & LED INDICATOR ANNUNCIATOR....................................................................................................................................30
ACM-32A LED INDICATOR ANNUNCIATOR ............................................................................................................................................................. 30
LDM-32 LED DRIVER ANNUNCIATOR....................................................................................................................................................................31
LCD-80 LCD MIMIC ANNUNCIATOR (DUAL MODE) IN ACS MODE............................................................................................................................31
LCD-80 LCD MIMIC ANNUNCIATOR (DUAL MODE) IN TERMINAL MODE....................................................................................................................32
MAIN PROGRAMMING MENU.............................................................................................................................................. 35
PARTIAL SYSTEM PROGRAMMING ..................................................................................................................................... 36
LIB LOOP STYLE 4 OR STYLE 6 (2=STY)..............................................................................................................................................................37
TIME DELAYS (3=TDLY) ......................................................................................................................................................................................38
AUDIO VISUAL POWER SUPPLIES (4=AVPS)..........................................................................................................................................................38
ZONE BOUNDARY (5=ZBND)................................................................................................................................................................................39
LOCAL PARAMETERS (7=LOCP)...........................................................................................................................................................................40
ADDITIONAL SYSTEM PARAMETERS (9=PARM)..................................................................................................................................................... 41
INTERNATIONAL DISPLAY OPTION (0=CONT, 1=IDO)............................................................................................................................................43
FULL SYSTEM PROGRAMMING .......................................................................................................................................... 43
PARTIAL POINT PROGRAMMING ........................................................................................................................................44
TYPE ID (1=TYPID) ............................................................................................................................................................................................45
OPTIONAL FEATURES (4=OPTNS)........................................................................................................................................................................47
REMOVING A DEVICE (5=REMV) ......................................................................................................................................52
CHANGING THE PASSWORD 6=PSWD............................................................................................................................... 52
A Forgotten Password?...............................................................................................................................................................................52
CHANGING THE “ALL SYSTEMS NORMAL” MESSAGE (7=MSG).......................................................................................... 52
ACCESSING THE HISTORY LOG (8=HIS)............................................................................................................................ 53
WHAT IS A SOFTWARE ZONE ................................................................................................................................................................................54
FORWARD-ACTIVATING ZONES .............................................................................................................................................................................54
CONTROL BY EVENT -LISTS AND EQUATIONS .........................................................................................................................................................54
SOFTWARE TYPE-ID’S - AN OVERVIEW........................................................................................................................63
PAGE 41010/2020 INSTALLATION AND PROGRAMMING MANUAL
RECOMMENDED TYPE ID’S FOR COMMON APPLICATIONS ......................................................................................................................................... 63
System Common Output Modules................................................................................................................................................................65
Software Zones ............................................................................................................................................................................................66
A fan that starts in firemode with associated duct detector:........................................................................................................................68
A fan that stops in firemode, with associated duct detector.........................................................................................................................69
Fire Trip Relay ............................................................................................................................................................................................ 69
1010/2020INSTALLATION AND PROGRAMMING MANUALPAGE 5
SECTION 1: INSTALLATION
PANEL OVERVIEW.
The following section describes the Keypad functions, the cabinet sizes, the 1010 (4 loop) and the
2020 (10 loop) Analogue Fire Detection System.
USING THE 1010/2020 DISPLAY INTERFACE ASSEMBLY (DIA)
THE KEYPAD
DESCRIPTION
The Keypad on the right has both Alpha and Numeric facilities for each button, in most cases to
enter an Alpha character you may need to press the button more than once. In the case of entering
Loop 3 Detector 33, you will need to use the Next Char button to advance the cursor on the LCD
display between each keystroke, as D and the number 3, share the same button.
THE “ACK NEXT” BUTTON
When pressed allows you to scroll through the list of Alarms, Faults and Isolates on the LCD
display, the “ACK NEXT” button is also used to acknowledge any alarms or faults that may appear
on the LCD display
THE “EXT BELL ISOL” BUTTON
“EXT BELL ISOL” will isolate all CON and FORC type outputs flagged with “Bell Isolate”. This is to
prevent the main bells from ringing during routine testing. Also once an alarm has been
acknowledged, you can press the “EXT BELL ISOL” button, and the bells will silence and remain
silenced. If automatic bell cut-off is set, then once the cut-off is initiated the EXT BELL ISOL will
remain isolated until a system reset. If bell cut-off is not set, the EXT BELL ISOL can be toggled
on/off by pressing the button.
Please also refer to TDLY setting in programming section for further information on Bell Isolate
PAGE 141010/2020 INSTALLATION AND PROGRAMMING MANUAL
LOOP WIRING SPECIFICATION
EXPLANATION OF LOOP BOARDS.
The LIB-200A is a 1-loop board for the 1010 & 2020 panel and can support 99 detectors and 99
modules. The field wiring is electrically isolated from the rest of the system so that any two-ground
faults on separate loops will not cause invalid replies from devices. A short to any other system
circuit will not cause communication loss. The LIB-200A has an earth fault detection circuit with
selectable high/low sensitivity and isolate. The LIB-200A has two LED’s; yellow displays earth fault
and red indicates alarm condition.
The LIB-400 is a two Loop version, and has the same features as the LIB-200A,
LOOP WIRING SPECIFICATION
The recommended wiring to be used is two core twisted pair, .75mm2 minimum.
Style 4. (Loop does not return to the panel)
Port A, (Channel A) 3800M maximum, 50 Ohms resistance maximum.
Port B, (Channel B) 3800M maximum, 50 Ohms resistance maximum
Style 6. (Closed loop, returning to panel)
Total Loop, 3800M maximum, 50 Ohms resistance maximum.
1010/2020INSTALLATION AND PROGRAMMING MANUALPAGE 15
COMMON FAULT FINDING TECHNIQUES
If using optional shielded twisted pair cable to minimise radiated emissions of radio
frequency energy, do not allow the shield drain wire to enter the cabinet. Connect the drain wire
to the outside of the cabinet via an earth type connector. Maintain the continuity of the shield wire
throughout the loop but do not connect to any devices, and only earth one end.
Before connecting the loop to the LIB-200A or LIB-400 card, carry out the following tests;
1. Check continuity of loop wiring, by placing a short on one end and reading the short with a
multimeter at the other end.
2. Check the loop resistance, same as above (be sure to set the multimeter to ohms), the loop
resistance cannot exceed 50 ohms, which is 25 ohms per leg. (See examples above).
3. Check for devices incorrectly wired, set the multimeter to diode Test, and place the leads on the
cable, the reading should be approx. .645,- reverse the leads- now the reading should be approx.
1.2 or higher, if both readings read low- this indicates a device incorrectly wired, or a short on the
wiring. Note: (Each device has a diode installed)
4. Voltage reading, set the multimeter to D.C. volts and read the voltage at the loop card before
connecting the loop, the reading should be approx. 24 volts, now connect the loop, the reading
should now be 15-16 volts. If the voltage goes down low this could indicate a short on the line, or
there is a device incorrectly wired (possible Reverse polarity), find the device and correct the loop
connections at that device.
5. Earth Fault test, Select ohms on the multimeter and check between each leg of the loop and
earth, if the reading falls below 50,000 ohms, an earth fault will appear on the loop when
connected, find the cause of the earth fault and rectify. (Possible causes of an earth fault are
moisture, inadequate insulation from surrounding building, equipment or materials).
NOTE:
A note on ‘Loop Resistance Measurement’, when ISO-X devices are present. When power is
removed from the Loop, the positive side of the circuit is opened at each ISO-X isolation module.
To measure the Loop resistance, temporarily place a jumper between Terminals 2 and 4 on each
ISO-X while taking measurements. Remember to remove all the jumpers and test all isolator
modules when you have finished taking the readings.
PAGE 161010/2020 INSTALLATION AND PROGRAMMING MANUAL
NETWORK WIRING SYSTEMS
The Noti-fire-net network wiring system is to be wired in 1.5mm2- 2core twisted pair (no shield)
The network cable can run up to 1 klm between nodes (Each Fire Panel is a Node). For optimal
performance, Noti-fire Net should be run in a closed loop (style 6), however, Noti-fire-Net does have
the ability to run in an open-ended format (style 4). The cable is terminated on to a network card
(see the Noti-fire-Net manual for termination data).
RS-485 AND RS-232 CIRCUITS
The 1010/2020 has multiple RS-232 and RS-485 circuits, the illustrations below show the positions
and where to find them.
RS-485 circuits used for Annunciators wired outside of the Panel, are to be wired in 2 core Twisted
Shielded. Total RS485 run should not exceed 1.5 k’s in length. A second 2-core twin for 24Vdc is
also required for powering the Annunciators. (The last Annunciator must have a 120-ohm resistor
fitted across the RS-485 circuit). The shield must be earthed at the panel end, to the nearest earth
point immediately inside the Panel.
RS-485 circuits used for Terminal mode operation (LCD-80tm direct from the DIA) wired outside the
Panel, are to be wired in 4 core Twisted Shielded, or 2 x 2 core Twisted Shielded, and 2 core twin
for power supply requirements if needed. (The last Annunciator must have two 120-ohm resistors
fitted across the RS-485 circuits) The shields must be earthed at the Panel end, to the nearest earth
point immediately inside the Panel.
RS-232 circuits used for printer’s etc, wired outside of the Panel, are to be wired in Twisted Shielded
wiring and not to exceed 15 mtrs in length. The shield must be earthed at the Panel end, to the
nearest earth point immediately inside the Panel.
The following illustrations indicate the connection points for RS-485 and RS-232 circuits.
PRINTER CONNECTIONS
The following section indicates the terminations required, connecting a printer to various points on
the 1010/2020 Fire Panel.
When converting to a DB9 or a DB25 pin connector, follow the tables below for connection details.
PAGE 181010/2020 INSTALLATION AND PROGRAMMING MANUAL
CONNECTING A LAPTOP IN TERMINAL MODE TO EMULATE A PRINTER
A Laptop computer can be used in lieu of a printer for uploading the history file or capturing reports
from the fire panel.
Set the Laptop up in terminal mode, and connect as per the instructions above for connecting a
printer to the SIB card. (Terminals 2, 3, & 4).
Place the Laptop in “terminal mode” (Hyperterm or equivalent) and set with the following
options for the COM port.
2400 Baud.
7 Data bits.
1 Stop Bit.
Even Parity.
Xon/Xoff handshaking.
Select “Capture text to file” in the Terminal Mode program on the Laptop.
Then Press the Special Function button on the 1010/2020 Panel,
and press “2=HIS”, and follow the prompts.
The 1010/2020 panel will now upload the entire history log to the Laptop computer which can then
be saved to disk for permanent records.
TERMINAL MODE PROGRAMMING FROM A LAPTOP COMPUTER
A Laptop computer can also be used in Terminal Mode to operate and program the panel in lieu of
using the system keypad. This makes for much faster input of device descriptions etc when not
using Verifier TM.
Terminal Mode Settings:
2400 Baud.
7 Data bits.
1 Stop Bit.
Even Parity.
Xon/Xoff.
SIBDB9DB25Contact Notifier Inertia Fire Systems for
10 TxRx 2Rx 3Function key setting in Terminal Mode.
1010/2020INSTALLATION AND PROGRAMMING MANUALPAGE 19
ANNUNCIATOR TERMINATIONS
RS-485 FROM SIB CARD TO ANNUNCIATORS
The RS-485 circuit must be wired in 2 core twisted pair, and can be run to a distance of 1.5 klms,
The 24Vdc must be from the Non-resettable terminals on the power supply, or a remote 24Vdc-
power supply can be used.
A record of any external power supplies used must be placed within the 1010/2020 enclosure,
preferably in a place easily recognisable to service personal.
LCD-80TM Connection
The LCD80TM is a terminal mode remote LCD mimic. Ie: It displays whatever is on the main LCD.
PAGE 201010/2020 INSTALLATION AND PROGRAMMING MANUAL
CONNECTING AND PROGRAMMING AN LCD-80 (ACS MODE) FROM A LAPTOP
The following section details the programming procedure for programming LCD-80 (Dual Mode)
Mimics. Note the terminations for a DB-9 or DB-25 pin connector.
LAPTOP TO LCD-80 TERMINATIONS
LCD-80DB-9Db-25
1 Rx3 Tx2 Tx
6 ref5ref7 ref
7 Tx2 Rx3 Rx
Programming outline:
Remove 24vdc power.
Connect the RS-232 interface to the Laptop as shown above.
Reconnect 24vdc to the LCD-80
Insert the PK-1 Programming Key onto the connector P6.
Program the LCD-80.
Exit Program mode by removing the Programming Key.
The Laptop must be in “terminal mode” and set with the following options:
1010/2020INSTALLATION AND PROGRAMMING MANUALPAGE 21
PROGRAMMING CUSTOM MESSAGES
Once in Program mode, the LCD-80 ceases all communication on the RS-485 and waits for
commands from the RS-232 circuit. The LCD-80 screen will display:
READY FOR PROGRAMMING
Configure the Laptop in Terminal Mode, and it will display:
ENTER 1 to 9 FOR 9 CUSTOM MESSAGES
OR 0 FOR CUSTOM POINT LABEL:
Any one of the nine custom messages may be programmed by pressing the respective number
followed by ENTER on the keyboard. The LCD-80 screen and the display monitor will display either
a default message or whatever message was last stored in the unit. Text cannot be immediately
entered since the cursor starts at the end of the message. The LCD-80 programmer must edit the
message using the backspace key, then enter a new message.
Once the message has been edited, press the ENTER key to store the message.
The screen will return to the display,
READY FOR PROGRAMMING.
These custom messages have various character widths and are displayed under different conditions
present within the fire alarm system.
Number
Message
Conditions under which each message will be displayed
Number
1Standard display banner for the LCD-80.
2Displayed under Normal conditions
3Displayed when communications between LCD-80 and the control panel have
been interrupted.
4Displayed under all Alarm conditions.
5Displayed under all Fault conditions.
6
7
8
Messages 6 through 9 are not displayed on the LCD-80.
These messages are sent to a printer connected to the LCD-80.