Noshok Noshok 3540 Series Tension & Compression Force Transducers Manual

Page 1
3540 Series
Tension & Compression Force Transducers
Operating Manual
1010 West Bagley Road, Berea, Ohio 44017 I P 440.243.0888 I F 440.243.3472 I www.noshok.com
Page 2
Table of Contents
1 SAFETY NOTE
1.2 G
1.3 R
1.4 B
1.5 Q
1.6 O
1.7 M
1.8 A
ENERAL DANGERS IF THE SAFETY INSTRUCTIONS ARE NOT FOLLOWED
ESIDUAL DANGERS
AN ON UNAUTHORISED CHANGES AND MODIFICATIONS
UALIFIED STAFF
PERATING LOCATION CONDITIONS
AINTENANCE
CCIDENT PREVENTION
2 SCOPE OF DELIVERY
3 DEPLOYMENT AREAS AND USAGE INSTRUCTIONS
4 DESIGN AND METHOD OF OPERATION
4.1 M
4.2 M
EASURING ELEMENT
EASURING PROCEDURE AND OUTPUT SIGNAL
5 DEPLOYMENT LOCATION CONDITIONS
5.1 A
5.2 M
5.3 D
MBIENT TEMPERATURE
OISTURE AND CORROSION PROTECTION
EPOSITS
2
2 2 2 3 3 3 3 4
4
4
4
4
5
5
5 5 5
6 MECHANICAL INSTALLATION CONDITIONS OF TENSION /
COMPRESSION FORCE TRANSDUCERS
6.1 P
6.2 G
RECAUTIONS TO TAKE DURING ASSEMBLY
ENERAL INSTALLATION GUIDELINES
7 ELECTRICAL CONNECTION
8 TECHNICAL DATA
9 ACCESSORIES
9.1 B
9.2 A
UILT-IN ELEMENTS: ARTICULATED HEADS
CCESSORY CABLES
10 NOTES
6
6 7
7
9
12
12 13
14
1
1010 West Bagley Road, Berea, Ohio 44017 I P 440.243.0888 I F 440.243.3472 I www.noshok.com
Page 3
1 Safety note
1.1 Use for intended purpose
NOSHOK 3540 Series Tension & Compression Force Transducers are intended for the measurement of static and
dynamic tension or compression force. These devices have been constructed and tested in accordance with the safety regulations for electronic measuring equipment. Any other usage is deemed to be incorrect. The transducers can only be guaranteed to operate correctly and safely if the information in the operating instructions is complied with. The legal and safety regulations that apply (e.g. VDE 0100). This also applies to the use of accessories. The transducer is not intended to be used a safety element. The correct and safe operation of this transducer depends on correct transportation and proper storage, installation and assembly and careful operation and maintenance.
1.2 General dangers if the safety instructions are not followed
Force transducers made by NOSHOK are manufactured in accordance with the latest state of technology and are safe during operation. However, the transducers can be the source of residual danger if they are used or operated improperly. Any person who is entrusted to install, start up, maintain or repair a force transducer must have read and understood the operating instructions, particularly the technical safety instructions.
to the respective application must also be observed during use
1.3 Residual dangers
The performance and scope of delivery of the transducer only cover a sub-area of force measuring technology. The technical safety aspects of force measuring technology must also be planned and implemented by the system planner / equipper / operator in such a way that residual dangers are minimised. The existing regulations must be complied with. Residual dangers associated with force measuring technology must be pointed out.
1010 West Bagley Road, Berea, Ohio 44017 I P 440.243.0888 I F 440.243.3472 I www.noshok.com
2
Page 4
The following symbols are used in these operating instructions:
! Danger
Note
1.4 Ban on un
The transducer must not be modified from a structural or technical safety point of view or opened without the express permission of NOSHOK. Any modifications cancel our liability for any resulting damage.
1.5 Qualified staff
These transducers must only be used by qualified staff in accordance with the technical data in connection with the safety requirements and regulations mentioned in the following. The legal and safety require­ments for the respective application must also be observed. This also applies to the use of accessories. Qualified staff are persons who are familiar with the installation, assembly, start-up and operation of the product and have the qualifications to carry out their work.
1.6 Operating location conditions
The transducers must be protected from mechanical and electrical damage.
authorized changes and modifications
1.7 Maintenance
The force transducers in the 3540 Series are maintenance-free. During welding work the transducer must be bypassed with a
copper wire (min. 50 mm2) so that welding current does not flow through the transducer and weld the force introduction points.
3
1010 West Bagley Road, Berea, Ohio 44017 I P 440.243.0888 I F 440.243.3472 I www.noshok.com
Page 5
1.8 Accident prevention
Although the specified nominal force in the destruction range is a multiple of the measuring range limit, the relevant accident
!
prevention regulations of the employer’s liability insurance association must be taken into consideration.
2 Scope of delivery
Tension & compression force transducer, 2x lock nuts, operating manual
3 Deployment areas and usage instructions
T
he transducers are intended for measuring static and dynamic tension and / or com the transducers can also be used in situations where little space is available. The force transducers are suitable for harsh environmental conditions and tough operational demands. They are maintenance free and can also be installed in locations that are difficult to access. The wide range of output signals allows NOSHOK force transducers to be adapted to many difference usage conditions. As precision measuring devices, the transducers must be handled with care during transportation and assembly. Shocks (e.g. colliding with a hard surface) can also cause unexpected overloading during measuring operation, causing permanent damage.
pression force. Because of their extremely small dimensions,
The limits for the permitted mechanical, thermal and electrical loads are listed in the “technical data”. These must be complied with.
4 Design and method of operation
4.1 Measuring element
Innovative transducer manufacturing methods using the DMS principle have recently been developed. Etched wire strain gauges are not used in this case. The entire Wheatstone bridge with the necessary equalisation resistances and temperature compensation is realised using a thin-film method on a metallic, pot-shaped body. This thin-film sensor is then welded into in an appropriately shaped measuring spring with the aid of a laser welding method. The force is introduced into the force transducer via two threaded ends. The thin-film sensor and the optional electronics are sealed against moisture and dust.
1010 West Bagley Road, Berea, Ohio 44017 I P 440.243.0888 I F 440.243.3472 I www.noshok.com
4
Page 6
4.2 Measuring procedure and output signal
The force acting in the measuring direction causes the measuring spring to become elastically deformed and therefore also the welded-in thin­film cell. This deformation generates a resistance change in the individual bridge resistors. If the measuring bridge is now supplied with a feed voltage, a measuring signal that is proportional to the force occurs at the bridge output. This signal can either be output directly (c=2 mV/V) or supplied as a standardised 4-20mA or 0-10V output signal with the aid of integrated amplifiers.
5 Deployment location conditions
5.1 Ambient temperature
The temperature range of -20°C to +80°C that is specified in the data sheet applies with regard to deployment. The specified error limits are not guaranteed outside this temperature range. Temperature gradients in the force transducer must be avoided if possible. One-sided or local heating of the force transducer can cause large measuring errors.
The
temperature errors specified in the data sheet always relate to the entire measuring device up to the plug or the end of the cable (including the integrated amplifier).
5.2 Moisture and corrosion protection
Tropical climates and condensation are not a problem because the transducers comply with protection class IP 67 in accordance with EN 60529:1991+A1:2000 / IEC 529. The entire measuring spring is made from stainless steel. The amplifier casing with plug connection is made from aluminium. The design of the accessory cable also complies with protection class IP 67.
5.3 Deposits
Dust, dirt and other object must not be allowed to form deposits in such a way that they create a force short-circuit to the measuring spring, which would falsify the measuring signal.
5
1010 West Bagley Road, Berea, Ohio 44017 I P 440.243.0888 I F 440.243.3472 I www.noshok.com
Page 7
6 Mechanical installation conditions of tension /
compression force transducers
6.1 Precautions to take during assembly
Force measuring equipment is extremely sensitive and must be
handled carefully.
Attention must be paid to the installation position and therefore the load
direction when the force transducers are being installed.
Torsional moments, off-centre loads and lateral loads cause
measuring errors and can permanently damage the transducers.
Care must therefore be taken to keep the transducer free of lateral
loads and torsion during assembly (e.g. when tightening the lock nuts).
Overloading must be prevented at all times.
The output signal (2mV/V, 4...20mA, 0...10V) is noted on the name
plate (Fig. 3). The connection assignments are also noted on name plate and can also be found in the section entitled “Electrical connection”. T
he polarity must be correct at all times.
the
Type Model
Signal
Power suply
S# Product no.
UB+ Pin assignment – power supply +
0V/S- Pin assignment – power supply - / signal -
S+ Pin assignment – signal +
Tension
Compression
1010 West Bagley Road, Berea, Ohio 44017 I P 440.243.0888 I F 440.243.3472 I www.noshok.com
Fig. 3 Name plate
6
Page 8
6.2 General installation guidelines
The loads acting upon the force transducer must be as exact as
possible in the load direction.
Torsion and lateral force must be avoided.
Tension and/or compression force is introduced via two axial threaded
pins in the above-mentioned model series. The supplied lock nuts must not come into contact with the deformation body. In order to avoid interfering force, NOSHOK recommends the use of articulated heads (see chapter 9.1).
Fig. 4 Installation situation of a tension & compression force transducer
7 Electrical connection
Electrical and magnetic fields often generate interf measuring circuit. This interference essentially emanates from high voltage current running parallel to the measuring lines, but can also be caused by contactors or electric motors operating in the vicinity. Interfering voltage can also be introduced galvanically. This particularly occurs in cases where the measuring chain is earthed at various points that do not have the same potential.
To avoid the coupling in of interference, please note the following:
Always use shielded, low-capacity measuring cables (all NOSHOK cables
meet these requirements, see chapter 9.2).
Do not route the measuring cable parallel to high-voltage current and
control cables.
ering voltage in the
7
1010 West Bagley Road, Berea, Ohio 44017 I P 440.243.0888 I F 440.243.3472 I www.noshok.com
Page 9
Avoid leakage fields from transformers, motors and contactors.
The transducer, the amplifier and the display unit must not have
m
ultiple earths. Attach all equipment to the same protective conductor. The plug or cable connection assignments can be found on the name plate. Unless otherwise agreed, the following assignments are used as standard.
Round connector M12x1, 4-pin
UB+/S+
4
1
OV/S-
3
2
940E01
Round connector M12x1, 4-pin
UB+
S+
4
1
OV/S-
mV/V Output
(4 –
wire)
Power supply: UB+ Power supply: 0V/UB-/S-
Signal: S+ 4 - 4 black
Signal: S
_
1 1 1 brown
3 3 3 blue
2 - - white
4...20 mA (2 – wire)
0...10 VDC (3 – wire)
Colour coding
cable
3
2
940E04
Shield
Housing Housing
The cable shield is connected to the earth of
Housing
Shield
the transducer. The shield of the accessory cables is connected to the knurled nut and therefore the transducer earth. The earth cables can be extended or shortened without problems. Only shielded and low-capacity cables must be used for extending. The shield must also be properly connected.
1010 West Bagley Road, Berea, Ohio 44017 I P 440.243.0888 I F 440.243.3472 I www.noshok.com
8
Page 10
8 Technical data
Model series
Nominal force Fnom
Force limit 150 % F Breaking limit > 300 % F
Permissible fluctuation
3540
1/ 2 / 3 / 5 / 10 / 20 / 30 / 50 / 100 / 200 / 300 / 500 kN
nom
nom
+/ - 50 % F
acc. to DIN 50100 *
nom
4 … 20mA 2-wire technology; Output signal (Output signal range: C
)
n
0 ... 10 V 3-wire technology;
2 mV/V 4-wire technology
(R Bridge 6500 Ω) Comb. error < 0.2 % C
n
Relative backlash width (Hysteresis) < 0.1 % Cn Creeping, 30 min. at F
nom
0.1 % Cn Nominal temperature range -20 °C … 80 °C Storage temperature -40 °C … 100 °C Temperature influence - Meas.range
- Null signal
Vibration resistance
0.2 % F
0.2 % F
20g, 100h, 50...150Hz acc. to IEC68-2-6 Fc
nom
nom
/10K /10K
Protection class IP 67 acc. to EN 60 529 / IEC 529
Electrical connection
Round connector M12x1, 4-pin or cable output 10 ... 30 VDC (4 ... ≤ 20 mA
Auxiliary power
12 ... 30 VDC (0 ... 10 V) 2 ... 10 VDC (mV/V) Current output: 4 … 20 mA:
Power consumption
Signal current Voltage output: < 10mA
Burden ≤ (UB–6V)/0.024 A for 4...20 mA output
Adjusting time
≤ 1 ms (within 10 % to 90 % F
nom
) Interfering emission acc. to EN 61326 Interference immunity acc. to EN 61326
Electrical protection class
Reverse polarity, overvoltage and short circuit protection
Measuring element made from stainless steel
* i.e. use next load level for higher load
9
1010 West Bagley Road, Berea, Ohio 44017 I P 440.243.0888 I F 440.243.3472 I www.noshok.com
Page 11
Plug-model 2 – 30 kN
Bowl R
Counternut MA
see table
Model with fix cable connexion
Nom. force
1,2,3 kN 25,2 22 24 23 4,3 1,5 6 59 43 62 66 70 M12 9,5 60 60 5 kN 25,2 22 24 23 4,3 1,5 6 59 43 62 66 70 M12 9,5 60 60 10 kN 25,2 22 31 23 4,3 1,5 6 59 43 62 66 77 M12 9,5 80 60 20 kN 25,2 26 33 34 3,8 2 10 59 43 62 66 101 M20x1,5 17 100 300 30 kN 27,5 27,5 40 34 3,8 2 10 61,5 44 63 67 108 M20x1,5 17 120 300
A B D E F G H J K1 K2 K3 L M
2 – 30 kN
N-
0,1
Bowl R MA
(Nm)
1010 West Bagley Road, Berea, Ohio 44017 I P 440.243.0888 I F 440.243.3472 I www.noshok.com
10
Page 12
Plug-model from 50 kN
Bowl R
Counternut MA
see table
Model with fix cable connexion
Nom. force
50 kN 35 50 40 5 2 12 43 62 66 130 M24x2 20 150 500 100 kN 54 54 68 10 3 19,5 44 64 68 190 M39x3 34 200 2500 200 kN 67 67 82 12 3 22,5 45 65 69 231 M45x3 42 250 4000 300 kN 73 73 98 14 3 28 49 69 73 269 M56x4 50 300 6000 500 kN 94 94 113 17 3 32 59 79 83 320 M64x4 58 400 9000
D E F G H K1 K2 K3 L M
C
from 50 kN
N­0,1
BowlR MA
(Nm)
11
1010 West Bagley Road, Berea, Ohio 44017 I P 440.243.0888 I F 440.243.3472 I www.noshok.com
Page 13
9 Accessories
9.1 Built-in elements: articulated heads
Nom. force
2 kN 148±3 9,5 5 kN 148±3 9,5 10 kN 155±3 9,5 20 kN 219±4 16 30 kN 226±4 16 50 kN 276±4 19,5 100 kN 405±7 31 200 kN 466±13 36 300 kN 568±11 45 500 kN 665±13 51
H T min.
srew in depth
Swivel heads acc. DIN ISO 12240-4,
D1= 12 to 25 dimension column KD2= 40 to 80 dimension column E
Nom. force in kN
0…10 0,115 32 16 12 H7 15,4 50 M12 22 22 66 12 19 20…30 0,415 50 25 20 H7 24,3 77 M20x1,5 34 34 102 18 32 50 0,750 60 31 25 H7 29,6 94 M24x2 42 42 124 22 36 100 2 92 28 40-0.012 45 142 M39x3 65 65 188 23 55 200 3,5 112 35 50-0.012 56 160 M45x3 68 75 216 30 65 300 8,6 160 49 70-0.015 77,9 200 M56x4 80 98 280 42 85 500 12 180 55 80-0.015 89,4 230 M64x4 85 110 320 47 100
1010 West Bagley Road, Berea, Ohio 44017 I P
Weight
in kg
A B
∅D1 ∅D2
F G GL
L M SW
K
440.243.0888 I F 440.243.3472 I www.noshok.com
12
Page 14
9.2 Accessory cables
13
Cable socket, M12x1 plug
4-pin with cable
1010 West Bagley Road, Berea, Ohio 44017 I P 440.243.0888 I F 440.243.3472 I www.noshok.com
2m 5m 10m Variant
▪ ▪ straight ▪ ▪ offset
Page 15
10 NOTES:
1010 West Bagley Road, Berea, Ohio 44017 I P 440.243.0888 I F 440.243.3472 I www.noshok.com
14
Page 16
CORPORATE HEADQUARTERS
1010 W est Bagley Road, Berea, Ohio 44017 P 440.243.0888 F 440.243.3472 E-mail : noshok@noshok.com Web : www.noshok.com
NK163540OM-1
Loading...