NOSHOK 850-2-2-50/400-2-060-6-PC, 850-1-2-50/400-2-025-6, 850-2-8-50/400-2-090-6, 850-2-8-50/400-2-060-6 User manual

Page 1
USER MANUAL
S W I T C H
Electronic Temperature Switch
SERIES
850
Page 2
Copyright
All rights to these operating instructions are reserved. These operating instructions, including
extracts thereof, must not be copied or translated into other languages without our written
permission.
Safety Instructions and Warnings
Please read these instructions before installing and starting up the pressure switch. Failure to
follow the instructions will make all guarantee, warranty and compensation claims null and
void.
connection, and the correct tools must always be used.
complied with.
• Damaged devices must not be started up. If damage occurs during operation, suitable
measures must be taken to prevent persons or property from being put at risk by the damaged
pressure switch.
• The switch must only be repaired by NOSHOK.
temperature
temperature
1
Page 3
Exclusion of Liability
NOSHOK guarantees that the pressure switch is in perfect working condition when it is delivered.
The basis consists of the technical data in the data sheet and these operating instructions.
Liability cannot be accepted for the suitability of the pressure switch.
Electrical and Mechanical Connection
The technical regulations must be complied with during installation and dismantling.
The system must be depressurized prior to installation and dismantling.
Safety regulations must be complied with, particularly when working on the electrical
system. All connections to external electrical equipment must be made in accordance with
regulations.
The power to system must always be swit tch is being connected.
Temperature Switch Description
The temperature switch has one analog output and one switching output or two switching out­puts. The switching output(s) is (are) adjusted using the two buttons: set point, reset point (hysteresis), switching function (normally closed/normally open contact).
The programmable analog output is a special feature. It can be adjusted in 0.1° steps within a span of at least 20% of the temperature range.
2
Page 4
+Supply
S1
1
-Supply
2
3
4
R
L
Sig
+Supply
S1
1
-Supply
2
3
4
S2
R
1
R
2
Round Connector M 12 x 1 (4-pin)
Signal Connector Colors of
Optional Wires
Supply: + 1 brown
Supply: - 3 blue
Switch output S 1 4 black
Switch output S 2 or
2 white
analog output
Recommended accessories:
M12x1 socket with 2m cable
• straight version, order no.: FS-2-4P
• angled version, order no.: FA-2-4P
switching to p potential 1 switching output and 1 analog output 2 switching outputs
3
Page 5
Switching On and Off
Status-LED Switching Output
1 2
The temperature switch is switched on when the supply voltage is applied. There is no on/o switch. A brief initialization phase occurs when the supply voltage is applied to the switch. The display and the set point LED illuminate. The measuring range (min- and max. temperature) and the unit are indicated briey. The outputs are inactive during this time.
After initialization the switch is in normal operating mode. The temperature appears on the display, the switching outputs are active and the LED’s indicate the status of the switching outputs.
Programming
Briey pressing button S1 or S2 causes the relevant set point to be displayed. The status LED’s ash for as long as the set points are being displayed.
Pressing the buttons for longer (press and hold down button until display ashes) causes the current temperature to be taken over as the set point. The hysteresis remains unchanged. The switching output(s) can be programmed using the control buttons independently from the present temperature, per the programming sequence on page 6.
The programming sequence must run without interruptions. If delays of about 20 seconds or more occur, the switch automatically exits programming mode and switches to normal mode. All previous changes are lost.
4
Page 6
Parameter description / programming
With two switching outputs
Temperature units
Degree Celsius
Degree Fahrenheit
Switch 1, Set Point Select set point for rst switch
Switch 1, Reset Point Select reset point for rst switch
Contact 1 Select contact function for rst switch
normally open Select normally open contact
normally closed Select normally closed contact
Switch 2, Set Point Select set point for second switch
Switch 2, Reset Point Select reset point for second switch
Contact 2 Select contact function for second switch
normally open Select normally open contact
normally closed Select normally closed contact
Store
1) The pressure units setting applies immediately for the switching point settings, the reset points
and for the process pressure 4-digit LED display.
The previous changes are only accepted if button 2 is pressed about 15 seconds after the previous button press!
5
Page 7
6
Page 8
With one switching output and one analog output
Temperature units
Degree Celsius
Degree Fahrenheit
Switch 1, Set Point Select set point for rst switch
Switch 2, Reset Point Select reset point for rst switch
Contact 1 Select contact function for rst switch
Normally open Select normally open contact
Normally closed Select normally closed contact
Current high Select temperature value for 20mA
Current low Select temperature value for 4mA
Store The previous changes are only accepted if button 2 is
1) The pressure units setting applies immediately for the switching point settings, the reset points
and for the process pressure 4-digit LED display.
pressed about 15 seconds after the previous button press!
7 8
Page 9
Page 10
Technical data
Temperature Ranges -58 to +392°F
Measurement Units °C or °F (selectable)
Sensor PT100 class B or PT100 class A
Supply Voltage 12...30 Vdc, overload and reverse polarity protection
Power Consumption 50mA, without load current
Process Connections
• Fixed Thread
• Compression Fitting
Materials
Process Connection
• Housing
Stem and Working Pressure
Outputs 2 switching outputs PNP or
-58 to +752°F
-58 to +1112°F
-328 to +1112°F
ripple <10%
1/2NPT, 1/4NPT 1/2NPT Other connections on request
Stainless steel 1.4571 (316Ti); other materials or coatings on request Stainless steel, display cover plastic
• from stem length (EL) 50mm: ø6 x 0.75mm (up to 40 bar)
• from EL 50mm: ø8 x 1.75mm (up to 100 bar)
• from EL 50mm: Special parts made of solid material (up to 500 bar) Fast response time version (up to 12 bar)
• EL 25mm: ø3 x 0.25mm without taper
• EL up to 100mm: ø6 x 0.25mm with taper to ø3 x 0.25mm
• from EL 100mm: ø8 x 1.75mm with taper to ø6 x 0.25mm with taper to ø3 x 0.25mm
1 switching output PNP and analog output 4…20mA
9
Page 11
Switching outputs
A
V
.022
7U
R
Supply
=
• Switching function
• Switching rating
• Adjustment
- Set Point
- Reset point
Analog output
Signal
adjustable normally closed (NC) or normally open (NO) contact 100mA per switching output Programmable via the display
0.1° steps withhin temperature range
0.1° steps from beginning temperature range until max. set point –0.1°
4…20mA; 2-wire, programmable in 0.1° steps, span at least 20% of the temperature range
Load resistance
Dependent on the supply voltage; the relevant formula is
Display 4-digit 7-segment LED display, red, 7.6mm high
Accuracy Switching output, analog output and Display:
Accuracy of PT100 + 0,1% of the temperature range
Repeatability 0.05%
Electrical connection M12 x 1 (4-Pin)
Temperature range
Storage Ambient Thermal Eect
EMV to IEC / EN 61 326
-22...+176°F
-13...+158°F
0.006% of Full Scale/°F
IEC 61000/4/2 ESD: B IEC 61000/4/3 HF: A IEC 61000/4/4 Burst: A IEC 61000/4/5 Surge: A IEC 61000/4/6 HF: A
Protection class IP65 according IEC 529
Weight 0.66 lbs.
10
0
Page 12
DIMENSIONS Inches (mm)
11
Page 13
CE – Conformity
Remove the device as soon as device malfunctions start to occur. The internals cannot be
maintained by the customer. Replace the device or return it to the manufacturer to have it
tested.
The switch complies with all requirements of EN 61 326 with regard to interference emission and immunity for use in industrial areas. NOSHOK recommends the use of shielded cables. Installation and cable routing must be carried out correctly in order to maintain the eective protection from electromagnetic interference.
Maintenance
The temperature switches that are described in this document are maintenance free. The equip­ment will also operate in a stable state for long periods, meaning that regular adjustment or the like is not required.
12
Page 14
Cleaning
The exterior of the 850 Series Temperature Switch can be cleaned using a soft, moistened cloth. Heavy soiling can be removed using a mild cleaning agent.
The switch must not be opened for cleaning! Aggressive chemicals or hard scrubbing can damage the surface, particularly the display lm.
Disposal
The packaging and used parts must be disposed of in accordance with the regulations of the country in which the device is installed.
13